L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 2
1.1) Typed / Generic xPS
GENERIC INFORMATION
It is a standard information which can be configured at any level.
Examples :
- Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 3
1.1) Typed / Generic xPS
Mapping SPS
It is an input which is produced by mapping to
another DP. Each state of this DP is mapped and
corresponds to a state of the mapping SPS
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 4
1.2) Add / Configure a SPS (1)
1) SPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation
level in Electric hierarchy. Some SPS are System Info.
2) SPS attributes Short Name :
SCE Key + appears in C264 local SOE
Long Name :
appears in viewers + printers
Detection Mode :
permanent : DI remains ON as far as signal is ON
Profiles :
Add the reference of the profile
Persistence filtering :
SPS should remain valid “Set” or “Reset” during the
configured timer
Time tagging :
LHMI display : done at starting/end of signal filtering
yes = SPS in state list (MSC)
Forcing Management :
auto force
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 5
1.2) Add / Configure a SPS (2)
3) SPS can be acquired by DIU/CCU board, IED. Some SPS are computed by C264
application (C264 automation, …)
=> Relations under a SPS
Wired on : DI Channel
SPS acquired by DIU/CCU board
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 6
1.3) Add / Configure a DPS (1)
1) DPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation level in Electric hierarchy. Some DPS are System Info.
2) DPS attributes Short Name :
SCE Key + appears in C264 local SOE
Long Name :
appears in viewers + printers
Profiles :
Add the reference of the profile
Motion & Persistence filtering :
Motion : eliminate transients 00 and/or 11 motion states
Persistence : DPS should remain valid “Open” or “Closed”
during the configured timer
Time tagging :
done at starting/end of motion
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :
yes = DPS in state list (MSC)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 7
1.3) Add / Configure a DPS (2)
3) DPS can be acquired by DIU/CCU board, IED. Some DPS are computed by C264
application (C264 automation, …)
=> Relations under a DPS
Wired on :
DPS acquired by 2 channels (“open” and “closed”) on
DIU/CCU board
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 8
1.4) Add / Configure a MPS (1)
LHMI display :
yes = DPS in state list (MSC) Forcing Management :
if FSS enabled, auto/manual force
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 9
1.4) Add / Configure a MPS (2)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 10
1.4) Add / Configure a MPS (3)
3) MPS can be acquired by DIU/CCU board, IED. Some MPS are computed by C264
application (C264 automation, …)
=> Relations under a MPS
Wired on :
MPS acquired by a maximum of 16 channels on
DIU/CCU boards
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 11
Summary
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 12
2.1) Add / Configure a MV (1)
1) MV can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation
level in Electric hierarchy. Some MV are System Info.
2) MV attributes in General Tab Short Name :
SCE Key + appears in C264 local SOE
Long Name :
appears in viewers + printers
Analogue Type :
Analogue (AI,CT/VT,IED)
or Digital Measurement
Profiles :
Add the reference of the profile
Forcing Management :
if FSS enabled, automatic force to a given value
LHMI display : MV transmission :
yes = MV in measurements list SBUS, LHMI
(MSC)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 13
2.1) Add / Configure a MV (2)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 14
2.1) Add / Configure a MV (3)
Scaling Low :
Linear / Quadratic
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 15
2.1) Add / Configure a MV (4)
Wired on AI Channel :
Channel to be configured (cf. next slide)
Has for IED address :
MV acquired by IED Wired on DI Channels :
Digital Measurements acquired by a maximum of 64
channels on DIU/CCU boards
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 16
2.1) Add / Configure a MV (5)
Transducer range :
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 17
2.2) Add / Configure a TPI (1)
1) TPI can ONLY be added under a Tap Changer object belonging to a Transformer
module.
=> Add / Configure a Tap Changer object :
Built-in function :
Tap Changer
Execution timeout :
Time allowed for Tap Changing
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 18
2.2) Add / Configure a TPI (2)
2) TPI attributes :
2.1) General Tab TPI type :
- Analogue Tap Position acquired by AIU or IED,
- Coded Digital Measurement (1/N, decimal,
gray, BCD) acquired by DIU
Profiles :
Add the reference of the profile
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 19
2.2) Add / Configure a TPI (3)
2) TPI attributes :
2.2) Value Features Tab
Minimum / Maximum Value :
Should comply with Tap Changer object
configuration
Thresholds definition :
raw values for LLL, LL, L, H, HH, HHH
thresholds
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 20
2.2) Add / Configure a TPI (4)
2) TPI attributes :
2.3) Scaling Tab (for Analogue TPI only)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 21
2.2) Add / Configure a TPI (5)
Wired on DI Channels :
Digital TPI acquired by a maximum of 64 channels on
DIU/CCU boards
Wired on AI Channel :
Channel to be configured
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 22
2.3) Add / Configure a Counter (1)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 24
2.3) Add / Configure a Counter (3)
3) Counter can be acquired by DIU/CCU board, IED. Some Counters are computed by
C264 application (C264 automation, …)
=> Relations under a Counter Wired on :
Single counter => 1 DI Channel
Double counter => 2 DI Channels
integrate :
Counter computed by MV integration (example : P)
Counter type is not “Standard” but “Energy import”
or “Energy export”
Integration of P or Q :
In case the scale and unit is to big (MVarh for ex.), if energy is changing of less than
1MVarh in 10 minutes, the value is not sent (counter is integer so 0.2 value is the value is
not sent (counter is integer so 0.2 value is equal to 0).
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 25
Summary
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 26
3.1) Typed / Generic xPC
TYPED CONTROL
It is an information which is representing a special functionality regarding
the MiCOM C264 inner automations.
Examples :
- Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC,
Sync CB Close
GENERIC CONTROL
It is a standard control which can be configured at any level.
Examples :
- Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 27
3.2) Add / Configure a SPC (1)
1) SPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation
level in Electric hierarchy. Some SPC are System Info.
2) SPC attributes General Tab
Short Name :
SCE Key + appears in C264 local SOE
Long Name :
appears in viewers + printers
Profiles :
Add the reference of the profile
Activation Mode :
- transient => configure pulse duration
- permanent
LHMI display : - permanent until feedback
yes = SPC in control list (MSC)
Inter Control timeout :
no possibility to execute 2 consecutive orders during this
timer
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 28
3.2) Add / Configure a SPC (2)
Bay Local/Remote :
Bay Local => control from LHMI allowed, from
OI & SCADA not allowed
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed, from
SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 29
3.2) Add / Configure a SPC (3)
4) SPC can be executed on DOU/CCU board, IED. Some SPC are computed by C264
application (C264 automation, …)
=> Relations under a SPC Auto/Manu dependency :
blocks the operator control if an automation
is in progress => connect to SPS/DPS giving
automation status
Feedback definition :
for C264 acknowledgement
cf. slide “§3.4”
Has for IED address :
SPC executed by IED
Wired on : DO Channel
SPC executed on DOU/CCU board
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 31
3.3) Add / Configure a DPC (2)
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed, from
SCADA forbidden
Note : This is internal automation existing and configurable for all xPC.
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 32
3.3) Add / Configure a DPC (2)
4) DPC can be executed on DOU/CCU board, IED. Some DPC are computed by C264
application (C264 automation, …)
=> Relations under a DPC
Auto/Manu dependency :
blocks the operator control if an automation is in progress =>
connect to SPS/DPS giving automation status
Has for IED address :
SPS executed by IED
Feedback definition :
for C264 acknowledgement
cf. slide “§3.4”
Wired on : DO Channel
DPC executed on DOU/CCU board
2 Associated DO channel status SPS :
for hardwired DPC only
2 Interlock SPS (open/close):
holds a logic allowing/blocking the controls
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 33
3.4) Configure a xPC feedback
DPC
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 34
3.5) Add / Configure a SetPoint (1)
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 35
3.5) Add / Configure a SetPoint (2)
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
Control Uniqueness
Substation Local/Remote :
SS Local => control from OI allowed, from
SCADA forbidden
Note : This is internal automation existing and configurable for all Setpoints.
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 36
3.5) Add / Configure a SetPoint (3)
4) SetPoints can be executed on DOU/CCU board, IED. Some SetPoints are computed
by C264 application (C264 automation, …)
=> Relations under a SetPoints
DO Channels :
C264 will close DO channels using configured code (BCD,
binary, …)
Auto/Manu dependency :
blocks the operator control if an automation is in progress =>
connect to SPS/DPS giving automation status
AO Channels :
C264 will set AO channel
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 37
Summary
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 38
4.1) SPS Status
GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 39
4.2) DPS Status
MV STATUS MEANING
VALID MV in between min/MAX and/or L/H threshold
UDEFINED No DI channel or more than one activated DM
SELF CHECK FAULTY Faulty DI/AI Channel on board
TOGGLING Toggling filtering has detected behaviour
UNKNOWN IED acquiring DP is disconnected from C264
FORCED MV is Forced C264 (FSS enable)
SUBSTITUTED STATE N * MV is Substituted by Op. (FSS enable)
SUPPRESSED MV is Suppressed by Oper. (FSS enable)
OVERRANGE Acquisition out of range
OPEN CIRCUIT No current on AI channel (mA)
OVERSHOOT [1,2,3] Over H, HH, HHH Threshold
UNDERSHOOT [1,2,3] Under L, LL, LLL Threshold
Quality => gives the nature of invalidity GSE
L2 - 02-DATAPOINTS CONFIGURATION - Rev G - P 42