0900766b816a5796

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

https://www.phoenixcontact.

com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)

Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 1-phase, output: 48 V DC/10 A

Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective
system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical
operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5
V DC ... 56 V DC are covered.

Your advantages
 Quick tripping of standard circuit breakers
 Reliable starting of difficult loads
 Preventive function monitoring

Key Commercial Data


Packing unit 1 pc

GTIN

GTIN 4046356307680
Weight per Piece (excluding packing) 1,600.000 g
Custom tariff number 85044030
Country of origin Thailand

Technical data
Dimensions
Width 90 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm

01/09/2019   Page 1 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Technical data
Dimensions
Depth with alternative assembly 93 mm

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height 6000 m

Input data
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC (UL 508: ≤ 250 V DC)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 5.1 A (120 V AC)
2.3 A (230 V AC)
4.8 A (110 V DC)
2.4 A (220 V DC)
Nominal power consumption 572 VA
Inrush surge current < 20 A (typical)
Mains buffering > 20 ms (120 V AC)
> 20 ms (230 V AC)
Input fuse 12 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor

Output data
Nominal output voltage 48 V DC ±1 %
Setting range of the output voltage (USet) 30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C ... 60 °C, UOUT = 48 V DC)
POWER BOOST (IBoost) 13 A (-25°C ... 40°C permanent, UOUT = 48 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes

01/09/2019   Page 2 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Technical data
Output data
Feedback resistance max. 60 V DC
Protection against surge voltage on the output < 60 V DC
Active current limitation IBOOST = 13 A (for short-circuit), approximately
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 80 mVPP (with nominal values)
Output power 480 W
Typical response time <1s
Maximum power dissipation in no-load condition 16 W
Power loss nominal load max. 41 W

General
Net weight 1.7 kg
Efficiency > 93 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 900000 h (25 °C)
> 630000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active
components, 50 mm vertically
Assembly instructions
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm
vertically bottom

Connection data, input


Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 18
Conductor cross section AWG max. 10
Stripping length 7 mm
Screw thread M3

Connection data, output


Connection method Screw connection

01/09/2019   Page 3 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Technical data
Connection data, output
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 10
Stripping length 7 mm
Screw thread M3

Connection data for signaling


Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 18
Conductor cross section AWG max. 10
Screw thread M3

Standards and Regulations


Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CSA
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
EN 50178/VDE 0160 (PELV)
and their assembly into electrical power installations
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410

01/09/2019   Page 4 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Technical data
Standards and Regulations
Standard – Protection against shock currents, basic requirements for
EN 50178
protective separation in electrical equipment
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Standard - Approval for medical use IEC 60601-1, 2 x MOOP
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to
Semi F47-0706
mains voltage dips
Information technology equipment - safety (CB scheme) CB Scheme
Rail applications EN 50121-4
Overvoltage category (EN 62477-1) III

Environmental Product Compliance


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”

Drawings

Block diagram

L (+)

active

N (-) PFC

DC OK
I < IN
13
14

Classifications
eCl@ss

eCl@ss 4.0 27040702


eCl@ss 4.1 27040702
eCl@ss 5.0 27242213
eCl@ss 5.1 27242200
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002

01/09/2019   Page 5 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Classifications
eCl@ss
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701

ETIM

ETIM 2.0 EC001039


ETIM 3.0 EC001039
ETIM 4.0 EC002540
ETIM 5.0 EC002540
ETIM 6.0 EC002540

UNSPSC

UNSPSC 6.01 30211502


UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004

Approvals
Approvals

Approvals

DNV GL / CSA / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / cUL Listed / SEMI F47 / EAC / EAC / cULus Recognized /
cULus Listed

Ex Approvals

UL Listed / cUL Listed / cULus Listed

Approval details

DNV GL 
  http://exchange.dnv.com/tari/  TAE000014W

CSA 
  http://www.csagroup.org/services-industries/product-listing/  2162676

UL Listed 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 123528

01/09/2019   Page 6 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Approvals

UL Recognized 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 211944

cUL Recognized 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 211944

IECEE CB Scheme 
  http://www.iecee.org/  SI-2283 A1

cUL Listed 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 123528

SEMI F47     SEMI F47

EAC 
    EAC-Zulassung


 RU C-
EAC   
DE.A*30.B.01082

cULus Recognized 
    

cULus Listed 
    

Accessories
Accessories
Assembly adapter

01/09/2019   Page 7 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Accessories

Assembly adapters - UWA 182/52 - 2938235

Universal wall adapter for securely mounting the power supply in the event of strong vibrations. The power supply is
screwed directly onto the mounting surface. The universal wall adapter is attached at the top/bottom.
 
 

Device protection

Type 3 surge protection device - PLT-SEC-T3-230-FM-UT - 2907919

Type 2/3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 230 V AC/DC.
 
 

Type 3 surge protection device - PLT-SEC-T3-60-FM-UT - 2907917

Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 60 V AC/DC.
 
 

Mounting rail adapter

DIN rail adapter - UTA 107 - 2853983

Universal DIN rail adapter


 
 

Redundancy module

Diode - QUINT-DIODE/48DC/2X20/1X40 - 2320160

DIN rail diode module 48 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.
 
 

01/09/2019   Page 8 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Accessories

Redundancy module - TRIO-DIODE/48DC/2X10/1X20 - 2866527

Redundancy module with function monitoring, 48 V DC, 2x 10 A, 1x 20 A


 
 

Thermomagnetic device circuit breakers

Thermomagnetic device circuit breaker - CB TM1 1A SFB P - 2800836

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
 
 

Thermomagnetic device circuit breaker - CB TM1 2A SFB P - 2800837

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
 
 

Thermomagnetic device circuit breaker - CB TM1 3A SFB P - 2800838

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
 
 

Thermomagnetic device circuit breaker - CB TM1 4A SFB P - 2800839

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
 
 

01/09/2019   Page 9 / 10
https://www.phoenixcontact.com/gb/products/2866682

Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682


Accessories

Thermomagnetic device circuit breaker - CB TM1 5A SFB P - 2800840

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
 
 

Phoenix Contact 2019 © - all rights reserved


http://www.phoenixcontact.com

01/09/2019   Page 10 / 10