Tac 32 ICON 32 Manual
Tac 32 ICON 32 Manual
Tac 32 ICON 32 Manual
Every attempt has been made to ensure that this documentation is as accurate and up-to-date as
possible. However, Vertical Express assumes no liability for consequences, directly or indirectly,
resulting from any error or omission. The material contained herein is subject to revision. Please report
any problems with this manual to Vertical Express, P.O. Box 2019, Memphis, Tennessee 38101.
Contents
Preliminary Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Prepare for Temporary Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Configure the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Temporary Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Runbug Set Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Electronic Starter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Mechanical Starter Set Up with ESP200 Overloads . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Pump Motor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
I-2/I-3 Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Relief Pressure Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Low Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Selector Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Mount the Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Hoistway Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20
Wireway and Conduit Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21
Typical Hoistway Conduit/Duct Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22
Typical Front Conduit/Duct Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
Typical Rear Conduit/Duct Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24
Interlock Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-25
Traveling Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27
Hoistway Entrance Frames and Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28
Cab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28
Door Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28
Selector Box Mounting and Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28
Formed Rail Selector Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-29
T-Rail Selector Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-30
Twin Post Selector Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31
Tape Selector Bolt Kit for Crosshead Mount (200BWY001) . . . . . . . . . . . . . . . . . . . 1-32
Car Top Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
Swing Return Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-34
Machine Room Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-34
This page
intentionally
left blank.
Preliminary Installation
INSTALLATION
Install the following items. Refer to the Vertical Express Installation Manual (located
at: http://www.verticalxpress.com/component_manuals/Installation Manual), and
the installation instructions that ship with the equipment.
• Jack, jack follower guides (as required), rail brackets and rails
2. Pipe and install power from the mainline disconnect to the controller.
See Figure 2 on page 1-4.
• Conduit for the wires from the mainline disconnect must be installed on the
same side of the controller cabinet as the motor starter.
• The fourth wire ground from the disconnect is to be landed on the dedicated
ground bar of the controller, not the motor starter heatsink.
3. Verify that CON19, CON20, and CON21 are removed on the IOF Card. See
Figure 1.
Ground Bar
Low Voltage
Wire Routing
(as needed)
Installation
INSTALLATION
(continued) Configure the UPS
1. When on temporary operation, connect the following:
a. The AC receptacle cord from the IOF Card - CON18, pins 1, 2, and 3.
b. The AC plug from the IOF Card - CON18, pins 4, 5, and 6.
• The UPS should not be in the AC circuit during temporary operation. See
Figure 3.
• If battery lowering is not required for the job, no UPS will be provided.
• When battery lowering is not present, Manufacturing installs jumper wires
from CON18 pin 1 to pin 4, pin 2 to pin 5, and pin 3 to pin 6 on the IOF Card.
• The UPS may be mounted below the controller - Use the shipping bracket
and screws to hold the UPS in place, and wire the plug through a knock
out in the bottom of the controller.
2. Use a temporary jumper to connect EPD1 and EPD2 (located in the Trades
Access Panel, on the top of the controller). See Figure 4.
The EPD1 and EPD2 jumper will be replaced by an auxiliary set of contacts in the dis-
connect to prevent the control system from operating on any form of alternate power
when the disconnect is in the OFF position.
Temporary Operation
Only connect the approved thyssenkrupp pendant station (runbug, part number
9817323) for temporary operation. The pendant station connects directly to the
IOF Card (bottom left corner) at the connector “RUNBUG.”
Runbug Set Up • For Electronic Starters - Confirm that there are Manufacturing installed temporary
run jumpers between MUTS/USS1 and 134/MCC1. See Figure 5.
• For Across The Line Starters - See Figure 6 on page 1-7.
NO JUMPER 115
DOWN UP
ON RUNBUG 115
CAR BYPASSED
EPD's
9A:2 9A:1
131 121 121
TR5 (BLK) 9:5 131
131
MOTOR
PROTECTION
134
USS2
DSS2
TSRCPU
AC2
AC2
IOF AC2
Figure 5 - Temporary Operation Pendant Station (RUNBUG) Connection for Electronic Motor Starting
Runbug Set Up
INSTALLATION
(continued) • For Across The Line Starters - Confirm that there are Manufacturing installed
temporary run jumpers between 134, MCC1 and USS1. See Figure 6.
• The EPEN relay is energized by input EPD2 from the Trades Access Panel.
• On runbug, the CPU Card operation/faults is irrelevant to Up and Down oper-
ation because the operation is dependent on 120VAC discrete feed to relays
and solenoids from the pendant station.
ON/OFF 102
KEYSWITCH MACHINE-ROOM BYPASSED
EPD's
RUN/STOP 107
TR1 (ORG) 107
HOISTWAY BYPASSED
ENABLE
EPD's
115
NO JUMPER 115
DOWN UP ON RUNBUG
CAR BYPASSED
EPD's
9A:2 9A:1 121
131 121
TR5 (BLK) 9:5 131
131
MOTOR
PROTECTION
134
9:1 MCC2
MCC2
MC2
MCC1
TR6 (RED/BLK) 9:6 MCC1
DSS1
MC1
USS2
DSS2
TSRCPU
AC2
AC2
AC2
IOF
Figure 6 - Temporary Operation Pendant Station (RUNBUG) Connection for Across the Line Motor Starting
Runbug Set Up
(continued) 1. Remove the plug at CON16 on the IOF Card. See Figure 7.
CON16
Initial power application occurs in the next step. If incorrect, the electronic starter
may be damaged.
2. View the nameplate sticker on the electronic starter to determine its voltage rating,
and view the power unit data tag for the motor voltage rating.
a. Compare these ratings to the known building voltage provided at the disconnect.
Before continuing, correct as required.
Most electronic starters are rated at 200-460VAC (and for special applications up to
575VAC), and should not be damaged by incorrect voltage from the disconnect that is
within this range. However, Electronic Starter #787AF14 is rated for 200-230VAC, and
application of 3 phase voltage above that rating could damage it.
b. Turn ON the mainline disconnect.
3. Use a volt meter on the AC mode, and confirm that the secondary output from XFMR1
is between 108VAC and 132VAC.
If the voltage is not correct, do not continue until this issue is resolved.
6. Remove CON9A, located at the bottom left corner of the IOF Card. Be sure to save
CON9A as it will be reinstalled after temporary operation.
Runbug Set Up
INSTALLATION
(continued) 7. Install the RUNBUG plug at CON9 on the IOF Card. See Figure 8.
RUNBUG
Plug
8. Fill the power unit fluid reservoir with the appropriate fluid for this job.
AC LED
MOTOR STATUS
STOPPED
SCROLL UP
EXIT MENU
OR SAVE ENTER MENU
SCROLL DOWN
• The electronic starter displays MOTOR STATUS STOPPED when the system is normal.
Reset the starter if it reads otherwise and, before continuing, correct any problem indi-
cated on the display.
• The starter display reverts to MOTOR STATUS STOPPED after 5 minutes of inactivity.
1. Verify that the Starting Amps = the Motor Nameplate Amps x 3 (Mfg. default).
Optional: 2 x FLA = minimum setting, 4.5 x FLA = maximum setting.
2. From the MOTOR STATUS menu, press . The STATUS menu displays.
INSTALLATION
(continued)
6. Press once and OVERLOAD AMPS displays.
a. If the value is correct, skip to Step 8.
b. If the value is not correct, continue to Step 7.
INSTALLATION
Swapping motor leads to correct motor rotation will result in a motor wiring
fault. Motor rotation is controlled through adjustments in the starter and
also the line input to the starter.
2. Momentarily press UP and SAFE on the temporary run box, and observe the
direction of the motor rotation (clockwise rotation is standard for Vertical Express
equipment when viewed from the shaft end).
ABC = Standard Dry (AP) units (CW rotation as viewed from the shaft end). The
motor is mounted to the left of the pump.
CBA = Standard Wet (EP) units (CCW rotation as viewed from the pump end).
– If the motor rotation is correct, continue to Step 5.
– If the rotation is incorrect, complete the appropriate procedure below.
• For Electronic Starters - Change the line rotation setting in the starter.
a. Press once. The STATUS menu displays.
h. Press to accept the value, or to reject the change. If the wrong value is
accepted, repeat steps e. through h.
5. Confirm the motor rotation. It may take multiple attempts to get the incoming line
phase relationship correct.
L1 L2 L3
1 3 5
MC2
2 4 6
Electronic
Motor
Starter
T1 T2 T3
T3 T6
T2 T5
T1 T4
I-2/I-3 Valve
The I-2/I-3 Valve is preset by Manufacturing, assembled on the power unit, and has been
tested and adjusted. The presets are attached inside the controller, ensure movement of
the car, and reduce final adjustment time.
• The I-2/I-3 Valve requires a minimum static system pressure of 90 PSI to function
properly.
• Adjust and confirm the Relief Pressure and Low Pressure on each job—at this
time if possible.
• If the empty sling is too light to achieve 90 PSI, defer the Low Pressure adjustment
until the cab is installed and 90 PSI is achieved.
• Valves by other manufacturers: refer to the applicable valve product manual for
initial setup - Bypass/Low Pressure and Relief Pressure Adjustments.
I-2/I-3 Valve
INSTALLATION
(continued) Relief Pressure Verification
This preliminary check is to ensure that the pipe couplings and valve will not be dam-
aged if the elevator system’s oil flow or platform become restricted. The final check
for the relief pressure is set with the procedure Final Relief Pressure with Full Load on
page 2-33.
Immediately stop the power unit if the pressure exceeds 625 PSI.
3. While monitoring the pressure gauge, run the power unit in the up direction from
the runbug in short bursts. Once confirmed that the pressure will not exceed 625
PSI, the pump motor can run constantly to verify the relief pressure setting.
4. Adjust the pressure relief (if necessary) to reduce pressure below 625 PSI.
a. IN (CW) = Increase Relief Pressure
b. OUT (CCW) = Decrease Relief Pressure
5. Briefly open the Manual Lowering Valve to relieve pressure from the valve, and
confirm that the valve is fully closed when finished.
When operating elevator from the controller, follow all safety precautions.
• If the low pressure adjustment is made with the CPUC online, temporarily set
the Z44 timer to 10 seconds, and run the motor less than 10 seconds at a
time from Inspection Operation.
• OUT = Counterclockwise, CCW
IN = Clockwise, CW
1. Ensure that the car is empty and the manual lowering valve is closed.
3. Disconnect CON15 (on the IOF Card in the controller) to disable the
valve’s up slow solenoid.
4. Turn the Low Pressure adjustment screw OUT 13/4" beyond the cover
plate. See Figure 12 on page 1-16.
5. Turn the Low Pressure adjustment screw IN by hand until it touches the regu-
lator piston.
6. Turn the power ON, and use the runbug to start the motor.
7. Turn the Low Pressure adjustment screw IN just until the car starts to move.
8. Turn the Low Pressure adjustment screw OUT until the car movement stops.
9. After the car stops, turn the Low Pressure adjustment screw OUT an additional one-
half turn.
Low Pressure
Adjustment Lowering & Leveling
Speed Adjustment
Down Slowdown
Adjustment
Down Stop
Adjustment
Up Leveling
Adjustment
Selector Tape
INSTALLATION
Mount the Tape Close floor equipment is not required for this control system; see Floor Landing
and Close Floor Leveling Magnet Installation on page 2-19.
Selector tape must be handled carefully. One kink will ruin the entire tape.
1. Install the top tape support bracket. See the job layout for the proper quadrant
and position.
2. Attach the selector tape to the top tape support bracket; loop the tape over the
bracket. The loop should be a minimum of 6" at its widest point. See Figure 13
on page 1-18 or Figure 14 on page 1-19.
3. Move to the bottom of the hoistway. Attach a spring plate and tape plate to the
selector tape at a point that will be no less than 6" below the selector box when
the car is on the buffers.
4. Install the bottom tape support bracket on the guide rail 181/2" below the bottom
of the spring plate.
5. Install the other spring plate on the tape support bracket. Ensure that the selec-
tor is between the spring plate and bracket.
6. Stretch the two selector tape springs between the spring plates. If properly
installed, the springs will be one and a half times their normal length; e.g., a 10"
spring will be stretched to 15".
7. Check the bow dimension in the selector tape. If the dimension is incorrect,
adjust the tape at the bottom support bracket.
8. Ensure that the selector tape is even with the bottom spring plate. Measure from
about 2" below the bottom mounting bracket, and cut off the excess selector
tape.
9. Verify that the centerline of the selector tape is aligned within 5/16" of the center-
line of the guide rails and also free of kinks throughout the hoistway.
10. The 3" wide x 3" vertical plane of the tape must be parallel to the back of the rail
±5/16" of the centerline of the guide rails and also free of kinks throughout the
hoistway.
дΗ
½" × 1½"
дΗ
дΗ
6" Minimum
Tape Plate
д " × 1"
Spring Plate
д" × 1"
дΗ
дΗ
Bow Dimension, 1" – 2"
Tape Plate дΗ
18½"
Selector Tape Springs
*springs MUST extend Extend to 1½ times
to 1½ times original size. original size, appx. 15¼"
Spring Plate
Selector Tape
Support Bracket
Selector Tape
INSTALLATION
Forged Rail Clip, 15#
6¼" × 2"
дΗ
дΗпϭΗ
дΗ
дΗпϭΗ Spring
Plate
Selector Tape Springs
*springs MUST extend
to 1½ times original size
(appx. 15¼").
дΗ
дΗпϭΗ
Selector Tape
Hoistway Wiring
The wiring and conduit installation details represent a typical two car group, and installa-
tion for other car and group configurations is similar.
All wiring run in the duct is tied back on each side – separate high voltage from
low voltage. Do not run any low voltage wiring (including any communication wir-
ing) with any wiring that is high voltage switching, such as motor leads.
• Use electrical metallic tubing (EMT) in conduit runs longer than 6 feet.
• Check the job layout to determine the proper quadrant for location of equipment.
• Anchor bolts and hardware (for fastening conduit to the wall) are not furnished as part
of the wiring package.
• All conduit, wireway, wire, and cable is furnished in bulk and must be cut to length.
• 21/2" x 4" wireway (duct) is provided for the door interlock wiring and hall node riser.
The hall node riser consists of hall nodes mounted within the duct at each floor loca-
tion to provide interconnection and communication to hall devices such as position
indicators, hall calls, and hall lanterns for up to two cars.
• Install one 3/4" EMT run at each landing with a rear opening.
• Install EMT from the wireway to the 4" x 4" box at the rear wall.
• For rear applications, a rear riser of hall nodes is also required. The rear riser of hall
nodes is mounted in the same duct as the front riser. The rear riser provides the hall
device interconnections for up to two cars with rear openings.
• Strain bolts are supplied for installing down the hoistway wireway (at as many places
as may be necessary) to adequately support the hoistway wiring.
• Common functions within a group are wired to a single controller from the hoistway,
and then cross-connected to the remaining cars within the same group (grouped con-
trollers only).
INSTALLATION
The following procedure is a suggested method of installation. See the job wiring
diagrams and the wiring diagrams on the following pages.
Required Wireways/Conduits
1. Mount the junction box to the guide rail at a point above the center point of car
travel and also above the entrance header. See the job layout for the proper
quadrant.
5. Run conduit and mount boxes for the position indicators, the lanterns,
and the pit stop switch.
1-22
Splice
Machine 2½" x 4"
Room Wireway
Car 2 Front PI or Combo PI/Lantern
Typical Hoistway Conduit/Duct Layout
©Vertical Express
CAR 2
Hoistway Wiring
INSTALLATION
Divider Beam
Hall Station, 2½" X 4" Wireway
Fire Service ½" Straight Connector (Flex)
Switch
Installation ½" Flex Conduit
½" Straight Connector
FRONT VIEW
Divider Beam
½" Flex Conduit
Door Interlock 2½" X 4" Wireway
½" Combination Coupling
Installation
½" Clamp ½" Straight Connector (Flex)
½" Flex Conduit
½" EMT Conduit with ½" Straight Connector (EMT) ¾" Clamp
Hall Station,
Fire Service ½" Straight Connector (Flex)
Switch
½" Flex Conduit
Installation
Divider Beam ½" Straight Connector (Flex)
4" x 4" Outlet Box
¾" EMT & Fittings
2½" X 4" Wireway
½" or ¾" Straight Connector (Flex) ¾" Clamp ¾" Clamp ¾" Flex Conduit
Hall Lanterns,
Position Indicators
Installation
½" or ¾" ¾" Combination Coupling ½" or ¾" Straight
Flex Conduit Connector (Flex)
Door Interlock
Installation
½" Straight Connector (Flex)
½" Flex Conduit ½" Clamp ¾" Clamp
½" EMT Conduit with ½" Flex Conduit
½" Straight Connector (EMT) ½" Straight Connector (Flex)
4" x 4" Outlet Box
Divider Beam
¾" EMT & Fittings
2½" X 4" Wireway
Interlock Wiring
INSTALLATION
See Figure 15 on page 1-26.
For job specific connections, see the job wiring diagrams and job specific Field Wiring Chart (940KW).
Hoistway Access (HWA) Landing interlocks connect to the following dedicated inputs:
CLOSED & LOCKED inputs; used for standard passenger doors & closed/locked input contacts for freight doors.
Signal Return
IOF IOF
Input Name Connection Name Connection Description
2H2 IB CON5-2 AC1B CON5-1 Dedicated input for the bottom HWA landing hoistway door contact.
2H5 IT CON5-4 AC1B CON5-3 Dedicated input for the top HWA landing hoistway door contact.
Dedicated input for the series string of all front non-HWA landing
216 IF CON5-6 AC1B CON5-5
hoistway door contacts.
Dedicated input for the series string of all rear non-HWA landing
226 IR CON5-8 AC1B CON5-7
hoistway door contacts.
CLOSED & NOT LOCKED inputs; used for closed & not locked input contacts for freight door applications.
Signal Return
IOF IOF
Input Name Connection Name Connection Description
For freight door applications: Dedicated input for the bottom HWA
3H2 CB CON13-2 AC1B CON13-1
landing hoistway door contact.
For freight door applications: Dedicated input for the top HWA land-
3H5 CT CON13-4 AC1B CON13-3
ing hoistway door contact.
For freight door applications: Dedicated input for the series string of
316 CF CON13-6 AC1B CON13-5
all front non-HWA landing hoistway door contacts.
For freight door applications: Dedicated input for the series string of
326 CR CON13-8 AC1B CON13-7
all rear non-HWA landing hoistway door contacts.
Interlock Wiring
(continued)
This is a reference drawing. Inputs not used per job will be jumped out permanently. See job wiring diagrams.
AC1B
5:1 13:1
Interlock AC1B AC1B
at Bottom IB 3-1 CB 3-5 Non HWA
HWA Door X2 Input Input X2 BTM Closed
5:2 13:2
CPU CPU
2H2 3H2
PLD SP SP PLD
5:3 13:3
AC1B AC1B
Interlock
at Top IT 3-2 CT 3-6 Non HWA
HWA Door X2 Input Input X2 Top Closed
5:4 13:4
CPU CPU
2H5 3H5
PLD SP SP PLD
5:5 13:5
Interlock AC1B AC1B
String of
IF 3-3 CF 3-7 Non HWA
Front Non
X2 Input Input X2 Front Closed
HWA Doors 5:6 13:6
CPU CPU 316
216
PLD SP SP PLD
5:7 13:7
Interlock AC1B AC1B
String of
IR 3-4 CR 3-8 Non HWA
Rear Non
X2 Input Input X2 Front Closed
HWA Doors 5:8 13:8
CPU CPU
226 326
PLD SP SP PLD
CHKDS 8-6
X1 OUTPUT
CPU
AC2
IOF
INSTALLATION
Formed Rail
Hatch Mounting Assembly Mid Hatch Junction Box
JUNCTION BOX
MOUNTING 2½" EMT to MR (optional)
All traveling cable wires and hoistway wires must enter the controller
cabinet on the right side where the CPUC and IOF Cards are located.
LOW
VOLTAGE
WIRING
Door Operator
Mount the door operator(s) and complete the external mechanical adjustments. See the
appropriate Vertical Express door operator manuals and the job wiring diagrams for
instructions.
For systems using Vertical Express door operators, which will be communicating to the
controller via CAN, configure the CAN loading of the door operator at the time of installa-
tion. Typical installations should have loading resistors removed/disabled on the door
operator. See the Service Information section of this manual for more information.
2. Move the selector box toward the tape until all the guide halves just touch the tape.
Tighten the selector box to the bracket.
3. Align the selector box with the selector tape so that the tape will go through the guides
in a straight path. The guides must not bend the tape.
4. Align the auxiliary sensor assembly with the selector box alignment pins and the con-
nector on the main sensor assembly.
5. Be careful not to cross-thread the screws, and turn screws into the box about four
turns.
6. Press the auxiliary sensor assembly into place. Tighten the screws enough to com-
press the washers.
INSTALLATION
Use provided fastener package 200MR2 Use provided fastener package 200MR1
to attach the bracket to the selector tape. to attach the bracket to the stile.
Formed Rail
Selector Tape
Stile
Selector Harness
To Car Header
Notes:
1. For opposite hand mounting, move bracket to other side of selector box.
2. When car is at top of hoistway, align selector with tape. The sensor board position is adjustable.
3. Use 196WT1 stile selector bracket with formed rails.
Use provided fastener package 200MR2 Use provided fastener package 200MR1
to attach the bracket to the selector tape. to attach the bracket to the stile.
Selector Tape
Stile
To Car Header
Notes:
1. For opposite hand mounting, move bracket to other side of selector box.
2. When car is at top of hoistway, align selector with tape. The sensor board position is adjustable.
3. Use 196WT2, 196WT3, 196WT4, and 196WT5 stile selector brackets with t-rails.
INSTALLATION
1. Align selector with tape when car is at top of hoistway, sensor board position is adjustable.
2. Selector bracket (268YT001) mounts to selector with fastener package (200MR2).
For ICON32, use the supplied bolts, washers, and lock washers.
T-Rail Stile
Selector Mounting
Plate (165BYP002)
Selector
Tape
Crosshead
Channel
Guide Shoe
Bracket
Selector
Harness
Selector Bracket
(268YT001)
Bolt Kit (200CAH002)
Crosshead Mount
• Back of rail to this side of mount, 12" maximum
• Weld gussets provided for cases that crosshead mount does not fit.
Crossheads
дΗ
дΗdžвΗ
ϻШІЋΗ
дΗ
дΗdžвΗ
INSTALLATION
Required Material – Door operator harness - front & rear, as required
– Auxiliary swing return harness, as required – Fan and lights harness
– 21/2" wireway - rear doors only – 1/2" flex conduit and fittings
• Slotted end caps and cover plates are shipped from Manufacturing in a wiring
package.
• In all steps, leave any excess wire in the header.
• Unless stated otherwise, all of the following steps are for all jobs.
1. Insert the end of the selector harness through the end of the header and into the
main swing return. Connect flex conduit to the car header end cap, or where the
selector harness enters the car; leave wires disconnected in the swing return.
2. Connect the front door operator harness to the slotted cover plate, and pull the
MTA connectors through the header and into the main swing return; leave dis-
connected in the swing return.
3. On jobs with selective doors, wire the rear door operator harness as follows:
a. Begin in the rear header nearest the door operator, and connect the flex con-
duit from the rear door operator harness to the slotted cover plate.
b. Pull the rear door operator harness out through the rear header cover plate
to the 21/2" wireway that runs along the side of the car top.
c. In the second hole of the 21/2" wireway, attach flex conduit onto the harness.
d. In the opposite end of the 21/2" wireway cover, start at the second hole and
attach the next section of flex conduit to the cover plate of the front header.
e. Route the harness cable through the front header and pull the connectors
into the main swing return; leave disconnected in the swing return.
4. Connect the wires from the door protective device to the door operator.
5. Install conduit, and pull lights and fan wiring to main swing return terminal strip.
6. Pull the front auxiliary swing return harness through the header and into the
main swing return.
2. Connect the traveling cable to the swing return rail terminals (RT). See the swing
return terminal labels and the job wiring diagrams.
The LD-16 door operator has an adapter harness that wires the operator into the COP rail
terminals (RT).
3. Connect the lights and fan wiring (L10, L10s, L20, and ground) to the swing return ter-
minal strip.
3. Make wiring connections between the swing return (RT) and the elevator controller.
4. The various I/O will be assigned connections to the CNA Card(s), the IOF Card, the RT
(rail terminals), and the DPIA Card. See the wiring diagrams and provided job specific
Field Wiring Chart (940KW).
• Route the mainline power through the top left-hand corner of the controller.
• Route the hoistway wiring and traveling cable through the top right-hand corner of
the controller.
• Group jobs only: Working from the right-hand side of the controllers, wire control-
ler cross-connects between the controllers.
5. Wire the building power and other necessary connections (cab lighting, telephone,
etc.) to the Trades Access terminals.
Contents
Preliminary Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Remove Temporary Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
User Interface Tool (UIT) Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Software Verification Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Safety Processor Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Configure the Safety Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
CAN Node Address Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Verify Proper Resistive Loading for the CAN Channels . . . . . . . . . . . . . . . . . . . . . . . 2-11
CAN Node Configuration via the Startup Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
I/O and Safety String Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Troubleshooting I/O Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Car Top Inspection Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Selector Tape Magnet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Selector Tape and Box Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Magnet Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Preliminary Setup for Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Hoistway Scan Through the Startup Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Door Setup and Final Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
I-2/I-3 Valve - Final Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Valve Adjustment Up Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Valve Adjustment Down Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Performance Check with Full Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33
Final Relief Pressure with Full Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33
Floor Position & Leveling Magnet Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34
Terminal Slowdown Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35
Verify Proper Function of the UP Terminal Slowdown Magnets via the UIT . . . . . . . . . 2-35
Verify Proper Function of the DOWN Terminal Slowdown Magnets via the UIT . . . . . . 2-36
Final Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-37
ESP200 Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-37
Electronic Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-38
Operational Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-39
Configure the THY02 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-39
Additional Operational Adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-41
Save Parameters and Backup Job Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42
This page
intentionally
left blank.
Preliminary Adjustment
Before beginning this section, the following must be completed:
1. The hoistway and traveling cable wiring.
2. The selector tape installation.
3. All components and sub-systems prepared for Automatic Operation.
ADJUSTMENT
4. The Valve Low Pressure and Bypass are set.
5. The leveling speed is set to 10-12 FPM.
6. Connect the disconnect auxiliary contact between EPD1 and EPD2 terminals of
the Trades Access Panel. This action prevents alternate power from powering up
the controller with the disconnect in the OFF position.
7. Install plugs 9a, 19, 20, and 21 to corresponding connectors on the IOF Card.
9. Confirm that the Watchdog (WD) LED on the CPUC is illuminated. See Figure 1
on page 2-4.
10. Confirm that the AC, P24, and P24G LEDs on the IOF Card are illuminated.
See Figure 1.
11. Confirm that the P24GS LED on Power Supply Module (PSM) P24GS is illumi-
nated. The P24GS fuse and PSM are located on DIN Rail above IOF Card.
CPUC CARD
Vertical
Express Block Select Block Select Block Select Block Select
Real Time Motion System Clock Startup Wizard Inspector’s Tests
Enter Pin #
ENTER ENTER ENTER ENTER
Motion/Position Time hh:mm:ss Start Wizard?
ADJUSTMENT
FLT
1 2 3 4 Status Date mm:dd:yy UP = Yes DN = No RFL
UP DN ESC ENTER TFR
Arbiter No
Yes SCCB
Pin: 1234144 Velocity
(if incorrect, press reset) Set the Time? Clear CN Config SCC2-SCCn
Notes: ENTER UP = Yes DN = No SCCT
Config CNs
• Use UP and DN to scroll Set the Date? (Set Car Call Bottom,
QUICK COMMANDS Auto Hoistway Scan
through blocks. UP = Yes DN = No 2,3,.... top in order)
• Press ENTER to select. Show Faults* Write to Flash
• While in block menus, Show Fault Details* Save Job to USB
use UP and DN to navigate. Clear Faults*
• Use ESC to back out. Block Select
Reset Fault List
Logoff UIT?
Front Car Call
Rear Car Call UP = Yes DN = No
UP Hall Call
DN Hall Call
Block Select Show Stable Leveling
Adjustments Show I/O
*only displays if faults are present.
ENTER
ESC
Adjust Car/Group
Commands Common
Commands Upload
SUBMENU SUBMENU SUBMENU SUBMENU SUBMENU
Commands Startup
Adjust Car/Group Commands Commands Commands Commands
Commands Group Common Upload Startup Group
Front Door
Rear Door
Job Parameters (Jxx) CJR UFWCNC DCN GPN
SUBMENUS DSL UFWCNH ELD SCA
Car Information
Code Blue (Cxx) FCP UFWSPF JRT SCAI
FJR UFWSLF PRT SUC
Desination Dispatch
GET OSDMI SCF SDC
Doors (Dxx)
IOView OSDM SPC SRU
Emergency Power (Exx) STUA
IRL UDLS SRD
Fire Service (Fxx) STU
IRLR UDLR SSI
Fixtures (Xxx) TECC
RFL SHL
Homing & Shutdown (Hxx) TECCR
RRF PIG
Incon Riser (Rxx) WRTG
SCC
Motion (Mxx) SFL
Options 1 (Oxx) SFLR
Options 2 (Zxx) SRC
Parking & Zoning (Lxx) TMP
Position System (Pxx) TSR
Security (Sxx) TSRT
Traffic VER
WJR
WRT
2. Press any button while Vertical Express is displayed in the UIT window, and enter the
pin number - 1234144. See Figure 2.
If the wrong pin number is entered, continue to press UP until Vertical Express appears in
the display window, then enter the pin number again.
1 2 3 4
BLOCK SELECT
ADJUSTMENTS
ADJUST MENU
COMMANDS COMMON
c. Press UP until VER displays, press ENTER, and window displays this data:
ADJUSTMENT
v = version • If any of the safety nodes are offline, the car is shutdown and a fault is logged.
x = version number • Background color removed for clarity.
r = revision
y = revision number
This controller contains software that is under AECO A17.7 Control. When
replacing boards or functions involving this controlled software, verify that
the replacement or updated software is the same version listed on the
580AMY marker attached to the controller.
Fill out the following chart. If any processor/node reports version zero (0), the device
is not communicating; see Troubleshooting.
2. Use the following information to verify that either the SP Good LED or the SP Bad
LED is illuminated.
• SP Good LED illuminated: Continue to CAN Node Address Assignment on
page 2-8.
• SP Bad LED illuminated: Continue to CAN Node Address Assignment on
page 2-8.
The SP Bad should be glowing until the safety nodes are online and
indicate a ready to run condition. Configure the Safety Processor if
the IOF Card was exchanged with another controller.
• SP Good/SP Bad LEDs toggle back and forth: The Safety Processor is not
configured. Continue to the next procedure.
1. Find the Safety Processor (SP) Programming Jumper JP2 (located on the IOF Card
next to RSTSP).
3. From the UIT, press any button while Vertical Express is displayed, and enter the pin
number - 1234144. If the wrong pin number is entered, continue to press UP until Ver-
tical Express appears in the window, then enter the pin number again. See Figure 2 on
page 2-6.
4. From the UIT, access Block Select Adjustments and press ENTER.
8. Press RST on the CPUC Card. Once the controller recovers, repeat the steps to access
the main menu screen.
At this point, the Safety Processor is configured and either the SP Good or the SP Bad LED
should be illuminated.
NEW The SP BAD LED will remain lit until the safety nodes are online and indicate a ready to run
condition.
Overview CAN nodes must be correctly addressed by jumpers in order to be properly identified by
the controller software for I/O assignment. The CAN Node Address Assignment procedure
uses the DCN Command to display each of the possible nodes (0-11), and this information
is recorded so that the node addressing is set correctly for each node. CAN resistive load-
ing is checked and corrected as necessary to ensure stable communications to all nodes.
The nodes are then configured to prepare for Automatic Operation.
CAN nodes may not indicate ONLINE until they have been successfully configured (TECC).
1. Have some paper and pen/pencil ready to record the following data for future
use: Node ID, SmartName, online status, and channel.
ADJUSTMENT
BLOCK SELECT
ADJUSTMENTS
ADJUST MENU
COMMANDS STARTUP
CN Node=0
UP:+ DN:—
The CN Node ID (selected from step 6) displays, followed by its SmartName. The DCN information will begin to scroll
from left to right on both lines at different rates, see image below. Pressing UP or DOWN will pause the scroll until the
UP or DOWN is pressed again.
ICON32 Controllers should have the MODCTRL1 node on CH: 2 — the main interface node
for the typical job mounted on the center divider of the controller.
9. Press ESC.
11. Verify the addressing jumpers for any CAN Node Card used in the system. See Table 1
on page 6-11.
A CAN node may be CN, CNA, or any future CAN Node Card. When the jumpers are
populated on the card, the jumpers assigned functions are the same across the card
assemblies.
ADJUSTMENT
CN Card 4 OFF ON OFF OFF
CN Card 5 OFF ON OFF ON
CN Card 6 OFF ON ON OFF
CN Card 7 OFF ON ON ON
CN Card 8 ON OFF OFF OFF
CN Card 9 ON OFF OFF ON
CN Card 10 ON OFF ON OFF
CN Card 11 ON OFF ON ON
Table 1 - CN Card Node Addressing
14. Confirm any CAN node designated "CH:2" is wired to CCH/CCL. See job prints.
15. Confirm any CAN node designated "CH:3" is wired to HC1H/HC1L. See the job
prints.
1. Turn OFF, Lockout, and Tagout the mainline disconnect. All cars in the group
must be de-energized to correctly measure resistance on the Hall and Group
CAN channels.
HC1H/HC1L is only necessary if that channel has been assigned node(s), see
CAN Node Address Assignment procedure.
3. Measure the resistive loading for the Car CAN channel, between CCH and CCL.
a. Measure from CON2 or CON3 on the IOF Card (located in the controller) across
CCH and CCL. The typical measurement is 60 ohms +/-3 ohms.
b. If the resistive loading is incorrect, see CAN Channel Resistive Loading Verification
on page 4-7.
Remove all power from connected controllers before performing any Group and
Hall CAN channel resistance checks.
5. Perform the following appropriate procedure. If either procedure does not apply to the
job, continue to step 6.
• If the Hall CAN channel is used and the controller is not connected to other controllers
(grouped):
If the wrong pin number is entered, continue to press UP until Vertical Express
ADJUSTMENT
appears in the display window, then enter the pin number again.
1 2 3 4
d. The car doors are closed, and the Car Door Bypass switch on the IOF is in the OFF
position.
e. The hoistway doors are closed, and the Hoistway Door Bypass switch on the IOF is
in the OFF position.
f. All Emergency Protective Devices (EPD) in the safety string are in the ready to run
position.
The safety processor system is configured by manufacturing and the CAN nodes should,
upon power up, result in an illuminated SPGOOD LED. If not, SPGOOD and SPBAD LED’s
will toggle and a 1920 Fault is registered. For details, see Configure the Safety Processor
on page 2-8.
Any open interlock circuit will cause a power loss at 121 (IOF CON4-3) via SAFCPU or
SAFSP. See the job wiring diagrams to troubleshoot any missing voltages.
5. Scroll to Real Time Motion > ENTER > Quick Commands, then scroll to Show I/O.
6. Verify the I/O states per Table 2 on page 2-16. If the I/O states do not match the
chart, use the job wiring diagrams for the following:
a. If an optional I/O is not as indicated, and not used by the system, ignore it.
ADJUSTMENT
c. Verify that the door circuits (interlock and gate switches) are made.
EPNP, PRSW, OLTO are required to be in the active state to permit expected
operation.
• EPNP may prohibit up runs.
• OLTO will shut the car down.
• PRSW will prevent a down run.
7. Press ENTER.
8. Verify the I/O Port # and Correct I/O Pattern per Table 2 on page 2-16.
9. Confirm that the SPGOOD, NPGOOD, and PLDGOOD LED’s (located on the IOF
Card) are illuminated (green LED’s).
d. Press ENTER.
f. Press ENTER.
h. Correct issues causing critical faults. For details, see Diagnostics section.
• SAFE, CDCF, CDCR, CST and all interlock inputs (port 3) must be active with no critical
controller faults in order for SAFSPM, SAFCPU, SAFCPM, and TSRCPU to be active.
• Any optional I/O present in the job software must be in the indicated state for the
Correct I/O Pattern column.
• MCC2, MCC2M = Only seen on jobs with electronic or Wye-Delta (2 contactor) starting.
• MUTS, MCF = Only seen on jobs with electronic starting.
• MCE, MCD = Only seen on jobs with across-the-line (1 contactor) starting.
• PRSW = Only seen on jobs equipped with a low pressure switch.
• OLTS, OLTO = Only seen on jobs equipped with viscosity control thermostats.
• INHA, INHAM = Only seen on jobs with hoistway access.
• Bit Patterns provided are for jobs with electronic starting and hoistway access.
• I/O locations marked with an X are either unassigned or have a signal assigned whose
status is unimportant at this point. If required, refer to the job’s Car I/O Assignment
Sheet.
2. If Ports 1 - 10 all display zeros, both the Safety Processor and the NTSD
Processor have mismatched I/O with the CPU.
a. Verify F1 on the IOF Card is good.
b. Reload the controller generic files and the job configuration files.
ADJUSTMENT
c. Configure the Safety Processor. See page 2-8.
d. Perform the following from the Startup Wizard.
• Clear CN Config?
• Config CN.
3. If the SP and NP I/O mismatch faults still exist, then communication is faulty
between the IOF and the CPUC Cards. See the Troubleshooting section for more
help.
2. Ensure that the car door bypass and hoistway door bypass switches on the IOF
are in the OFF position.
4. Confirm that the car top inspection switch is in the INSP position.
5. Ensure that the car will not run with the car top stop switch in the STOP position.
7. Verify that the car will only run Up when UP and ENABLE are pressed.
8. Confirm that the car will only run Down when DOWN and ENABLE are pressed.
9. Ensure that the car will not run with the car door or any hoistway door open.
10. Verify that the car will not run when any contact in the safety circuit is opened (pit
stop switch, final limits, fireman’s stop, emergency exit, car stop switch). See the
Safety Circuit page in the job wiring diagrams.
Magnet Placement
• Floor level magnets are the only magnets placed on the front (or car side) of the
tape. See Figure 6 on page 2-22.
• Slowdown and directional magnets are placed on the side of the tape facing away
from the car (back side). See Figure 4 on page 2-20 and Figure 5 on page 2-21.
• Handed references are noted as if facing the tape from the car.
• The magnets have their magnetic south marked with a yellow stripe. The yellow-
striped south side faces out and should be visible for all tape magnets except the top
floor slowdown (NTSD) magnets.
Magnet Placement
(continued)
ADJUSTMENT
5. Start placement of the top edge of the first terminal slowdown magnet "D"
inches above the top of the selector box mark. Place the magnets end to end
with the south polarity facing out (yellow side out).
6. Start placement of the directional limit magnets 91/4" below the top of the selec-
tor box mark. Place two 8" magnets end to end with the south polarity facing out
(yellow side out).
The magnets must be extended up the hoistway far enough so that the
selector sensors cannot run off of the magnets at the extreme limit of travel
up past the top floor. See Figure 8 on page 2-24.
Magnet Placement
(continued)
To top of hoistway
and top tape mount
Section A-A
No Stripe note the difference Yellow Stripe
(North Pole) (South Pole)
Slowdown Directional
Magnet(s)
A A Mark the tape at the
Limit Magnet(s)
top of selector box.
½" ½"
Selector Box
Start placement of directional
limit magnets 6¼" below
the tape mark at the top
of the selector box.
Magnet Placement
(continued)
To top of hoistway
and top tape mount
ADJUSTMENT
slowdown magnets D inches above the
tape mark at the top of selector box.
D Mark the tape at the
top of the selector box.
Contract Speed Dimension D # of Magnets
(fpm) (inches) End to End
0 - 75 start 1" below mark 3
76-100 5 4
101-125 10 5
126-150 15 5
9¼"
151-200 23 6
B B
Section B-B
Yellow Stripe
(South Pole)
Slowdown Directional
Magnet(s) Limit Magnet(s)
½" ½"
Magnet Placement
(continued)
Mark the tape at the top of the selector box.
3¾"
½"
Selector Box
Position the
template on
the tape.
Magnet Placement
(continued)
ADJUSTMENT
3¾"
½"
Selector Box
D D
Position the
template on
the tape.
Close Floor
Leveling Magnet Typical Leveling Magnet
Yellow Stripe Car Side of Selector Tape
(South Pole)
Magnet Placement
(continued)
Requirement: The selector cannot be moved past the Terminal Slowdown or the Directional
Limit at the extreme limits of car travel. End to End Stacking Gap
1. Add additional magnets to the ends of Terminal Slowdown & Directional Limit Magnets. When installing multiple
2. Evenly divide additional magnets (from the chart) between each track of magnets. magnets end to end, make
3. Stack the magnets end to end. See End To End Stacking Gap (right). sure there is no gap
between the magnets.
Gaps may cause controller
and operational problems.
ADJUSTMENT
3. Gate switch (CDCF, CDCR) and limit setting (DOL, DCL - DOL and DCL are always
required for Automatic Operation, regardless of door operator type).
4. Card configuration and setup.
5. Verify that the car stops on the directional magnets 1 - 11/2" out of the terminal
landings.
• Before the car can run on Automatic Operation, the selector must scan (count)
the number of selector tape holes between floors.
• Any time a leveling magnet or directional limit magnet is moved, the hoistway
must be scanned again.
Reminder: Before starting a hoistway scan, the door operator limits (DCL, DOL) must be
correctly adjusted.
8. Repeatedly press UP until the UIT displays Auto Hoistway Scan.
9. Press ENTER to scan the hoistway, and the UIT displays Auto Hoistway Scan.
The Auto Hoistway Scan will automatically run the car at leveling speed to the bottom
directional limit, and then up to the top directional limit, scanning the hoistway tape to
learn the floor levels. If the hoistway scan was successful, the car should have leveled
down into the top terminal landing.
a. If the hoistway scan was not successful, verify and correct magnet placement and
orientation.
• Leveling speed = 8-12 FPM.
• Gate/Lock circuits are not opening up during the run.
• Direction limits should not exceed 11/2" from the terminal landing.
• The appropriate NTS and LV I/Os must be active when on DL.
• The proper polarity of each magnet must be used.
b. To view learned floor levels, scroll to Commands > Commands Common >FCP.
10. The UIT displays Write to Flash, and this function saves all settings and values to the
CPU’s card memory. Press ENTER to perform this operation.
11. When NEXT TEST? displays, press ENTER and the UIT displays Save Job to USB. This
action archives the job’s controller CPU files to a USB memory stick.
a. Install the manufacturing-provided USB flash drive included with the job.
b. Press ENTER to perform this operation, and the UIT displays Backing Software.
c. When the UIT displays Backup Complete, press ENTER and then press DOWN to
exit the Startup Wizard.
d. On the IOF Card, place the door disconnect switch in the OFF position.
Before starting this section, verify that the Preliminary I-2/I-3 Valve Setup has
ADJUSTMENT
been performed. See the I-2/I-3 Valve component manual.
Up Leveling
Adjustment
Down Slowdown
Adjustment
High Pressure
Relief
Down Stop
Adjustment
Use the UIT to monitor the speed for leveling or high speed.
• Block Select > Real Time Motion > Speed
• Block Select > Real Time Motion > Quick Commands > Show Stabilized Leveling
The controller requires positive valve stops for reliable operation. If the valve stop
is adjusted too soft, it will result in operational issues.
The Up Slowdown adjustment screw is a sensitive adjustment. Use small increments to
change the adjustment. See Figure 9 on page 2-27.
1. Use the UIT to verify or set the selector slowdown point adjustments, P17 and P18,
per the job’s top speeds and Table 3 on page 2-36. For slowdown interactions related
to stabilized leveling, see the I-2/I-3 Valve Reference on page 5R-7.
3. Place controller on Automatic Operation, and send the car to the lowest landing.
4. Run the car to the floor above, and observe the leveling zone.
5. Adjust the Up Slowdown for 3–4 inches of stabilized leveling, as verified with the UIT,
"Show Stabilized Leveling."
Each time the Up Slowdown Adjuster is changed, the Up Leveling Speed must be
rechecked.
6. Run the car on Inspection Operation, and adjust the Up Leveling. The leveling speed
should be 10-12 FPM. Use the controller’s UIT (not logged in) to display the car speed.
When operating the car from the controller, ensure all safety precautions are
followed.
8. Determine the stabilized leveling zone. The stabilized leveling does vary some
ADJUSTMENT
between runs with the I-2/I-3 Valve.
a. Note the average of 5 runs.
b. Adjust the Up Slowdown and Up Leveling speed (as necessary) to achieve
an average of 3-4 inches of Up Stabilized Leveling and 10-12 FPM of level-
ing speed.
Up Stop and Up Start Because Up Stop affects Up Start, Up Stop must be adjusted first.
Recommended = Minimum 1 turn more Up Start than Up Stop.
1. Adjust Up Stop for a soft but positive stop. See Figure 9 on page 2-27.
Up Stop Up Start
IN (cw)
Stop Softer Start Smoother
2. Use the controller’s UIT (not logged in) to display the car speed.
3. Set the lowering speed while the car is in motion during an Up or Down run.
a. Turn the Lowering Speed adjustment in one-half turn increments. See Figure 9 on
page 2-27.
b. After each adjustment, leave the flat end of the screw pointed 45 degrees to the
tank return line.
c. Run the car to confirm the correct Down High Speed as displayed on the con-
troller’s UIT home screen.
Lowering Speed
One-half Turn Increments
OUT (ccw)
Increase Lowering Speed
If no speed change occurs with one full turn on the lowering speed adjuster, DO
NOT CONTINUE TO TURN IT OUT. Ensure the DN Start adjustment is turned out at
least one turn more than the DN Stop adjustment; should the issue remain, refer
to the troubleshooting section of the valve component manual.
The Down Leveling Speed and the Down Stop adjustments must be performed together
since Down Stop affects Down Leveling Speed. Down Leveling Speed, however, does not
affect Down Stop.
2. Adjust Down Stop for a positive stop. See Figure 9 on page 2-27.
To avoid damage to the piston face and seat, never turn the Down Lowering and
Leveling Speed adjustment unless the car is in motion or resting on the buffers.
3. Adjust the Down Leveling Speed to 10–12 FPM.
Down Stop
Stop Softer
IN (cw)
Increase Leveling Speed
Down Leveling Speed
Less than one-quarter turn increments
OUT (ccw)
Increase Leveling Speed
2. Adjust the Down Start to obtain a smooth start. Ensure that the car achieves full
speed on a one-floor run. If not, make Down Start more positive. See Figure 9 on
page 2-27.
ADJUSTMENT
Down Start
IN (cw) Start Smoother
Down Slowdown Make the Down Slowdown adjustment in very small increments as soon as a change
is observed in the leveling zone. The car will overshoot the landing if the adjustment
is turned out too far.
Down Slowdown
Shorten Leveling Zone
OUT (ccw) Increase Leveling Speed
Softer Up Slowdown
1. Turn Down Slowdown out in small increments until the car has a leveling zone of
3–4 inches. See Figure 9 on page 2-27.
2. Determine the stabilized leveling zone. The stabilized leveling does vary some
between runs with the I-2/I-3 Valve.
a. Note the average of 5 runs.
b. Adjust the Down Slowdown and Down Leveling speed (as necessary) to
achieve an average of 3-4 inches of Down Stabilized Leveling and 10-12
FPM of leveling speed.
3. Run the car down on Inspection Operation to recheck down leveling speed, and
readjust Down Leveling, if necessary, for 10–12 FPM.
• It may be necessary to slightly alter the point in the hoistway where the
slowdown is initiated to achieve optimum valve and car performance, P17
(Up) and P18 (Down).
• For slowdown interactions related to stabilized leveling, see the I-2/I-3 Valve
Reference on page 5R-7.
This procedure applies to three-stop jobs and higher, and verifies that the valve is
stopping the car at the master floor the identical way in both directions. Do not worry
about floor level accuracy in this procedure, because the floor levels will be adjusted
in the Floor Position & Leveling Magnet Adjustment on page 2-34.
Valve Adjustment
(continued)
2. Run the empty car on Automatic Operation up into the master floor. Note where the
car sill is in relation to the master floor hatch sill.
3. Run the empty car on Automatic Operation down into the master floor. Note where the
car sill is in relation to the master floor hatch sill.
4. Achieve a valve stop that results in the same final car location in both travel directions.
To avoid damage to the piston face and seat, never turn the Down Lowering and
Leveling Speed Adjustment unless the car is in motion or resting on the buffers.
How to change the leveling speeds for the appropriate travel direction.
• Increase the leveling speed - To increase car momentum and put the car further in
its travel direction upon the stop.
• Decrease the leveling speed - To decrease the car momentum and shorten the final
resting place of the car in its travel direction.
The UP and DOWN stop adjustments need to be firm so that the stop can be felt slightly (a
soft but noticeable bump at the stop), as this prevents fluid temperature-based variations
in performance and allows the control system to achieve increased car level positioning
control.
1. Place the empty car on Automatic Operation at the master floor or at the top floor of a
two-stop job.
2. Force an UP relevel, and verify that the control system and the valve place the car at
floor level.
a. On the I-2/I-3 Valve, slowly turn the Manual Lowering Valve (t-handle) counter-
clockwise (ccw) to open, allow the car to lower slightly, then quickly turn the valve
clockwise (cw) to close.
b. Ensure that the car went low enough: >1/2" with P19 & P22 at default value.
• If the car did not go low enough: Troubleshoot the Manual Lowering Valve to
identify the problem, and repeat the relevel check until correct.
• If the car went low enough: The motor and valve should energize and
place the car back at floor level.
2. Run the car on Automatic Operation, and the check performance at all floors. All
valve functions will become firmer at upper landings. If adjustments are
necessary, it will affect the empty car performance.
• The Down Leveling Speed will increase and the Down Leveling Zone will be
ADJUSTMENT
shorter. It may be necessary to change the Down Slowdown adjustment to be
certain there are at least 2 inches of leveling.
• If necessary, turn IN on the Down Slowdown to increase the leveling zone.
• The Up Leveling Speed will increase. The Up Leveling Zone will change between
no load and full load. Do not change any adjustments made with no load if there
is at least 1 inch of Up Leveling Zone with a full load.
• If necessary, turn OUT on the Up Slowdown adjustment to increase the Up Level-
ing Zone.
3. Verify that the car is obtaining full speed in both directions on a one-floor run.
4. Record the working pressure in the up direction. The working pressure value will
be used in the next procedure.
1. Place the controller on Inspection Operation, close the line shut-off valve,
and set Z44 = 10 seconds.
Do Not adjust the relief pressure to 150%, as allowed by code, unless the
entire hydraulic system has been replaced.
3. Add 25% to the working pressure recorded in step 4 of the previous procedure,
and set the relief valve to relieve at this new pressure value.
4. Stop the power unit, and tighten the locknut on the relief pressure adjustment.
6. Open line shut-off valve, place car on Automatic Operation, and reset Z44 = 2.
½"
Cover
8" Magnet TSMC Card
Selector Tape Guides
ЯΗ TSAC Card
Car Side
Top Down View Showing Tape Selector Assembly with Tape, Magnets, and Magnet Glue
2. Adjust the terminal slowdown magnets so that they activate 2–4" after the
selector slowdown.
ADJUSTMENT
Example
Both up and down car speeds are 100 FPM. Table 3 shows that the up selector
slowdown is 939 counts (each count = 1/40"). Therefore, the up terminal slow-
down magnet should activate 18–20" before the landing. The down selector
slowdown is 683 counts, so the down terminal slowdown magnet should acti-
vate 12–14" before the landing.
Verify Proper Function of the UP Terminal Slowdown Magnets via the UIT
1. In the UIT, scroll to Block Select Adjustments > Adjust Car/Group > Position Sys-
tem > P17, and press ENTER to edit the value.
2. Press UP or DOWN to adjust P17 to one half of the recommended value from
Table 3 on page 2-36.
3. Place the car at a floor below the top terminal landing. This action will allow the
car to achieve contract speed in the up direction.
5. Restore P17 to the value indicated in Table 3. If the slowdown magnets were
repositioned to achieve proper operation, add 43 to the value of P17 for each
inch the magnets were moved.
6. Scroll to Block Select Adjustments > Adjustment Car/Group > Car Adjustments >
WRT, and issue a WRT Command to save the adjustments.
7. Attach each magnet in its final location with two small beads of silicone caulk.
See Figure 10 on page 2-34.
Verify Proper Function of the DOWN Terminal Slowdown Magnets via the UIT
1. In the UIT, scroll to Block Select Adjustments > Adjust Car/Group > Position System >
P18, and press ENTER to edit the value.
2. Press UP or DOWN to adjust P18 to one half of the recommended value from Table 3.
3. Place the car at the first non-close floor above the bottom terminal landing. This action
will allow the car to achieve contract speed in the down direction.
5. Restore P18 to the value indicated in Table 3. If the slowdown magnets had to be
repositioned to achieve proper operation, add 43 to the value of P18 for each inch the
magnets were moved.
6. Scroll to Block Select Adjustments > Adjustment Car/Group > Car Adjustments > WRT,
and issue a WRT Command to save the adjustments.
7. Attach each magnet in its final location with two small beads of silicone caulk. See
Figure 10 on page 2-34.
Final Adjustments
ESP200 Overload
Before the elevator is turned over to the customer, overloads must undergo
this procedure.
ADJUSTMENT
1. Run the car up with a full load, and measure the stabilized running current at
each sensing loop.
Take the stabilized running current measurements with a clamp-on AC ammeter
connected directly below the sensing loops.
2. Calculate the full load amps adjustment. The full load amps adjustment equals
the highest reading in Step 1 + 10%.
The full load amps adjustment must not be set outside the calibration range
on the overload faceplate. To do so may prevent the overload from tripping
and may also damage the motor.
3. Set the full load amps adjustment dial equal to the value calculated in Step 2.
See Figure 11.
4. Verify that the car will run the entire length of the hoistway with a full load.
Final Adjustments
(continued)
Electronic Starter
MOTOR STATUS
STOPPED
SCROLL UP
EXIT MENU
OR SAVE ENTER MENU
SCROLL DOWN
• The electronic starter displays MOTOR STATUS STOPPED when the system is normal.
Reset the starter if it reads otherwise and, before continuing, correct any problem indi-
cated on the display.
• The starter display reverts to MOTOR STATUS STOPPED after 5 minutes of inactivity.
1. Verify that the Starting Amps = the Motor Nameplate Amps x 3 (Mfg. default).
Optional: 2 x FLA = minimum setting, 4.5 x FLA = maximum setting.
2. From the MOTOR STATUS menu, press . The STATUS menu displays.
Electronic Starter
(continued) 7. Press once to access the value.
a. Press or to adjust the value of the flashing digit.
b. Press to move to the next digit.
ADJUSTMENT
Operational Adjustments
Configure the THY02 Card
The THY02 Card, powered by 24VDC, is a receive-only device. See Figure 12.
• REC+ and REC- are for 485 communication protocol.
• CANH and CANL are for CAN communication protocol used with ICON32.
1. Set the S1 Dip Switch #3 to the ON position.
2. Set the controller adjustment O43=9 for the Car CAN Channel (CCL/CCH).
Dip
Function
Switch
ON = Self-test Mode. Unit ignores data link inputs. 1
3. L10 - L34 for lobby request (parking options) - some jobs ship with parking enabled.
4. Multistage jacks.
a. JRT set to desired time.
b. O29 = 6-10 seconds.
c. O44 - # motor starts to trigger a jack resync.
d. O30 - Jack resync interval in days (1-3).
e. O32 - Jack resync door.
5. Fire service.
a. F10 - Main fire return landing.
b. F11 - Alternate fire return landing.
ADJUSTMENT
4. Press ENTER to select the Startup Wizard, and then press UP.
6. Press ENTER, and press ENTER again, and the UIT displays Save Job To USB.
7. Insert the USB flash drive for the job, and press ENTER. The CPU will
create a backup folder in the tke folder, and save the job software. This
process will take several minutes.
9. Press DOWN.
This page
intentionally
left blank.
Contents
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
No Known Application Rule I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-29
Control System Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33
SP Fault Codes - Safety Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
NP Fault Codes - NTSD Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-45
WPT Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-46
This page
intentionally
left blank.
Adjustments
Adj Unit Range Definition
Code Blue Door Hold Time - The time the doors will remain opened at the code blue desig-
nated floor. If, after this time, the Hospital Service switch has not been activated, the doors
C10 sec. 0–900
will close and the car will return to normal operation.
Note: If the AST timer expires before CBH, the car will return to Automatic Operation.
Code Blue Response Priority 1-15 - Use this adjustment to establish priorities for the cars
responding to Code Blue Operation.
C11-C25 cars 0–ncars
C11 is the highest priority car followed by C12, etc.
A zero (0) for this adjustment turns OFF the Code Blue Operation for the car.
C26 — 0–1 Group Code Blue Operation - Set to 1 to enable.
Limited Door Reversal Type
Values:
DIAGNOSTICS
D10 — 0–2 0 = Disabled
1 = Active with EE only
2 = Active with SE or EE
Nudging Enable
Values:
0 = Disable
D11 — 0–2
1 = Enable
2 = Enable with DOB override
The door open button causes the doors to fully reopen during nudging.
Front Door Type
Values:
0 = No Door
1 = Electronic Door Operator using 6300PY_ Card
2 = Discrete Door Operator
3 = Freight Door (freight doors with auto open and auto close)
4 = Freight Manual (freight doors with no auto open, no auto close, no door times, and no
D12 — 0–8 door watchdog protection timer)
5 = Freight Auto Open (freight doors with auto open only, no door watchdog protection
timer)
6 = Freight Auto Close (freight doors with auto close only, and with door
watchdog protection timer)
7 = Electronic Door Operator with CAN serial link. ICON32 with UDC (6300PA) Card or
LD-16 Door Operator
8 = Electronic Door Operator with RS-485 serial link
Rear Door Type
Values:
0 = No Door
1 = Electronic Door Operator using 6300PY_ Card
2 = Discrete Door Operator
3 = Freight Door (freight doors with auto open and auto close)
4 = Freight Manual (freight doors with no auto open, no auto close, no door times, and no
D13 — 0–8 door watchdog protection timer)
5 = Freight Auto Open (freight doors with auto open only, no door watchdog protection
timer)
6 = Freight Auto Close (freight doors with auto close only, and with door
watchdog protection timer)
7 = Electronic Door Operator with CAN serial link ICON32 with UDC (6300PA) Card or
LD-16 Door Operator
8 = Electronic Door Operator with RS-485 serial link
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
2 = 10D-3/10D-4; pre A17-2008 (Type 3 or 4). Alternate Power.
E10 — 0-2
3 = 10D-0A (Type 1); PowerVator with traction.
4 = 10D-3/10D-4; A17-2008 (Type 3 or 4). Alternate Power.
5 = Not applicable.
6 = 10D-3/10D-4; A17 2016 (Type 3 or 4).
Note: Power cycle is required for changes to take effect.
Emergency Power Return Floor (Car) - During an Emergency Power return phase, this
E11 floor 1–nf
adjustment sets which floor the car will attempt a return to.
Emergency Power Door - For use with selective doors, this adjusts which door will open at
the return floor (when returning to landing).
E12 F/R 0–1f Values:
0 = Front
1 = Rear
Emergency Power Manual Select Time - When in manual select mode, this adjusts the time
E13 sec. 10–300
delay before the car is actually selected (Type-4 only).
Okay To Hold Doors Open on Emergency Power.
Values:
E14 — 0–1
0 = False
1 = True
Emergency Power Return Floor (Group) - During an Emergency Power return phase, this
E17 floors 1–nfloors
adjustment sets which floor the car will attempt a return to.
Maximum Elevators on Emergency Power - This is the maximum number of cars allowed to
E18 cars 1–ncars
run simultaneously on Emergency Power Operation.
Emergency Power Extended Lowering Time - Use this adjustment to set the time allowed
E19 min. 2–10
for cars to arrive at the emergency power floor.
Emergency Power Lowering - This adjustment sets the automatic lowering sequence for
E20-E34 ncars 0–ncars Emergency Power Operation.
Note: E20 would be the first elevator to lower, and E34 would be the last elevator to lower.
Emergency Power Run - This adjustment sets the automatic select to run sequence for
E35-E49 ncars 0–ncars Emergency Power Operation.
Note: E35 would be the first elevator to run, and E49 would be the last elevator to run.
Emergency Power Lower Timer - This adjustment sets the time for each group in the lower-
ing sequence.
E50 sec. 0–60
Note: If the groups are powered up simultaneously, the previous group has sufficient time
to initialize and begin to lower.
Emergency Power Auto Select Timer - If the groups are powered up on Emergency Power
E51 sec. 0–100 simultaneously, this adjustment sets the time for each group in the lowering sequence to
initialize and begin lowering.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
Hall Fire Door Open Time - This adjustment sets the value of the Phase 1 door open time
for special (Houston) Fire Service.
Notes:
F17 0.1 sec. 0–255 • Cars recalled to the fire floor on Phase 1, with corresponding doors held open, will close
the doors after this time delay.
• Additional door open push button (input FSDO) per car is required in the hall for this
operation so that the doors may be reopened on demand by fire personnel.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
close at reduced door speed during Phase 2 Fire Service.
2 = The safety edge is inhibited (no door re-open from the safety edge), and the doors
close at normal door speed during Phase 2 Fire Service.
3 = The safety edge is functional (doors will re-open from the safety edge), and the doors
close at normal door speed during Phase 2 Fire Service.
Fire Lift - Use this adjustment to designate an elevator as a Fire Lift.
Note: This adjustment only applies to fire service types that require the
designation of Fire Lifts.
F20 — 0–1
Values:
0 = The elevator is not designated as a Fire Lift.
1 = The elevator is designated as a Fire Lift.
B44 Phase 2 Activation Location - Only use this adjustment for B44 Fire Service Operation.
Note: This adjustment will determine whether Phase 2 Operation is allowed to activate/
deactivate only at the main return landing, or activate/deactivate at the main or alternate
F21 — 0–1 return landing.
Values:
0 = Phase 2 can activate only at the main return landing.
1 = Phase 2 can activate/deactivate at main or the alternate return landing.
This adjustment will set the 1998 B44 Fire Service, Phase 2 return door speed.
Note: If F23=1, the door closes in response to the initial Phase 2 recall
activation done at nudging speed. This action occurs without regard to adjustment F19
(used to set up the safety edge operation and the door
F23 — 0–1
closing speed during Phase 2). See also: D11, D19, D40, Z16.
Values:
0 = The doors close at a speed determined by the F19 adjustment.
1 = The doors close at nudging speed.
This adjustment will set 2000 Fire Service (A17 & B44) Phase 2 recall floor.
Values:
F24 — 0–1
0 = Phase 2 recall will take the car to the main fire floor.
1 = Phase 2 recall will take the car to the current active fire floor.
This adjustment will set the Fire Service Return Indicator (Fire Hat).
Note: The F25 setting has no effect on the 2004 Fire Service. The Fire Hat light will remain
active while either Phase 1 or Phase 2 is active.
F25 — 0–1 Values:
0 = The Fire Hat light is active during Phase 1 Recall and, where applicable, during Phase
2 Recall. The light will deactivate when the car arrives at the fire floor.
1 = The Fire Hat light will remain active while Phase 1 or Phase 2 is active.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
H21 sec. 0-30
return floor.
J10 pounds 500–65000 Capacity - The rated car capacity.
Car ID - The car number within a group, beginning with 1. Used by the software for identi-
J11 — 1–# of cars fication and I/O assignments. See ELD for the designator - used by programs and people
for identification. Note: Altering this value may cause some features to malfunction.
Car Communication Number.
Values:
J12 — 0–240
0 = The controller computes the comm number from the car and group number.
1-255 = Force to the selected comm number.
J13 — 1–8 Group ID - The group number within a multiple group network, beginning with 1.
Lobby Floor - This adjustment sets the lobby to the proper car opening (beginning with 1 =
J14 floor 1–nf bottom floor).
Note: This floor number may not be the building floor number.
Relevel on the Stop Switch - Permits a re-level with the in Car Stop Switch active and the
CST input not active; Does not permit a re-level for the Fireman's Stop Switch(es).
J19 — 0–1 Values:
0 = No releveling while the Emergency Stop Switch is thrown.
1 = Up releveling only while Emergency Stop Switch is thrown.
Stop Switch Type - This adjustment sets the value to the type of stop switch provided on
this installation.
J20 — 0–1 Values:
0 = Keyed stop switch.
1 = Public access stop switch.
Lobby Elevator Request - Number of cars requested to park at the lobby.
Values:
L10 cars 0–ncars
0 = Disable
1 = Enable
Lobby - This adjustment sets the designated floor position number for the lobby floor, and
L12 floors 1–nfloors
is also used as the homing floor for the lobby elevator request.
Zone 1 Floor - The car stays at the last floor served for normal operation.
Notes:
• When parking is enabled and a car becomes free, it will be sent to one of the zone floors
L14 floors 1–nfloors
(after a time delay - L25).
• L14 through L19 allow for six different zone or parking floors.
• The number of zone floors used is set by L20.
L15 floors 1–nfloors Zone 2 Floor - See L14.
L16 floors 1–nfloors Zone 3 Floor - See L14.
L17 floors 1–nfloors Zone 4 Floor - See L14.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
0 = Front
1 = Rear
Independent Overrides Lockouts - This adjustment (when enabled) allows the Car Inde-
pendent Service to override the Car Call Lockouts.
O20 — 0–1 Values:
0 = Disabled
1 = Enabled
Hoistway Access Top Floor - This adjustment sets which landing is designated for the top
O21 floor 2–nf landing of hoistway access operation.
See also:O11, O22, Z38, and Z39.
Hoistway Access Top Zone - When the car runs on hoistway access, this zone is the dis-
tance (in inches) above the top hoistway access floor.
O22 inches 0–168
Note: Modifying this parameter requires SP & NP Configuration.
See also: O11, O22, Z38, and Z39.
Viscosity Return Floor - This adjustment sets which return floor is used for viscosity opera-
O23 floor 1–nf
tion.
Transfer Calls on Door Close - This adjustment (if enabled) allows call transfers to occur
while the doors are closing.
O24 — 0–1 Values:
0 = Disabled
1 = Enabled
Non-Interference Time - This adjustment sets the delay (in seconds) after the doors close,
O28 sec. 5–60
and before SAPB calls can be latched. This time delay gives priority to car calls.
Jack Resync Lower Time - This adjustment sets the time allowed for a jack resync to be
O29 sec. 5–30
completed once the car reaches the bottom and begins the resync operation.
Jack Resync Interval - This adjustment sets the number of days between automatic jack
—
O30 1-3 resync operations.
See also: FJR and JRT
O31 floor 1–nf Jack Resync Landing - This adjustment sets the return landing for jack resync return.
Jack Resync Door - This adjustment sets the preferred door to open at the jack
resync return landing during jack resync operation.
O32 F/R 0–1 Values:
0 = Front
1 = Rear
Lobby Recall Return Landing - This adjustment sets the landing that lobby recall will return
O33 floor 1–nf
to during lobby recall operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
Values:
P12 — 0–1
0 = False (Front Leveling Zone)
1 = True (both Front and Rear Leveling Zones)
Long Terminal Slowdowns.
Values:
P15 — 0–1
0 = Slowdown vane active only at slowdown points.
1 = Slowdown vane active at terminal landing floor levels.
Up Slowdown Distance (for tape selectors) - This adjustment sets the distance before the
target floor where the Up slowdown begins. To cause an earlier slowdown, increase the
P17 dpp 0–65535 P17 adjustment.
Notes:
• There are 512 dpp counts per foot.
Down Slowdown Distance (for tape selectors) - This adjustment sets the distance before
the target floor where the Down slowdown begins. To cause an earlier slowdown, increase
P18 dpp 0–65535 the P18 adjustment.
Notes:
• There are 512 dpp counts per foot.
Encoder Level Distance - This adjustment sets the distance away from the floor level count
P19 dpp 0–512 that will cause the car to relevel. Encoder leveling also requires adjustment P21 = 1.
Note: There are 512 dpp counts per foot.
Encoder Count Tolerance - The encoder position count must be within the encoder count
tolerance, when level at that floor.
• The encoder recalibration at LVU and LVD vanes must not change the encoder count by
P20 dpp 0–1024 more than the encoder count tolerance.
• Failure of either the position count or the recalibration will result in the loss of encoder
position with recovery of a floor hunt or terminal hunt.
• There are 512 dpp counts per foot.
Encoder Leveling.
Values:
P21 — 0–1
0 = No encoder leveling
1 = Encoder leveling enabled
Encoder Leveling Hysterisis - This adjustment prevents dithering on the re-level activation
point.
• When the car is level, then the value of P22 is added to P19 encoded level distance to
increase the level distance by P22.
P22 dpp 0–16
• When the car crosses the re-level distance then the hysterisis is removed.
• The effect is to create a dead zone where the car will not re-level when sitting on the re-
level point.
See also: P19, P21
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
input to register the associated car call.
Values:
0 = Lockout Override activation does not register the corresponding car call.
S39 — 0–3 1 = Lockout Override activation registers the corresponding car call.
2 = While on Program A security, the Lockout Override activation registers the corre-
sponding car call.
3 = While on Program B security, Lockout Override activation registers the correspond-
ing car call.
S40 floor 0–nf Neonatal Landing A.
S41 floor 0–nf Neonatal Landing B.
S42 floor 1–nfloors Group Security Floor.
Group Security Type - This adjustment (for group functions only) is a type of required
Tenant Security.
See also: S10 (CAR security type).
Values:
0 = (TYPE 0) No security required, or the group invokes security and the car homes and
shuts down if the return landing (S11) is set.
1 = (TYPE 1) Car call lockouts in the group.
2 = (TYPE 2) Car call lockouts in the group with override inputs in the car.
S43 — 0–11 3 = (TYPE 3-1) Car call lockouts in the group with override inputs in the car.
4 = (TYPE 3-2) Security override output only.
5 = (TYPE 4) Group hall card readers is an invalid selection for the car.
6 = (TYPE 5) Security override output only.
7 = (TYPE 6) Car call lockouts at the car level.
8 = (TYPE 7) Car call lockouts at the car level (no group function).
9 = (TYPE 8) Contract configured security.
10 = (TYPE 9) Contract configured security.
11 = Ethernet security.
S50 floor 0–nf Neonatal Landing C.
S51 floor 0–nf Neonatal Landing D.
Emergency Dispatch to Secured Floors.
S52 — — 0 = Disable
1 = Enable
V10 sec. 0–900 VIP Call Door Standing Time.
VIP Call Priority - Establish priorities for car response to VIP calls.
Values:
V11-V25 — 0–16 0 = Disable service
V11 = Highest priority call
V25 = Lowest priority call
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
X23 — 3–4 Values:
3 = 3-character display
4 = 4-character display
GAL Tone Timer Adjustment - This adjustment sets the actual length of time that floor
X24 0.1 sec. 1–20
passing tone signal will be active (to indicate the car is passing or arriving at a new floor).
X25 1/16 sec. 1–48 Flashing Timer - This adjustment sets the flashing rate of flashing jewels.
Hall CAN Channel PI Number of Display Characters.
Note: For the Car PI, see X23.
X28 — 3–4
Set to 3 = 3 character display
Set to 4 = 4 character display
Independent Service Call Latch - This adjustment allows Independent Service to latch car
calls while the doors are open; effected by O78 Adjustment.
Values:
Z12 — 0-2
0 = Disable independent service call latch.
1 = Enable independent service call latch, and flush all car calls on arrival.
2 = Enable independent service call latch, and leave further car calls latched on arrival.
Forcing Door Close - This adjustment is used for MAC DC door operators. DC will not be
active during a run. Possibly used for freight, if required.
Values:
Z15 — 0-3 0 = No MAC
1 = Front MAC Only
2 = Rear MAC Only
3 = Both Front and Rear MAC
Z26 — 0-255 —
Car Fan Turn Off Timer - This adjustment sets the car idle time required before the cab fan
Z33 sec. 0-3600
turns off.
Car Light Turn Off Timer - This adjustment sets the car idle time required before the cab
Z34 sec. 0-3600
lights turn off.
Hoistway Access Bottom Floor Door Selection.
Values:
0 = Front
Z38 — 0-1
1 = Rear
Note: Modifying this parameter requires SP & NP Configuration.
See also: O11, O21, O22, and Z39.
Hoistway Access Top Floor Door Selection.
Values:
0 = Front
Z39 — 0-1
1 = Rear
Note: Modifying this parameter requires SP & NP Configuration.
See also: O11, O21, O22, and Z38.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
Commands
Name Definition
CJR This command clears the jack resync statistics.
DCN Display CN stats and channel/port assignments where:
Name = User friendly name of the node stored in the CPU
On = State of CAN communication (Online=1, Offline=0)
RxTot = Total number of frames received
ID = CN address per CN jumpers JP(7,6,5,4)
Ch = Physical channel (2=COP, 3=Hall)
DCN SP = Number of shared ports between cars (Remote I/O Box)
TP = Number of total ports used by this CN
channel: Where 2=>Car, 3=>Hall
numPorts: 0-15 defines the number of ports used by this CN
DIAGNOSTICS
port0 port1...port15: For each physical CN port used by this CN, list the associated port in I/O layout matching
the IMS I/O screen column.
DSL Display Stabilized Leveling Distance.
Elevator Designator Display - This command displays the ASCII designator for this car. ELD shows the designa-
ELD
tor displayed by Owner's IMS Group Dispatch Window. See also PIG.
FCP Floor Count Position Display Command - This command displays the encoder position count for each floor.
FJR Force Jack Resync - This command signals an immediate request for a jack resync operation.
GET Parameters - This command retrieves the saved parameters from the EEPROM and moves them into RAM.
• The CPU only works with parameter values that are stored in its RAM memory.
GET • To display a parameter that caused an out of range error, type GET and press Enter.
• To eliminate a parameter error, enter a value in the appropriate range, save with the WRT Command, and
recall with the GET Command.
GPN Display Group Node - This command displays which node the car is communicating to (for group functions).
IOView IOView - This command displays the I/O names by bit location.
Inconspicuous Riser Lockouts - This command displays front landings that are locked out by the Inconspicuous
IRL
Riser Operation.
Inconspicuous Riser Lockouts Rear - This command displays rear landings that are locked out by the Inconspic-
IRLR
uous Riser Operation.
JRT Jack Resync Time - This command sets the time of day that a jack resync will occur.
OSDM Operating System Diagnostics - This command displays information to be sent to the log file.
PIG Group Floor Display - This command changes the position indicator display for the group.
Pressure Relief Test - This command allows the car to run to the stop ring to perform a Pressure Relief Test.
1. Place the car at the top landing.
2. Put the car on Inspection Operation.
PRT
3. Run the car onto the Top Directional Limit (DL).
4. Issue the PRT Command.
5. Run the car UP on Inspection Operation past the DL.
Scan Call Assignment Table - This command reviews the scan assignment table of all floors that effect group
SCA
(hall call) service.
Set Car Call - This command sets the nth landing car call. For rear calls, see SRC.
SCC
See also: SCCB, SCCT, SDC, SRC, SRD, SRU, and SUC.
Set Close Floor - This command allows viewing and editing of the close floor table. Note: This automatically
SCF
sets itself up during a hoistway scan. Close floor is 4–16 inches of travel between floors.
Set Car Call Bottom - This command sets the bottom landing car call. To set, type SCCB and press Enter.
• If the bottom landing has a front opening, the front car call will be set.
SCCB
• If the bottom landing does not have a front opening, the rear car call will be set.
See also: SCC, SCCT, SDC, SRC, SRD, SRU, SUC
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
ARNI Automatic Run Indicator
ATB Attendant Bypass Pushbutton
ATBI Attendant Bypass Indicator
ATDB Attendant Down Pushbutton
ATDC Attendant Door Close Speed
ATDI Attendant Down Indicator
ATT Attendant Service
ATTI Attendant Service Indicator
ATUB Attendant Up Pushbutton
ATUI Attendant Up Indicator
AUTOI Automatic Operation Indicator
AUTO2I Automatic and/or Security Operation Indicator
BUZ Buzzer - Floor Passing, Fire, and Nudging
BYSG Bypass Safety Gear Switch
C1-C64 Car Call - Combination I/O
CAPT Capture Operation
CAPTD Capture Operation Door Open
CAPTI Capture Operation Indicator
CAPTR Capture Operation Reset
CB Hoistway Door Closed Bottom
CB1-CB64 Code Blue Call - Combination I/O
CBAI Code Blue Active Indicator (Per Car)
CBELL Freight Door Call Bell
CBI1-CBI64 Code Blue Call - Input
CBJG Code Blue Indicator (Any Car)
CBO1-CBO64 Code Blue Call - Output
CBR1-CBR64 Code Blue Call - Rear - Combination I/O
CBRI1-CBRI64 Code Blue Call - Rear - Input
CBRO1-CBRO64 Code Blue Call - Rear - Output
CCEM Car Call Ind Enable Main
CCER Car Call Ind Enable Remote
CCIE Car Call Indicator Enable
CCM Control Cutout Main Station
CCPO Car Call Panel Open
CCR Control Cutout Remote Station
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
DISVIP Input - If active, the car will not be considered for VIP Operation
DJ1-DJ64 Down Hall Call Lockout Jewel Outputs
DL2-DL64 Hall Call - Down - Lockout
DLB Direction Limit - Bottom
DLO2-DLO64 Hall Call - Down - Lockout Override
DLOR2-DLOR64 Hall Call - Down - Rear - Lockout Override
DLR2-DLR64 Hall Call - Down - Rear - Lockout
DLT Direction Limit Top
DO Door Open
DO1 Door Open
DO1R Door Open Rear
DO2-DO64 Hall Call - Down - Output
DOB Door Open Button - Front
DOBR Door Open Button - Rear
DOH Door Open High Speed
DOHR Door Open High Speed - Rear
DOI Door Open Indicator
DOIR Door Open Indicator - Rear
DOL Door Open Limit
DOLR Door Open Limit - Rear
DOPE Door Operation Enable - Front
DOPER Door Operation Enable - Rear
DOR Door Open - Rear
DORL Door Open Reversal Limit
DORLR Door Open Reversal Limit - Rear
DPK Down Peak Operation
DPKJ Down Peak Jewel
DR2-DR64 Hall Call - Down - Rear - Combination I/O
DRI2-DRI64 Hall Call - Down - Rear - Input
DRJ1-DRJ64 Down Rear Hall Call Lockout Jewel Outputs
DRO2-DRO64 Hall Call - Down - Rear - Output
DSPJ Dispatch Failure Jewel
DSPJ1-DSPJ16 Car # Dispatch Failure Jewel
DWDI Door Watchdog Indicator
DWDRI Door Watchdog Rear Indicator
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
FSDFI Fire Service - Door Failed Indicator
FSDO Fire Service - Fireman's Door Open
FSE Fire Service Sensor - Equipment
FSH1 Fire Service - Hall - Main - On
FSH1A Fire Service - Hall - Main - On
FSH2 Fire Service - Hall - Main - Off
FSH2A Fire Service - Hall - Main - Off
FSH3 Fire Service - Hall - Aux - On
FSH3A Fire Service - Hall - Aux - On
FSH4 Fire Service - Hall - Aux - Off
FSH4A Fire Service - Hall - Aux - Off
FSH5 Fire Service - Hall - Main - Reset (Bypass)
FSH5A Fire Service - Hall - Main - Reset (Bypass)
FSHX Fire Service Phase 2 Switch Hold (Front)
FSHXR Fire Service Phase 2 Switch Hold (Rear)
FSI Fire Service Indicator (Phase 1 or 2)
FSM Fire Service Sensor - Main
FSMFI Fire Service - Main Floor Indicator
FSPO Fire Service Panel Open
FSR Fire Service Phase 1 Recall Active
FSRI Fire Service Return Indicator
FSRR Fire Service Rear Door Closing PH1/PH2
FSSR Fire Service Sensor Reset
FST Fire Service Sensor - High Temperature
FSX Fire Service Sensor - Auxiliary
GCL1-GCL64 Car Call Lockout - Group Wide
GCLR1-GCLR64 Car Call Lockout - Rear - Group Wide
HABD Inspection - Hoistway Access - Bottom - Down
HABDM Inspection - Hoistway Access - Bottom - Down - Monitor
HABU Inspection - Hoistway Access - Bottom - Up
HABUM Inspection - Hoistway Access - Bottom - Up - Monitor
HATD Inspection - Hoistway Access - Top - Down
HATDM Inspection - Hoistway Access - Top - Down - Monitor
HATU Inspection - Hoistway Access - Top - Up
HATUM Inspection - Hoistway Access - Top - Up - Monitor
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
IUL In Use Light
IUO1-IUO63 Inconspicuous Riser Call - Up - Output
IUR1-IUR63 Inconspicuous Riser Call - Up - Rear - Combination I/O
IURI1-IURI63 Inconspicuous Riser Call - Up - Rear - Input
IURO1-IURO63 Inconspicuous Riser Call - Up - Rear - Output
LBYST Lobby Stop If Passing Lobby Stop At Lobby
LVD Level Down
LVU Level Up
LWA Loadweigher - Anti-nuisance
LWB Loadweigher - Bypass
LWBI Loadweigher - Bypass - Indicator
LWD Loadweigher - Dispatch
LWO Loadweigher - Overload
LWOI Loadweigher - Overload - Indicator
MCC1 Motor Contactor Control #1
MCD Motor Contactors De-energized
MCF Motor Contactor Fault
MCM Motor Contactor Output Monitor
MEC Medical Emergency - Car
MEH Medical Emergency - Hall
MEHI Medical Emergency - Hall Indicator
MEI Medical Emergency - Indicator
MTSTRT Motor is Starting - Indicator - Output
MUTS Motor Up To Speed Input from Electronic Motor Starter (EMS), used by controller for MCE & MCD states.
NATLA Neonatal Hold at Landing A
NATLB Neonatal Hold at Landing B
NATLC Neonatal Hold at Landing C
NATLD Neonatal Hold at Landing D
NATLH Neonatal Hold at Any Landing
NATLI Neonatal Operation Indicator
NATX Neonatal Operation Inputs; x = Floor Number (Baby Monitor)
OFLNI Off Line Indicator
OOSI Out of Service Indicator
PI1-PI64 Position Indicator - Light Up - Car or Controller For Car and Hoistway
PIA1-PIA64 Position Indicator.- Light Up - Alternate Landing Hoistway
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
UO1-UO63 Hall Call - Up - Output
UPK Up Peak Operation
UPKJ Up Peak Jewel
UR1-UR63 Hall Call - Up - Rear - Combination I/O
URI1-URI63 Hall Call - Up - Rear - Input
URJ1-URJ64 Up Rear Hall Call Lockout Jewel Outputs
URO1-URO63 Hall Call - Up - Rear - Output
VIP1-VIP64 VIP Call - Combination I/O
VIPI VIP Indicator per Car
VIPJG VIP Indicator any Car
VIPR1-VIPR64 VIP Rear Call - Combination I/O
VPI1-VPI64 VIP Call - Input
VPO1-VPO64 VIP Call - Output
VPRI1-VPRI64 VIP Rear Call - Input
VPRO1-VPRO64 VIP Rear Call - Output
Designator Name
ACCI Audible Car Call Indicator
ADC Auxiliary Door Close
ADCL Auxiliary Door Close Limit (DCL)
AES Security-activate Hall Call Enable Subset
ALB Alternate Lobby Operation
ALTJ Alternate Floor Fire Service Jewel
AOV Security - Activate Car Call Overrides
ARDC Auxiliary Rear Door Close
ARDCL Auxiliary Rear Door Close Limit (DCL)
ARL Arrival Lantern
ARLR Arrival Lanterns - Rear
ATD Attendant Operation Door Speed
ATDR Attendant Operation Door Speed - Rear
BEEP Coded Car Call Entry Code Button Acknowledge
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
FS2HI Fire Service Phase 2 Hold Indicator
FS2NI Fire Service Phase 2 Switch On Indicator
FSCDB In-car Secondary Fire Switch Door Bypass
FSCDM In-car Secondary Fire Switch Door Bypass Monitor
FSDB Fire Service Door Bypass
FSDOM Fire Service Fireman's Door Open Monitor
FSDOX Fire Phase 1 Alternate Floor Door Open
FSH6 Fire Service Phase 1 On (Tertiary Switch)
FSH7 Fire Service Phase 1 Off (Tertiary Switch)
FSH8 Fire Service Phase 1 On (Quaternary Switch)
FSH9 Fire Service Phase 1 Off (Quaternary Switch)
FSTFL Fire Service Top Final Limit
GL1M Gate And Lock Monitor #1
GL2M Gate And Lock Monitor #2
HCLA Security - Hall Call Lockout Activate
HCLD Hall / Car Lantern - Down - Front
HCLU Hall / Car Lantern - Up - Front
HCPR Hall Call Power Rear
HFJ Hall Call Power Failure Jewel
HFSJ Phase One Fire Service Jewel
HG Bit-packed Per-floor Combined Up & Down Hall Gongs
HGR Bit-packed Per-floor Combined Up & Down Hall Gongs
HLPWY Help is on the way
HOLD Next Up Hold Car
HPZ1 Hall Call Power Zone 1
HPZ1R Hall Call Power Zone 1 Rear
HPZ2 Hall Call Power Zone 2
HPZ2R Hall Call Power Zone 2 Rear
HPZ3 Hall Call Power Zone 3
HPZ3R Hall Call Power Zone 3 Rear
INDOP Independent Operation
JRSI Jack Resync Indicator
KPM Coded Car Call Entry Car Station In Keypad Mode
LWPI Load Weigher - Percent Indicator
MAINJ Main Floor Fire Service Jewel
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
1006 The hoistway interlock failed to close.
• A blocked hoistway door.
The safety string opened during a run & caused an emer-
1007 • An open device in the safety string. Clipped interlock
gency stop.
The motor contactor is already energized (MCD/MCE) - A run
• Software activation error. MUTS signal wiring.
1008 initiation was issued, but either MCD was already inactive, or
• Defective relays/contactors for across the line starting..
MCE was already active.
• A valve contact error (MCD is open). • Valve monitor input shows active at wrong time - output wir-
• A Down run failure. ing, solenoid, IOF Card.
1009
• Either the valves or MC are not ready. • MUTS signal wiring.
• MCD is inactive, or MCE is active during a Down run. • Defective relays/contactors for across the line starting.
• Defective MCD input.
• Motor contactor error (MCD Open).
• Defective MCE input.
1010 • MCD failed to energize or MCE failed to de-energize after
• Defective MC contact. MUTS signal wiring.
run.
• Defective relays/contactors for across the line starting.
Possible Causes:
• A defective MCD/MCE input.
• The motor contactor failed to energize (MCD/MCE).
• A defective MC1/MC2 auxiliary contact.
1011 • MCD is active, or MCE is inactive after a run.
• A defective MCF input.
• Motor Contactor Fault (MCF) input is activated.
• MUTS input.
• A UTS output from EMS. EMS parameter is not correct.
1012 Job image error - Invalid number of floors. —
NV hardware failure - The software issued a command to
1013 modify non-volatile memory that was not completed, or com- —
pleted with invalid results.
Possible Causes:
• Memory error.
NV checksum error - The data in non-volatile memory was
1014 • Bad/low CPU battery.
lost.
Possible Solution:.
• Issue a GET Command followed by a WRT Command.
Software error - The software is making an invalid NV
1015 —
request.
Software error - The NV is full and cannot hold another client
1016 structure. There is no more room for data in non-volatile —
memory.
Software error - A change in run type occurred during a run.
1017 The car is not performing an emergency stop and the soft- —
ware has changed the type of run.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
• A defective hoistway scan.
• A defective CPU.
Floor tables of the encoder counts are not set up when
• A defective CPU battery.
attempting an auto run. When the elevator is not on inspec-
1056 • Loose battery connections.
tion operation, and the level reference in non-volatile mem-
• An improper power unit setup.
ory for any floor is invalid.
• Improper selector signals.
• Verify the Position and/or Motion adjustments.
The encoder is out of tolerance at the floor level - The car is
at floor level, and the encoder position count is different than
1057 • A defective encoder.
the floor position count by more than the value in adjustment
P20.
Selector position wrong at limit of travel - The car is at the
bottom or top of its travel limit and the selector has deter-
1058 —
mined that the closest floor is not the corresponding bottom
or top floor.
Bad encoder re-calibration - Two consecutive encoder re-cal-
ibrations were out of range. The encoder reported a count
1059 • A defective encoder.
(while at two consecutive floors) that was different from each
floor position count by more than adjustment P20.
• Other system fault interrupted the setup.
The selector setup was not completed - The selector setup
1060 • A defective CPU.
either failed or was terminated before completion.
• A defective selector
Selector setup position count table error - The setup has • A defective selector.
1061 determined that a value for a floor was invalid, and the setup • Wrong number of floors in the job image.
is invalidated. • Wrong job image.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
specified.
Bad initialization of non-volatile memory - This fault can
occur if a new section of non-volatile memory is allocated by • Memory is temporarily unavailable - Reset the CPU.
software, but the memory was not available at that time. • A software error.
1081
Note: This fault can also occur when updating software or • Corrupted memory: load (generic and job image) software.
performing an INIT or INIT ALL. The Remote FAST (if open) • A bad CPU Card.
will display which section of non-volatile memory failed.
Bad save to non-volatile memory - This fault can occur if a
• Memory is temporarily unavailable - Reset the CPU.
save to non-volatile memory is attempted by software but the
• A software error.
1082 memory was not available at that time.
• Corrupted memory: load (generic and job image) software.
Note: The Remote FAST (if open) will display which section of
• A bad CPU Card.
non-volatile memory failed.
Bad recall of non-volatile memory - This fault can occur if: • Memory was temporarily unavailable - Reset the CPU.
• A recall from non-volatile memory is attempted by soft- • A job image error - Check for incorrect TAG sizes through
ware, but the memory was not available at that time, or the WRT Command.
1083 • If a memory segment is set to an invalid size, or • A job image error - Check for variables set incorrectly
• If a variable is set out of its valid range. The Remote FAST through the GET Command.
(if open) will display which section of non-volatile memory • Corrupted memory: load (generic and job image) software.
failed. • A bad CPU Card.
• For car nodes - Use the DCN Command to determine the CN
node ID (first failed node displays).
• Check all wiring and connections at the failing node.
• Invalid configuration - See the DCN Command and verify
1085 An SPI error has been detected on an CAN node.
that the port numbers are correct.
• Issue the TECC Command to make sure all of the nodes are
configured.
• A bad CN expansion or expansion card cable.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
have. • A defective left dynamic sensor.
The right dynamic jack sensor did not activate when it should • Improper left dynamic sensor installation.
1121
have. • A defective left dynamic sensor.
The car was already in slowdown when the dynamic jack
• Improper left dynamic sensor installation.
resynch sensors were activated.
1122 • A defective left dynamic sensor.
Note: Dynamic sensors should activate 12 inches before the
• The slowdown distance is too long.
slowdown point.·
1123 Up Run stalled. • Z44 value exceeded.
1124 Car top inspection Node B CAN communication is offline. —
1129 SEL Node A/B data mismatch. —
• Noise.
1130 Car top inspection Nodes A/B Data mismatch.
• DPIA Card.
1133 SEL Node A reported a duplicate node. —
1134 SEL Node B reported a duplicate node. —
1135 Car top inspection Node A reported a duplicate node. • DPIA not configured.
1136 Car top inspection Node B reported a duplicate node. • DPIA not configured.
1141 SEL Node A data error. —
1142 SEL Node B data error. —
• DPIA Card.
1143 Car top inspection Node A data error. • Car CAN issue.
• Noise.
• DPIA Card.
1144 Car top inspection Node B data error. • Car CAN issue.
• Noise.
• Check the selector.
Up Run stalled due to a command to Run Up, but no encoder
1150 • Z44 too short.
pulses were detected with Z44.
• Car not moving.
1151 SEL Node A SPI Loop Error. —
1152 SEL Node A CAN communication is offline. —
1153 SEL Node B CAN communication is offline. —
• DPIA Card.
1154 Car Top Inspection Node A CAN communication is offline. • Car CAN issue.
• Noise.
1155 DZ Node A CAN communication is offline. —
1156 DZ Node B CAN communication is offline. —
1157 DZ Node A/B data mismatch. —
1158 DZ Node A reported a duplicate node. —
1159 DZ Node B reported a duplicate node. —
1160 DZ Node A data error. —
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
not in the door zone - The safety string opens, stopping all Check all connections and verify no added relays to sole-
car motion. noid outputs. Should this continue to happen, replace the
IOF Card.
• Remove the jumpers to restore operation.
FPGA detected programming jumpers active - When IOF Card • Cycle operation to inspection and back to automatic. This
jumpers JP2 or JP3 are placed in the 1-2 position to allow fault indicates a timing issue with hardware on the IOF Card.
1538
CPU programming of the FPGA's, this fault registers and the Check all connections and verify no added relays to sole-
safety string opens. noid outputs. Should this continue to happen, replace the
IOF Card.
Safety processor system detected ambient temperature out
of range - The ambient temperature sensor on the IOx has
• Resets when the detected temperature returns to the
1539 reported the controller temperature to be outside the accept-
acceptable range.
able range for continued operation (5°F to 167°F, or -15 °C to
75 °C). The safety string opens, stopping all car motion.
1540 FPGA has opened the safety string via the SAFCPU output. • Check other existing associated fault codes.
Motor starter monitor fault - The IO for starter control has
• Use the TFR Command to reset.
1541 been detected in an invalid state. Either MCC1/MCC1M or
• Cycle operation to inspection and back to automatic.
MCC2/MCC2M are in unequal states.
1685 Invalid CN version. • Update CN software or replace the CN Card.
Possible Cause:
• CN/HN has a safety critical I/O, and it did not respond to the
1687 CN No Poll Response - The inputs are cleared. controller’s request. All I/Os on that node are cleared.
Possible Solution:
• Check power and communication to that node.
Possible Cause:
1689 Maximum Safety Nodes Exceeded - The car was shutdown. • The job configuration has too many CN ports with safety I/
Os on it.
Invalid CN Configuration - The job configuration has an
1690 —
invalid CN configuration.
1691 Invalid message ID on Channel 1. —
1692 Invalid message ID on Channel 2. —
1693 Invalid message ID on Channel 3. —
1705 End of run test failed circuits. —
Rear selector vane set but I/O not present - P12>0, but is
1707 —
missing the rear selector input.
• Reload generic and job image.
1726 Thread non-responsive.
• Replace CPU.
• Check power supply for proper current rating.
1850 Power disturbance detected on P24 volt power supply.
• Check grounds, etc.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
Revert from hoistway access operation to automatic detected - • Voltage present on outputs with no demand means
2705 The SP detected Up or Down solenoids active while on hoistway failed IOF Card output device(s).
access operation without hoistway access run inputs.
Revert from machine room inspection to automatic detected -
2706 The SP detected Up or Down solenoids active while on machine
room inspection without machine room inspection run inputs.
• Check the car top inspection inputs.
2707 During car top inspection an invalid I/O was detected. • Check the car CAN channel.
• Check the DPIA.
• Check the car door bypass switch.
2708 During bypass operation an invalid I/O was detected.
• Check the hoistway door bypass switch.
• Check the hoistway access inputs.
2709 During hoistway access operation an invalid I/O was detected. • Check the car CAN channel.
• Check the DPIA.
• Check the machine room inspection switch.
2710 During machine room inspection, an invalid I/O was detected.
• Check the machine room inspection buttons.
Bottom limit override crosscheck failure - The SP detected that • Check BLO.
2711
BLO and BLOM are in the same state. • Check BLOM.
The test outputs were not commanded within three (3) auto- • Reload the generic and job software.
2712
matic runs. • Replace the CPU Card.
• Check Real Time Motion > Show Faults
2713 Safety string output test failure. • Check all wiring/connections to the IOF Card.
• Replace the IOF Card.
• IOF Card device failure - Try RFL, TFR, and cycle INSP to
2714 CHKHA crosscheck failure.
reset. If it returns or is chronic, replace the IOF Card.
• Check the car CAN channel.
2715 TSMC data message was not received.
• Check TSMC.
• Check the car CAN channel.
2716 Car top data message was not received.
• Check the DPIA.
2717 Top hoistway access data message was not received. • Check the hall CAN channel
2718 Bottom hoistway access data message was not received. • Check the HN Board
• Check Car CAN loading, connections, and cable routing.
2719 A corrupted TSMC Node A CAN message was received.
• Replace the TSM Card.
• Check Car CAN loading, connections, and cable routing.
2720 A corrupted TSMC Node B CAN message was received.
• Replace the TSM Card.
• Check Car CAN loading, connections, and cable routing.
2721 A corrupted car top CAN message was received.
• Replace the DPIA Card.
2722 A corrupted top hoistway access CAN message was received. —
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
DIAGNOSTICS
• RFL, RRF.
2806 A FAST solenoid output test failure. • Use a meter to check the UFSM input during an Auto Up run. If no VAC,
then use job diagrams to troubleshoot the output voltage supply.
• Issue an FLT command.
2807 A safety string output test failure. • Check all wiring/connections to the IOF Card.
• Replace the IOF Card.
• Check the car CAN channel.
2808 TSMC data message Node A was not received.
• Check the TSMC.
A corrupted TSMC Node A CAN message was • Check the Car CAN loading, the connections, and the cable routing.
2809
received. • Replace the TSM Card.
A corrupted TSMC Node B CAN message was • Check the Car CAN loading, the connections, and the cable routing.
2810
received. • Replace the TSM Card.
A corrupted main CPU CAN message was • Noise on Car CAN channel or failing communication chip on CPU.
2811
received • Check the Car CAN loading, the connections, and the cable routing.
2812 A duplicate TSMC Node A was detected. —
• Check Car CAN channel loading, cable routing, shielding, & connec-
2813 A car CAN channel bus Off failure.
tions.
2814 A programming jumper was enabled. —
A/C peak reference timeout - The NP lost A/C
2815 • Failed device on the IOF Card.
power, so the A/C inputs cannot be sampled.
2816 A duplicate TSMC Node B was detected. —
A TSMC data message Node B was not • Check the car CAN channel.
2817
received. • Check the TSMC.
A TSMC Node A and Node B data
2818 —
mismatched.
2819 NP failed to configure the IOF FPGA. • Perform SPC again. If a persistent fault, replace the IOF Card.
2820 Bottom limit override and running fast. • Check DFS output and solenoid wiring.
• Failing input/output on IOF Card - Try RFL, TFR, & cycle INSP to reset.
2821 TSRCPM went false during fast valve test.
• Verify that the valve solenoid wiring matches the wiring diagrams.
TSRCPM went false during safety string output • Failing input/output on IOF Card - Try RFL, TFR, & cycle INSP to reset.
2822
test. • Verify that the valve solenoid wiring matches the wiring diagrams.
• Check power to the selector.
2823 Selector message timed out at power ON. • Check the Car CAN channel.
• Replace the TSMC.
• Noise on Car CAN channel or failing communication chip on TSMC.
2824 Selector Node A corrupted version message.
• Check Car CAN loading, connections, and cable routing.
• Noise on Car CAN channel or failing communication chip on CPU.
2825 Selector Node B corrupted version message.
• Check Car CAN loading, connections, and cable routing.
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
WPT Diagnostics
WPT Tool
Fault Codes Label Description
3402/3702 PS Parameter set error
3403/3703 EE EEPROM writing or reading fault
3404/3704 OC Overcurrent
3405/3705 RS Faulty reference switch
3406/3706 IE Internal software fault
3407/3707 AP Fault by position counter, door width > 3.5m
3408/3708 TS Faulty temperature sensor
3409/3709 NE Encoder not connected
3410/3710 CF Closing force potentiometer defect
3411/3711 ME Fault by motor or encoder
3412/3712 SS Standstill fault, door is blocked
3413/3713 TH Temperature of the electronic or motor too high
3414/3714 FE Set during manual change of coupler movement parameter
3415/3715 ES Fault by encoder, signals out of limits
3416/3716 PI Position input (ABSPOS) Invalid
3418/3718 BE Electrical error during rotor angle detection, no current is flowing (motor not connected)
3419/3719 BM Mechanical error during rotor angle detection; door stalled wrong rotation direction; press LEARN
3450/3750 -- Software timing error --- only IE is set
3451/3751 -- Wrong interrupt warning --- only IE is set
3452/3752 -- Stack size error --- only new software start-up
3453/3753 -- SCI send error --- only ICE
3454/3754 -- Software-watchdog failed --- only new software start-up
3455/3755 -- Flash cannot be read
3456/3756 -- Flash checksum wrong
3457/3757 -- Illegal state-machine state
3458/3758 -- EEPROM protection error
3459/3759 -- RAM protection error
3464/3764 -- Learn bits protection error
3465/3765 -- mfu.flag.dc_mode bit protection error
3466/3766 -- Learn bits protection error
3480/3780 -- Unknown reset source detected
3481/3781 -- Illegal address reset detected
3482/3782 -- Watchdog reset detected
3483/3783 -- Closing over-speed detected
3490/3790 -- Current offset measurement failed
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
Contents
Controller CAN System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Configure the CAN Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
CAN Node Address Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
CAN Channel Resistive Loading Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Car CAN Channel 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Hall CAN Channel 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Group CAN Channel Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
CAN Channel Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Correct an Offline CAN Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Ping a CN Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Troubleshooting I/O Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
I/O Reference Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Selector I/O Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
CE MicroComm Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Motor Data for Siemens Electronic Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
Transformer Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
On-Card Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
IOF Card (6300AHV001) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
IOF - LED Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
IOF - Shunt Jumper Definitions/Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
IOF - CON Jumper Definitions/Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
IOF - Push Buttons and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
IOF Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
IOF Connectors/Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
CPUC Card (6300AHT001) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
CPUC - LED Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
CPUC - Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
CPUC Shunt Jumper Definitions and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
CPUC Power Supply Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
CPUC Switch Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
CAN Node - LED Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
CAN Node Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
LHV Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
L24/LHV/S24-1/S24-2 Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
CAN Selector LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
This page
intentionally
left blank.
(Local I/O)
CCH/CCL
RCH/RCL
SPI Bus
IOF
Discrete Interface
Hoistway Access
Inputs, Valve, Starter,
Viscosity Sensor, IOF
Pressure Switch,
18 Spare Active
Low I/O
TROUBLESHOOTING
To other controllers Group CAN Bus
in the same group. RCH/RCL CCH/CCL
Group CAN Segment
CE
DPIA MicroComm
Card
Located in the Car
1. Have some paper and pen/pencil ready to record node information for future use.
BLOCK SELECT
ADJUSTMENTS
ADJUST MENU
COMMANDS STARTUP
6. CN Node = 0 displays. Press UP or DOWN to select the proper CAN Node ID, and
press ENTER.
CN Node=0
UP:+ DN:—
TROUBLESHOOTING
communicate: 2 = Car, 3 = Hall
V: Software version
uP18Fxxxx microprocessor version for that node
SP: # of shared ports
TP: # of total ports assigned to the node
Bottom Line Display
Port assignments for ports 0 (zero) through 15 = the numbers
represent the port number of the I/O map the port is to use, and all
unused ports for a node receive a port assignment of 255.
CNA Cards always have 12 total ports assigned to them.
ICON32 Controllers always have MODCTRL1 on CH:2 as node 0 (zero). Additional
nodes are optional per job requirements.
9. Press ESC.
11. Verify the addressing jumpers for any CAN Node Card used in the system. See
Table 1 on page 4-6.
A CAN Node may be CN, CNA, or any future CAN Node Card.The jumper
assignments are the same.
19. Check resistance between HC1H and HC1L on the IOF (60 ohms +/-3 ohms is typical).
• If the resistance is correct, continue this procedure.
• If the resistance is not correct, go to go to CAN Channel Resistive Loading Verifica-
tion on page 4-7.
20. Restore power to any controllers previously de-energized.
21. Issue a TECC Command.
Block Select Adjustments > Commands Startup > TECC.
22. Issue a DCN Command.
Block Select Adjustments > Commands Startup > DCN.
23. Verify that all nodes with SmartName previously recorded from step 8 on page 4-5 are
reported as being ONLINE:1.
1. Position the car so that there is access to the operating panels, and verify that
the controller is de-energized.
3. In the COP, verify that a 121 ohm axial leaded resistor is installed across the CCH
and CCL rail terminals.
TROUBLESHOOTING
4. In the controller, verify that the CPUC Card jumpers CCC and CCT are ON. See
Figure 1.
5. In the controller, verify that R120 on the MODCTRL1 CNA Card is not installed.
The CNA Card is located on the center divider panel.
6. For cars with more than one CNA assigned to the Car CAN Channel:
a. Verify that the nodes are connected in parallel (daisy-chained).
b. Verify that none of the CNA Cards have R120 populated.
CPUC CARD
JUMPER CCC=ON
CNA CARD
JUMPER CCT=ON
R120 Node
7. On the freight door interface box (or other interface box types):
a. Remove R20 and R21 from the CN Card.
b. Remove R120 from the CNA Card.
Not all freight door interface boxes use CAN node direct interfacing, some use relays con-
trolled from I/O’s located in other components of the control system.
8. With all nodes connected (and power off), measure resistance from any node in the
system between CCH and CCL to confirm the resistive load is 60 ohms +/- 3 ohms.
Perform this procedure if a Hall CAN channel is used each time a new controller is started
up, including grouping the new controller to an already running controller.
1. Turn OFF, Lockout, and Tagout the mainline disconnect for all controllers in the group.
b. CN Card.
• R20 and R21 installed.
• JP11 = 1-2.
• JP12 = 1-2.
c. CNA Card.
• R120 installed.
HC1H/HC1L cross-connects on CON40 of the IOF Card should be installed and cross-wired
to properly verify loading for the whole group.
3. Measure the following resistances to confirm the resistive load is 60 ohms +/- 3 ohms.
a. The IOF Card between HC1H and HC1L.
b. The lobby panel interface box (or other interface box node) between HC1H and
HC1L.
6. Verify that all previously recorded nodes with SmartNames are reported as
ONLINE:1.
TROUBLESHOOTING
Figure 2 - Hall CAN Termination
Connect either Ethernet or RCH/RCL for group communications, but not both.
3. Leave the RCH/RCL wires disconnected; if left unplugged, then CON40 with
other cross-connects would be unplugged from the controller until needed.
1. Cross-connect RCH/RCL between all cars in group. See Figure 3 on page 4-10.
2. Enable the terminating resistor on the CPUC for the controllers on each end of
the cross-connect.
» Install RCT and RCC.
3. Disable the terminating resistor on all other CPUC Cards of the remaining
(intermediate) controllers in the group.
» Remove RCT and RCC.
CON40 CON40 Jumpers RCC & CON40 Jumpers RCC & CON40
Jumpers RCC & Jumpers RCC &
RCT INSTALLED RCT REMOVED RCT REMOVED
CPUC CPUC CPUC CPUC RCT INSTALLED
Hall CAN Link (HC1H/HC1L), only required when there is a node present on CH3
Indication Problem Verification
Resistance reads ~60 ohms. N/A N/A
Verify the correct jumper and resistor
HC1H to Resistance does not read ~60 Termination jumpers and resistors
settings on CPUA and all termination
HC1L ohms. are set incorrectly.
points on the HC1 Link.
Wires crossed, wrong value for
Resistance is not a divisor of 120
termination resistors, or shorts to Verify and correct.
ohms.
other circuits.
Indication Problem Verification
Resistance reads Open Circuit. N/A N/A
HC1H or
Resistance = measurement A short between SHHC1 and HC1H
HC1L Verify and correct.
between HC1H and HC1L. or HC1L.
to SHHC1
Resistance is not the value mea-
Shorts to other circuits. Verify and correct.
sured between HC1H and HC1L.
1. Before performing this procedure, verify the following: The CAN nodes and status
will display either a
a. THY02 Card: SW1-3 = ON. 1 = online
or a
b. Every CAN Node JP14 =1-2. 0 = offline
right side of the node name.
2. Cycle power to the system (if it was necessary
to correct a jumper position).
Process Does the node status
Complete indicate 0 = offline?
IF NO
IF YES
TROUBLESHOOTING
3. Verify the node status.
IF YES
Locate the node and
confirm that the node
has power and that
the fuses are good.
IF YES
Replace the node.
2. Press UP or DOWN to select the proper CN Node number, press ENTER, and Ping a
Port? displays.
3. Press UP, and then press UP or DOWN to select the port of interest.
4. Press ENTER, and the selected CN Card displays. The ping information scrolls across
the display. See Figure 4.
DCN –Display Stats CN:n NodeName----Online:n Pcks:n Ch:n v:n uPLPC23xxSP:n TP:n
Up: Next DN: Prev Ports: n, n+1, n+2, 255, n+4 ...
TROUBLESHOOTING
See Selector I/O Troubleshooting Section
16
17 00000101 INCTM INCTU INCTD INCTU2 INCTD2 INCT INHA INHAM
• SAFE, CDCF, CDCR, CST and all interlock inputs (port 3) must be active with no
critical controller faults in order for SAFSPM, SAFCPU, SAFCPM, and TSRCPU to
be active.
• Any optional I/O present in the job software must be in the indicated state for the
Correct I/O Pattern column.
• MCC2, MCC2M = Only seen on jobs with electronic or Wye-Delta starting.
• MUTS, MCF = Only seen on jobs with electronic starting.
• MCE, MCD = Only seen on jobs with across-the-line (1 contactor) starting.
• PRSW = Only seen on jobs equipped with a low pressure switch.
• OLTS, OLTO = Only seen on jobs equipped with viscosity control thermostats.
• INHA, INHAM = Only seen on jobs with hoistway access.
• Bit Patterns provided are for jobs with electronic starting and hoistway access.
• I/O locations marked with an X are either unassigned or have a signal assigned
whose status is unimportant at this point. If required, see job’s Car I/O Assign-
ment Sheet.
2. If Ports 1 - 10 all display zeros, both the Safety Processor and the NTSD Processor
have mismatched I/O with the CPU.
a. Check the F1 pico fuse on the IOF Card.
b. Reload the controller generic files and the job configuration files. See Upload Soft-
ware to CPU Cards on page 6-36.
c. Configure the Safety Processor. See page 2-8.
d. From Startup Wizard, scroll to Clear HN Config? > Config HN/CN > Verify All CN's.
3. If the SP and NP I/O mismatch faults still exist, then communication is faulty between
the IOF and the CPUC. Replace the IOF or CPUC Cards.
• LVUR*, LVDR*,DZ1R*, DZ2R* are only used for close floors—for that close floor,
activate these I/Os instead of LVU, LVD, DZ1, DZ2.
• The I/O states for Bits 5-8 are a copy of the first four bits shown in Port 15 at a close
landing; requires P12=1.
Troubleshooting Guide
Problem and
Possible Solutions
Possible Causes
Car will not move from 1. Check EPNP. It should be active for normal power. Can prevent Up runs depending on E10
Car Top Inspection value.
Operation with I/O & 2. Check PRSW. It should be active for normal conditions, and will prevent Down runs.
safety string checkout 3. Check OLTO. It should be active for normal conditions, and will prevent UP runs.
performed • 1074 fault is issued for inactive PRSW input.
• 1019 fault is issued after a run attempt with OLTO inactive.
4. Verify that the appropriate INCTx inputs activate from the inspection button activation.
5. Troubleshoot the inspection station wiring per the job prints.
Safety Processor (SP) • The SP monitors the safety critical inputs of the elevator system using safety nodes.
bad LED • The SP monitors inputs for these functions: Door State, Door Bypassing, Inspection Opera-
tion (including Hoistway Access), Terminal Speed Reduction, and Speed Limit Enforcement.
• All of these except Terminal Speed Reduction are also monitored by the CPU and the PLD.
• In the event a safety node fails, loses communication, or reports an I/O state that disagrees
with another monitoring subsystem, the SP BAD illuminates and faults are logged.
• It is normal for the SP to remove power to the safety string without logging any faults for
TROUBLESHOOTING
conditions that are considered normal operation.
Example: IF/IR/IT/IB and no DCL = An open car door, SP inhibits a run until door is closed
(or bypassed).
Safety Processor not 1. Configure the Safety Processor.
configured for the job 2. Clear the faults by navigating to the Real Time Motion screen.
a. Press ENTER, and then press ENTER a second time.
b. Press UP and DN until Reset Faults appears in the display window.
c. Press ENTER.
d. Press UP until Show Faults appears in the display window.
e. Determine if the controller has issued any faults.
Pay specific attention to the 27xx fault series, as they are Safety Processor Faults. To cor-
rect these faults, see the Diagnostics section.
3. Disconnect IOF CON1, CON11, CON12, and CON40 (if anything is wired to them).
a. Is the SP Good LED illuminated?
b. Check and troubleshoot the recorded faults for hoistway access related I/O issues.
How to locate the Use the job prints or the text files.
I/O of Interest 1. Use the System Port Assignment from the text file or Port/Bit location from job prints.
2. Access Quick Commands > Show I/O? to monitor the I/O.
(Block Select Real Time Motion > ENTER > ENTER > Show I/O?).
3. Press UP or DOWN to select the port of interest. The display will show two ports at the same
time. Each row will show: Bit Assignment #, Assigned I/O name followed by the present
state of all eight bits for the port. The bit order is 1-8, left to right on the display.
Row 1: 1 INCN 01000101
Row 2: 1 BYCST 00000000
• This I/O display is in metered logic.
• This I/O display is "live" and changes when the input changes.
4. Press ENTER to cycle through each bit's I/O name.
5. Press UP or DN to scroll to different ports.
6. Press ESC to exit Quick Commands.
Problem and
Possible Solutions
Possible Causes (cont.)
The CAN node failed 1. Verify the node LEDs: PWR is ON steady, and STAT is flashing slow.
verification. Most likely 2. Verify the jumper positions. See CAN Node Address Assignment on page 4-4.
the "In Mask" or "Call • If the address jumpers are correct, see Configure the CAN Nodes on page 4-4.
Mask" has an error JP14 = position 1-2.
caused by unstable JP8 = OFF.
communications during • If jumpers were corrected, press RST.
the configure process. 3. Verify that CE MicroComm Card (THY-02) SW1 position 3, is in the ON position.
4. With power removed from the controller, verify 60 ohms +/-3 ohms between CCH/CCL. See
the CAN Channel Troubleshooting Guide (if needed).
5. Use the DCN command to ensure that the associated node reports as online
6. Issue a TECCR Command (Block Select Startup Wizard > Clear CN Config).
7. Issue a TECC Command (Block Select Startup Wizard > Config CN).
Jack will not resync 1. Verify if BLO is populated in the I/O map, port 8 bit 2. If not, contact ITS Field Engineering.
2. The following are also required for jobs which have a bottom final limit: BLOM and CHKBLO
inputs and a BLO relay.
3. Issue a WJR Command. See when and why the last resync happened.
4. Issue a FJR Command. The car should immediately perform a jack resync.
5. To change the frequency of jack resync, check and adjust the following parameters: O29,
O30, O31, O32, and O44.
Hoistway access not Hoistway Access inputs are not checked for conflicts until Hoistway Access is enabled.
functioning 1. Verify these adjustments are set per job conditions: Z38, Z39, O21, O11, and O22.
2. Use job prints to troubleshoot hardware/wiring issues related to Hoistway Access switches.
SP/NP/PLD not online 1. Disconnect all CAN channels from the IOF Card.
2. Use VER or Status to check reported software versions for each processor.
3. If still v0r0, then if all are v0r0, replace the CPU.
4. If any one processor (SP/NP/PLD) reports a version/revision, replace the IOF Card.
Controller stuck on The IOF has two inputs, and both inputs have to indicate that Normal Power or Emergency
Emergency Power Power Operation are activated.
Operation IOF CON18, pin 1 has 120 VAC for normal power.
IOE CON39, pin 6 has zero VDC for normal power.
• Connection issue between trades and CON39 of IOF Card.
• Bad generator contact for EPNP.
• If voltages are correct at the IOF Car, a failed IOF Card.
CE MicroComm Troubleshooting
TROUBLESHOOTING
If the THY02 Card fails to display and the PIs fail to display the test sequence, the
THY02 Card is most likely the issue.
If PIs have power when the controller's disconnect is turned OFF:
• The CE MicroComm Card and Hoistway Access switches are fed 24VDC from F-P24HF
for grouped controllers having CE PIs.
• Open the fuse holder F-P24HF to remove 24VDC from the PIs and HA switches.
TSP TSP
CAN High CCH BLUE CCH BLUE CANH RED CEPI1
1
IOF
Controller
Traveling
1 (COM)
Cable
2 (VIN)
3 (DATA)
CEPI
Car PI Card
Primary Secondary
Print No. Voltage Connections Configuration Voltage Connections Configuration
874DA1 208 H1 & H2 None 120 X1 – X4 X1—X3, X2—X4
240 H1 & H4 H1 – H3, H2 – H4
874DA2 120 X1 – X4 X1—X3, X2—X4
480 H1 & H4 H2 – H3
874DA3* 240 H1 & H4 H1 – H3, H2 – H4 120 X1 – X4 X1—X3, X2—X4
380 H1 & H2
874DA4* None 120 X1 – X4 X1—X3, X2—X4
400 H1 & H3
416 H1 & H4
874DA5 None 120 X1 – X4 X1—X3, X2—X4
600 H1 & H2
200 H1 & H2
874DA6** None 120 X1 – X4 X1—X3, X2—X4
220 H1 & H3
874DB1 208 H1 & H2 None 120 X1 – X4 X1—X3, X2—X4
240 H1 & H4 H1 – H3, H2 – H4 120 X1 – X4 X1—X3, X2—X4
874DB2
480 H1 & H4 H2 – H3 120 X1 – X4 X1—X3, X2—X4
TROUBLESHOOTING
874DB3 600 H1 & H2 None 120 X1 – X4 X1—X3, X2—X4
200 H1 & H2
874DC1* None 120 X1 – X4 X1—X3, X2—X4
220 H1 & H3
380 H1 & H2
874DC3* 400 H1 & H3 None 120 X1 – X4 X1—X3, X2—X4
415 H1 & H4
208 H1 & H2
874DJ1* 208 H2 & H3 None 120/240 X1 – X4 X1—X3, X2—X4
575 H1 & H4
380 H1 & H2
874DJ2* 400 H3 & H4 None 120/240 X1 – X4 X1—X3, X2—X4
415 H1 & H4
240 H1 & H4
H1 – H3, H2 – H4 X1—X3, X2—X4
874DJ4* 400 H1 & H4 120/240 X1 – X4
H2 – H3 X2 – X3
480 H1 & H4
230 H1 & H4 H1 – H3, H2 – H4
874DK1 120 X1 – X2 None
460 H1 & H4 H2 – H3
230 H1 & H4 H1 – H3, H2 – H4
874DL1 120 X1 – X2 None
460 H1 & H4 H2 – H3
874DL2* 208 H1 & H2 None 120 X1 – X3 None
874DL3* 575 H1 & H4 None 120 X1 – X4 None
874DP1 208 H4 & H4 None 120/240 X1 – X4 X1—X3, X2—X4
200 H1 & H2
874DW1 None 120 X1 – X4 X1—X3, X2—X4
220 H1 & H3
* Used for 50 Hz AND 60 Hz applications.
** Used ONLY for 50 Hz applications.
On-Card Diagnostics
IOF Card (6300AHV001)
NPGOOD PLDGOOD
SPGOOD PLDBAD CPUC Card
JP2 NPBAD JP3 See page 4-24
SPBAD
RSTSP
RSTNP
CLR_FLT
SAFSP
SAFCPU
SAFE
NTSNP
TSRCPU
DOORS
MCC1
MCC2
UFS
USS
DFS
DSS
Controller
Inspection
Hoistway
Door
Bypass
Door
Disconnect
CON47
CON9A CON46 RUN AC P24 P24GS P24G Car
STOP Door
Bypass
TROUBLESHOOTING
OFF door bypass switch use,
or
Car doors are open and the end of a run check is not active (typically not viewable LED
activity due to the speed of that check)
P24 Green ON ON if 24VDC is present at CON20 and fuse F-P24 is good.
ON if 24VDC is present at CON20 and fuses F-P24GS and F-P24G are good (or if 24VDC is
P24G Green ON
fed by another powered-up car in the group via CON21 cross-connections).
P24GS Green N/A Not used.
DFS Green ~ ON if the system is trying to energize the DOWN FAST valve solenoid.
DSS Green ~ ON if the system is trying to energize the DOWN SLOW valve solenoid.
UFS Green ~ ON if the system is trying to energize the UP FAST valve solenoid.
USS Green ~ ON if the system is trying to energize the UP SLOW valve solenoid.
MCC1 Green ON ON if the system is trying to start the pump motor (contactor or electronic starting).
ON if the system is trying to start the pump motor (contactor starting) or provide power to
MCC2 Green ~
the starter (electronic starter).
ON if the CPUC is allowing a complete safety string (SAFCPU output commanded ON). OFF
SAFCPU Green ON
when the CPUC has opened the safety string (SAFCPU output commanded OFF).
ON if safety processor is allowing a complete safety string (SAFSP output commanded ON).
SAFSP Green ON OFF when the safety processor has opened the safety string (SAFSP output commanded
OFF).
SAFE Green ON ON if 120VAC from a complete safety string is present at terminal 131 as seen by the CPUC.
ON if the NTSD processor is allowing a high speed run (NTSNP output commanded ON).
NTSNP Green ON OFF when the NTSD processor is forcing the FAST solenoids off when the selector encoun-
ters a terminal slowdown magnet (NTSNP output commanded OFF).
ON if the CPUC is allowing car movement in a terminal zone (TSRCPU output commanded
ON). OFF when the CPUC is forcing all valve solenoids off when the selector encounters a
TSRCPU Green ON
terminal slowdown magnet and other terminal speed reduction efforts have failed to slow
down the car (NTSNP output commanded OFF).
*Certain system conditions will let the SP or NP open the safety string, have SPGOOD/NPGOOD LEDs illuminated, and have
no faults. Example: Interlock Open (IT,IF, IR, IB, CT, CB, CF, or CR).
IOF Fuses
Current
Fuse Function
Rating
F-EP 0.5AFeeds 120VAC to the EPEN relay coil.
F-PS 3.0AFeeds 120VAC to the controller power supplies.
F-AC1A 6.0AFeeds 120VAC to the car, including door operators and car DC power supply.
F-AC1B 0.5AFeeds 120VAC to the hoistway door interlock circuits.
F-AC1SC 3.0AFeeds 120VAC to the safety circuit, including Triac outputs.
F-P24 4.0AFeeds 24VDC lower voltage supplies and all 24V I/O in the controller.
Feeds 24VDC to the hall risers wired to this controller.
F-P24G Variable
Variable based on power requirements of risers connected to this controller.
F-P24GS N/A Not Used.
Feeds 120VAC from the T1 transformer X1 tap (CON16-1) to the source voltage for the EPEN relay
F-AC1 Variable
and contacts (CON18-1) to feed the system AC power (does not fuse UPS output).
F-P24L 1.0A Feeds 24VDC to the CPUC Card.
IOF Connectors/Wiring
SHIELD
SHCC1 SHIELD
To SHCC1
WHT/BLUE SHT/BLUE
Lobby HC1L CON1 HC1L
Panel BLUE/WHT BLUE/WHT
HC1H HC1H
YELLOW To Top HN
CON11 TCH2 Rear Riser
WHT/RED Cross Connect
All Via G24
CE PI (THY02) RED
Rail CON2 P24G
Terminal CNA Cards
SHIELD
SHCC1
P24XC
YEL TOP-SHLD
HC1H
SHCC
SHRC
HC1L
WHT/BLUE
RCH
G24
RCL
SHCC HC1L
YEL TP-WHT BLUE/WHT
CCL HC1H
CON3
YEL TP-RED CCH YELLOW To Top HN
CON40
CON12 TCH2 Front Riser
YEL (8) G24 WHT/RED
G24
YEL (7) RED
204 P24G
YEL (6) AC1B
TRAV 202 HWA Bottom Door
YEL (5) Closed Contact
Cable
TROUBLESHOOTING
121 3H2
YEL (4) CON4 AC1B
CST HWA Top Door Freight Door
YEL (3) Closed Contact Application Only
115 3H5
CON13
YEL (2) AC1B
AC2 Non-HWA Front Door
Closed Contacts
YEL (1) 316
AC1A
BLK AC1B
AC1B Non-HWA Rear Door
HWA Bottom * Closed Contacts
Interlock WHT/BLK 326
2H2
BLK G24
HWA Top * AC1B
WHT/BLK P24
Interlock
2H5 TPSL
TAN CON5
AC1B TPDL CON14
Non-HWA Front*
Interlocks WHT/TAN G24
216 P24
GRAY
AC1B TPSR
Non-HWA Rear*
Interlocks WHT/GRAY TPDR
226
MR Safety * 102
Circuit (opt.)
107 CON6 Runbug Remove With Runbug
BLUE
HWY Safety
107
Circuit WHT/BLUE CON9A
115
ON
OFF
STAT CPU Status Red
LED flashes continuously at 100ms
0 sec. 1 sec. 2 sec. rate if no job file is loaded to flash or
ON
a bad reload of data to flash has
OFF occurred.
TROUBLESHOOTING
LNK Ethernet Link Green not in reset, FPGA is configured, and
Watchdog has not timed out.
RX Ethernet Receive Green Varies depending on activity Ethernet Status - Link Good
LED flashes while Ethernet Link is
TX Ethernet Transmit Green Varies depending on activity
receiving.
LED flashes during activity on the
USBD USB Device Green Varies depending on activity
USB device port.
CHKSTOP ~ Green Varies depending on activity Manufacturing use.
CPUC - Connectors
Connector Name Function
CON1 IOF InterfaceInterface connector to IOF Card
CON4 485 Currently not used
Standard RJ45 connector and MDI pin out, used for Inter-Group communication instead
CON5 Ethernet
of CAN (RCH/RCL)
CON6 USB Host Standard USB Type A connector, used for loading software to the CPUC Card
CON7 UIT User Interface Tool connector
CON8 USB Device Standard USB Type B connector, used for connecting Owner’s IMS via a PC’s USB port
CON11 RS232 D-Shell Standard RS232 9 pin D-Shell for connecting Owner’s IMS via a PC’s serial port
TROUBLESHOOTING
CAN Card Node (Channel 3) 1 to 2 Normal operation.
Group Addressing JP14 1 to 2
2 to 3 Programming uploading software.
Note: This data not currently used.
JP3 JP2 JP1 JP8
CAR 1 OFF OFF OFF ON
CAR 2 OFF OFF ON ON
CAR 3 OFF ON OFF ON
CAR 4 OFF ON ON ON
CAR 5 ON OFF OFF ON
CAR 6 ON OFF ON ON
CAR 7 ON ON OFF ON
CAR 8 ON ON ON ON
COMMON CAN* OFF OFF OFF OFF
*These jumpers should remain OFF for
typical CAN applications.
CAN Jumpers
(continued)
485 Serial PI
P24/G24 Input
CAN Communication
LHV Jumpers
L24/LHV/S24-1/S24-2 Cards
IN
OUT
K8 = Output #8
K7 = Output #7 CON1 CON2 Pin 1-8 = I/O 1-8
Pin 9 = G24
K6 = Output #6 Pin 10 = P24
K5 = Output #5
CON3
K4 = Output #4 (On-Card I/O Port)
K3 = Output #3
K2 = Output #2
K1 = Output #1
TROUBLESHOOTING
S24-1 Card S24-2 Card
6300VC1 6300VL1
CON2 CON1 CON2 CON1
OUT Port IN Port OUT Port IN Port
Pin 1 = P24
24VDC CON3B
Pin 2 = I/O
POWER Pin 1 = I/O5
Pin 3 = CCIE
CON11 & LED1 Pin 2 = I/O6
Pin 4 = G24
CON12 Pin 3 = I/O7
CCIE Cross
Connections Pin 4 = I/O8
CON3 - CON3 Pin 5 = P24
CON10 Pin 1 = I/O1
Pin 2 = I/O2 CON3A
Pin 3 = I/O3 Pin 1 = I/O1
Pin 4 = I/O4 Pin 2 = I/O2
Pin 5 = I/O5 Pin 3 = I/O3
24VDC POWER LED Pin 6 = I/O6 Pin 4 = I/O4
Pin 7 = I/O7 Pin 5 = P24
Pin 8 = I/O8
TROUBLESHOOTING
This page
intentionally
left blank.
Contents
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Controller Assembly (2102BB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Power Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Controller Assembly (2102BB) - Replacement Parts List . . . . . . . . . . . . . . . . . . . . . . 5-6
Freight Door Cabinet Assembly (2104AF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Manual Freight Door Cabinet Assembly (2104BL) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Fire Service Cabinet (2104AE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Selector Assembly (2105AG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Replacement Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Cards and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Replacement Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
Controller User Interface Tool (UIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
Primary Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
Access the UIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
UIT Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
CAN Node Configuration via the Startup Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
CAN Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Command Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Card Changing Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
Door Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
CAN Node Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
L24, S24-1, S24-2, LHV, LHV 4x4 Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
TSMC/TSAC Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
IOF Card Changing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
CPU Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Software Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
Software Version Confirmation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
How to Format a USB Flash Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32
USB Flash Drive Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
Backup the Job Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
Upload Software to CPU Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
Upload Software Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-37
Software Updates to Safety Node Devices over CAN . . . . . . . . . . . . . . . . . . . . . . . . 5-37
Configure the Safety Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
This page
intentionally
left blank.
Replacement Parts
Controller Assembly (2102BB)
DPIA Card
Power Panel
Transformer
Starter
SERVICE INFORMATION
Contactor
Power Panels
Electric Motor Starter Din Rail with Ethernet Switch
Terminal Block
CE PI Micro
Comm Card
Transformer
IOD Card
Starter
3 Pole
Contactor
CE PI Micro
Comm Card
Transformer
IOD Card
IEC Contactor
Relay
Power Panels
(continued)
Single Phase
Din Rail with Ethernet Switch
Terminal Block
CE PI Micro
Comm Card
Transformer
IOF Card
IEC Contactor
Capacitor
Motor
Starter
Relay
SERVICE INFORMATION
SERVICE INFORMATION
874DA5 Transformer, PR 600V, SEC 115/115V, .5KVA, 1PH, 60Hz
874DA6 Transformer, PR 200/220V, SEC 115/115V, .5KVA, 1PH, 50Hz Only
Transformers
874DB1 Transformer, PR 208V, SEC 115/115V, .75KVA, 1PH, 60Hz
874DB2 Transformer, PR 240/240V, SEC 115/115V, .750KVA, 1PH, 60Hz
874DB3 Transformer, PR 600V, SEC 115/115V, .750KVA, 1PH, 60Hz
874DC1 Transformer, PR 200/220V, SEC 115/115V, .750KVA, 1PH, 50/60Hz
874DC3 Transformer, PR 380/400/415V, SEC 115/115V, .750KVA, 1PH., 50/60Hz
200BWN001 ICON32 Front Inspection Station
200BWN002 ICON32 Rear Inspection Station
Misc.
200BMR001 Selection Harness Extension
196BMK001 Bracket Assembly, MicroComm Card
6
5
1
7
2
2
11
4
10
15
2
3 21
5
22
23
18
20
19
7 8
SERVICE INFORMATION
(only top bracket shown)
14 9
2, 3
13
4, 5, 6, 7 12
10
11
SERVICE INFORMATION
2 409BR7 Fuse Panel, MDA, 250V, 2A
3 412AN1 Fuse Block, 250V, 1 Position
4 804BC1 TVS RC Contactor, 110-230VAC
5 690CA3 Power Relay, DPDT, 6A, 24VDC
6 558AX2 Extraction Lever Relay
7 770BK1 Socket Relay
8 834BW1 Terminal Block, DIN Rail Clamp
9 834BX1 Terminal Block, DIN Rail, 5.2mm Wide
10 684AD10 DIN Rail, 6 3/4" Long
11 672BW1 Power Supply, 85-132VAC, 24VDC, 2.5A
12 786AX6 PCB Locking Standoff
13 834AN5 Terminal Block, Grounding, 5 Position
14 200CCN001 CNA Freight Door Kit
4 1
6
Tighten thumb
screws just enough
to flatten helical lock
washers on the
thumb screws.
Replacement Sensors
844AA4 - Thermostat,
84" ± 1" "B" Over Temp [170 degree F]
"A"
JACK SENSORS
SERVICE INFORMATION
Fiber Optic Optical Sensor (610AN1)
SERVICE INFORMATION
S24-1 Card (6300VC) S24-2 Card (6300VL)
F_P24GS F_10
F_AC1 F_AC1A F_P24G
F_EP F_AC1SC
F_AC1B F_PS F_P24
SERVICE INFORMATION
Cable Information
PIN 1
White/Green
CAT5 CABLE Green Pair 3
Selector/SPI Loop White/Orange
Blue
Ethernet Cable White/Blue Pair 1 Pair 2
Orange
White/Brown
Brown Pair 4
Top View
CAT5 CABLE
220DK_ RJ45 Connector
Side View
SERVICE INFORMATION
Vertical Express
1 2 3 4
Primary Menus
Block Select Block Select Block Select Block Select Block Select Block Select
Adjustments Real-Time Motion System Clock Startup Wizard Inspector Tests Log-Off UIT?
• Press UP or DOWN to navigate through the menu blocks.
• Press ENTER to go forward.
• Press ESC to go back.
• For a list of the submenus, see the UIT Menu Tree starting on page 5-21.
2. Press any button while Vertical Express is displayed in the UIT window, and enter
the pin number - 1234144. See Figure 1 (above). If the wrong pin number is
entered, continue to press UP until Vertical Express appears in the window, then
enter the pin number again.
Vertical
Express Block Select Block Select Block Select Block Select
Real Time Motion System Clock Startup Wizard Inspector’s Tests
Enter Pin #
ENTER ENTER ENTER ENTER
Motion/Position Time hh:mm:ss Start Wizard? FLT
1 2 3 4 Status Date mm:dd:yy UP = Yes DN = No RFL
UP DN ESC ENTER TFR
Arbiter No
Yes SCCB
Pin: 1234144 Velocity
(if incorrect, press reset) Set the Time? Clear CN Config SCC2-SCCn
Notes: ENTER UP = Yes DN = No SCCT
Config CNs
• Use UP and DN to scroll Set the Date? (Set Car Call Bottom,
QUICK COMMANDS Auto Hoistway Scan
through blocks. UP = Yes DN = No 2,3,.... top in order)
• Press ENTER to select. Show Faults* Write to Flash
• While in block menus, Show Fault Details* Save Job to USB
use UP and DN to navigate. Clear Faults*
• Use ESC to back out. Block Select
Reset Fault List
Logoff UIT?
Front Car Call
Rear Car Call UP = Yes DN = No
UP Hall Call
DN Hall Call
Block Select Show Stable Leveling
Adjustments Show I/O
*only displays if faults are present.
ENTER
ESC
Adjust Car/Group
Commands Common
Commands Upload
SUBMENU SUBMENU SUBMENU SUBMENU SUBMENU
Commands Startup
Adjust Car/Group Commands Commands Commands Commands
Commands Group Common Upload Startup Group
Front Door
Rear Door
Job Parameters (Jxx) CJR UFWCNC DCN GPN
SUBMENUS DSL UFWCNH ELD SCA
Car Information
Code Blue (Cxx) FCP UFWSPF JRT SCAI
SERVICE INFORMATION
FJR UFWSLF PRT SUC
Desination Dispatch
GET OSDMI SCF SDC
Doors (Dxx)
IOView OSDM SPC SRU
Emergency Power (Exx) STUA
IRL UDLS SRD
Fire Service (Fxx) STU
IRLR UDLR SSI
Fixtures (Xxx) TECC
RFL SHL
Homing & Shutdown (Hxx) TECCR
RRF PIG
Incon Riser (Rxx) WRTG
SCC
Motion (Mxx) SFL
Options 1 (Oxx) SFLR
Options 2 (Zxx) SRC
Parking & Zoning (Lxx) TMP
Position System (Pxx) TSR
Security (Sxx) TSRT
Traffic VER
WJR
WRT
CAN Nodes Before using the Startup Wizard, the door operator and safety system nodes must be
installed and completely wired to the cards (CNA, Selector, DPIA, CNs, etc.). When the cor-
rect termination scheme is used, CAN channels 2 (and 3 when required) should measure
60 ohms +/- 3 ohms, with power removed and all connections made.
5. Skip Automatic Hoistway Scan. When Auto Hoistway Scan? displays, press UP.
Command Sequence
To properly configure the CAN Nodes, issue these commands in the order written:
TECCR, TECC.
TECCR The TECCR Command resets all online CAN nodes’ configuration. See Figure 2.
TECCR -
Complete, Now must TECC
this car and car 2.
TECC The TECC Command configures all online CAN nodes. See Figure 3.
CAN resistive loading will affect the configuration. Before issuing a TECC Command,
check the loading for Channel 2 or Channel 3 (if used).
DCN The DCN Command displays the status of all CN Cards, and has the ability to
SERVICE INFORMATION
ping specific ports to verify operation. See Figure 4 on page 5-24.
• The status of the CAN Node Cards located on either Channel 2 or Channel 3.
• Specific CN data:
– Communication status
– Node ID
– Number of ports assigned
– Specific ports assigned
Executing a DCN Command prompts the user to enter specific parameters; the
requested data appears in the UIT window. If a line is scrolling, press UP to pause
the screen, and then press UP to resume scrolling.
Command Sequence
(continued)
DCN – Display Stats CN:n NodeName----Online:n Pcks:n Ch:n v:n uPLPC23xx SP:n TP:n
UP: Next DN: Prev Ports: n, n+1, n+2, 255, n+4
ENTER
CN: CN Node ID (selected).
NodeName : name assigned to the node selected.
Select CN Node CN Node: (0-11) ----Online: online status;
number of interest. Up: + DN: 1 = online, 0 = offline
Pcks : number of data packets received.
ENTER Ch : CAN channel node is assigned;
2 = CCH/CCL, 3 = HC1H/HC1L
v : node software version.
Ping a Port? uPLPC23xx : node hardware version.
Up: Yes DN: No No/
SP : number of Shared Ports assigned the node.
ENTER
TP : number of Total Ports assigned the node.
Ports : lists the control system port number
Yes assigned to the node’s physical I/O port. (255
indicates an unassigned port.) A node card having
CN Node previously 12 ports will have 12 ports listed, only the used
chosen is the CNn Port: (0-16) ports will have a port numbers assigned them.
UP: + DN: -
indicated (CNn).
Select the Port of CN : CN Node selected previously.
interest from Port : Port number selected previously.
chosen CN. ENTER v : node software version.
LPC23xx : node hardware version.
Bit : bit assignment.
CNn Portn v:# LPC23xx IOName : I/O name assigned to bit.
**Bit#, IOName, Data, IO, Call Data : indicates I/O state;
1- inactive, 0 - active.
IO : indicates I/O as input or output;
1 – input, 0 – output.
Call : indicates I/O as a hall/car call;
1 – call, 0 – non-call
3. Note the connector locations, and then remove all connectors from the old card.
4. Note the jumper positions and socketed resistor configurations, and then
remove the old card.
5. Place jumpers and resistor configurations in same positions as on the old card.
SERVICE INFORMATION
cables are correctly marked so they may be correctly reconnected after replacing the
suspected failed card.
3. Note locations, and remove all connectors from the I/O Cards.
TSMC/TSAC Card 1. Position the car to easily access the car top, if possible.
5. Disassemble the selector. See the Selector Assembly (2105AG) on page 5-12.
12. Press UP until Auto Hoistway Scan? appears, and then press ENTER.
2. Insert the manufacturing-supplied USB flash drive into the USB Host Port (CON6 on
the existing CPUC Card). Most USB flash drives may be used, if they are properly for-
matted and have the correct file folder structure. See USB Flash Drive Preparation on
page 5-34.
Transferring software between the CPUC and USB flash drives requires a few
minutes to complete. Resetting the card during this time could result in corrupt-
ing the USB and the CPUC.
3. Issue a UDLS Command.This process will backup image and generic software files
from the CPUC to the USB flash drive.
Controller UIT: Block Select Adjustments > Commands Upload > UDLS.
IOF Card
(continued) 6. Disconnect CON40. This process removes the P24XC feed from other controllers
in the group. See Figure 5 on page 5-28 for the remaining steps in this section.
8. Verify that the P24GS PSM (located on the DIN rail above the IOF) is not
illuminated.
10. Remove the CPUC Card from the plastic standoffs of the IOF Card, and
place the CPUC Card on a static-free surface.
11. Remove the IOF Card from the controller cabinet, and place the IOF Card
on a static-free surface.
1. Transfer the following items from the old card to the new card.
• Plastic Standoffs.
• CON9A.
• Jumpers JP2 and JP3 (in 2-3 positions).
• Any fuses including, but not limited to, F-AC1.
– Use the job prints to verify that all necessary fuses are populated with
the correct size and fuse type.
SERVICE INFORMATION
– F-P24GS on the IOF Card is not used, a PSM is located on the DIN rail
above the IOF Card to supply voltage.
2. Install the CPUC Card onto the IOF Card. Take care not to bend pins that join the
CPUC and the IOF Cards together. The pins are located at CON1, CPUC Card.
4. Replace all connectors except CON40, CON1, CON12, and CON11 on IOF Card.
IOF Card
(continued)
CON11 CON1
CON40 SPGOOD, SPBAD LEDs CON6 on the
Pins that join CPUC
CPUC Card
JP2 Jumper Card to IOF Card
CON12
JP3 Jumper
CON5
WD LED
CPU Replacement
Back Up the Job Software
1. Place the controller on Inspection Operation.
2. Insert the manufacturing-supplied USB flash drive into the USB Host Port (CON6
on the existing CPUC Card). Most USB flash drives may be used, if they are prop-
erly formatted and have the correct file folder structure. See USB Flash Drive
Preparation on page 5-34.
Transferring software between the CPUC and USB flash drives requires a
few minutes to complete. Resetting the card during this time could
result in corrupting the USB and the CPUC.
3. Issue a UDLS Command. This process will backup the generic and job
configuration files to the USB flash drive.
Controller UIT: Block Select Adjustments > Commands Upload > UDLS.
3. Unplug the Ethernet cable (if used) from CON5 of the CPUC Card.
4. Set jumper positions on the replacement CPUC Card to match the faulty CPUC
Card.
5. Confirm that all LEDs on the IOF Card are not illuminated.
6. Carefully uninstall the faulty CPUC Card. Take care not to bend the pins that join
the CPUC to the IOF Card, CON1 of the CPUC Card.
SERVICE INFORMATION
7. Remove the UIT and standoffs from the faulty CPUC Card.
The UIT Card is bound to the specific job configuration (software) for the job. The UIT
Card will not permit the adjustment of any other job.
During replacement:
• Do Not Swap UIT Cards between controllers/CPU Cards.
• Remove the UIT Card from the failed CPUC Card.
9. Carefully install the replacement CPUC Card onto the IOF Card. Before applying
pressure, ensure that CON1 of the CPUC properly aligns with the IOF Card's mat-
ing pins.
CPU Replacement
(continued)
10. For jobs where the Hall CAN channel is being used, remove CON1, CON12, and
CON11 on the IOF Card.
11. Where Ethernet communication is used, leave the Ethernet cable disconnected from
CON5 on the CPUC Card.
12. Use the USB with the job's backup files (from the UDLS earlier), and copy the backup
files into the update folder of drive. See USB Flash Drive Preparation on page 5-34.
14. Install the USB flash drive (used earlier) into CON6 on the CPUC Card.
17. Press and hold UDL until the STAT LED blinks Morse Code `Z' (two long and two short
blinks). When complete, the STAT LED blinks 3 times before CPUC Card resets itself.
If the upload takes longer than 15 minutes, or if the STAT LED blinks every 100ms contin-
uously, the upload has failed. Cycle power to the controller and then remove the USB from
the CPUC Card. See Upload Software Troubleshooting on page 5-37.
18. After the upload is successful, verify that the controller will run from Inspection Oper-
ation. Should the car fail to run, troubleshoot fault codes and I/O states to determine
the issue. See Troubleshooting I/O Issues on page 4-13.
19. Place the door disconnect switch in the Door Disconnect position.
21. Use Quick Commands, and issue car calls to verify Automatic Operation. This action
verifies the hoistway scan. If the car will not run on Automatic Operation, perform a
new hoistway scan.
Block Select Real Time Motion > Quick Commands > Front Car Call/Rear Car Call.
22. Reconnect CON40, CON1, CON11, and CON12 on the IOF Card.
23. Reconnect the Ethernet cable (if used) to CON5 on the CPUC Card.
Software Management
Software Version Confirmation
How to determine which versions of software are running in the control system which
determine how the control system functions.
1. Verify that the Controller Inspection Switch in on INSP.
2. Press any button while Vertical Express is displayed in the UIT window, and
enter the pin number - 1234144. See Figure 6.
If the wrong pin number is entered, continue to press UP until Vertical Express
appears in the display window, then enter the pin number again.
1 2 3 4
SERVICE INFORMATION
a. When BLOCK SELECT ADJUSTMENTS displays, press ENTER.
BLOCK SELECT
ADJUSTMENTS
ADJUST MENU
COMMANDS COMMON
c. Press UP until VER displays, press ENTER, and window displays this data:
v = version Each of the safety nodes have two safety processors. Both
x = version number processors should display the same version of software.
r = revision
y = revision number
This controller contains software that is under AECO A17.7 Control. When
replacing boards or functions involving this controlled software, verify that
the replacement or updated software is the same version listed on the
580AMY marker attached to the controller.
4. Fill out the following chart, and note the software version.
A USB flash drive is used to load software files into the CPUC, DPIA, Selector, and CAN
Node cards (of all types). A manufacturing-supplied USB flash drive ships with each job.
The USB has the current version of the job configuration file software and documentation
for the job.
1. Use Windows Explorer to access the USB flash drive; the recommended USB flash
drive is part number 9811126.
3. Determine the size of the USB flash drive, select the appropriate option from the File
System drop-down box, and click Start. See Figure 7 on page 5-33.
• If the flash drive is less than 2GB, select the FAT option.
• If the flash drive is 2GB or larger, select the FAT32 option.
SERVICE INFORMATION
If USB flash drive is less than 2GB If USB flash drive is more than 2GB
1. At the root of the USB flash drive, create a "tke" folder. When creating folders on the
USB flash drive, all folder names must be in lowercase for the CPU to recognize the
folder names. See Figure 8.
2. Inside the "tke" folder, create two separate folders: "update" and "backup."
3. Access the generic file (if required) and place a copy of the generic file into the
"\tke\update" folder.
4. Create a subfolder in the "\tke\backup" folder for each elevator controller being
updated/reloaded.
Helpful Tip: The "\tke\backup" location is a convenient place for quick access to files at
a later time.
5. Access the needed software, and place a copy of each elevator's configuration (.cfg)
file in the corresponding subfolder of the "backup" folder. The job configuration file
name has the elevator job number ("xxxnnn") included in it. See Table 1.
tke Folder
6. Use Windows Explorer to access the job files placed in the "\tke\backup\" folder
and copy the required elevator's "jobxxnnnn.cfg" file to the "\tke\update" folder.
7. Use Windows Explorer to verify that the required software files are in the "/tke/
update" folder on the USB flash drive.
• Only one version of generic file is permitted in the folder at a time.
• If multiple job files are placed in the update folder, the STAT LED will continuously
flash every 100ms.
• If multiple generic files are present in the update folder at the time of an update,
the CPUC Card could become corrupted, requiring the Recover Utility to be used.
• The generic and configuration upload may be processed either individually
or simultaneously.
• The CPU uploads the configuration (_.cfg) file located in the "\tke\update"
folder. When the upload completes, the _.cfg file is deleted from the update
folder.
• The generic file remains in "\tke\update\" folder until manually deleted. This
is to facilitate updating generic files across a group of controllers using one
USB flash drive.
2. Insert the prepared USB flash drive into the CON6 USB port on the CPUC Card.
SERVICE INFORMATION
Transferring software between the CPUC and USB flash drives requires a
few minutes to complete. Resetting the card during this time could result in
corrupting the USB and the CPUC.
3. Enter the UDLS Command to copy the "jobxxnnnn.cfg" file and generic file from
the CPUC Card to the "\tke\backup\jobnumber" folder on the USB Flash Drive.
From UIT: Block Select Adjustments > Commands Upload > UDLS.
4. Once the backup is complete, remove the USB flash drive from the CPUC, and
return the car to operation.
Recommendations • Before starting any software updates in control system, backup the software.
• For grouped controllers: When updating the master controller, isolate it from the rest of
the group by disconnecting IOF CON40, CON1, CON11, and CON12 as well as CPUC
CON5. This action will cause the next car to take over the master controller of group
operations assignment while software is being loaded. After software is loaded and
operation is restored, restore the connectors and cable.
Uploading software to the CPU requires a few minutes to complete. Resetting the
card during this time could result in corrupting the USB flash drive and damaging
the card.
2. Insert the prepared USB flash drive into the CPUC Card, CON6 USB port.
5. Press and hold UDL until the STAT LED blinks a Morse Code `Z' (two long and two
short blinks). When the upload is complete, the STAT LED blinks 3 times before the
CPUC Card resets itself.
• If the upload takes longer than 15 minutes, or if the STAT LED blinks every 100ms
continuously, the upload has failed. Cycle power to the controller and then remove the
USB from the CPUC Card. See Upload Software Troubleshooting on page 5-37.
• If the CPU is stuck in Zmodem for longer than 15 minutes, remove power from the
card, and remove the USB flash drive.
6. After the upload is successful, issue the following commands from Block Select
Adjust > Commands Common: GET, WRT, RFL, and RRF.
8. Cycle power.
9. Verify that the controller will run from Inspection Operation. Should the car fail to run,
troubleshoot fault codes and I/O states to determine the issue. See Troubleshooting
I/O Issues on page 4-13.
10. Place the door disconnect switch in the Door Disconnect position.
12. Use Quick Commands, and issue car calls to verify Automatic Operation. Hall
calls do not function while on Door Disconnect Operation.
Block Select Real Time Motion > Quick Commands > Front Car Call/Rear Car
Call.
If the job configuration file was a manufacturing file and not a back up copy of an
adjusted job (from the UDLS Command), perform a new hoistway scan and adjust
for the job (Fire Service, HWA, EP, security, date/time, etc.). See the Adjustment sec-
tion of this manual.
14. Verify that the car and hall buttons function correctly.
1. Verify the folder structure and the file location within the folder structure. See
USB Flash Drive Preparation on page 5-34.
2. Use a different USB flash drive (recommended device: part number 9811126).
4. Format the USB flash drive. Create a new folder structure and copy needed
file(s) into the Update folder. See How to Format a USB Flash Drive on
page 5-32.
SERVICE INFORMATION
Software Updates to Safety Node Devices over CAN
1. Move the needed files into the "\tke\update" directory. See Table 2 on
page 5-38 for file identification.
See also: USB Flash Drive Preparation on page 5-34.
3. From the UIT, press any button while Vertical Express is displayed, and enter the
pin number - 1234144. If the wrong pin number is entered, continue to press UP
until Vertical Express appears in the window, then enter the pin number again.
4. From the UIT, access Block Select Adjustments and press ENTER.
8. Press RST on the CPUC. Once the controller recovers, repeat the steps to access the
Main Menu Screen.
At this point, the Safety Processor is configured and either the SP Good or the SP Bad LED
should be illuminated. The SP BAD LED will remain lit until the nodes have been taught
and configured.
REFERENCE SECTION
REFERENCE SECTION
Reference Section Contents
Contents
UIT Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5R-3
Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5R-4
CNA Fixed I/O Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5R-7
ICON32 I/O Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5R-8
I-2/I-3 Valve Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5R-9
This page
intentionally
left blank.
Vertical
Express Block Select Block Select Block Select Block Select
Real Time Motion System Clock Startup Wizard Inspector’s Tests
Enter Pin #
ENTER ENTER ENTER ENTER
Motion/Position Time hh:mm:ss Start Wizard? FLT
1 2 3 4 Status Date mm:dd:yy UP = Yes DN = No RFL
UP DN ESC ENTER TFR
Arbiter No
Yes SCCB
Pin: 1234144 Velocity
(if incorrect, press reset) Set the Time? Clear CN Config SCC2-SCCn
Notes: ENTER UP = Yes DN = No SCCT
Config CNs
• Use UP and DN to scroll Set the Date? (Set Car Call Bottom,
QUICK COMMANDS Auto Hoistway Scan
through blocks. UP = Yes DN = No 2,3,.... top in order)
• Press ENTER to select. Show Faults* Write to Flash
• While in block menus, Show Fault Details* Save Job to USB
use UP and DN to navigate. Clear Faults*
• Use ESC to back out. Block Select
Reset Fault List
Logoff UIT?
Front Car Call
Rear Car Call UP = Yes DN = No
UP Hall Call
DN Hall Call
Block Select Show Stable Leveling
Adjustments Show I/O
*only displays if faults are present.
ENTER
ESC
Adjust Car/Group
Commands Common
Commands Upload
SUBMENU SUBMENU SUBMENU SUBMENU SUBMENU
Commands Startup
Adjust Car/Group Commands Commands Commands Commands
Commands Group Common Upload Startup Group
Front Door
Rear Door
Job Parameters (Jxx) CJR UFWCNC DCN GPN
SUBMENUS DSL UFWCNH ELD SCA
Car Information
Code Blue (Cxx) FCP UFWSPF JRT SCAI
FJR UFWSLF PRT SUC
Desination Dispatch
GET OSDMI SCF SDC
Doors (Dxx)
IOView OSDM SPC SRU
Emergency Power (Exx)
REFERENCE
IRL UDLS STUA SRD
Fire Service (Fxx) STU
IRLR UDLR SSI
Fixtures (Xxx) TECC
RFL SHL
Homing & Shutdown (Hxx) TECCR
RRF PIG
Incon Riser (Rxx) WRTG
SCC
Motion (Mxx) SFL
Options 1 (Oxx) SFLR
Options 2 (Zxx) SRC
Parking & Zoning (Lxx) TMP
Position System (Pxx) TSR
Security (Sxx) TSRT
Traffic VER
WJR
WRT
Cable Connections
Notes: Third party equipment may require additional wiring not shown, see manufacturer’s document for wiring requirements.
*Not cross-connected for battery lowering option.
**Only cross-connected when CAN device is connected on CAN Channel 3.
^Only cross-connected when remote Fire Service keyswitch option is provided and I/O are present in job image.
Cable Connections
(continued)
REFERENCE
Door Op.
DPWR2 18AWG DPWR2 (if req.)
DPWR3 18AWG DPWR3
Notes: Third party equipment may require additional wiring not shown, see manufacturer’s docs for wiring requirements.
AC1/AC2 from Trades Panel is for cab lighting.
AC1A/AC2 from IOF is for the elevator control system.
Hoistway Connections
G24 18AWG G24 HCIE 18AWG HCIE
P24G 18AWG P24G U1 18AWG U1 Hoistway
U2 18AWG U2 Cable
P24HF 18AWG P24HF
Ux 18AWG Ux
Connections
HATU 18AWG HATU
Controller Rail Term.
Reference
Hoistway Connections
UR1 18AWG UR1
CNA Connections
5R - 6
FSH3 18AWG FSH3 FS Sw.
Remote AC1B
CNA Connections
©Vertical Express
EPJ CON13 AC1B
TPDR 18AWG TPDR From Closed Switch String –
Connections
316 (CF) Front Non-HA Landings
TRDL 18AWG TPDL
IOF
TP*SR 18AWG TP*SR AC1B
From Closed Switch string –
TP*SL 18AWG TP*SL 326 (CR) Rear Non-HA Landings
Reference Section CNA Fixed I/O Charts
Pin No. CON15 Pin No. CON13 Pin No. CON6 Pin No. CON5
1 SHCC 1 G24 1 1 FSH1
2 CCL 2 G24 2 2 FSH2
3 CCH 3 G24 3 3 FSH5
CON14 4 24VDC 4 4 FS1I
1 G24 5 24VDC 5 5 FSH3
2 P24G 6 24VDC 6 6 FSH4
7 7
Pin No. CON12 Pin No. CON11 8 8
1 SPAH1 1 HLUR1
2 SPAH2 2 HLUR2 Pin No. CON4 Pin No. CON3
3 SPAH3 3 HLDR2 1 DOB 1 PI4
4 SPAH4 4 HLUR3 2 DCB 2 PI5
5 SPAH5 5 HLDR3 3 DOBR 3 BUZ
6 SPAH6 6 HLUR4 4 DCBR 4 CLU
7 SPAH7 7 HLDR4 5 FSC1 5 CLD
8 SPAH8 8 HLDR5 6 FSC2 6 CLUR
7 FSRI 7 CLDR
Pin No. CON10 Pin No. CON9 8 FSCC 8 CLFS
1 UR1 1 HLD5
2 UR2 2 SOA Pin No. CON2 Pin No. CON1
3 DR2 3 ISC 1 CR1 1 CCIE
4 UR3 4 SPAL1 2 CR2 2 C1
5 DR3 5 SPAL2 3 CR3 3 C2
6 UR4 6 SPAL3 4 CR4 4 C3
7 DR4 7 SPAL4 5 CR5 5 C4
REFERENCE
8 DR5 8 SPAL5 6 PI1 6 C5
7 PI2 7 DAU
Pin No. CON8 Pin No. CON7 8 PI3 8 DAD
1 D5 1 HCIE
2 HLU1 2 U1
3 HLU2 3 U2
4 HLD2 4 D2
5 HLU3 5 U3
6 HLD3 6 D3
7 HLU4 7 U4
8 HLD4 8 D4
P17/P18
Selector Slowdown Point
Car Position
Level
Level
Floor
Floor
This figure shows the requirement of 3"-4" of leveling distance. If the car
slowdown and approach to the floor results in longer leveling than 3"-4",
car performance and fluid could degrade due to unnecessary fluid heating.
P17/P18
Selector Slowdown Points P17/P18 too small
Top (no leveling distance,
Speed car re-levels)
3"-4" of
Speed
stabilized leveling
Car
P17/P18
too large
(excessive leveling distance)
Level
Level
Floor
Floor
Car Position
This figure shows the effect of using the P17/P18 Adjustments to control the leveling
distance. If the car slowdown and approach to the floor is comfortable as adjusted in
the valve but results in incorrect leveling distance (3"-4"), move the P17/P18
Selector Showdown Point properly.
P17/P18
Selector Slowdown Point Valve Slowdown too soft
(no leveling distance,
REFERENCE
Top car re-levels)
Speed
3"-4" of
Speed
stabilized leveling
Car
Valve Slowdown
too aggressive
(excessive leveling distance)
Level
Floor
Level
Car Position
Floor
This figure shows the effect of using the I-2/I-3 Valve Slowdown Screw Adjustments to control
the leveling distance. If the car showdown point P17/P18 is set but leveling is incorrect (not 3"-4"),
move the Valve Slowdown Screw.
• UP SLDN Screw: IN = Shorter leveling distance, increased leveling speed, softer feel to slowdown.
• DOWN SLDN Screw: OUT = Shorter leveling distance (with full load the distance is even shorter),
Set for at least 2" of leveling with a full load and increase P17
to help with full load down floor approach.
OK
Up Leveling
Adjustment
Down Slowdown
Adjustment
High Pressure
Relief Adjustment REFERENCE INFORMATION
Down Stop The closer the flats on the lowering
Adjustment
& leveling screw get to perpendicular
with the axis of the tank return line,
Down Start
the more likely the valve will lock
Up Stop Up Slowdown up in the down direction.
Adjustment
Adjustment Adjustment
1. Make adjustments with the car empty. RELIEF Appx. з" out
2. Ensure system has at least 90 PSI static Turn CCW until screw disengages from piston, then CW
pressure before adjusting. LOW PRESSURE until resistance is felt, turn CCW an additional 3 turns
3. Do not adjust the valve unless oil
UP LEVELING Turn CCW until the screw stops, then CW 2 turns
temperature is between 80° - 110° F.
4. Do not attempt to adjust the Lowering and UP STOP Turn CW until the screw stops, then CCW 2 turns
Leveling Screw unless the car is moving
UP SLOWDOWN Turn CW until the screw stops, then CCW 4 turns
or resting on the buffer stands with
pressure off the lowering piston, or valve UP START Turn CW until the screw stops, then CCW 3 turns
damage may result. DOWN START Turn CW until the screw stops, then CCW 6 & one-half turns
5. Leveling speed and zone adjustments are
DOWN STOP Turn CW until the screw stops, then CCW 6 turns
sensitive and may require multiple attempts.
DOWN
6. After completing final adjustments, Turn CW until screw stops, then CCW 5 & three-eighths turns
SLOWDOWN
bleed the car down slightly with the
LOWERING &
manual lowering valve to see if it levels Turn CW until the screw stops, then CCW 3 turns
LEVELING
back up with the floor. If not, the slowdown
MANUAL
adjustments need to be rechecked. Turn CW until the screw stops (closed)
LOWERING
Never operate above 600 PSI! Open Manual Lowering valve slightly, shut off valve to jack line and run
RELIEF the car up on Machine Room Inspection. Turn Relief screw CW to increase pressure, CCW to reduce
pressure. Close Manual Lowering valve and recheck pressure, adjust Relief screw as necessary.
Stop the run, vent pressure with the Manual Lowering valve, and open the shut off valve.
This is a quick reference for the I-2/I-3 Valve for use by experienced mechanics.
See the I-2/I-3 Valve component manual for procedure and troubleshooting information.
Adjustment 2 Adjustment 3
Starting Acceleration Fast Speed
Adjustment 5
Deceleration to Leveling Speed
Adjustment 1
Speed
Adjustment 5
Leveling Zone Deceleration to Full Stop
Set at 3"-4"
Adjustment 4
Leveling Speed
Set at 10-12 FPM
REFERENCE
N/A N/A No adjustment. Set by pump capacity.
Lowering & Adjust in less than one-eighth turn increments. Hold screw
Reduce leveling speed Increase leveling speed
Leveling* to tighten locknut so settings don’t change. Very sensitive.
4
Decrease leveling speed,
Up Leveling Increase leveling speed, May affect UP Slowdown.
softer slowdown firmer slowdown
Down Increase leveling zone, Decrease leveling zone, Very sensitive. Must find "sweet spot" of about one-eighth
Slowdown firmer slowdown softer slowdown turn range to affect adjustment. Affects Down Leveling.
5
Up Decrease leveling zone, Increase leveling zone,
Very sensitive. More CCW gives more abrupt slowdown.
softer slowdown, firmer slowdown,
Slowdown
increase leveling speed decrease leveling speed Affects Up Leveling.
* If the valve locks up in the down direction due to the orientation of the flats on the lowering and leveling screw, run the car
up and change the orientation of the screw 90° while the car is moving to restore function.
This page
intentionally
left blank.