Quest 110 Dual
Quest 110 Dual
Quest 110 Dual
Quest 110
Installation,Operation
Installation, Operation and
and Maintenance
MaintenanceInstructions
Instructions
– Read and Save These Instructions –
This manual is provided to acquaint you with the dehumidi-
fier so that installation, operation and maintenance can
proceed successfully. Ultimate satisfaction depends on the
quality of installation and a thorough understanding of this
equipment. The dehumidifier is built around tested engi-
neering principles and has passed a thorough inspection for
quality of workmanship and function.
Features:
• High capacity
• High efficiency
• Environmentally friendly
• Patent pending dual-air distribution
TS-879
Specifications subject to change without notice. 1 10/15 Rev. D
Quest 110 Dual Installation, Operation and Maintenance Instructions
Table of Contents
Safety Precautions..................................................................... 3
1. Intended Application(s)..........................................................4
2. Registration .........................................................................4
3. Specifications .....................................................................4
4 . Installation ......................................................................... 5
4.1 Remove Compressor Shipping Support....................... 5
4.2 Location 5
4.2A How to hang dehumidifier................................ 5
4.3 Electrical Requirements............................................... 6
4.4 Install Leveling Feet...................................................... 6
4.5 Condensate Water Removal......................................... 7
5. Ducting ......................................................................... 8
5.1 Outlet Duct Kit.............................................................. 8
6. Operation ......................................................................... 8
6.1 Humidity Control Adjustment...................................... 8
6.2 Fan Switch...................................................................... 8
7. Maintenance 8
7.1 Air Filter 9
8. Service ......................................................................... 9
8.1 Technical description...................................................... 9
8.2 Troubleshooting............................................................ 10
9. Service Parts List..................................................................12
10. Accessory/Replacement Parts List...................................12
11. Wiring Diagram....................................................................13
Warranty ....................................................................... 14
1-877-420-1330 www.QuestHydro.com
2 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
Safety Precautions
Read the installation, operation and maintenance instructions carefully before installing and operating this device. Proper
adherence to these instructions is essential to obtain maximum benefit from your Quest 110 Dual indoor air quality
system.
1-877-420-1330 www.QuestHydro.com
3 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
2. Registrations
The Quest 110 Dual units conforms to unified standard UL 60335-2-40 and CSA standard C22.2.60335-2-40.
3. Specifications
1-877-420-1330 www.QuestHydro.com
4 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
4. Installation
CAUTION! Remove compressor shipping tie from the unit. Failure to remove shipping tie will
cause excess vibration to be transmitted to the frame.
4.2 Location
The Quest 110 Dual can be installed in a variety of locations to meet the owner’s needs; other considerations include:
1. P
roviding access to a 115 VAC power outlet (10’ power cord is provided).
2. Locating near a floor or other suitable drain.
3. Mount at least 4” above drain. (P-trap recommended - See pg. 8)
4. Do not install the Quest 110 Dual with the exhaust of the unit within 1’ of a wall or obstruction. Do not place the unit
near open water.
5. Duct work not recommended for gardening (DO NOT duct heat out).
6. Hanging not required - Floor install is ok.
note: plumb
condensate water
P-trap to drain or
(see section 4.5 for more info) reclamation
B reservoir
B
A A A
Optional
A A Humidistat
A B (4020175)
B Bottom view
of unit and Bracket Figure 1: Recommended install shown
bracket (4036568)
4.2A How to hang dehumidifier
A. Attach brackets (PN 4036568) with feet. Tighten with 5/8” wrench.
B. Attach chain or SunGrip to bracket. Ensure materials have adequate weight rating.
1-877-420-1330 www.QuestHydro.com
5 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
CAUTION! For proper drainage, the unit must be mounted so the drain outlet is at least 4”
above the floor drain, and must be fully supported under the base.
4.4 Installing Feet
Included with your Quest 110 Dual are four leveling feet. It is important to level the unit for
proper draining.
CAUTION! Note: Operating the unit immediately after bringing it to an upright position can
possibly damage the compressor. A short amount of time is needed (10 minutes) to allow the oil to
return to it’s reservoir for lubrication.
1-877-420-1330 www.QuestHydro.com
6 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
CAUTION! The Quest 110 Dual drains via gravity, therefore, it does not have the ability to push condensate
(water) upwards. The drain hose must run down towards the drain location. Condensate can be drained by using the 5/8”
clear vinyl hose and the 3/4” threaded adapter provided. Ensure the threaded adapter is threaded in tightly.
CAUTION! The Quest 110 Dual requires a drain trap. Creating a drain trap allows a small amount of water to
build up in the trap area of the clear hose. This prevents air from back flowing through the hose and into the dehumidifier;
essentially causing the unit to backflow water out of the corners of the machine. Position the trap in the hose
approximately 8”-10” from the dehumidifier and make sure the highest point of the trap is still at least 2”below the black
drain port adapter on the dehumidifier. If the highest point of the trap is above the drain port, water will back flow into
the dehumidifier. Check the hose regularly to ensure water is draining properly.
Pretzel Loop
Standard Loop
1-877-420-1330 www.QuestHydro.com
7 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
5. Ducting
5.1 Duct Kit (P/N 4033039)
A factory designed outlet duct kit can be purchased to accept 10” ducting to both outlets of the Quest 110 Dual.
Contact your dealer or order online.
6. Operation
6.1 Humidity Control Adjustment
The humidity control is an adjustable switch that closes when the relative humidity of the air in which it is located rises to
the dial set point. It opens when the RH drops 4 to 6% below the set point.
4031882
The dehumidifier will run until the relative humidity (RH) is reduced to the humidity control dial setting.
Quality humidity meters are available from the factory and are recommended to accurately monitor humidity levels.
Refer to the options and accessories table in this document.
7. Maintenance
CAUTION! NOTE: Do not operate the unit without the filter or with a less effective filter. The
heat exchange coils inside the unit could become clogged and require disassembly to clean.
1-877-420-1330 www.QuestHydro.com
8 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
1-877-420-1330 www.QuestHydro.com
9 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
8.2 Troubleshooting
Blower runs with fan switch AUTO but compressor cycles on & off.
1. Low ambient temperature and/or humidity causing unit to cycle through defrost mode.
2. Defrost thermostat defective.
3. Defective compressor overload.
4. Defective compressor.
1-877-420-1330 www.QuestHydro.com
10 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
Blower does not run with fan switch in either position. Compressor runs briefly but cycles on and off.
1. Loose connection in blower circuit.
2. Obstruction prevents impeller rotation.
3. Defective blower.
4. Defective blower switch.
Evaporator coil frosted continuously, low dehumidifying capacity.
1. Dirty air filter or air flow restricted.
2. Defrost thermostat loose or defective.
3. Low refrigerant charge.
If none of the above has fixed the issue, call technical support at 1-800-533-7533.
1-877-420-1330 www.QuestHydro.com
11 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
Part No Description
4034887-02 Evaporator
4036474 Capillary Tubes
4035407 Compressor
4029510 Filter/drier
4034109 Condenser
4026360 Impeller
4033032-06 50mfd 370V Capacitor - Compressor
4035235-04 7.5mfd 370V Capacitor - Impeller
4026221 Leveling Foot
4031376 Defrost Thermostat
4027172 Humidity Controller
4025560 Fan Switch
4036568 Bracket
Part No Description
4031062 Filter MERV 8
4033036 Filters 4-Pack, MERV 8
4033037 Filters 12-Pack, MERV 8
4028616 Caster Kit
4033038 Pump Kit
4033039 Duct Kit, Supply
4035646 Duct Kit, Return
4026969 10” Flex Duct
4022126 10” Flex Duct (Insulated)
4020175 Remote Dehumidistat
1-877-420-1330 www.QuestHydro.com
12 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
1-877-420-1330 www.QuestHydro.com
13 info@QuestHydro.com
Quest 110 Dual Installation, Operation and Maintenance Instructions
1-877-420-1330 www.QuestHydro.com
14 info@QuestHydro.com