01) CP Training-STARDOM Introduction

The document introduces STARDOM, Yokogawa's network-based control system. STARDOM controllers have compact designs that provide significant cost savings. They come in modular and low power consumption models. STARDOM uses controller event buffers to enable highly reliable communication even under bad network conditions.

Uploaded by

Saad Bro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
210 views64 pages

01) CP Training-STARDOM Introduction

The document introduces STARDOM, Yokogawa's network-based control system. STARDOM controllers have compact designs that provide significant cost savings. They come in modular and low power consumption models. STARDOM uses controller event buffers to enable highly reliable communication even under bad network conditions.

Uploaded by

Saad Bro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

STARDOM Introduction

Ng Chye Wee
Yokogawa Engineering Asia Pte Ltd Network Based Control System

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
1
Agenda
1. Basic of STARDOM and its positioning

2. STARDOM New E2Bus Module-Architecture


Solution for Wide Area Distributed IO System

3. FCN-500 Introduction

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
2
Basic of STARDOM and its
positioning

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
3
STARDOM

Network Based Control System

STrategic ARcher for new business DOMain

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
4
STARDOM Installation Map
(As of March 2020)

EUROPE
AUSTRIA(25)
BELGIUM(10)
BOSNIA AND
HERZEGOVINA(5)
SWITZERLAND(3) Europe
CZECH(5)
GERMANY(17) Asia NORTH and CENTRAL
SPAIN(12)
FRANCE(246)
More than AMERICA
Middle
30,000 units
UNITED KINGDOM(102) CANADA(97)
GREECE(65) East UNITED STATES (1069)
HUNGARY(122) MEXICO(5)
IRELAND(1) over 78 countries
ITALY(23)
LUXEMBOURG(2) Africa
NETHERLANDS(449)
NORWAY(2)
POLAND(111)
Oceania
ASIA
PORTUGAL(14)
ROMANIA(33) BANGLADESH(129) South
RUSSIA(1578) BRUNEI(2) America
SERBIA(1) CHINA(2903)
SLOVAKIA(1) MIDDLE EAST HONG KONG(7)
INDONESIA(135)
SLOVENIA(8) UAE(488)
INDIA(831)
UKRAINE(10) BAHRAIN(1666)
IRAN(200)
OCEANIA JAPAN(5944)
AFRICA IRAQ(29) AUSTRALIA(3190) KAZAKHSTAN(160)
KOREA(109)
MOROCCO(8) KUWAIT(93) NEW ZEALAND(300)
ALGERIA(611) OMAN(350)
SRI LANKA(2) SOUTH AMERICA
EGYPT(256) MALAYSIA(70) ARGENTINA(364)
QATAR(101)
KENYA(1) PAKISTAN(5) BRAZIL(367)
SAUDI ARABIA(5506)
LIBYA(3) PHILIPPINES(10) CHILE(34)
SYRIAN(16)
MAURITIUS(1) SINGAPORE(800) COLOMBIA(130)
TURKEY(11)
NIGERIA(11) THAILAND(347) ECUADOR(1)
YEMEN(126)
SUDAN(2) TURKMENISTAN(6) PERU(130)
BOLIVIA(6)
TUNISIA(2) TAIWAN(29) VENEZUELA(50)
JORDEN(2)
TANZANIA(16) VIET NAM(65)
GHANA(10)
SOUTH AFRICA(82) * Based on the delivered number of CPU Module(NFCP501/502,NFCP050,NFCP100) and FCJ
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
DO NOT DISTRIBUTE
DO NOT DISTRIBUTE 5
STARDOM –Hybrid PLC

Hybrid
DCS PLC
PLC

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
6
Yokogawa’s Controllers Environment
Large

FA-M3R
Centum VP

Scale
(I/O
Size)
Stardom

UT Advanced UT Advanced
Small Redundancy Function No Redundancy Function Modular Type (Building Block) Compact Type

PA (Process Automation) FA (Factory Automation)

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
7
STARDOM Components

2
Types

Modular & Redundancy-enabled Wide Temperature Range


Field Control Node Low Power Consumption

Modular model Low power consumption model Long Base Type


• I/O modules max.79 • Low power (Typical 2.1W) • Redundant Power Module
• Up to 9 I/O units • 41 I/Os embedded
• Redundant CPU/Power available • 3 additional I/O slots
• 110/220VAC, 24VDC available • -40 to +70 degC

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
8
9
STARDOM Controllers
• Compact footprint of STARDOM controllers gives significant
cost reduction especially in remotely distributed and

Compact
hazardous locations.
• Additional cost savings in duplexed configuration where
design CPUs are mounted on the same base plane thus does not
require separate racks or panels.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
9
10
STARDOM Key Features

Integration
• Controller Event Buffer realize high reliable
communication for bad network condition.
• FAST/TOOLS can handle event buffer for
For highly reliable communication recovering Trend Graph.

Network Network
Fail Recover

When network recovered,


event buffer FAST/TOOLS read event buffer
Trend Value and time stamp for recovering Trend Graph with
are stored to event buffer on buffered value and time stamp.
controller.

Value
Network
recovers

Trend stops Time -> Trend recovers

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
10
11
STARDOM Key Features

Openess & Seamless


Connectivity Integration .
FOUNDATION Fieldbus

HART

Serial
Modbus
Industrial use
surveillant Camera

Card Reader
Graphic Panel
Supports a wide range of
fieldbus protocols
Rich SCADA ■ FOUNDATION fieldbus H1, HART,
communication Modbus, PROFIBUS-DP, CANopen, RS-
■ DNP3, Modbus, OPC available 232/422/485
using CPU ports
■ Eliminates need to invest in
communication modules and
communication gateways

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
11
12
STARDOM Key Features
• FAST/TOOLS SUPPORTS STARDOM native

Seamless
communication.
• Process control Related Graphics(Faceplate,

Integration Tuning Panel, Controller Status) are


automatically made on just by reading
STARDOM definition

Controller health check window

Faceplate window
Tuning window

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
12
STARDOM Key Features

Highly Key Component Redundancy

Reliable
- Base, CPU, Control Network, Expansion
module, Expansion bus

DCS inherited high reliable design


- ECC memory on CPU Module
- No Chip on base board
- No Fan Architecture

RAS Feature embedded


- CPU status, temp,
internal bus
- Analog input module
detects disconnection
and short circuit by
checking loop status

RAS: Reliability, Availability and


Serviceability

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
13
14
STARDOM Key Features

• Hot swap function enables module


Easy replacement without stopping
Maintenance
Hot Swappable Modules
control.

Application, data are automatically


copied to stand-by side

CPU Replace

Remove terminal block for disconnecting Replace New I/O module and
field wirings. attach terminal block. Tools not required
IO Replace (No need to disconnect each field wiring)
IO definition automatically copied

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
14
15
STARDOM Key Features
• Supports high quality software parts or templates that reduces engineering efforts
and improved reusability.

Ease
• Utilizes global standard IEC 61131-3 (five programming languages).
• Tag-based definitions simplify engineering and re-mapping of tags or memory
address assignments are not required.
of Engineering &
• Supports Function Block Diagram, Ladder Diagram, Structured Text, Instruction List
Maintenance
and Sequential Function Chart

Function Sequential
Ladder Instructio
Block Function Structured
Diagram n List
Diagram Chart Text (ST)
(LD) (IL)
(FBD) (SFC)

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
15
Stardom New Features (E2bus)

E2 bus
Interface Module
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
16
Stardom New Features (E2bus)

E2 bus
Interface Module

1
9
2
7 or 9
8
3
4 7 4
With one CPU module, 5
the maximum number
of units that can be 6 2
controlled is three times
greater (9 units), and the
maximum number of modules
is 79.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
17
Stardom New Features (E2bus)

E2 bus

Duplex bus High environmental Resistance


(-20 to 70 Deg C)
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
18
Stardom New Features (Wireless I/O)

FN110
Field Wireless
Communication
Module

#1

LN90
Interface Adapter

#2

500 m #20

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
19
Stardom New Features (Wireless I/O)

Wireless communication Specification


Protocol ISA100 WirelessTM (IEEE802.15.4)
No. of Wireless devices Max. 20 units
Topology Star
Reachability Up to 500 m distance
Update time 1, 2, 4, 8, 16, 30sec, 1, 2, 5, 10, 20, 30, 60min

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
20
FCN-500 Hardware Configuration

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
21
Power Supply
Module
Power Supply
Module

FCN-500
CPU Module
FCN-500 Configuration

IO Module FCN-500
IO Module CPU Module

1
IO Module

22
2
IO Module
3
IO Module

© Yokogawa Electric Corporation


| Document Number | June 1, 2017 |
4

IO Module
5

IO Module
6

IO Module
 Duplex Power & CPU Module, 1 node
FCN-RTU Hardware Configuration

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
23
Power Supply
Module

FCN-RTU CPU
Module

1
IO Module

2
IO Module

3
 Short Base

IO Module
 Single Power
FCN-RTU Configuration

Power Supply

24
Module
Power Supply
Module

© Yokogawa Electric Corporation


| Document Number | June 1, 2017 |
FCN-RTU CPU
Module
1

One Base Unit only, no expansion IO Module


2

IO Module
3

IO Module
 Long Base

IO Module
5

IO Module
 Duplex Power

IO Module
7

IO Module
8

IO Module
Applications and Industries

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
25
26
Broad Range of Applications and Industries

Energy Oil & Gas Water Chemical Mining


• Geothermal • Offshore/On • Water/Wast • Poilymer • Materials
Well shore ewater Ratio Handling
Monitoring Production Treatment Mixing System
• Solar • Water • Distribution • MSG • Crushing
Injection • Irrigation • Alcohol
Thermal • Ore
• Terminal • Flood Plant Grinding
• Power Automatio Warning • MMA • Flotation
Monitoring • Oil/Gas System Synthesis
• Wind Pipeline • Leach &
• Sludge • Ammonia CIL
Turbine • NG Incineration pipe leak
SCADA Distribution • Tailing,
• Water Gate detection
Lube Oil Dewatering
• Heat/CO2 Valve • Air
Recovery Control • Acid Wash,
Fiscal Separation
• Metering Elution,
Metering • District • Bakelite Refining
• Dispensing Metering Powder
Station Area • Dispensing
Bays
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
26
27
Broad Range of Applications and Industries

Iron & Transportation Paper Other


Steel • Power Monitoring • Water Applications
• Weighing • Interface to GIPAM Extraction • Distillery
Control & (diGital Integrated • Paper • Starch
Monitoring Protection & Compressor Production
• Rotation Monitoring skid • Centrifugal
Rack Equipment) • Screening Control
• Coke Oven • Tram location • Washing • Cyber Sea
• Continuous monitoring • Bleaching • Milk Production
Casting • Traffic • Effluent (Pasturisation)
• Reheat Management Treatment • Protein
Furnace System Extraction
• Various • Flare Control
Utilities • Aviation
• Environment
Monitoring

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
27
28
Applications For Remote Autonomous Processes
Small Compressor Stations Interlock on Pig/Scraper Loading Terminals Intermediate Oil Storage

Annotation Annotation Annotation Annotation

Block Valve Stations Gas Dehydration

Annotation Annotation

Intelligent RTU/PLC

Reduction/Metering Line Heaters Nitrogen Injection Oil / Gas Separators

Annotation Annotation Annotation Annotation

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
28
STARDOM’s New E2Bus
Module – Architecture
Solution for Wide Area
Distributed IO System

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
29
30
Concept of FCN-500 Extension Bus Enhancement
In 2016, the STARDOM PLC FCN-500 was released with the concept of
“Faster, Stronger Smarter.” Now, the FCN-500 is scalable with a new
extension bus, the E2 bus. With the new E2 bus, the powerful CPU
module of the FCN-500 demonstrates its true value.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
30
31
FCN-500 Extension Bus Enhancement Overview
 E2 bus, a new extension bus for the FCN-500

 Features
 Applicable to large system
 Three times the max. number of I/Os E2 bus interface
module
 Distributed I/O
 Transmission distance extended
 Flexible arrangement
 Select from various sizes of base module
 High reliability
 Redundant bus
 High maintainability
 Online module exchange
 RAS Information
 High environmental resistance
 Withstands temperatures from -20 to 70 ℃

Note: The E2 bus cannot be used together with an existing SB bus repeat module.
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
31
32
E2 Bus: List of Newly Released Models

Product Model Overview

E2 bus interface module N2EB100 Extends the FCN-500 unit

Base module (short, for E2 bus) Base module with available 5


N2BU051
(alias: Short base module) slots for the FCN-500 E2 bus

Base module (compact) Base module with available 3


N2BU030
(alias: Compact base module) slots for the FCN-500 E2 bus

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
32
33
E2 Bus Interface Module
 Newly released: E2 bus interface module
 Used to extend units of the FCN-500
 Model: N2EB100
 Master and slave function in a Unit number setting (rotary switch)
1: Control unit (master module)
single module
2–9: Unit number of extension unit
 2 modules required for (slave module)
duplex bus configuration on one
base module
 Off-the-shelf cable and connector * Upstream towards master module
 UTP straight cable CAT5e or higher
 Ethernet cable
 RJ-45 connector
PORT1/UP Upstream unit
Master module: Used as the first line
Slave module: Connects to the upstream*
unit
Downstream unit
PORT2/DOWN
Master module: Used as the second line
Slave module: Connects to the
downstream unit Front of module
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
33
34
E2 Bus Feature: Supports Large Systems
 Three times the maximum I/Os of the SB bus system
 Max. number of extension units: 8
 Max. number of I/O modules: 79 (with single CPU and single E2 bus)
 68 modules with duplex CPU and duplex E2 bus
 The number of CPU modules can be reduced for large systems
 The powerful CPU can handle larger systems within a short task period
 Reduced hardware and engineering costs

Max. I/O configuration example CPU load comparison between NFCP100 and NFCP50x
Former CPU
SB bus E2 bus (NFCP100)
NFCP501/502
+ E2 bus
(3 units) (9 units) + SB bus
Task period 100 msec
AI 96 288
AO 32 96
DI 256 768
DO 256 768
PID loop 32 96
Total I/O 640 1920
CPU load 69% 22% 57%

Recommended to (duplex CPU)


be less than 60 %

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
34
35
E2 Bus Feature: Distributed I/O
 Transmission distance between units: 100 m
 Max. total transmission distance per line: 800 m (with 8 extension units)
 Extension units as remote I/O
 Greatly reduces wiring cost compared with wiring all signals to the control unit

SB bus E2 bus
Max. 8 m / line Max. 100 m / between units
Control unit First line

100m
8m
Second line

Extension units can be distributed across


control panels or buildings.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
35
36
Option: Fiber Optic Cable Conversion
 Convert the system from Ethernet cable to fiber optic cable
 Using third parties’ media converters (repeater type) and fiber optic cable
 Extends the transmission distance
 Max. total transmission distance: 5 km per line
* Transmission distance between media converters follows the converter specification.
 Eliminates the effects of noise on the cable

Note: Refer to the Yokogawa Web site below (registration required) for the verified media converters.
“System Requirements” => “Verified Peripherals ”page in the “YOKOGAWA Partner Portal STARDOM” site.
https://partner.yokogawa.com/global/member/rtu/peripheral/index.htm
Refer to the TI 34P02Q91-01E “FCN/FCJ Installation Guide” for installation precautions.

Water treatment plant Water intake

Media converter Media converter

Fiber optic cable Ethernet cable

Ethernet cable

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
36
【2. Release Information】
37
System configuration example using fiber optic cable
Media Converter Ethernet cable Fiber optic cable

example Total distance of first line: 4km


2 km 2 km

1 km 2 km 2 km

Total distance of second line: 5 km

Out of support example The distance between media converters must be within the converter
specification.
Only a pair of media converters can be used * For the verified converters, the distance is up to 2 km. (As of April 2018)
between two units.
3 km

Media converters must be no more than 3 pairs per line.

2㎞ 2㎞ 1㎞ 1㎞

Total distance of second line: 6 km


The total transmission distance per line must be within 5 km.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
37
38
E2 Bus Feature: Flexible Arrangement
 Select from various sizes of base module
 Compact (new), short*1, and long base modules can be used as both control and
extension units depending on the installation space and/or required number of I/Os
 E2 bus can be duplexed*2
 2 lines of daisy-chain connection
 Each of two E2 bus master module ports can be used as a separate line
 With 2 lines, up to 8 extension units can be connected (or all 8 units on 1 line)
*1 Please use the N2BU051 (new) as a short base module. The NFBU050 does not support the E2 bus.
*2 When the compact base module is used as a control unit, the E2 bus cannot be duplexed.

System configuration example Second line extension units


First line extension units

Control unit

Master module

Space in the control panel can be used effectively by selecting the appropriate base module

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
38
E2 Bus Feature: High Reliability
 Duplex configuration
 Operation can be continued even if the E2 bus interface
module or cable fails
Note: If the power to the extension unit goes off, communication to the
downstream extension units is also lost

Option of the duplex bus


Ring like topology is available by connecting 2 busses
in the opposite direction

Even if the power to one extension unit goes off, the connection
between the control unit and the other units can be maintained.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
39
40
E2 Bus Feature: High Maintainability

 Same FCN-500 Maintainability


 Remote I/O modules have the same maintainability as conventional I/O modules
 I/O modules and E2 bus interface modules are hot-swappable

 System information

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
40
41
E2 Bus Feature: High Environmental Resistance

 Ambient temperature range of the E2 bus interface module: -20 to 70℃


 Unit extension and remote I/O distribution are possible in harsh environments

SB bus E2 bus
The control unit by itself supports a Even with multiple unit configuration, each
temperature range of -20 to 70℃
unit supports the wide temperature range of
-20 to 70℃

In case of multiple unit configuration,


the temperature range is 0 to 55℃

*Ambient temperature range of all the modules in the unit must be


-20 to 70℃. Some modules have installation restrictions.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
41
42
Short Base Module for E2 Bus
 Added short base module for E2 bus
 Model name: N2BU051
 NFCP501/NFCP502 + E2 bus configuration is
available
 Works as either control or extension unit
 Same size as existing short base module
 The NFBU050 is mainly used as a low power
consumption, high environmental resistance base 5 slots for CPU, I/O and
module for the FCN-RTU CPU 1 slot for
E2 bus I/F modules
power supply

Short base module key spec comparison Seal for identification


Base module (short) Base module (short, for E2 bus)
Model NFBU050 N2BU051
Current consumption 25 mA 35 mA
Available CPU NFCP050, NFCP100, NFCP501, NFCP502 NFCP501, NFCP502
Internal bus redundancy × ○
E2 bus support × ○
Ambient temperature range -40–70℃ (only with NFCP050) -20–70℃

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
42
43
Compact Base Module
 Added new compact base module to the FCN-500 *1 lineup
 Model name: N2BU030 Comparison with FCJ
 Compact size with 3 slots Compact base module

 E2 bus is available
 Works as small footprint control unit or remote I/O
 Duplex E2 bus is available for extension units*2
 Can be used for FCJ  FCN-500*3 replacement
 Same width as FCJ*4

Control unit 1 Slot for


power supply
3 slots for CPU, I/O
and E2 bus I/F modules
Extension unit

FCJ

*1 NFCP050 (FCN-RTU) is NOT available. Future support is under consideration.


*2 Duplex E2 bus is NOT available as a control unit.
*3 Deeper than the FCJ. Not all FCJs can be replaced due to differences in I/Os.
*4 When replacing panel mounted FCJ, the mounting hole for the FCJ can be utilized.
See TI 34P02Q91-01E “FCN/FCJ Installation Guide” for the detail.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
43
Introduction of FCN500

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
44
STARDOM Release

STARDOM Renewal
New FCN-500 CPU release
■Higher performance
■Simplified operation
■Higher reliability
- New FCN CPU release
- Engineering tool
Engineering tool enhancement
enhancement
■Logic Designer enhancement
- Communication function
enhancement R4.02/R7.50
- Enhancement for upstream market (2016/4 FD)
- PC environment enhancement
- FCN-RTU enhancement for
R3.50/R7.40 ※R4.01 is for specific
upstream market
(2015/6 FD) customers
- PC environment enhancement

R3.20/R7.10 - FCN/FCJ enhancement for R3.40/R7.30


(June, 2012 FD) upstream market (Software FD: Mar., 2014)
- VDS viewer enhancement (Hardware FD: May, 2014)
- New modules for power
/ upstream market R3.30/R7.20
- IT security (March, 2013 FD)

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
45
FCN-500 CPU Module
 Newly released models
 NFCP501(with 2 Ethernet ports)
 NFCP502(with 4 Ethernet ports)
(In this presentation, “NFCP500” refers to the NFCP501 and NFCP502)
Faster
 Features
 Higher performance
 Faster CPU
 More networks
Stronger
 High speed communications
 Higher reliability
 Wider operation temperature coverage
 Heightened protection
Smarter
 Improved file system
 Simplified operation
 Simplified quotation
 Shortened startup time
 Simplified redundancy Strengthens your core
 PC-less maintenance
competencies!
| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
46
FCN-500 CPU Module Appearance
Same size as NFCP100
Switches and LED for
maintenance operations
CPU cover

Ethernet ports 3 and 4


(NFCP502)

SD LED
SD card slot

Wire lock hole


Battery Without CPU cover

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
47
Comparison Between NFCP500 and NFCP100

Item NFCP501/NFCP502 NFCP100


CPU Atom E3815 1.46 GHz MMX-Pentium 166 MHz
Memory Main 256 MB* with ECC 128 MB with ECC
Static 2 MB with ECC, backed up by battery 1 MB with ECC, backed up by battery
RAM (retained data area: max. 700 KB) (retained data area: max. 410 KB)
System card No need 1 slot (CF)
Removable media 1 slot (SD), for maintenance -
Verified SD Memory Cards :SanDisk
SDSDXS-016G, SDSDB-008G, SDSDB-004G
Serial port RS-232-C, 1 port <-
Network I/F 1000/100/10 Mbps Ethernet, 4 ports 100/10 Mbps Ethernet 2 ports
(NFCP502) or 2 ports (NFCP501)
Battery Li battery (online exchange available) Li battery (online exchange unavailable)
Duplex configuration Available (without dedicated license) Available (with dedicated license)
CPU cover With wire key hole -
Ambient temperature 0° to 55°C (standard type) 0° to 55°C
(Operation) -20° to 70°C (extended temperature
range type)

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
48
Comparison Between NFCP500 and NFCP100 (Function)

Software NFCP NFCP Remarks


500 100
Basic Functions
Control, engineering functions OK OK IEC61131-3, Logic Designer (IEC engineering tool)
Java functions △ OK WWW server, e-mail, FTP client/server, logging, user Java
application development environment using PPP functions
Option Functions
APPFs 1 OK OK (With Standard Functions)
Communication: FA-M3, MELSEC, SYSMAC, Modbus, DNP3
(With Extended Functions)
In addition to the above APPFs, PAS and Gas Flow
Calculation*1
APPFs 2 *2 ー OK SAMA, General, Temperature controller communication, Power
monitor communication, Boiler control, Boiler auxiliary control
InfoWell △ OK Web application, E-mail application, Graphic, Logging
User application development kit △ OK Java application development kit
Webmetry basic library △ OK Libraries creating web-based monitoring applications

OK: Ready △:Future plan ー: No release plan


*1 Excluding parameter setting window and report file functions (logging)
*2 These APPFs will be opened as samples to ensure compatibility with the NFCP100

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
49
Simplified Setup and Maintenance

 Current challenges of FCN-100/FCJ


 Because of the complicated license system, making estimates and
product setup are burden for sales persons or engineers.
 Difficulty of making estimates
 Engineer’s hesitation due to complicated setup procedures
 High total cost by adding license fee for each

In order to solve the above challenges,


controller software licenses are bundled in
advance.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
50
Simplified Quotation Process
Previous CPU New CPU
[Option license]
(NFCP100,NFJT100) (NFCP500)
PAS

FA-M3 No need to select licenses


Select option * These licenses and basic software
MELSEC licenses are embedded in HW in advance.
SYSMAC

Modbus

DNP3
オプション
AGA オプション
ライセンス
Option
ライセンス
license Embedded
・・・ licenses
Basic Select CPU
Select basic license
Software type only [HW]
[Basic license] License
CPU
Single (Standard)
CPU CPU
Duplex CPU
Select HW Base, PU, Base, PU, (Extended)
IO IO
[HW] Base

CPU PU, IO,



Base
Easy quotation process
PU, IO,
… Simple, easy to understand

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
51
STARDOM Release

 Software licenses are selectable NFCP50x- NFCP50x-


APPF Sxx Wxx
by suffix code (Standard) (Extended)
 NFCP50x-Sxx: Standard functions PAS - ○
 IEC61131-3 based controller with
FA-M3 comm. ○ ○
communication functions
 NFCP50x-Wxx: Extended functions MELSEC comm. ○ ○
 In addition to the standard functions, SYSMAC comm. ○ ○
PAS, Gas Flow Cal., InfoWell (future)
Modbus comm. ○ ○
Caution: licenses cannot be added later on. If you
are not sure about the licenses to be used, the DNP3 comm. ○ ○
extended functions model is recommended.
Gas Flow Cal. - ○(*1)
InfoWell - △
 Common functions Others(*2) ー ー
 CPU module duplex, SNTP server/ ○: Support, -: No support, △:Future plan
client, and FOUNDATION Fieldbus *1. AGA logging and web setting windows are not
supported at release time
module duplex are configurable. *2. APPFs below are out of support and opened as samples
to ensure compatibility with the NFCP100
SAMA, General, Temperature Controller
Communication, Power Monitor Communication,
Boiler Control, Boiler Auxiliary Control

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
52
Simplified Redundancy
 For duplex CPU module configuration, just install 2 of the same
CPU modules.
 Simple select checkboxes on the Resource Configurator and set DIP
switches on the base module.

Same type of
modules

 Restriction on duplex CPU configuration


 Modules must be of the same type and suffix code of CPU module.
A paring of the NFCP501 and NFCP502 is not allowed for duplex CPU.
Bundled basic software license is common for single and duplex
CPU module configuration

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
53
Simplified Redundancy
 For duplex CPU module configuration, just install 2 of the same
CPU modules.
 Simple select checkboxes on the Resource Configurator and set DIP
switches on the base module.

Same type of
modules

 Restriction on duplex CPU configuration


 Modules must be of the same type and suffix code of CPU module.
A paring of the NFCP501 and NFCP502 is not allowed for duplex CPU.
Bundled basic software license is common for single and duplex
CPU module configuration

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
54
Simplified Setup
License must be set up No need to set up licenses
< Previous CPU (NFCP100,NFJT100) > < New CPU (NFCP500) >
STARDOM
License Server (web)

Web site access


-> Input order ID
Download license files for
information
every FCx
Order ID
sheet Set IP address

License
files
Set IP address

Download license to each FCx

Setup is much more efficient

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
55
Easy Maintenance : Battery Replacement
 Hot-swapping battery
 The battery can be removed and installed from the front side of the CPU
module
 The battery can be replaced without stopping control

Previous New CPU


CPU (NFCP501, NFCP502)
(NFCP100)

The battery is
on the back-side

New CPU detects the discharged battery


A system alarm will be generated

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
56
Faster CPU
 5 times faster than the previous model
 A faster CPU means faster processing
 Turbomachinery
 Compressors
 Conveyors
 Flow calculation
 Wind power generation, etc.
 Various solutions can be implemented in addition to complicated
control applications
28 ms
NFCP500 Room for additional solutions*
■ I/O access
I/O処理時間
■ SRAM
141 ms SRAMアクセス
access
■ PID Calc.
PID演算
NFCP100

CPU load
NFCP500 19%
0 20 40 60 80 100 120 140 160 NFCP100 95%
(CASE Study: 120 PID loops with 150 msec scan rate on redundant CPU)
* Environments for additional solutions will be provided in the future.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
57
Network Interface Enhancement

 New model with 4 Ethernet ports: NFCP502


Port Functions
・ Dual redundant control network can be used (between
several FCN/FCJ units, and between an FCN and VDS ← Same functions
1, 2 as the NFCP100
*)
・ Single and separated configurations are also available
・ For separated networks [ NFCP502 ]
3,4

*Dual redundant network between an FCN and FAST/TOOLS can be


used with any combination of ports of the NFCP502

 Enhanced communication speed Port 4


 Up to 1 Gbps Port 3

Port 2
Port 1

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
58
More Networks
 More flexible network configuration with additional ports
 Communication processing is improved thanks to a powerful CPU

Ethernet port 3 and 4


(NFCP502)
Control network
Dual redundant
control network must Redundant control network
be connected to the
port 1 and 2

Independent network
Exclusive port for
on each port
engineering or maintenance
Field network Redundant field network*

VJET Engineering PC

FA-M3V Remote I/O HMI

* User application is required for redundant field network

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
59
Improved Environmental Resistance
 NFCP500 ambient temperature range during operation
 Standard type: 0 to 55 ℃
 Extended temperature range type: -20 to 70℃

FCN-500 ambient temperature range


CPU type Ambient Conditions
temperature range
FCN-100 NFCP100 0 to 55℃ -

Upcoming NFCP50x-x0x (Standard) 0 to 55℃ -


model
NFCP50x-x1x (Extended At least one module with a
temperature range) 0 to 55℃ temperature range of 0 to 55℃ is
included
All power supply and IO modules’
-20 to 70℃ temperature range must be -20 to
70℃

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
60
STARDOM Release
Standard temperature range (0 to 55℃)
Single CPU configuration Duplex CPU Short base configuration
Max. 25 IO modules configuration Max. 3 IO modules
Max. 20 IO modules

NFSB100

NFSB100
NFSB100
PWM

PWM

PWM

PWM
DMY

CPU

CPU

CPU

CPU
IOM
IOM
IOM
IOM
IOM
IOM
IOM

IOM
IOM
IOM
IOM

IOM
IOM
IOM
NFBU200 NFBU200 NFBU050
NFCB301 NFCB301

NFSB100

NFSB100
NFSB100
PWM

PWM
PWM
DMY

IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM

IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
NFBU200 NFBU200

NFCB301 NFCB301
NFSB100

NFSB100
NFSB100
PWM

PWM
PWM
DMY

IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM

IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
NFBU200 NFBU200

Extended temperature range (-20° to 70℃)


Single CPU configuration Duplex CPU Short base configuration
Max. 8 IO modules configuration Max. 3 IO modules
Max. 6 IO modules
NFPW444

NFPW444

NFPW444

NFPW444
NFCP500

NFCP500

NFCP500

NFCP500
DMY

IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM

IOM
IOM
IOM
IOM
IOM
IOM

IOM
IOM
IOM
NFBU200 NFBU200 NFBU050

Some modules have installation restrictions


| Document Number | June 1, 2017 |
© Yokogawa Electric Corporation
61
Heightened Protection
 CPU cover
 Switches, SD card slot, and battery on the right side of the CPU module
can be protected with a CPU cover
 CPU cover can be locked with a cable lock
< With CPU cover> < Without CPU cover>

CPU Cover
Wire lock hole

 SD card access restriction to prevent unauthorized access


 Protection can be selected from three levels Protection level
 Any SD card can be used Low
 Only SD cards with password authentication are available
 SD cards cannot be used High

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
62
Improved File System Stability

 Embedded flash memory (SSD 1 Gbyte) instead of system card (CF)


in the FCN-100/FCJ

 Stable file system


 Even in case of a sudden power failure, important user data is secure.
 Files and directories are fully protected.
 The robust file system is field-proven in the FCN-RTU and protected
even in harsh environments for long years.

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
63
Thank you !

| Document Number | June 1, 2017 |


© Yokogawa Electric Corporation
Co-innovating tomorrow is a registered trademark of Yokogawa Electric Corporation. 64