201A Series: Protection Relays

The 201A is a 3-phase voltage monitor that protects motors from 190-480V AC. It has advanced LED diagnostics to indicate normal operation or fault conditions. The microcontroller-based device constantly monitors voltages and will deactivate the output relay if harmful conditions like low voltage, unbalance, or phase reversal are detected. It features an auto-ranging voltage selection, compact DIN rail or surface mount design, and visual fault indications.

Uploaded by

Luis Romero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views2 pages

201A Series: Protection Relays

The 201A is a 3-phase voltage monitor that protects motors from 190-480V AC. It has advanced LED diagnostics to indicate normal operation or fault conditions. The microcontroller-based device constantly monitors voltages and will deactivate the output relay if harmful conditions like low voltage, unbalance, or phase reversal are detected. It features an auto-ranging voltage selection, compact DIN rail or surface mount design, and visual fault indications.

Uploaded by

Luis Romero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Protection Relays

Voltage Monitoring Relays

201A SERIES
3-Phase Voltage/Phase Monitor

Description
The 201A is a 3-phase, auto-ranging, dual-range voltage monitor
that protects 190-480 V ac, 50/60 Hz motors regardless of size.
The product provides a user selectable nominal voltage setpoint
and the voltage monitor automatically selects between the
200 V and 400 V range. The 201A includes advanced single LED
diagnostics, where color and light patterns distinguish between
faults and normal conditions.
This unique microcontroller-based voltage and phase-sensing
device constantly monitors the 3-phase voltages to detect
harmful power line conditions. When a harmful condition is
detected, the 201A’s output relay is deactivated after a specified
trip delay. The output relay reactivates after power line conditions
return to acceptable levels for a specified restart delay time.

Features & Benefits


FEATURES BENEFITS
Wiring Diagram Proprietary Constant monitoring of single-phase, low voltage,
201A WITH MOTOR CONTROL microcontroller voltage unbalance, phase reversal, harmful power
based circuitry line conditions. High voltage monitoring optional.
Compact design for 8-pin; Allows flexiblility in panel installation
DIN rail or surface mount
Auto-sensing wide Automatically senses system voltage between
voltage range 190 - 480 V ac. Saves setup time.
Quick visual indicator for cause of trip. LED
Advanced LED indications include: normal operation, power-up
diagnostics restart delay, reverse-phase trip, unbalance/
single-phase trip, high/low voltage trip

Accessories
OT08PC Octal 8-pin Socket
8-pin 35 mm DIN rail or surface mount. Rated at
10 A @ 600 V ac. Surface mounted with two #6
screws or snaps onto a 35 mm DIN rail.
201A WITH ALARM CONTROL

Ordering Information
MODEL LINE VOLTAGE DESCRIPTION

201A 190–480VAC DIN rail or surface mountable


Includes high voltage detection. DIN rail or
201A-9 190–480VAC
surface mountable

© 2020 Littelfuse, Inc. Rev: 2-A-061220


1-A-062716
www.littelfuse.com/
www.littelfuse.com/201a
Protection Relays
Voltage Monitoring Relays

201A SERIES

Specifications Standards Passed


Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Frequency 50/60 Hz
Radio Frequency Immunity
Functional Characteristics
(RFI), Radiated 150MHz, 10 V/m
Low Voltage (% of setpoint)
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power
Trip 90 % ±1 %
& controls
Reset 93 % ±1 %
Surge
Voltage Unbalance (NEMA)
Immunity IEC IEC 61000-4-5, Level 3, 4 kV line-to-line;
Trip 6%
Level 4, 4 kV line-to-ground
Reset 4.5 %
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to
Optional High Voltage
a level of 6 kV line-to-line
(% of setpoint)
Hi-potential Test Meets UL508 (2 x rated V + 1000V for 1 min.)
Trip 110 % ±1 %
Safety Marks
Reset 107 % ±1 %
UL (OT08PC octal
Trip Delay Time
socket required) UL 508 (File #E68520)
High/Low Voltage Fault 4 seconds
Dimensions H 44.45 mm (1.75”); W 60.33 mm (2.38”);
Unbalance & Phasing Faults 2 seconds
D (with socket) 104.78 mm (4.13”)
Restart Delay Time
Weight 0.7 lbs. (11.2 oz., 317.51 g)
After a Fault 2 seconds
Mounting Method DIN rail or surface mount
After a Complete Power Loss 2 seconds
(plug in to OT08PC socket)
Output Characteristics
Socket Available Model OT08PC (UL Rating 600 V)
Output Contact Rating (SPDT)
Pilot Duty 480 VA @ 240 V ac
The 600 V socket can be surface mounted or installed on DIN Rail.
General Purpose 10 A @ 240 V ac
Note: Manufacturer’s recommended screw terminal torque for the OT Series Octal Sockets is
General Characteristics
12 in.-lbs.
Temperature Range -20° to 70°C (-4° to 158°F)
Must use Model OT08PC socket for UL Rating!
Trip & Reset Accuracy ±1%
Maximum Input Power 5W
Relative Humidity 10–95%, non-condensing per IEC 68-2-3
Terminal Torque 12 in.-lbs. (for OT08-PC socket)
Wire Gauge 12-22 AWG solid or stranded
Transient Protection
(Internal) 2500 V for 10 ms