Equipment Submittal Index
Item Description Submittal No Sample No
Foam System Equipment
1 Deluge Valve BFP-SMA2995-001 BFP-031
2 Foam Nozzles BFP-SMA2995-002 BFP-032
3 Monitered gear operated butterfly valve BFP-SMA2995-003 BFP-033
4 Foam Inductor BFP-SMA2995-004 BFP-034
5 Foam tank BFP-SMA2995-005 BFP-035+035A
6 Pilot line sprinklers BFP-SMA2995-006 BFP-036
7 Foam BFP-SMA2995-007 BFP-037
8 HDPE Undergound pipe BFP-SMA-2995-008 BFP-038+038A
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-001
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection foam deluge System
Equipment Inball Deluge valve
Manufacturer Inball
Supplier Sizanani valves
Address Cranberry Crescent
midrand
Contact Person Keegan Randall
Tel No +27 11 315 1161
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company AApproved
Responsibility
BApproved with
Tel No Remarks
Cell No C
Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specification Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Engi Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system conform to
specification except wher noted on non conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isolat N/A
(ii) Equipment checked for remote control or BMS interfacing compatibility N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-002
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection foam deluge System
Equipment K20 Foam nozzles
Manufacturer Angus Fire
Supplier TIMA
Address 10 an Smuts ave
Bardene
Boksburg
Contact Person Steve Bastuba
Tel No +27 11 894 1343
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibility
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specification Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the En Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system conform to
specification except wher noted on non conformance
form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isol N/A
(ii) Equipment checked for remote control or BMS interfacing compatibili N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-003
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection foam deluge System
Equipment Monitered gear operated butterfly valve
Manufacturer Inball
Supplier Kerr Valves
Address Heidelberg Rd
Doornfontein
Johannesburg
Contact Person Zenzo Phiri
Tel No +27 11 334 2060
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Engi Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system conform to
specification except wher noted on non conformance
form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isolatN/A
(ii) Equipment checked for remote control or BMS interfacing compatibilityN/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-004
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection foam deluge System
Equipment Foam inductor
Manufacturer Angus
Supplier TIMA
Address 10 Jan Smuts ave
Bardene
Boksburg
Contact Person Steve Bastuba
Tel No +27 11 894 1343
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Engi Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system conform to
specification except wher noted on non
conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isolat N/A
(ii) Equipment checked for remote control or BMS interfacing compatibility N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-005
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection foam deluge System
Equipment STAINLESS STEEL TANK
Manufacturer TIMA
Supplier TIMA
Address 10 Jan Smuts ave
Bardene
Boksburg
Contact Person Steve Bastuba
Tel No +27 11 894 1343
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system conform to
specification except wher noted on non
conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical i N/A
(ii) Equipment checked for remote control or BMS interfacing compatibN/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-006
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection Misting System
Equipment Pilot line sprinkler
Manufacturer Tyco
Supplier Tyco
Address 10 Ride road
laser park
Honeydew
Contact Person Deon Van Zyl
Tel No +27 11 794 2217
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system
conform to specification except wher noted
on non conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical iN/A
(ii) Equipment checked for remote control or BMS interfacing compatib
N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-007
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection Misting System
Equipment Foam
Manufacturer Fire safety designs
Supplier Safe quip
Address 20 Patrick Rd
Jet park
Kuils rivier
Contact Person Paige Haw
Tel No +27 11 397 7723
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Eng Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout
Drawing Numbers DWG-ENV-MP-DFS-001-4
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system
conform to specification except wher noted
on non conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isola N/A
(ii) Equipment checked for remote control or BMS interfacing compatibilit N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-008
To Spoormaker & Partners Rev No 1
Sub.Date 27/1/2022
Prepared by Morne van der Merwe
Attention Jannie Havenga
Project MWP Eskom Project No MWP Eskom
Service Fire Protection Misting System
Equipment HDPE Piping
Manufacturer Inkulu Plastic pipes
Supplier Thusanong piping and fitting
Address Trevallyn
industrial park west
Kya sands
Contact Person Divian
Tel No +27 11 708 6133
Email [email protected]
For Client/Client Authorized Representative/Client Agent use only
Name Approve Status
Company A Approved
Responsibil
B Approved with
Tel No Remarks
Cell No C Not Approved
Email
Remarks (Note: If the area is inadequate add remarks as an addendum)
System & Fuction Description Foam Protection
Function of the System Fire Protection System - Foam
Non Conformance to Specificat Confirms to Specification
Equipment Technical Data Sheet
Manufactures Data
(i) Signed off Specification Yes
(ii) Technical Data & Design Capacities Yes
(iii) Warranty Yes
Descriptive Literature
(i) Catalogue & Brochures Yes
(ii) Dimentional Drawings Yes
(iii) Manufacturing Specification & Shop Drawing Yes
Operating Standards & Instructions
(i) First, Second & Final Fix Quality Inspection sheet Yes
(ii) Pre-start Checklist No
(iii) Start-Up & Stopping Procedures Yes
(iv) Inspection during Operation Yes
(v) Adjustment parameters Yes
(vi) Testing Procedures Yes
(vii) Operators Roles & Responsibilities Yes
(viii) Proper operation of the installation shall be demonstrated to the Eng Yes
Maintenance Instructions & Procedures
(i) Preventative Maintetance Action Yes
(ii) Freqency/Schedules of Routine Maintenance Yes
(iii) MTTF & MTTR of Major Equipment To Follow
(iv) Critical Spares Yes
(v) Spares List No
(vi) Trouble Shooting Guidelines Yes
Drawings
Drawing Description Data Centre Phase 2- Block C & D Ground floor fire water layout
Drawing Numbers DWG-ENV-MP-M-FW-001-2
Drawing type Submission
(i) Shop Drawing Mechanical Layout Yes
(ii) Shop Drawing Electrical Layout N/A
(iii) Shop Drawing Controls Layout Yes
(iv) Builders Requirent N/A
(v) As Built Drawing Mechanical Layout To Follow
(vi) As Build Drawing Electrical Layout N/A
(iii) As Built Drawing Controls Layout N/A
Equipment Submittal Checklist
(i) Is index included, mark-up and all pages numbered No
(ii) Does the equipment/sub-system
conform to specification except wher noted
on non conformance form Yes
(a) Access for equipment Yes
(b) Installation Instructions Yes
(c) Access for service or repair work Yes
Equipment/Component Interface
(i) Equipment checked for adequate power supply an local electrical isola N/A
(ii) Equipment checked for remote control or BMS interfacing compatibilit N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A
Remarks (Note: If the area is inadequate add remarks as an addendum)