Application - Generator Protection
Application - Generator Protection
General Points
All generators require basic protection against overcurrent and stator short
circuits.
The larger the generator the greater the requirement for protection. Spending
money on protection at the front end will avoid costly generator repairs and loss
of revenue when the generator is out of action.
Generators that run in unmanned situations also require protection to shut down
automatically in case of a fault.
Hospitals
Military Installations
Airports
Oil & Gas Industry
Public Utilities
SEG have over 30 years experience generator protection and have developed
four different product lines to suit any application or Budget.
Basic Line – Low cost single function relays for small generators where no specialist
protection is required.
Professional Line – DIN Rail mounted relays suitable for generators ranging from
250kVA to 2MVA. Digital multifunction relays with communication facilities.
High Tech Line – Door or rack mounted digital multifunction relays with
communication facilities and disturbance recording facilities. Suitable for
generators over 2MVA.
For generators below 250KVA circuit breakers with internal thermal and short time
The time delay on the overcurrent relay needs to be set with the rest of the power
distributions scheme in mind to achieve correct discrimination. To help with these
time settings we have included our relays on a number of electrical software
packages including Amtech Protect 2003 and ERACS.
To isolate the generator in the event of a continuous overload along with a drop
in frequency.
If no AVR is present and the voltage control is manual then sudden changes of
load will result in a voltage increase or decrease.
Phase faults in generator are rare but can occur and must be protected against.
They can develop in the windings and end turns, where all three phases are in
close proximity, or in the slots if there are two coils in the same slot. These faults
often change to ground faults but must still be detected in either case.
The protected zone is determined by the location of the CT’s, the differential
protection may also operate on double or triple pole short circuits occurring
outside the generator but within this zone.
All generators running in parallel with other generators or with the public grid must
be protected against motor operation (reverse power)
When the engine fail begins to act as a motor and will draw around 15% of its
rated power from the system which may be more than the system can supply.
Secondly there is a danger of explosion or fire from unburned fuel in the diesel
engine during motor operation.
Steam turbines tend to over heat when the steam supply is cut off. This is due to
the loss of steam which keeps the turbine blades at a stable temperature.
When a generator operates in parallel with the grid, the electrical supply utilities
require additional stand alone protection for:
This isolates the generator from the grid in the event of a mains failure or
interruption within a very short time.
For more details please refer to the application note on G59 protection.
In systems where many single phase loads are fed it is likely that the generator is
load unbalanced which can also be caused by an open phase, one pole of a CB
open or by a stator winding fault.
In addition the MRQ1 relay from the High Tech Line offers additional exciter over
and undercurrent supervision and diode failure supervision.
Stator earth fault protection is recommended for all generators with a line to line
voltage greater than 3KV independent of their KVA rating.
As most MV generator stator winding problems are phase to ground faults this is
very important protection.
As the field circuit of the generator is ungrounded a single earth fault will not
generally affect the operation of the generator. In the event of a second ground
fault however a portion of the field winding will be short circuited resulting in
unbalanced air gap fluxes which may cause rotor vibration which will damage
the machine very quickly.
The probability of a second ground fault occurring is much greater than the first
one as the first fault increases the stress to ground at other points of the field
winding.