Combined Osp-Pds Sow-Aljouf-Checkpoint
Combined Osp-Pds Sow-Aljouf-Checkpoint
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
CHK’D
DESCRIPTION
ATTACHMENT-1
NO.
DOCUMENT
PREPARED BY
SZS OSP/PDS-LAN-WAP
DATE
CHK’D BY
SCOPE OF WORK &
APPROVED
CONSTRUCTION SPECIFICATIONS
ITC/PPD/PROJS. ENGG DIV.
DDC for
JGT
ASU
BY:
DATE:
THIS DOCUMENT IS
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 1
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
TABLE OF CONTENTS
CHK’D
CHK’D BY
2.3 DOCUMENTATION
APPROVED
PART 3 - BASIC REQUIREMENTS AND GUIDELINES
ITC/PPD/PROJS. ENGG DIV. 3.1 GENERAL CONDITION
3.2 CONSTRUCTION PROGRESS REPORTING
DDC
3.3 MATERIAL TESTS AND INSPECTION
JGT 3.4 AS-BUILT DRAWINGS
3.5 PROJECT RECORD BOOKS
3.6 OUTAGE SCHEDULE/SHUTDOWN COORDINATION
3.7 SAFETY REQUIREMENTS
3.8 QUALITY ASSURANCE/QUALITY CONTROL REQUIREMENTS
3.9 NON-DISCLOSURE AGREEMENT (NDA) AND Declaration of Non-Disclosure
Agreement (DND)
PART 4 - MATERIALS
4.1 OUTSIDE PLANT
CERTIFIED
4.2 INSIDE PLANT/STRUCTURED CABLING SYSTEM (PDS-LAN-WAP)
ASU 4.3 APPROVED MANUFACTURERS
BY:
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 2
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
DOCUMENT
SZS
PREPARED BY
DATE
CHK’D BY
APPROVED
DDC
JGT
CERTIFIED
ASU
BY:
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 3
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
DIVISION 16 - ELECTRICAL
CHK’D
DOCUMENT
This Project also provides the requirement for Construction of Inside Plant Telephone Cabling
SZS System, LAN-Premise Distribution System/Structured Cabling Systems for Voice & Data, New
PREPARED BY
Checkpoint – from the respective IT & Communication Room to the end users locations through
information outlets, Copper (UTP Indoor Type Cable) and its associated Data Cabinets, Joint
DATE
CHK’D BY
Boxes, Protectors, Data Distribution Panels and Conduits, Pull-Boxes, Junction Boxes,
Information Outlets, Dedicated Power Supply, Grounding System and other accessories for the
construction of Inside Plant Cabling Infrastructure, for Proposed New CHECKPOINT BUILDING
APPROVED
3). CONTRACTOR shall provide & Install the complete OSP/PDS-LAN-WAP cabling
CERTIFIED AND DATED
solution for IT & Communication related works whether shown or not shown in the
approved Detailed Drawings.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 4
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
and restoration after completion of civil work. (Refer to Drawing No. EA-896829, EA-
896830, EA-896831)
5). CONTRACTOR shall provide & construct a new & Dedicated Communication
Manholes for ITC use only and shall include Manhole Frame & Cover, Hardware &
DESCRIPTION
DATE
following section:
CHK’D BY 7.1 From new Checkpoint Bldg. to ITC Equipment Room located in Existing Admin
Building.
APPROVED 8). Furnish, supply and installation marker post and surface marker, joint boxes & heat
ITC/PPD/PROJS. ENGG DIV. resistance marker tag.
9). Supply and Installation of 1 each x 12 Core Fiber Optic Cable, Single Mode-Non
DDC
Metallic from New Checkpoint Bldg. to ITC Equipment Room located in Existing
JGT
Admin Building. All Fiber/Core shall be all splice with pigtail & terminated all in the
New F.O. Patch Panel, High Density 1U Sliding Fiber Panel & Cassette Type 12-LC-
Single Mode Blue with Pigtails iPatch Ready.
10). The new OSP Type Fiber Optic Cables shall be provided and install to interconnect
the New Checkpoint Building (IT&C Data Cabinet) having a physical “STAR”
Topology scheme.
11). Perform Fiber Optic Cable splicing using Fiber Cassette 12 LC Single mode Blue
iPatch ready with Pigtails & terminated all in High Density 1U Sliding Fiber Panel at
both end location for the following buildings:
CERTIFIED 11.1 New Checkpoint Building
ASU 11.2 Existing Admin Building (ITC Equipment Room)
BY:
12). Supply & installation of pre-terminated LC Duplex Type Fiber Patch Cables. The
quantity shall be provided for each section or link & multiply by four (for Outdoor
DATE:
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 5
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
(FM/TSD) or SEC-Project Proponent/User for the exact location & installation of the
said Special Purpose Information Outlets as needed.
2) The Outdoor Type Fiber Optic Cable, Non-Metallic Type with 12 Core minimum from
service entry pipe to Data Cabinet shall be installed in a 25.0 mm diameter Plenum
Type Corrugated Sub-Duct or Wrap with Fire Retardant Tape inside the IT&C Room
of New Checkpoint Building & Existing Admin Building. All Fiber/Core shall be all
splice with pigtail & terminated all in the F.O. Patch Panel.
NO.
DOCUMENT 3) Supply & install Information Outlets (Simplex/Duplex/Quadplex Type) for Voice/
Data, Wireless Access Points and Special Purpose Outlet for the New Checkpoint
SZS
PREPARED BY
Building. The proposed Special Purpose Information Outlet that are not shown in the
DATE approved layouts shall be coordinated to the assigned SEC-Project In-Charge
CHK’D BY (FM/TSD) or SEC-Project Proponent/User for the exact location & installation of the
said Special Purpose Information Outlets as needed.
APPROVED 4) Furnish, Supply & installation of CAT-6A UTP Cable (Voice/Data, Wireless Access
ITC/PPD/PROJS. ENGG DIV. Point Locations & S.P.O.) from new Data Cabinet to various Information Outlets
DDC within the New Checkpoint Building. All Cable Pairs (Indoor & UTP Copper Cables)
shall be terminated at Patch Panel and User Outlet location.
JGT
5) Supply, installation of rack mounted 19” UTP modular CAT-6A Type Intelligent Patch
Panels (CATEGORY 6A U/UTP PATCH PANEL) equipped with 12 Ports RJ45
modules/jacks inside equipment distribution cabinet in New Check Point Building.
6) Furnish, supply and installation of all support cabling structure (i.e. EMT Conduits,
Cable Raceways etc.).
7) Supply, installation of front access New 12U-Data Cabinet /Equipment Distribution
Cabinets (Racks, Rittal Type). The New Data Cabinet shall accommodate all active &
non-active components with space free for future expansion and subject for SEC-ITC
Planning & Projects Dept. for review & approval. (See Material Specification in Part 4).
CERTIFIED
8) Utilize the Existing 42 U Type Data Cabinet and Supply & install one(1) each rack
ASU mounted 19 inches fiber optic Intelligent HD 1U sliding fiber panel equip with one (1)
BY:
DATE:
each –Fiber Cassette 12 LC Single mode Blue iPatch ready complete with splice trays
and horizontal cable management rack to be installed at Existing ITC Room, Admin
Building. All Fiber/Core shall be all splice using Fiber Cassette 12 LC Type, Single
Mode Blue iPatch ready.
9) Supply of pre-terminated Category 6A UTP Patch Cables on both ends (1.5 Meters on
equipment Side & 3 to 5 Meters on User Side). The quantity shall be based on the
number of Information Outlets installed.
THIS DOCUMENT IS
NOT TO BE USED FOR 10) Supply and Install Grounding systems (Main Ground Busbar & Telecom Ground
CONSTRUCTION
FOR
OR
ORDERING Busbar) dedicated for IT& Communications Equipment.
MATERIALS UNTIL
CERTIFIED AND DATED 11) Supply of pre-terminated LC Duplex Type Fiber Patch Cables. The quantity shall be
provided for each section or link & multiply by four (for Indoor Cabling).
12) Tagging of cables and labeling of panel boards, cabinets and other ITC Equipment.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 6
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
13) Section Test of UTP Cables using SEC approved Test Equipment. All cable test
CHK’D
A.4.1 The Contractor shall provide/install/construct New Manholes & Conduit Systems,
as provision to interconnect the New Checkpoint Building to the Existing Admin
Building.
NO.
DOCUMENT A.5 CONTRACTOR shall supply and delivery of all permanent and expandable materials, tools
and equipment to complete the WORK.
SZS
PREPARED BY
A.6 CONTRACTOR shall be responsible for providing equipment and personnel required to
DATE
transport/deliver material to WORK SITE. SEC-ITC/Planning & Projects Dept.-Projects
CHK’D BY Engineering Division PRIOR shall submit the proposed Material & Equipment for the project
for review & approval to purchasing, delivery & installation of any IT&C related Equipment
APPROVED or Material.
ITC/PPD/PROJS. ENGG DIV. A.7 CONTRACTOR shall be responsible for providing equipment and personnel required to
DDC transport/deliver the material to the WORK SITE.
JGT
A.8 CONTRACTOR shall perform WORK in accordance with the requirements of this SECTION. The
COMPANY REPRESENTATIVE shall approve deviation in writing prior to implementation.
A.9 The CONTRACTOR shall perform complete Civil, Structural, Cabling Works, Installation, Testing
and Commissioning.
A.10 The CONTRACTOR shall supply all Communication Cabling, Civil Works and Materials required
completing this project whether or not shown in this SECTION or Drawings, unless otherwise
specified.
A.11 CONTRACTOR shall provide a dedicated Cabling System for Security Camera (CCTV) and Fire
CERTIFIED
Alarm Systems separate from ITC Cabling Infrastructure.
ASU
BY: END OF PART-1
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 7
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
shall only do construction Works. Refer to Part-9 for the List of these ITC-Approved
Contractors.
B. The Contractor shall be responsible for all work involved to accomplish the establishment and
provision of the complete IT & Communication Systems Facilities (Voice/Data, Wireless Access
Points and Special Purpose Information Outlet), which includes the survey, documentations,
supply, delivery, installation, testing, and commissioning.
NO.
DOCUMENT
C. All materials, equipment, and accessories needed for the successful installation of the complete
SZS IT & Communication Systems Facilities (Voice/Data, Wireless Access Points and Special
PREPARED BY
Purpose Information Outlet) for this Project unless otherwise specified, shall be new and
unused and shall be provided by the CONTRACTOR.
DATE
CHK’D BY
CERTIFIED
The electrical system shall be installed in accordance with the latest edition of American/or
International Standard and COMPANY Standards. In case of any discrepancy between the
ASU
BY: COMPANY Standards and any other standards, COMPANY Standard shall prevail.
3. WIRES AND CABLES
DATE:
a. All interior power, branch circuits and control wires shall be copper, stranded, Polyvinyl
Chloride (PVC) insulated, thermoplastic material, 75C maximum operating
temperatures, heat moisture flame resistant and rated 600V. Size of wire for power
lighting shall be No. 12 AWG and signal/control wires shall be No. 14 AWG.
THIS DOCUMENT IS
NOT TO BE USED FOR
b. All cable joints shall be made electrically and mechanically secured with approved wire
CONSTRUCTION
FOR
OR
ORDERING
(nut) connectors, then covered with two layers of insulating tape, covered with two
MATERIALS UNTIL
CERTIFIED AND DATED
layers of friction tape. All tapes shall be applied half wrap.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 8
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
c. During pulling of wires and cables, care must be exercised in pulling wires, into conduit,
CHK’D
not to kink the wire, put undue stress on the wire. No grease will be permitted in pulling
wires into conduit, soapstone or talc only being permitted for this purpose.
d. Wires Color Code
DESCRIPTION
Main service feeder (low voltage, power application other than for building):
A B C
Phase Conductors Red Yellow Blue
Neutral Black
Internal wiring (electrical wiring of building)
NO.
DOCUMENT
Phase Conductors Brown Red Orange
SZS
PREPARED BY
Neutral White
DATE
Grounding conductor Green with yellow Stripe.
CHK’D BY
e. All wiring shall be installed inside the conduits. All external wirings shall be rated for
APPROVED operation in 50C (122F), ambient temperatures.
f. Neutral Conductor or cable shall be the same size as the Phase conductor.
ITC/PPD/PROJS. ENGG DIV.
DDC
4. CONDUITS
JGT
a. Electrical metallic tubing shall be installed inside the building; minimum size shall be 20
mm. Diameter (3/4”).
b. The conduit shall run in the shortest straight runs whenever possible. Conduit runs
between lighting fixture and lighting fixture, fitting and fitting, lighting fixture and fitting
shall not contain more than four (4) quarter bends, including bends located at the
lighting fixture or fitting. All conduit bends shall comply with tables 346-10 of National
Electrical Code (NEC).
c. Seal and repair structures affected by conduit penetration.
CERTIFIED
5. JOINTS: All joints shall be made with standard couplings. The ends of all conduits shall be
ASU
BY: cut square, reamed, brought to a shoulder, threaded and red lead applied to male
DATE:
threads only. Running threads shall not be used.
6. INSTALLATION: Conduits and other parts of the electrical system, where exposed, shall be
painted to cover abrasions, wrench marks, or other damage to the original finish.
7. FABRICATION: All conduits bend in the JOBSITE shall have a radius not less than six
times the inside diameter of the conduits. Conduits shall be offset where necessary to
THIS DOCUMENT IS
enter the boxes of fittings perpendicularly or where required to improve the
NOT TO BE USED FOR
CONSTRUCTION OR
appearance of the WORK.
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
8. PULL BOXES:
a. Pull boxes with full removable cover shall be installed so that wires in them can be
accessible without removing any part of the building.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 9
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
b. Number of duplex type outlets shall be installed on floor and wall as required. The exact
location of general purpose outlet shall be coordinated with the equipment and furniture
arrangement for which they will be installed. Power outlets shall be rated 20 Amps. 220
volts. All the power outlets shall be flushed mounted.
10. MOUNTING HEIGHTS:
a. Power Outlets & Receptacle - As required (0.3 & 1.4 meter above finished floor)
NO.
DOCUMENT
b. Information Outlet or IP Telephone outlet - 0.3 to 0.5 meter above finished floor
SZS
PREPARED BY
B. COMMUNICATION WORKS:
DATE
B.1. OUTSIDE PLANT SYSTEM:
CHK’D BY
1. COMMUNICATION MANDHOLE & DUCTBANK INFRASTRUCTURE:
APPROVED
Construction of New Dedicated Communications Manhole, Handholes & duct bank
ITC/PPD/PROJS. ENGG DIV.
for all the AREAS as required and as specified herein:
a. Construction of Dedicated Communication Manhole & Duct Banks to route
DDC efficiently and systematically the proposed outside plant cables from main
JGT communications room to different buildings & other locations. These include
construction of concrete-encased duct bank, provision of sub duct, cable
entrance conduits, provision of pulling ropes, duct seals/plugs, cable
racks/support, marker posts & surface marker, labeling/tagging, warning tapes,
grounding systems, and others.
b. The proposed Communications Manhole & Duct Bank shall be constructed in
accordance with the Company Engineering & Constructions Standard.
c. The proposed 4.0” diameter PVC Conduit shall be encased in concrete (PVC
Conduit shall be “EB Type”). Concrete shall have a minimum compressive
CERTIFIED strength of 20.7 MPa (3,000 psi).
ASU
d. Manhole Layout shall include details of Frame & Cover, Cable Racks, Cable
BY:
Hooks, Grounding System, all hardware & accessories. Manhole Cover shall
DATE:
have an identifying mark “CAUTION & SEC COMMUNICATION” in English &
Arabic stamped in the cover.
e. Conduit Lateral configuration shall not have more than two 90 degree turns.
f. Conduit bends having less than a 36 inch radius shall not be used in conduit
laterals.
g. All IT&C Material Document Submittal shall be submitted to the Company (SEC-
THIS DOCUMENT IS ITC P&PD/Projects Engineering Div.) for review and approval prior to any
construction implementation.
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
c. Specify and show all the civil work and material requirements to provide a
standard OSP Cabling Infrastructure.
d. OSP Fiber Distribution Cables shall be provided with ID, i.e., length of cable,
NO.
CERTIFIED
j. Supply and Installation and cabling of Indoor Wireless Access Points with
watertight, dust-tight, and corrosion resistant material.
ASU
k. The Contractor shall insure that the quantity requirements meet for the outside
BY:
DATE:
plant cables to be distributed to different buildings and other different locations.
The quantity requirements shall consider both the current and future
requirements.
l. The new OSP network shall also include the installation/construction to
interconnect the outside plant tie cables for Saudi Telephone Company (STC)
THIS DOCUMENT IS
facility coming from the STC interface/distribution point.
NOT TO BE USED FOR
CONSTRUCTION
FOR
OR
ORDERING
m. Strategic Plan and Installation for the distribution of outside plant cable shall be
MATERIALS UNTIL
CERTIFIED AND DATED
done by the Contractor for the efficient utilization and management of
communications duct bank and cables.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 11
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
n. The distribution/routing, joints, and terminations of all Outside Plant Cables shall
CHK’D
p. All Materials shall be submitted to the Company (SEC-ITC Planning & Projects
Department / Projects Engineering Division) for review and approval prior to any
construction implementation
B.2. INSIDE PLANT / PREMISE DISTRIBUTION SYSTEM (PDS-LAN-WAP):
Construction, supply, installation, testing and commissioning of New Premise Distribution
NO.
DOCUMENT
locations:
SZS 1. The Contractor shall construct a new Premise Distribution System / Structured
PREPARED BY Cabling System for the New Checkpoint Building to economically, efficiently and
DATE
systematically route / distribute the Premises Cables / Inside House Cables to the
CHK’D BY
end users locations through information outlets. The installation shall specify and
show all the civil work and material requirements to provide a standard PDS-LAN-
APPROVED
WAP Cabling Infrastructure. These include installation of Data Cabinets, Data
Distribution Panels for UTP Copper (Copper (RJ-45) RSC-Conduit (Outdoor Riser
ITC/PPD/PROJS. ENGG DIV.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 12
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
8. All proposed Information Outlets for Voice & Data shall be provided with minimum of
CHK’D
one(1) spare per outlet for future use & maintenance purposes.
2.3 DOCUMENTATION:
DESCRIPTION
END OF PART-2
NO.
DOCUMENT
SZS
PREPARED BY
DATE
CHK’D BY
APPROVED
DDC
JGT
CERTIFIED
ASU
BY:
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 13
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
attention of the COMPANY (SEC-ITC P&PD/Projects Engineering Division) and shall obtain
3
DOCUMENT approval for such applicable requirements in writing from the COMPANY. The COMPANY
SZS reserves the right to reject any or the complete part of such WORK arising out of the
PREPARED BY CONTRACTOR’S own decision.
C. CONTRACTOR shall not procure any IT&C related materials until CONTRACTOR’s proposed
DATE
CHK’D BY
material for the project has been approved by the COMPANY (SEC-ITC Planning & Projects
APPROVED
Dept./Projects Engineering Division.
ITC/PPD/PROJS. ENGG DIV.
D. It is the CONTRACTOR’s responsibility to visit the WORK SITE and to satisfy himself as to the
DDC extent of the WORK, location and all conditions under which the WORK will be carried out. No
claims based on the lack of any such knowledge shall be entertained.
JGT
E. The CONTRACTOR shall furnish all WORK including services for the test and inspection
required by the COMPANY.
3.2 CONSTRUCTION PROGRESS REPORTING:
A. The CONTRACTOR shall submit Project Progress Reports to the responsible COMPANY
Project Engineer. The format shall be mutually agreed to between the CONTRACTOR and the
COMPANY REPRESENTATIVE.
Progress Report shall include:
a. Material Procurement and Delivery
CERTIFIED
b. Construction and Installation
BY:
ASU c. Testing and Commissioning
DATE:
d. Manpower and Equipment
e. Statement of items worked and/or completed during the reporting period.
f. Problem areas which can have adverse effect on the schedule
g. Overall Completion
h. Safety Meeting
may be decided by the COMPANY REPRESENTATIVE. All design (type) and production
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 14
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
B. The CONTRACTOR shall submit a detailed testing and inspection program to the COMPANY
CHK’D
REPRESENTATIVE for review, at least one (1) month before the commencement of testing.
The program shall include the Quality Assurance and Quality Control Monitoring Activity
Schedule.
DESCRIPTION
C. The COMPANY (SEC-ITC P&PD/Projects Engineering Division) reserves the right to reject any
materials proposed by the CONTRACTOR if the material does not conform to the specification,
or based on unsatisfactory past operating experience or any other reasons. In such cases, the
CONTRACTOR shall propose alternative material for review and acceptance by the
COMPANY.
D. CONTRACTOR shall not procure an IT&C related materials until CONTRACTOR’s proposed
NO.
material for the project has been approved by the COMPANY (SEC-ITC P&PD/Projects
DOCUMENT
Engineering Division).
SZS
PREPARED BY
3.4 AS-BUILT DRAWING
DATE
A. As the PROJECT nears completion, the “As-Built Drawings” shall be prepared by the
CHK’D BY
CONTRACTOR in sufficient details recording all Changes/Modifications and locations of
underground substructure or any sub-surface utilities that was identified and located in the field
during construction stages of the Project. The “As-Built” Drawings shall be prepared in
APPROVED
B. The “As-Built Drawings” shall be submitted to the COMPANY for review as to accuracy,
completeness, legibility and conformity to SEC Drafting Standards. If returned, the
CONTRACTOR shall make corrections and improve the quality as instructed prior to re-
submittal and COMPANY acceptance. The revised “As-built Drawings” shall be duly certified
and resubmitted to the COMPANY.
C. The As-Built Documents shall be submitted to the COMPANY within four (4) weeks after
Mechanical Completion of the PROJECT. As-Built Scope of Work and List of Materials shall be
included as part of the drawing.
CERTIFIED
ASU
BY:
DATE:
3.5 PROJECT RECORD BOOKS
The PROJECT Record Book shall contain the following documents as a minimum:
a. All calculation sheets.
b. Brief Technical Specification of all materials.
c. Material test reports of each major material installed.
d. All field test reports
THIS DOCUMENT IS
e. Commissioning and Site Test Reports
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 15
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
B. All outages shall be scheduled at least four (4) weeks in advance. Any requested outage must
be approved by the COMPANY at least two (2) working weeks before actual WORK is carried
out
DOCUMENT necessary precautionary measures for protection of construction worker and safety of general
public.
SZS
PREPARED BY
B. The CONTRACTOR shall comply with all the safety and loss prevention requirements under
DATE GI 65.111 relative to work permits and safe working procedures in substations, transmission
CHK’D BY lines and the requirements outlined in the schedule of contract document. The
CONTRACTOR shall submit a Loss Prevention Program or Safety Manual for this project
APPROVED for approval by COMPANY’s Loss Prevention Division prior to commencement of
ITC/PPD/PROJS. ENGG DIV. construction work.
DDC C. The CONTRACTOR shall refer and adhere to the safety rules, procedures and precautions
set forth in COMPANY’s Accident Prevention and Construction Safety Manuals personnel
JGT
should wear and use appropriate personal protective clothing and safety equipment while
working at the job site CONTRACTOR shall provide first aid/CPR facility for his personnel and
shall have qualified employees to Control and operate the facility.
D. In order to prevent theft/loss of material/equipment, the CONTRACTOR at site shall take all
necessary precautionary measures but not limited to:
1. All the materials under this contract shall be stored by CONTRACTOR in safe and
secured locations even if it is for short period of time.
2. If the equipment/materials are to be retained in SEC vicinities for a substantial period,
then the CONTRACTOR shall ensure that they are kept in locked containers or any other
CERTIFIED
appropriate method of storage which will keep the material/equipment not easily
ASU noticeable by people with any intention of theft or pilferage. Moreover, such containers
BY:
DATE:
shall be placed at a distance from the fence/boundary wall.
3. CONTRACTOR shall also consider all the storage requirements of the (i.e., temperature,
etc.) being stored in containers to avoid any damage during such storage period.
start until completion and communicated at different levels of the PROJECT organization. In
CHK’D
addition, CONTRACTOR shall also require manufacturers/ suppliers to develop, provide and
implement Quality Control Plan/Inspection and Test Plan for each major material/equipment.
1. CONTRACTOR shall submit to the COMPANY the Quality Control Plan/Inspection and
Test Plan for each major material/equipment of the PROJECT. The quality activities
including but not necessarily limited to, inspection and testing, for the material/equipment
shall be planned and documented in the form of a Quality Control Plan/Inspection and
Test Plan. The Quality Control Plan/Inspection and Test Plan shall be submitted to the
COMPANY together with the PROJECT Quality Plan/Quality Program.
NO.
2. The essential features of the required Quality Control Plan/Inspection and Test Plan are
3
DOCUMENT as follows:
SZS a. It is specifically identified to a particular material/equipment.
PREPARED BY b. It has provision for revisions to be made and is assigned a unique document
DATE
number.
CHK’D BY
c. It lists all the inspection and testing activities sequentially.
d. It states the location at which the activity is to be carried out.
APPROVED
e. It identifies the applicable standard, test procedure to be followed and the
acceptance criteria for the inspection or test activity.
ITC/PPD/PROJS. ENGG DIV.
DDC f. It identifies the extent of inspection, sampling frequency and sample size, or
JGT extent of check.
g. It identifies the hold point, witness point and surveillance point.
h. It identifies the record document to be generated, reviewed and retained.
The Quality Control Plan/Inspection and Test Plan shall indicate the scheduled dates of testing and
inspection at the designated location.
CERTIFIED
1.1 All COMPANY information & data shall be confidential and CONTRACTOR Personnel,
involved in the CONTRACT execution, shall not, under any circumstance, disclose the
ASU
BY: COMPANY information, documents, charts, designs, procedures & directives.
DATE:
1.2 CONTRACTOR shall, upon CONTRACT Signing and prior starting to perform WORKS,
shall sign the Non-Disclosure Agreement (NDA), in accordance with the Attachment-"Y"
of this Schedule “B”.
1.3 Every CONTRACTOR Personnel, working under this CONTRACT, shall sign the
THIS DOCUMENT IS
Declaration of Non-Disclosure Agreement (DND) in accordance with the Attachment-"Z"
NOT TO BE USED FOR
CONSTRUCTION OR
of this Schedule “B”.
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED END OF PART-3
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 17
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
CHK’D
PART 4 - MATERIALS
1. PVC conduit properties for outside plant cable facilities shall meet or exceed the
requirements according to 23-SMSS-1, 23-SMSS-2 and 25-SMSS-1 (Rev.-4). 110mm
diameter PVC conduit shall be used for all Outside Plant Network.
2. RSC-PVC coated conduit (Rigid Pipe for Outdoor Application).
3. EMT conduit. (PDS-LAN-WAP for Indoor Application)
4. Square duct cable raceway.
5. Flexible Corrugated Sub-Duct (Plenum & Non-Plenum Type).
NO.
DOCUMENT
B. TELECOMMUNICATION CABLES (VOICE AND DATA):
SZS
PREPARED BY
1. OSP Unshielded Broadband CAT-6A Cable
DATE Conductor: Solid Annealed Bare Copper; 23 AWG (0.57mm)
CHK’D BY Insulation: Solid Polyolefin
Jacket: Black Polyethylene Outer Jacket
APPROVED Balance Twisted Pairs: Unshielded
ITC/PPD/PROJS. ENGG DIV. Shielding System: Aluminum Tape Shield, Protection against EMI/RFI
Cable Assembly: 4 Balanced Twisted Pairs
DDC
Fully Field Core
JGT
purchase and shipment. The CONTRACTOR shall not procure any cable until
CONSTRUCTION OR
FOR ORDERING
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 18
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
h. CONTRACTOR shall field verify on site to determine/measure the length of Fiber Optic
CHK’D
Cables that are required in this project before any cutting or pulling of cables is to be
done.
D. TELEPHONE CABLE MARKER POST: All cable marker posts that will be used in this project
shall conform to COMPANY approved standard, Dwg. No. SB-036365.
DESCRIPTION
E. GROUND CABLE:
1. A minimum of No. 6 AWG the gauge necessary to provide 5 Ohms maximum ground
resistance and insulated (green with yellow stripes).
2. Underground bonding / interconnection shall be bare conductors not smaller than No. 2
AWG. The bare conductor shall be connected to the grounding rod and shall be buried not
NO.
less than 460 mm (18 inches) below grade level of the completed site.
3
DOCUMENT
F. GROUND ROD
SZS
PREPARED BY Ground Rod shall have a minimum dimension of 2.42M (8ft) long x 16mm (5/8 inch)
DATE diameter made of copper. Additional ground rod quantity or longer ground rod shall be
CHK’D BY
installed to provide 5 Ohms maximum ground resistance.
H. TELEPHONE PEDESTAL
All Telephone Pedestals shall be in accordance with SEC Standard Drawing SB-036369
Standard Pedestal Installation.
CERTIFIED
I. PULL-BOX
BY:
ASU The Pull-Box / Housing (36”X25”X8”, 36”x12”x5”, 36”x12”x4” etc. with two entrance holes
DATE: for 2-conduits &1-hole for grounding) shall be rigid, weatherproof, corrosion resistant,
NEMA–4X, KRONE metallic enclosure. These enclosures shall be supplied and installed
with all accessories needed for standard installation.
K. LABELS/TAGS
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 19
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
L. CONDUIT PLUGS/SEAL
1 All conduits (vacant and occupied) shall have watertight rubber plugs or seals with proper
fire stop ratings.
DESCRIPTION
2 Seal all Building Entrances conduits with watertight plugs & seal with CAULK Fire Barrier
Sealant.
M. GROUNDING MATERIALS
The CONTRACTOR shall provide copper - clad ground wires, which will satisfy the
requirements of COMPANY Materials Standard Specification, 10-SMSS-6 Rev. 1 clamps;
Connectors and other materials to be installed on the required grounding system shall be
NO.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 20
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
Ultimate Elongation
CHK’D
: 400%
Tensile Set Recovery : 95 %
Adhesion to Mortar : 3000 N/m
Shore "A" Hardness : 0.4 metric perms.
Service Temperature : Up to 90°C
DESCRIPTION
Re-coatability : Excellent
Chemically resistant to alkalis, acids, chlorides and sulfates.
2. Top coats, Aliphatic formulation, 300 microns dft:
Color : Black
Ultimate Elongation : 130%
Tensile Strength : 22 Mpa
NO.
DATE
CHK’D BY 3. On Below Grade Surfaces: A two-component, high-build, high-solids (at least 70%) coal tar
and epoxy resin with the following properties:
APPROVED Bond Strength to Concrete : 3 MPa
ITC/PPD/PROJS. ENGG DIV. Bond Strength to (Sandblast- : 7.5 MPa prepared) Steel
4. Water to be Used in Cleaning The Concrete:
DDC
Maximum Recommended Concentration
JGT
Form of Contamination Dissolved Solids Excluding
Those Listed Below:
PPM (%)
Sulfates, Alkali, Carbonates 500 0.05
Bicarbonates 400 0.04
Chlorides 300 0.03
Suspended Solids 500 0.05
pH Value 7.0-8.5
DATE:
Compressive Strength at 28 Days Age : 60 MPa
Modulus of Elasticity at 28 Days Age : 30,000 MPa
Slant Shear Bond Strength w/ Concrete : 60 MPa@ 28 Days Age
Coefficient of Linear Thermal Expansion : 11 x 10-6/°C
: Very Low (less than 1000 coulombs as per ASTM
Chloride Ion Penetrability
C1202-91)
THIS DOCUMENT IS Setting Time at 20°C : Initial - 6-1/2 Hours Final - 9 Hours.
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED 2. Concrete Surface: A high-built cementitious repair mortar with the following properties at
28 days age:
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 21
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
CHK’D
R. BACKFILL MATERIALS:
1. All materials and earthwork shall conform to the requirements specified in the COMPANY
Engineering Standards SCS-Q-002.
2. All backfill materials shall be furnished from a source accepted by the COMPANY
NO.
DOCUMENT
REPRESENTATIVE. Acceptance of a backfill source shall not mean automatic acceptance
of all materials obtained from the source, and the COMPANY REPRESENTATIVE may
SZS withdraw approval of the source at any time that materials produced by the source are not
PREPARED BY
suitable for backfill. If suitable, excavated material can also be used for backfill.
DATE
CHK’D BY
3. Certified Test Reports from the COMPANY approved testing agency shall be enclosed
along with the request to the COMPANY for approval of the material.
S. GROUT:
APPROVED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 22
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
4. The modular faceplate shall be Plastic, high impact, flame-retardant, UL-rated 94V-
CHK’D
thermoplastic with dust cover and with complete labeling/icon accessories in accordance to
ANSI/TIA/EIA-606 labeling standard.
5. UTP cable termination shall be based on EIA/TIA 568-B standard color-coding scheme.
6. Spring dust cover.
DESCRIPTION
DOCUMENT
(Issue December 25, 2016).
SZS
PREPARED BY
Quadplex Duplex
DATE Location/ Building WAP
S/N (4Data- (Wall Type)
CHK’D BY Name 2- Data
(Wall Type) (2-Data)
DDC
Total *01 *02 *01
JGT
*Indicates Minimum Estimated Quantity: CONTRACTOR shall Provide All ITC requirements whether shown
or not shown in the attached Layouts. Any additional quantity required in order to complete this project is
Contractor responsibility without any additional cost to the COMPANY.
THIS DOCUMENT IS
E. FIBER OPTIC INTELLIGENT PATCH PANEL :
NOT TO BE USED FOR
CONSTRUCTION OR
The 19 inches Fiber Intelligent (High Density minimum) Patch Panel (High Density 1U Sliding
FOR
MATERIALS
ORDERING
UNTIL
fiber Panel, accepts MPO panels, providing up to 48 duplex LC ports) capable to meet new
CERTIFIED AND DATED
requirements for Automated Infrastructure Management Monitoring and shall conform to 19”
rack/cabinet standards. It shall be modular type equipped with single mode LC Cassette 12 LC
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 23
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
Singlemode Blue with Pigtails iPatch Ready). It shall be equipped with all Cable Management
CHK’D
pair x 23 AWG). Both ends terminated on RJ-45 plug. CONTRACTOR shall supply 100% of the
total UTP Category 6 patch cables. Patch cord length on the equipment side shall be 1.5
meters long. Patch cord length on the user side shall be 3 meters or 5 meters long.
connectors on one end and two (2) connectors on the other end. Both ends shall have color-
DOCUMENT
coded both to facilitate identification of transmit and receive cores.
SZS
PREPARED BY
H. SECONDARY GROUNDING BUSBAR (SGBB) OR TELECOMM GROUND BUSBAR :
DATE
Telecommunications ground bus bar shall be 300 x 50 x 6 (mm) made of solid copper; equip with
insulated stand-off bracket.
CHK’D BY
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 24
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
DATE:
by the COMPANY.
M. LABELS/TAGS:
1. Labeling/tagging of all communications equipment and materials shall be in accordance to
EIA/TIA-606 standard.
2. Engraved plastic tags shall be used in tagging the proposed cables on the existing cable
THIS DOCUMENT IS
NOT TO BE USED FOR
trays, pull boxes, junction boxes, and terminal boxes. The tags on the cables laid on cable
CONSTRUCTION
FOR
OR
ORDERING
tray shall be placed in a uniform interval not exceeding 30 meters.
MATERIALS UNTIL
CERTIFIED AND DATED
3. Engraved plastic tags-adhesive back shall be installed on the front cover of all proposed
terminal boxes, junction boxes, and pull boxes.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 25
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
Note:
CHK’D
1. For Terminal boxes, these tags shall indicate the Contract number, type, location, and
link destination.
2. For Cables, these tags shall indicate the Contract number, cable size, cable type,
cable count, and link destination. Refer to schematic diagram of the design drawings
DESCRIPTION
DOCUMENT (UK)
4 KRONE – (GERMANY) 13 HUBBEL PREMISE WIRING (US)
SZS 5 COMMSCOPE/SYSTIMAX– (Ireland/US) 14 3M - (US)
6 PANDUIT – (US) 15 R & M (SWITZERLAND)
PREPARED BY
DATE
CHK’D BY
7 SIEMON – (US) 16 CORNING CABLE SYSTEM (US)
8 MOLEX PREMISES – (US) 17 CORDECK (US)
9 WIREMOLD-LEGRAND/WALKERDUCT
UNDERFLOOR DUCT SYSTEM (US)
APPROVED
4.4 CONTRACTOR shall supply all permanent and expendable materials, tools, equipment and
all else required for successful completion of this PROJECT, whether shown or not on the
Drawings. All materials supplied by CONTRACTOR shall be new and unused; such materials
shall meet all contractual standards and specifications.
BY:
ASU ground and in a dry place, not exposed to the sun.
DATE: 2. CONTRACTOR shall be responsible for safeguarding such items and ensuring that they are
treated with due care and maintained/used in a prudent manner.
END OF PART-4
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 26
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
B. The CONTRACTOR shall be responsible for returning all affected concrete and asphalt
surfaces to their original or better condition in accordance with COMPANY Standard Material
and installation specification and to the satisfaction of the COMPANY REPRESENTATIVE.
DOCUMENT areas/surfaces.
2. Placing of 110 mm diameter conduits.
SZS
PREPARED BY
3. Installation of 25 mm HDPE sub-duct (non-Plenum type) for Outdoor Application and
DATE installation of 25 mm diameter corrugated (Plenum Type) sub duct.
CHK’D BY 4. Concrete encasement of entrance conduits and all conduits crossing cemented pavement
and asphalt roads.
APPROVED 5. Installation of cable surface marker.
ITC/PPD/PROJS. ENGG DIV. 6. Construction of Dedicated Communication Manholes.
7. PDS-LAN-WAP Cabling Structural Support.
DDC
8. Other miscellaneous civil works.
JGT
DATE:
thick protection board and the interior surface of the Manholes shall be coated with two (2)
coats of elastomeric cementitious impermeable membrane.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 27
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
Room/Area of the building in accordance with COMPANY Construction Standard and shall
CHK’D
meet all the requirements of SEC Materials Specification 11-SMSS-14 (Rev 2)/48-TMSS-02
and manufacturer’s recommendation.
B. Sufficient extra length of the underground fiber optic cable shall be securely and carefully loop
inside the end Manholes for future splice requirements. All other location of Manholes shall be
DESCRIPTION
DOCUMENT E. The average loss per splice shall be 0.05 dB maximum (measured in both direction), the Optical
Fiber splice loss measured in each direction using an OTDR & Power Meter shall be 0.15 dB
SZS maximum.
PREPARED BY
DATE
F. Fiber Optic Splicing shall be done by experienced Fiber Optic cable splicers using an Automatic
CHK’D BY Fusion Optical Fiber Splicing Machine with built-in estimated Optical Fiber Splice Loss Reading
capability. The estimated splice loss shall be less than 0.05 dB.
APPROVED
DATE:
1. SEC FIBER OPTIC TELECOMMUNICATIONS SYSTEM
CONTRACT NO. :
PATCH PANEL NO. :
LINK DESTINATION :
CABLE TYPE/# OF CORES :
CABLE MANUFACTURER :
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
INSTALLATION YEAR :
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
END OF PART-5
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 28
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
applicable tests and measurements and test methods/procedures, which are required in order
to verify Manufacturer's equipment specifications, and other specifications, which are indicated
in these SOW/TS.
DOCUMENT which shall be submitted, to the Company for review and approval at two stages of the project.
These stages are as follows:
SZS
PREPARED BY
B. Preliminary Acceptance Test Plan and Procedures for Contractor installed equipment shall be
DATE provided as part of the Project.
CHK’D BY C. Detailed Acceptance Test Plan and Procedures (based on the Company approved Preliminary
Acceptance Test Plan and Procedures, and Manufacturer's Recommendations), which is to be
APPROVED provided at least two weeks prior to the start of Contractor's pre-commissioning tests.
ITC/PPD/PROJS. ENGG DIV.
DATE:
E. The Contractor must finish the pre-commissioning tests successfully and submit his test results
to Company Representative for evaluation before starting the Final Acceptance and
Commissioning Tests.
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 29
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
The following are general procedures and the order, which is to be followed during the final
acceptance and commissioning tests for the equipment, which is to be provided/installed, by
Contractor:
1. The Company shall designate its Representative(s) to witness the commissioning and
DESCRIPTION
acceptance tests prior to putting the system in operation, and commencing the system trial
period.
2. Contractor shall ensure that all mark-up construction documents/drawings pertaining to the
Commissioning Acceptance Test are handed over to the Company at least six (6) weeks
prior to the commissioning and acceptance test date.
3. Contractor shall submit 3 copies of pre-commissioning test results, acceptance test
schedule, and invite the Company in writing at least ten (10) working days before the
NO.
DATE
specified in the SOW/TS and that results are within the manufacturer's specified nominal
CHK’D BY values, previously approved by the Company.
5. Equipment tests shall include testing of all wiring for future expansion up to full capacity, by
APPROVED inserting appropriate modules or cards, as required.
ITC/PPD/PROJS. ENGG DIV. 6. The Commissioning and Acceptance Tests will be performed according to the following
order:
DDC
a. Physical/Mechanical Inspection
JGT
b. Inventory of Installed equipment, spare materials, and documents
c. Validation of As-Built Drawings
d. Local Tests
e. End-to-End Test (Overall System Performance)
f. The tests shall be performed in sequential order as listed above.
7. Contractor shall clear all major discrepancies pointed by Company representative before
resuming all related tests.
8. Final Testing and Commissioning tests shall include detailed testing of Contractor’s
supplied spare parts.
CERTIFIED
DATE:
(conventional and special, as recommended by the manufacturer(s) to be used in testing and
commissioning.
All test equipment must have updated valid calibration certificate from a recognized calibration-
laboratory In or Out-of-Kingdom. The Company shall not accept tests performed using un-
calibrated test equipment.
THIS DOCUMENT IS
NOT TO BE USED FOR
END OF PART-6
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 30
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
A. SEC STANDARDS:
1. SMSS: (Adopt Latest Edition)
a. 23-SMSS-1 (Rev-2) : PVC Conduits and Fittings for Underground Ducts
b. 24-TMSS-01 : Wireways, Cable Trays, Boxes & Enclosures
c. 25-SMSS-1 (Rev-4) : Specification for Duct Sealing Units
d. 11-SMSS-14 (Rev 2)/48-TMSS-02: Specifications for Non-Metallic Fiber Optic Cable
e. 48-TMSS-12: Fiber Optic Interconnecting Devices & Passive Components.
NO.
DOCUMENT
2. SES: (Adopt Latest Edition)
SZS
PREPARED BY
a. SES-T-559 : Communications Distribution Cables
DATE
b. SES-P-111.02/TES-T-111.02 :Communications Facility Grounding System
CHK’D BY c. SES-T-011 :Communications Symbols
d. TES-T-111.10 :Communication Feeder Cables
APPROVED e. TES-T-111.12 : Outside Plant (Communication) Standards and Practices for
ITC/PPD/PROJS. ENGG DIV. Facility Area Design & Remote Distribution Area Plan Design
f. SES-T-742/TES-T-111.17 : Building Engineering Fire Protection of Communication
DDC
Facilities
JGT
3. SCS: (Adopt Latest Edition)
a. SCS-T-557/TCS-T-111 : Communications/Underground Communications Cable
Installation
TCS-T-111.01: Acceptance/Commissioning, Test & Inspection of Communication
Network Equipment
TCS-T-111.02: Conduit Sealing for Underground Communication Cable
TCS-T-111.03: Communication Cable Splicing
TCS-T-111.04: Underground Telephone Cable Installation
TCS-T-111.05: Long Pulls and Reel Length Limitations of Underground
CERTIFIED
Telephone Cables
BY:
ASU TCS-T-111.06: Optical Fiber Cable Splicing
DATE: TCS-T-111.08: Installation of Underground Non Metallic Fiber Cable
TCS-T-111.11: Design and Installation of Underground Communications Conduit
and Manhole System.
4. SEC-IT HIGH LEVEL FACTS & REQUIREMENT DEFINITIONS FOR AN APPLICATION
(SW / HW / NW) SOLUTION
THIS DOCUMENT IS
B. SEC STANDARD DRAWINGS: (Adopt Latest Revision)
NOT TO BE USED FOR
CONSTRUCTION OR
1. SA-036350/TA-800094: Typical Duct Splaying Layout for Manhole Entry
FOR
MATERIALS
ORDERING
UNTIL
2. SB-036352: Joint Easement for Direct Comm. Power Cables
CERTIFIED AND DATED 3. SB-036353/TB-800067: Direct Buried Cable Trench Detail for Rocky Areas
4. SB-036354/TB-800079: PVC Conduit Installation Concrete Encased (Vital
Communications)
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 31
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
Communications)
6. SA-036356/TA-800096: Standard Manhole Type-1
7. SA-036357/TA-800097: Standard Manhole Type-2
8. SB-036358/TA-800098: Manhole Accessories (Communications)
DESCRIPTION
9. SB-036359: Std Manhole Materials Take-Off List and Typical Manhole Standards Guide
(Communications)
10. SB-036360: Road Crossing typical major Asphalt Auger Bore Method
11. SB-036361: Communication Cables Manhole Water Proof Treatment Installation.
12. SB-036362: Pipeline Crossing for Communication Cables
13. SB-036363: Electronic Marker System installation Details (Communications)
14. SB-036364: Road Crossing Typical Major Marl Road Open Cut for Comm. Cables
NO.
DATE
18. SB-036368: Detail and Assembly Drawing Main Distributing Frame (MDF)
CHK’D BY 19. SB-036369: Telecommunication Standard Pedestal Installation
20. SB-036370: PVC Conduit Installation Conc. Encased (Non-Vital Communications)
APPROVED 21. SB-036371: Conc. Encased Duct Det. for Rocky Areas (Non-Vital Communications)
ITC/PPD/PROJS. ENGG DIV. 22. SB-036373/TB-800077: Standard Communication Handhole (Traffic Type)
DDC
7.2 INTERNATIONAL STANDARDS: (Adopt Latest Edition)
JGT
A. BICSI-TDMM : Building Industry Consultative Services International-Telecom
Distribution Method Manual
B. EIA/TIA-568 A & B : Commercial Building Telecommunications Cabling Standards
C. EIA/TIA-569 : Commercial Building Standard for Telecommunications Pathways and
Spaces
D. EIA/TIA-570 : Residential and Light Commercial Telecommunication Wiring
Standard
E. EIA/TIA-606 : Controlistration Standard for the Telecommunication Infrastructure of
Commercial Buildings
CERTIFIED
F. EIA/TIA-607 : Commercial Building Grounding and Bonding Requirements for
ASU Telecommunications
BY:
DATE:
G. TSB-36 : Commercial Building Wiring Standard
H. TSB-67 : Transmission Performance Specifications for Field Testing of UTP
Cabling Systems
I. NEC-NFPA 70 : National Electric Code-National Fire Protection Association 70
J. NESC-ANSI C2 : National Electrical Safety Code-American National Standards Institute
K. UL : Underwriters Laboratories, Inc.
L. GTE Practices : No. 256-050-206 (or latest edition) Cabling Methods – Central Office
THIS DOCUMENT IS
NOT TO BE USED FOR Running & Securing Power Cable
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
END OF PART-7
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 32
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
SHEETS
EA-896829 TRENCH AND CONDUITS LAYOUT 01
EA-896830 MANHOLE/HANDHOLE FOLDOUT DETAILS 02
EA-896831 FIBER CABLE SCHEMATIC DETAILS 01
EA-896849 VOICE AND DATA CABLING LAYOUT 01
EA-896850 VOICE/DATA INSTALLATION DETAILS 01
SB-036373 OR SEC STANDARD HANDHOLE (TRAFFIC TYPE) 02
NO.
DOCUMENT
TB-800077
SB-036358 OR MANHOLE ACCESSORIES 02
SZS TA-800098
PREPARED BY
DATE
8.2 ATTACHMENT – 1A: DETAILS OF MATERIALS (New CHECKPOINT Building)
CHK’D BY
APPROVED
CERTIFIED
ASU
BY:
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED
OSP-PDS-LAN-WAP CABLING PLANT NO. INDEX DRAWING NO. PAGE NO. REV.
CONSTRUCTION SOW/PTS FOR
JOB ORDER NO. NEW CHECKPOINT BUILDING AT AL-JOUF PP PTS- 33
SE0546 A 21EF702 OF 01
EASTERN REGION SAUDI ARABIA 36
الشركة السعودية الموحدة للكهرباء
CERT.
SAUDI ELECTRICITY COMPANY
APP’D
CHK’D
DESCRIPTION
Attachment No. 1A
NO.
DOCUMENT
SZS
DRAWN BY
DATE
ENGINEERING DEPT.
JGT/DDC Of
OPERATING DEPT.
NEW CHECKPOINT BUILDING AT
AL-JOUF PP
Note: (For reference only, refer to SOW & Design
Drawings for Complete Details)
CERTIFIED
BY: AMT
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED Saudi Electricity Company
Kingdom of Saudi Arabia
LOT 1
DOCUMENT and Data)
SZS
01.03 Supply and Install Fiber Optic Cable: 1-12 Core Single Mode Intra LOT 1
DRAWN BY Building Installation: Loose Tube (breakout design) shall be suitable
DATE for indoor/outdoor installation.
CHK’D BY
01.04 Supply and Install PULL-BOX, 36” x 15” x 6” minimum with two(2)
entrance hole & 1 hole for grounding, NEMA-4X weather approved EA 1
APPROVED
type, hinge cover.
01.05 Supply and Install Information Outlets, installed in wall mounted
ENGINEERING DEPT.
01.06 Supply and Install Ground Rod ;2.42M (8ft) long x 16mm (5/8 inch)
LOT 1
diameter made of copper.
01.07 Supply and Install GROUND BUS BAR (GBB):
500 x 102 x 12 (mm) minimum, made of solid copper, equipped EA 1
CERTIFIED
with insulated stand-off bracket.
01.08 Supply and Install Communication Handhole, that includes Manhole
AMT LOT 1
BY: Cover, Cable Racks, Cable Holder, Ladder, Grounding Systems
DATE:
and other required Manhole Hardware Accessories.
LOT 1
01.09 Excavation, Trenching, Backfilling, Compaction, Asphalting
01.10 Supply and Install Communication Conduit Systems or Duct Banks,
LOT 1
Hardware Accessories, Terratape etc
01.11 The 19 inches Fiber Intelligent (High Density minimum) Patch Panel
(High Density 1U Sliding fiber Panel, accepts (4) InstaPATCH® 360
THIS DOCUMENT IS
modules or MPO panels, providing up to 48 duplex LC ports),
NOT TO BE USED FOR capable to meet new requirements for Automated Infrastructure
CONSTRUCTION OR EA 2
FOR
MATERIALS
ORDERING
UNTIL
Management Monitoring and shall conform to 19” rack/cabinet
CERTIFIED AND DATED standards. It shall be modular type equipped with Cassette 12 LC
Single Mode Blue with Pigtails iPatch Ready. It shall be equipped
with all Cable Management Rack and accessories.
01.12 Supply and Install Fiber Optic Patch Cord; high performance LOT 1
9-10/125μm Single-mode cables; duplex type (SC-LC and LC-LC
type connectors). Both ends shall have color-coded both to facilitate
identification of transmit and receive cores.
01.13 Supply and Install CONDUIT PLUGS/SEAL: LOT 1
DESCRIPTION
LOT 1
DOCUMENT Both ends terminated on RJ-45 plug; 3-5 meters long on the user
side & 1.5 meter on system side
SZS
DRAWN BY 01.17 Supply and Install Data equipment cabinet conforming to 19”
DATE rack/cabinet standards Double Section Type for Wall Mounting
CHK’D BY Cabinet equipped with: 12units Outdoor Type standard and height.
One (1) 6-way Rack Mounted Power Outlet, 220 V UK or Universal EA 1
APPROVED Type; Standard smoked glass front door with lock; Removable side
ENGINEERING DEPT.
panels with lock; Top mounted fan tray-4 fans, 220 VAC, 60 Hz;
JGT/DDC Earth continuity kit.
OPERATING DEPT.
CERTIFIED
BY: AMT
DATE:
THIS DOCUMENT IS
NOT TO BE USED FOR
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND DATED