Features:
1. Heating Mode H:
When Temperature ≤ Set T – Back T; Relay conduction, heating equipment begin to work;
when temperature ≥ Set T, Relay disconnect, heating equipment stop work;
2. Refrigeration mode C:
When Temperature ≥ Set T+Back T; Relay conduction, refrigeration equipment begin to work;
When Temperature ≤ Set T; Relay conduction, refrigeration equipment stop work;
3. Through the UP DOWN key, modify the parameter value, support short press/long press;
4. Long press SET to build more than 3S or continuous 6S without any key operation, exit quickly
set the interface, and save parameters;
1. In the operating interface, long press SET more than 3s, enter the parameters to set the
interface;
2. Enter the parameter to set the interface, through the short press SET key to switch to set the
parameters;
3. Through the UP DOWN key, modify the parameter value, support short press/long press;
4. Long press SET3s above or continuous 6S without any key operation, exit parameter set
interface, and save parameters;
Enter the parameter setting interface, switch to the alarm parameter ALA, turn on or off the
high-temperature alarm function by short pressing the STOP button, and if the high-temperature
alarm function closes, ALA displays \'----\' as a reminder;
Enter parameter setting interface, switch to alarm parameter OPH, turn on or off
high-temperature alarm function by short Press STOP button if high-temperature alarm function
closes, OPH show \'---\' to remind;