0% found this document useful (0 votes)
34 views2 pages

05.01 - Generator Data - 971407

This document provides technical specifications for a 162 megavolt-ampere generator including its electrical ratings, cooling system type, temperatures, losses, reactances, resistances, and time constants. Key details are the generator produces 137,700 kilowatts at 15,000 volts and has an efficiency of 98.53%. It uses a TEWAC and air cooling system and is rated for IEC standards.

Uploaded by

Xiangdong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views2 pages

05.01 - Generator Data - 971407

This document provides technical specifications for a 162 megavolt-ampere generator including its electrical ratings, cooling system type, temperatures, losses, reactances, resistances, and time constants. Key details are the generator produces 137,700 kilowatts at 15,000 volts and has an efficiency of 98.53%. It uses a TEWAC and air cooling system and is rated for IEC standards.

Uploaded by

Xiangdong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Rating

Project Name Soyo - CMEC


Generator type 9a5
Electrical Design Number 971407S
KVA 162000 kVA
Power Factor Leading 0.95
Power Factor Lagging 0.85
KW 137700 kW
RPM 3000 RPM
Rated Voltage 15000 Volts
Line Current 6235 Amps
Cooling System (OV / TEWAC / H2) TEWAC / Air
SCR 0.50
Site Altitude 99 Ft
Rated Cold Gas Temp 40 C
Exciter (Design Amps / KW / Voltage) 1016 A / 356 kW / 350 V
Exciter (IGNL / IFNL / IFFL) 302 / 327 / 922
Rating (i.e., ANSI / IEC) IEC
Temperature Class (i.e., B) B
Coolant (Type / FF / Flow) 33% Ethylene Glycol / 0.0010 / 700 GPM
Coolant Temp Point 1 23.5 C / 34.5 C
(Ambient/Coolant)
Coolant Temp Point 2 20 C / 31 C
(Ambient/Coolant)
Coolant Temp Point 3 30 C / 41 C
(Ambient/Coolant)
Guaranteed I2 SQ.T (s) 8
TIF (L-L / L-N / Residual) 0.001 / 0.016 / 0.016
Field Resistance @ 25 C 0.2519
Armature Resistance @ 25 C 0.001360
Single Phase Capacitance (uF) 0.418
Three Phase Capacitance (uF) 1.044
No-Load Saturation factor (S1.0 / S1.2) 0.0851 / 0.6791

Losses
Fan & Wind 814
Core 184
Load 270
I2R Arm 201
I2R Field 272
Misc 14
Exciter 25
Bearings 279
Total 2059
Efficiency 98.53%

Direct Axis Reactances (PU, Rounded)


Synchronous (XD) 2.02
Transient Sat (X’DV) 0.205
Transient Unsat (X’DI) 0.225
Subtransient Sat (X”DV) 0.140
Subtransient Unsat (X”DI) 0.165
Negative Sequence Sat (X2V) 0.140
Negative Sequence Unsat (X2I) 0.165
Zero Sequence Sat (X0V) 0.091
Zero Sequence Unsat (X0I) 0.091
Armature Leakage Sat (XLV) 0.115
Armature Leakage Unsat (XLI) 0.122
Armature Leakage (XLM) 0.120

Quaturature Axis Reactances (PU, Rounded)


Synchronous (XQ) 1.92
Transient (X’Q) 0.40
Subtransient Sat (X”QV) 0.14
Subtransient Unsat (X”QI) 0.16

Hipots
Armature / Field (Volts) 31000 / 3660

Resistances (Per Unit)


Armature (DC) (RA) 0.001262
Positive Sequence (R1) 0.0029
Negative Sequence (R2) 0.0140
Zero Sequence (R0) 0.0074

Time Constants (Seconds)


Direct:
Transient, Open Circuit (T’DO) 10.452
Transient, 3 Phase (T’D3) 0.948
Transient, Line – Line (T’D2) 1.664
Transient, Line – Neutral (T’D1) 2.020
Subtransient (T’’DO) 0.045
Subtransient (T’’D) 0.031
Armature (TA2 = TA3) 0.414
Armature (TA1) 0.313

Quadrature:
Transient (T’Q) 0.134
Transient, Open Circuit (T’Q0) 0.644
Subtransient (T’’Q) 0.031
Subtransient (T’’Q0) 0.087

You might also like