Power Transformers
Founded in 1969, ORTEA SpA is a leading company in manufacturing and engineering voltage
stabilisers and magnetic components.
Over forty years in the business and ongoing technical research have made of ORTEA a competitive
and technologically advanced company. Close co-operation between design, production and
marketing enables to meet the requirements of a constantly growing number of customers.
In 1996 ORTEA joined ICAR Group, made of Italian and European industrial units specialised in
manufacturing capacitors and power factor correction systems.
Beside standard production, ORTEA can be extremely flexible in developing and manufacturing
special equipment according to User’s specification. All this thanks to the experience gained over
many years of applied technological development.
Such development includes IT tools that enable the technical staff to elaborate electrical and
mechanical designs for each «custom product» on a quick and cost-effective basis.
ORTEA is well established in the global market. Thanks to strategically positioned offices and
distributors and efficient commercial relations, ORTEA’s products are installed and working in a large
number of countries.
www.ortea.com
ahead of time
Experience.
In its over 45 years of business, Ortea (founded in 1969) has gained experience and know-how that enabled
continuous growth and evolution. This never-ending process has allowed the Company to assume a leading role
worldwide in designing and manufacturing voltage stabilisers.
Reliability.
Thanks also to its long-established Quality System, ORTEA can ensure the production of reliable and long lasting
products, each one of them accurately tested.
Flexibility.
In addition to the standard production, ORTEA's extremely flexible organization is able to develop and manufacture
cost-effective special equipment based on the Customer's specification.
Speed.
ORTEA can manage the purchasing orders very quickly. Review of offer/order, design, production planning,
manufacturing and strict test routines: all the processes have been analysed and optimised in order to eliminate idle
time and shorten delivery terms.
Synergy.
Co-operation between Headquarters, Subsidiaries, Distributors and Customers aimed at a careful analysis of
markets and demand enable ORTEA the development of up-to-date products.
By working together, marketing, design, production and after-sales service allow the Company to meet the
necessities set forth by an increasingly globalised and competitive market.
After-sales.
The continuous monitoring and analysis of requests and claims carried out by the after-sales service enables the
improvement the quality of both products and service to the Customer.
ORTEA after-sales organization can act quickly, providing for precise issue analysis, supply of advise and know-how
and , if necessary, provision of spare parts in order to solve any anomaly.
Quality.
Aiming at providing for the best quality, the manufacturing process includes checks during production and detail
test sessions for each stabiliser.
The approved Integrated Managing System ensures the control of every manufacturing phase, starting from
R
checking the components at reception and ending with the best package in relation to the transport type.
The Integrated Managing System is ISO9001:2015 - ISO14001:2015 - OHSAS18001:2007 approved.
4
ORTEA SpA designs and manufactures low voltage power transformers for a diverse range of
applications using first rate materials and components.
A very flexible company organization – ORTEA’s distinctive character since ever – enables the
development of special solution based on the Customer’s specifications.
The design of the transformer is therefore customized still ensuring the high quality typical of the
standard products.
Operating mode at the required temperature class (B, F, H and up to 200°C), multiple windings,
regulating taps, vector group, on request connecting terminals are only a few examples of special
necessities that can be easily met.
Transformers can either be unprotected or housed inside a metallic IP21 enclosure. Although IP21 is the
standard construction, other protection degrees are available on request.
If necessary, transformer can be completed with accessories such as:
– multiple shields to increase protection;
– surge protective devices (SPDs) for an efficient discharge to ground of overvoltage and lightning;
– automatic circuit breaker for load protection;
– isolation controller;
– PT100 thermocouple and temperature control unit.
Construction
Transformers are manufactured with windings in either copper or aluminium (depending on rated
power and project technical and economic optimization) and magnetic core obtained with thin
magnetic steel sheets in order to reduce losses.
The isolation material used for the main isolation towards the core and for the windings isolation is
chosen on the basis of the required insulation class. The body of the transformer, duly assembled and
locked by means of clamping plates and vertical tie rods, is immersed into a polyester resin with
extremely low environmental impact. The process comprising immersion and further polymerization
through baking, allows for consolidating the structure and achieving the required isolation class.
Tests
The production process included frequent intermediate controls and a complete electric test on all the
transformers in order to guarantee full compliance with Customer’s requirements and reference
Standards (EN60076).
5
The most common fields where ORTEA’s transformers (single-phase, three-phase & three/single-
phase) can find their use are listed below:
– line separation (isolation transformers);
– non-linear load supply (K-rated transformers);
– UPS conversion groups;
– rectifiers and galvanic industry;
– solar;
– general purpose (supply of industrial system in the tertiary sector, power distribution for industrial
and retail structures, etc.).
Isolation transformers
Isolation transformers are specifically designed and manufactured to ensure load protection by means
of galvanic separation between the mains and the user.
Typical fields of application are telecommunication systems, data centre supply systems, ‘trafoless’
UPSs supply, bypass lines protection, public buildings and hospitals.
An isolation transformer is always fitted with an electrostatic shield between primary and secondary
windings for noise attenuation and discharge to ground of voltage surge.
Isolation transformer housed Windings are built in delta/star or delta/zigzag configuration (with available neutral point) in order to
inside an IP54 enclosure cancel the third and triplen harmonics.
fitted with a/c unit.
6
Harmonic generation results in increased current absorption and therefore higher losses.
In order to ensure that the thermal class temperature limit is respected, the transformer design must
keep into consideration the presence of said harmonics.
The K factor is an indication of how much the harmonic distortion affects the system: the higher is K, the
higher is the harmonic content that the transformer must withstand without any damage.
K20 Data centre, variable speed drives, data processing systems, PC.
It is worth reminding that a K-rated transformers does not cancel the harmonics in the system (except
for third and triplen harmonics), but is able to tolerate their effects.
In order to reduce or eliminate the harmonic content, it is necessary to arrange suitable filtering
equipment.
Beyond the standard rated power and voltage listed in the tables in the following, ORTEA is able to meet
any other specific requirement.
7
UPS transformers
These transformers are used in the AC/DC conversion and DC/AC rectifying groups typical of UPS
systems.
The transformers are usually extremely tailored to the UPS. Standard models cannot be defined, as each
transformer design is strictly linked to the UPS into which the transformer needs to be assembled.
Both the electrical properties and the mechanical characteristics satisfy precise specifications drawn
up by the ups manufacturer. A close co-operation is therefore an essential requisite for developing the
Transformer and reactor best solution.
for 800kVA UPS mounted
on a base frame. Thanks to the expertise achieved through decades of experience in this sector, ORTEA is able to design
and manufacture UPS transformers of any kind.
The partnership with major UPS producers worldwide is evidence of the high reliability achieved.
8
Reactors
Thanks to a wide experience and a close co-operation with Customers, ORTEA has achieved a specific
knowledge that allows for the construction of reactors suitable for all the different possibilities offered
by the great variety of applications where these magnetic components are used.
Being the production extremely versatile and flexible, ORTEA can provide with a wide range of solutions.
Both for outdoor and indoor installation, ORTEA produces single-phase and three-phase reactors either PFC system reactor with
with magnetic or air core, medium voltage insertion reactors, medium voltage choking inductors, tuning aluminium winding.
reactors, smoothing inductors, blocking reactors and current limiting reactors.
Any medium voltage reactor can be designed and built in compliance with the insulation classes
specified in the relevant Standards: 3.6kV, 7.2kV, 17.5kV, 24kV and 36kV.
Blocking, filtering and tuning reactors, together with capacitor banks, are used in power factor
correction systems and harmonic filters.
This type of reactor is usually provided with magnetic core thus allowing for high linearity even in
presence of current peaks much higher than the rated current (see the tables in the following for the
PFC system reactor with
standard range technical data).
copper winding.
All our reactors are designed and built in compliance with the relevant technical Standard (EN60076).
9
R
10
W D
H
H
W D
Dyn11 K4 Transformers
Technical data - standard model 10-3150kVA
10 150 430 94,5 3,5 360 x 220 x 370 80 600 x 400 x 600 105
12 170 530 94,5 3,5 420 x 240 x 420 90 600 x 400 x 600 115
15 180 660 94,7 3,5 420 x 250 x 420 100 600 x 400 x 600 125
20 210 720 95,6 3,5 420 x 250 x 420 110 700 x 500 x 700 150
25 240 860 95,8 3,5 420 x 270 x 420 125 700 x 500 x 700 165
30 270 1000 95,9 3,5 420 x 320 x 420 145 700 x 500 x 700 185
40 350 1250 96,2 3,5 - 4,0 600 x 350 x 460 210 800 x 700 x 850 265
50 410 1480 96,4 3,5 - 4,0 600 x 390 x 460 230 800 x 700 x 850 285
63 450 1550 96,9 3,5 - 4,0 600 x 420 x 490 250 800 x 700 x 850 315
80 630 1700 97,2 3,5 - 4,0 600 x 470 x 500 300 800 x 700 x 850 355
90 680 1800 97,3 3,5 - 4,0 600 x 470 x 500 325 800 x 700 x 850 380
100 740 1900 97,4 3,5 - 4,0 660 x 470 x 560 350 900 x 800 x 950 420
110 780 2000 97,5 3,5 - 4,0 660 x 470 x 560 370 900 x 800 x 950 440
125 870 2250 97,6 3,5 - 4,0 660 x 470 x 560 400 900 x 800 x 950 470
140 920 2450 97,6 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
160 960 2800 97,7 3,5 - 4,0 660 x 490 x 600 470 1000 x 1000 x 1150 580
180 1100 2950 97,8 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
200 1200 3150 97,9 3,5 - 4,0 700 x 530 x 640 560 1000 x 1000 x 1150 670
225 1290 3350 98,0 3,5 - 4,0 700 x 530 x 640 610 1000 x 1000 x 1150 720
250 1430 3600 98,0 3,5 - 4,0 760 x 550 x 680 660 1000 x 1000 x 1150 770
280 1470 3900 98,1 3,5 - 4,0 760 x 550 x 760 720 1000 x 1000 x 1150 830
315 1620 4250 98,2 3,5 - 4,0 760 x 560 x 760 760 1200 x 1100 x 1350 910
350 1730 4600 98,2 3,5 - 4,0 760 x 560 x 760 810 1200 x 1100 x 1350 960
400 1890 5450 98,2 3,5 - 4,0 840 x 580 x 780 900 1200 x 1100 x 1350 1050
450 2100 6100 98,2 3,5 - 4,0 840 x 580 x 780 970 1200 x 1100 x 1350 1120
500 2250 6750 98,2 3,5 - 4,0 840 x 590 x 880 1100 1200 x 1100 x 1350 1250
630 2780 7850 98,3 3,5 - 4,0 1100 x 610 x 950 1300 1400 x 1200 x 1550 1500
800 3000 9200 98,5 3,5 - 4,0 1100 x 620 x 1070 1500 1400 x 1200 x 1550 1700
1000 4050 10700 98,5 4,0 - 4,5 1200 x 630 x 1120 1900 1600 x 1300 x 1750 2200
1250 4950 12700 98,6 4,0 - 4,5 1200 x 700 x 1120 2300 1600 x 1300 x 1750 2600
1600 6200 15300 98,7 5,0 1400 x 800 x 1400 3100 2000 x 1600 x 2000 3500
2000 7600 18100 98,7 5,0 1400 x 850 x 1400 3800 2100 x 1700 x 2200 4300
2500 9000 21500 98,8 6,0 1700 x 900 x 1700 4000 2600 x 1700 x 2300 4600
3150 10700 25600 98,9 6,0 1700 x 1000 x 1700 4800 2600 x 1700 x 2300 5400
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
11
W D
H
H
W D
8 150 290 94,8 3,5 360 x 220 x 370 80 600 x 400 x 600 105
10 170 360 95,0 3,5 420 x 240 x 420 90 600 x 400 x 600 115
12 180 450 95,0 3,5 420 x 250 x 420 100 600 x 400 x 600 125
15 210 490 95,5 3,5 420 x 250 x 420 110 700 x 500 x 700 150
20 240 580 96,1 3,5 420 x 270 x 420 125 700 x 500 x 700 165
25 270 710 96,2 3,5 420 x 320 x 420 145 700 x 500 x 700 185
30 350 850 96,2 3,5 - 4,0 600 x 350 x 460 210 800 x 700 x 850 265
40 410 1000 96,6 3,5 - 4,0 600 x 390 x 460 230 800 x 700 x 850 285
50 450 1080 97,0 3,5 - 4,0 600 x 420 x 490 250 800 x 700 x 850 315
63 630 1150 97,3 3,5 - 4,0 600 x 470 x 500 300 800 x 700 x 850 355
70 680 1210 97,4 3,5 - 4,0 600 x 470 x 500 325 800 x 700 x 850 380
80 740 1320 97,5 3,5 - 4,0 660 x 470 x 500 350 900 x 800 x 950 420
90 780 1380 97,7 3,5 - 4,0 660 x 470 x 560 370 900 x 800 x 950 440
100 870 1520 97,7 3,5 - 4,0 660 x 470 x 560 400 900 x 800 x 950 470
110 920 1640 97,7 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
125 960 1880 97,8 3,5 - 4,0 660 x 490 x 600 470 1000 x 1000 x 1150 580
140 1100 1980 97,8 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
160 1200 2120 98,0 3,5 - 4,0 700 x 530 x 640 560 1000 x 1000 x 1150 670
180 1290 2280 98,1 3,5 - 4,0 700 x 530 x 640 610 1000 x 1000 x 1150 720
200 1430 2420 98,1 3,5 - 4,0 760 x 550 x 680 660 1000 x 1000 x 1150 770
225 1470 2620 98,2 3,5 - 4,0 760 x 550 x 760 720 1000 x 1000 x 1150 830
250 1620 2850 98,2 3,5 - 4,0 760 x 560 x 760 760 1200 x 1100 x 1350 910
280 1730 3180 98,3 3,5 - 4,0 760 x 560 x 760 810 1200 x 1100 x 1350 960
315 1890 3600 98,3 3,5 - 4,0 840 x 580 x 780 900 1200 x 1100 x 1350 1050
350 2100 4100 98,3 3,5 - 4,0 840 x 580 x 780 970 1200 x 1100 x 1350 1120
400 2250 4530 98,3 3,5 - 4,0 840 x 590 x 880 1100 1200 x 1100 x 1350 1250
500 2780 5250 98,4 3,5 - 4,0 1100 x 610 x 950 1300 1400 x 1200 x 1550 1500
630 3000 6180 98,6 3,5 - 4,0 1100 x 620 x 1070 1500 1400 x 1200 x 1550 1700
800 4050 7180 98,6 4,0 - 4,5 1200 x 630 x 1120 1900 1600 x 1300 x 1750 2200
1000 4950 8450 98,7 4,0 - 4,5 1200 x 700 x 1120 2300 1600 x 1300 x 1750 2600
1250 6200 10400 98,7 5,0 1400 x 800 x 1400 3100 2000 x 1600 x 2000 3500
1600 7600 12250 98,8 5,0 1400 x 850 x 1400 3800 2100 x 1700 x 2200 4300
2000 9000 14500 98,8 6,0 1700 x 900 x 1700 4000 2600 x 1700 x 2300 4600
2500 10700 17500 98,9 6,0 1700 x 1000 x 1700 4800 2600 x 1700 x 2300 5400
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
12
W D
H
H
W D
7 150 240 94,9 3,5 360 x 220 x 370 80 600 x 400 x 600 105
9 170 300 94,9 3,5 420 x 240 x 420 90 600 x 400 x 600 115
10 180 360 94,9 3,5 420 x 250 x 420 100 600 x 400 x 600 125
14 210 390 95,9 3,5 420 x 250 x 420 110 700 x 500 x 700 150
18 240 470 96,2 3,5 420 x 270 x 420 125 700 x 500 x 700 165
22 270 540 96,4 3,5 420 x 320 x 420 145 700 x 500 x 700 185
28 350 680 96,5 3,5 - 4,0 600 x 350 x 460 210 800 x 700 x 850 265
36 410 800 96,7 3,5 - 4,0 600 x 390 x 460 230 800 x 700 x 850 285
45 450 840 97,2 3,5 - 4,0 600 x 420 x 490 250 800 x 700 x 850 315
58 630 920 97,4 3,5 - 4,0 600 x 470 x 500 300 800 x 700 x 850 355
63 680 980 97,4 3,5 - 4,0 600 x 470 x 500 325 800 x 700 x 850 380
70 740 1080 97,5 3,5 - 4,0 660 x 470 x 500 350 900 x 800 x 950 420
80 780 1100 97,7 3,5 - 4,0 660 x 470 x 560 370 900 x 800 x 950 440
90 870 1230 97,7 3,5 - 4,0 660 x 470 x 560 400 900 x 800 x 950 470
100 920 1350 97,8 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
110 960 1550 97,8 3,5 - 4,0 660 x 490 x 600 470 1000 x 1000 x 1150 580
125 1100 1620 97,9 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
140 1200 1710 98,0 3,5 - 4,0 700 x 530 x 640 560 1000 x 1000 x 1150 670
160 1290 1820 98,1 3,5 - 4,0 700 x 530 x 640 610 1000 x 1000 x 1150 720
180 1430 1960 98,2 3,5 - 4,0 760 x 550 x 680 660 1000 x 1000 x 1150 770
200 1470 2150 98,2 3,5 - 4,0 760 x 550 x 760 720 1000 x 1000 x 1150 830
225 1620 2320 98,3 3,5 - 4,0 760 x 560 x 760 760 1200 x 1100 x 1350 910
250 1730 2510 98,3 3,5 - 4,0 760 x 560 x 760 810 1200 x 1100 x 1350 960
280 1890 3080 98,3 3,5 - 4,0 840 x 580 x 780 900 1200 x 1100 x 1350 1050
315 2100 3350 98,3 3,5 - 4,0 840 x 580 x 780 970 1200 x 1100 x 1350 1120
350 2250 3720 98,3 3,5 - 4,0 840 x 590 x 880 1100 1200 x 1100 x 1350 1250
450 2780 4350 98,4 3,5 - 4,0 1100 x 610 x 950 1300 1400 x 1200 x 1550 1500
580 3000 5100 98,6 3,5 - 4,0 1100 x 620 x 1070 1500 1400 x 1200 x 1550 1700
720 4050 5850 98,6 4,0 - 4,5 1200 x 630 x 1120 1900 1600 x 1300 x 1750 2200
900 4950 6950 98,7 4,0 - 4,5 1200 x 700 x 1120 2300 1600 x 1300 x 1750 2600
1100 6200 8350 98,7 5,0 1400 x 800 x 1400 3100 2000 x 1600 x 2000 3500
1400 7600 9900 98,8 5,0 1400 x 850 x 1400 3800 2100 x 1700 x 2200 4300
1800 9000 11800 98,9 6,0 1700 x 900 x 1700 4000 2600 x 1700 x 2300 4600
2200 10700 14100 98,9 6,0 1700 x 1000 x 1700 4800 2600 x 1700 x 2300 5400
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
13
R
14
W D
H
H
W D
Dzn0 K4 Transformers
Technical data - standard model 10-3150kVA
10 160 460 94,2 3,5 380 x 230 x 380 85 600 x 400 x 600 110
12 180 560 94,2 3,5 420 x 250 x 420 95 600 x 400 x 600 120
15 190 710 94,3 3,5 420 x 260 x 420 110 600 x 400 x 600 135
20 225 770 95,3 3,5 420 x 270 x 420 120 700 x 500 x 700 160
25 260 920 95,5 3,5 420 x 290 x 420 135 700 x 500 x 700 175
30 290 1070 95,7 3,5 420 x 340 x 440 155 700 x 500 x 700 195
40 375 1340 95,9 3,5 - 4,0 600 x 370 x 460 225 800 x 700 x 850 280
50 440 1580 96,1 3,5 - 4,0 600 x 410 x 460 250 800 x 700 x 850 305
63 480 1660 96,7 3,5 - 4,0 600 x 440 x 480 270 800 x 700 x 850 325
80 670 1820 97,0 3,5 - 4,0 600 x 470 x 530 330 800 x 700 x 850 385
90 730 1920 97,1 3,5 - 4,0 600 x 480 x 530 350 800 x 700 x 850 405
100 790 2030 97,3 3,5 - 4,0 660 x 480 x 530 380 900 x 800 x 950 450
110 830 2140 97,4 3,5 - 4,0 660 x 480 x 530 400 900 x 800 x 950 470
125 930 2400 97,4 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
140 980 2610 97,5 3,5 - 4,0 660 x 490 x 600 460 900 x 800 x 950 530
160 1030 2990 97,5 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
180 1180 3150 97,7 3,5 - 4,0 700 x 530 x 640 550 1000 x 1000 x 1150 660
200 1280 3360 97,7 3,5 - 4,0 700 x 530 x 640 600 1000 x 1000 x 1150 710
225 1380 3580 97,8 3,5 - 4,0 700 x 550 x 680 660 1000 x 1000 x 1150 770
250 1530 3840 97,9 3,5 - 4,0 760 x 550 x 760 710 1000 x 1000 x 1150 820
280 1570 4160 98,0 3,5 - 4,0 760 x 560 x 760 770 1000 x 1000 x 1150 880
315 1730 4540 98,0 3,5 - 4,0 760 x 560 x 760 820 1200 x 1100 x 1350 970
350 1850 4910 98,1 3,5 - 4,0 840 x 580 x 780 870 1200 x 1100 x 1350 1020
400 2020 5810 98,1 3,5 - 4,0 840 x 580 x 780 960 1200 x 1100 x 1350 1110
450 2240 6500 98,1 3,5 - 4,0 840 x 590 x 880 1040 1200 x 1100 x 1350 1190
500 2400 7200 98,1 3,5 - 4,0 1100 x 600 x 880 1180 1200 x 1100 x 1350 1330
630 2970 8370 98,2 3,5 - 4,0 1100 x 620 x 980 1390 1400 x 1200 x 1550 1590
800 3200 9800 98,4 3,5 - 4,0 1100 x 640 x 1120 1600 1400 x 1200 x 1550 1800
1000 4320 11400 98,5 4,0 - 4,5 1200 x 650 x 1120 2050 1600 x 1300 x 1750 2350
1250 5280 13540 98,5 4,0 - 4,5 1200 x 700 x 1200 2500 1600 x 1300 x 1750 2800
1600 6600 16400 98,6 5,0 1500 x 850 x 1500 3400 2000 x 1600 x 2000 3800
2000 8100 19300 98,6 5,0 1500 x 900 x 1500 4100 2100 x 1700 x 2200 4600
2500 9600 22950 98,7 6,0 1800 x 950 x 1800 4300 2600 x 1700 x 2300 4900
3150 11400 27300 98,8 6,0 1800 x 1000 x 1800 5200 2600 x 1700 x 2300 5800
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
15
W D
H
H
W D
8 160 310 94,5 3,5 380 x 230 x 380 85 600 x 400 x 600 110
10 180 385 94,7 3,5 420 x 250 x 420 95 600 x 400 x 600 120
12 190 480 94,7 3,5 420 x 260 x 420 110 600 x 400 x 600 135
15 225 530 95,2 3,5 420 x 270 x 420 120 700 x 500 x 700 160
20 260 620 95,8 3,5 420 x 290 x 420 135 700 x 500 x 700 175
25 290 770 95,9 3,5 420 x 340 x 440 155 700 x 500 x 700 195
30 375 900 95,9 3,5 - 4,0 600 x 370 x 460 225 800 x 700 x 850 280
40 440 1070 96,4 3,5 - 4,0 600 x 410 x 460 250 800 x 700 x 850 305
50 480 1160 96,8 3,5 - 4,0 600 x 440 x 480 270 800 x 700 x 850 325
63 670 1230 97,1 3,5 - 4,0 600 x 470 x 530 330 800 x 700 x 850 385
70 730 1290 97,2 3,5 - 4,0 660 x 480 x 530 350 800 x 700 x 850 405
80 790 1410 97,3 3,5 - 4,0 660 x 480 x 530 380 900 x 800 x 950 450
90 830 1480 97,5 3,5 - 4,0 660 x 480 x 530 400 900 x 800 x 950 470
100 930 1630 97,5 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
110 980 1750 97,6 3,5 - 4,0 660 x 490 x 600 460 900 x 800 x 950 530
125 1030 2000 97,6 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
140 1180 2110 97,7 3,5 - 4,0 700 x 530 x 640 550 1000 x 1000 x 1150 660
160 1280 2260 97,8 3,5 - 4,0 700 x 530 x 640 600 1000 x 1000 x 1150 710
180 1380 2440 97,9 3,5 - 4,0 760 x 550 x 680 660 1000 x 1000 x 1150 770
200 1530 2580 98,0 3,5 - 4,0 760 x 550 x 760 710 1000 x 1000 x 1150 820
225 1570 2790 98,1 3,5 - 4,0 760 x 560 x 760 770 1000 x 1000 x 1150 880
250 1730 3040 98,1 3,5 - 4,0 760 x 560 x 760 820 1200 x 1100 x 1350 970
280 1850 3390 98,2 3,5 - 4,0 840 x 580 x 780 870 1200 x 1100 x 1350 1020
315 2020 3840 98,2 3,5 - 4,0 840 x 580 x 780 960 1200 x 1100 x 1350 1110
350 2240 4350 98,2 3,5 - 4,0 840 x 590 x 880 1040 1200 x 1100 x 1350 1190
400 2400 4830 98,2 3,5 - 4,0 1100 x 600 x 880 1180 1200 x 1100 x 1350 1330
500 2970 5600 98,3 3,5 - 4,0 1100 x 620 x 980 1390 1400 x 1200 x 1550 1590
630 3200 6590 98,5 3,5 - 4,0 1100 x 640 x 1120 1600 1400 x 1200 x 1550 1800
800 4320 7660 98,5 4,0 - 4,5 1200 x 650 x 1120 2050 1600 x 1300 x 1750 2350
1000 5280 9000 98,6 4,0 - 4,5 1200 x 700 x 1200 2500 1600 x 1300 x 1750 2800
1250 6600 11100 98,6 5,0 1500 x 850 x 1500 3400 2000 x 1600 x 2000 3800
1600 8100 13100 98,7 5,0 1500 x 900 x 1500 4100 2100 x 1700 x 2200 4600
2000 9600 15500 98,8 6,0 1800 x 950 x 1800 4300 2600 x 1700 x 2300 4900
2500 11400 18700 98,8 6,0 1800 x 1000 x 1800 5200 2600 x 1700 x 2300 5800
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
16
W D
H
H
W D
7 160 260 94,3 3,5 380 x 230 x 380 85 600 x 400 x 600 110
9 180 330 94,6 3,5 420 x 250 x 420 95 600 x 400 x 600 120
10 190 385 94,6 3,5 420 x 260 x 420 110 600 x 400 x 600 135
14 225 420 95,6 3,5 420 x 270 x 420 120 700 x 500 x 700 160
18 260 510 95,9 3,5 420 x 290 x 420 135 700 x 500 x 700 175
22 290 580 96,2 3,5 420 x 340 x 440 155 700 x 500 x 700 195
28 375 730 96,2 3,5 - 4,0 600 x 370 x 460 225 800 x 700 x 850 280
36 440 860 96,5 3,5 - 4,0 600 x 410 x 460 250 800 x 700 x 850 305
45 480 900 97,0 3,5 - 4,0 600 x 440 x 480 270 800 x 700 x 850 325
58 670 990 97,2 3,5 - 4,0 600 x 470 x 530 330 800 x 700 x 850 385
63 730 1050 97,3 3,5 - 4,0 660 x 480 x 530 350 800 x 700 x 850 405
70 790 1160 97,3 3,5 - 4,0 660 x 480 x 530 380 900 x 800 x 950 450
80 830 1180 97,5 3,5 - 4,0 660 x 480 x 530 400 900 x 800 x 950 470
90 930 1320 97,6 3,5 - 4,0 660 x 490 x 600 430 900 x 800 x 950 500
100 980 1440 97,6 3,5 - 4,0 660 x 490 x 600 460 900 x 800 x 950 530
110 1030 1660 97,6 3,5 - 4,0 700 x 510 x 640 510 1000 x 1000 x 1150 620
125 1180 1730 97,7 3,5 - 4,0 700 x 530 x 640 550 1000 x 1000 x 1150 660
140 1280 1830 97,8 3,5 - 4,0 700 x 530 x 640 600 1000 x 1000 x 1150 710
160 1380 1950 98,0 3,5 - 4,0 700 x 550 x 680 660 1000 x 1000 x 1150 770
180 1530 2090 98,0 3,5 - 4,0 760 x 550 x 760 710 1000 x 1000 x 1150 820
200 1570 2290 98,1 3,5 - 4,0 760 x 550 x 760 770 1000 x 1000 x 1150 880
225 1730 2480 98,2 3,5 - 4,0 760 x 560 x 760 820 1200 x 1100 x 1350 970
250 1850 2680 98,2 3,5 - 4,0 840 x 580 x 780 870 1200 x 1100 x 1350 1020
280 2020 3250 98,2 3,5 - 4,0 840 x 580 x 780 960 1200 x 1100 x 1350 1110
315 2240 3580 98,2 3,5 - 4,0 840 x 590 x 880 1040 1200 x 1100 x 1350 1190
350 2400 3970 98,2 3,5 - 4,0 1100 x 600 x 880 1180 1200 x 1100 x 1350 1330
450 2970 4640 98,3 3,5 - 4,0 1100 x 620 x 980 1390 1400 x 1200 x 1550 1590
580 3200 5440 98,5 3,5 - 4,0 1100 x 640 x 1120 1600 1400 x 1200 x 1550 1800
720 4320 6240 98,6 4,0 - 4,5 1200 x 650 x 1120 2050 1600 x 1300 x 1750 2350
900 5280 7450 98,6 4,0 - 4,5 1200 x 700 x 1200 2500 1600 x 1300 x 1750 2800
1100 6600 8900 98,6 5,0 1500 x 850 x 1500 3400 2000 x 1600 x 2000 3800
1400 8100 10600 98,7 5,0 1500 x 900 x 1500 4100 2100 x 1700 x 2200 4600
1800 9600 12600 98,8 6,0 1800 x 950 x 1800 4300 2600 x 1700 x 2300 4900
2200 11400 15100 98,8 6,0 1800 x 1000 x 1800 5200 2600 x 1700 x 2300 5800
Losses on load are at 115°C with linear load and nominal voltage mains, 50Hz and nominal power.
Enclosure standard colour: RAL 7012.
The data above is for 400V±10% primary voltage and transformer ratio up to 1:2.
R
17
R
18
Warranty terms
19
CT-ORTEA-2018-S12-TRS-2EN