LLLL
LLLL
Contents
1
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
2
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
Past concept
Up to and including Version 2.3. fields has to be filled with PLC-internal information into
"communication units" in EPLAN in order to make bus data exchange with the PLC
configuration programs possible. However, the EPLAN user does not usually know the
required contents. In addition, the fields of the "communication units" in EPLAN are named
differently (universal) that to the PLC software (manufacturer-specifically).
3
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
4
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
1) Enter a "Network / bus cable-connection point" function definition per bus port.
a) Source: This is where the bus system begins.
b) End: This is where the bus system ends. Use this function definition, for example, to
identify the end of a ring bus system.
c) Input: The input is used to connect a device to a bus system. An additional device
can be connected to the bus system via a further output. Inputs and outputs are
mostly used on a card in pairs.
d) Output: Here a bus system that was previously supplied at an input of the same
device is forwarded. EPLAN assigns an output to its input.
e) Switch connection point: These connection points are used for so called "switches"
and are treated like busbar connection points. This way all connection points are
connected to each other.
f) General: Is used for Ethernet-based bus systems or for bus ports if these are both
input and output, for example for ASi or PROFIBUS. For Ethernet-based bus systems
enter the designation of the corresponding interface into the Bus interface: Name
property.
2) Select the corresponding bus system in the Bus system column.
3) Enter the Plug designation and, if necessary, a Connection point description. Leave
the Connection point designation empty.
Adapting macros
Macros only have to be revised if
1) A PLC box with "communication units" is used in the macro.
2) Bus ports are located in the macro.
5
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
Adapting projects
If a project from a previous version is opened in Version 2.4, data at "communication units"
are transferred into the new version, but are not displayed or evaluated. Unfortunately an
automatic conversion of the data from the "communication units" to the bus ports is not
possible. The check run "004045 Communication unit at PLC box" is available to find these
data.
The simplest way to transfer data from the "communication units" to the bus ports is to export
them from Version 2.3 and import them to Version 2.4 and later.
6
TechTip
EPLAN Platform Version 2.8
Version: August 16, 2018
6) The data is imported. Data that were located beforehand at the "communication units"
are now available at the single-line bus ports.
7) Open the message management and check the import messages. Correct the bus ports
that may be listed.
Cleaning a project
After the data at bus ports has been transferred, the "communication units" can be deleted
by using the compression run "Remove project data – Remove communication units at PLC
boxes".