FusionModule800 Smart Small Data Center

V100R001C20

Product Description

Issue 04
Date 2022-08-20

HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.


Copyright © Huawei Digital Power Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Digital Power Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei
Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope. Unless otherwise
specified in the contract, all statements, information, and recommendations in this document are
provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Digital Power Technologies Co., Ltd.


Address: Huawei Digital Power Antuoshan Headquarters

Futian,Shenzhen 518043

People's Republic of China

Website: https://e.huawei.com

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. i


FusionModule800 Smart Small Data Center
Product Description About This Document

About This Document

Purpose
This document describes the FusionModule800 Smart Small Data Center (smart
module for short) in terms of its positioning, features, typical application
scenarios, system architecture, and key technical specifications, helping readers to
systematically understand the FusionModule800.

Intended Audience
This document is intended for:
● Sales engineers
● Technical support engineers
● System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk


which, if not avoided, will result in death or
serious injury.

Indicates a hazard with a medium level of risk


which, if not avoided, could result in death or
serious injury.

Indicates a hazard with a low level of risk


which, if not avoided, could result in minor or
moderate injury.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. ii


FusionModule800 Smart Small Data Center
Product Description About This Document

Symbol Description

Indicates a potentially hazardous situation


which, if not avoided, could result in
equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not
related to personal injury.

Supplements the important information in the


main text.
NOTE is used to address information not
related to personal injury, equipment damage,
and environment deterioration.

Change History
Issue Date Description

04 2022-08-20 Updated section "Typical


Configurations."

03 2021-01-28 Updated sections


"Installation Guide" and
"Video Management."

02 2020-03-20 Updated section


"Preparations and WebUI
Login."

01 2019-12-13 This issue is the first


official release.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. iii
FusionModule800 Smart Small Data Center
Product Description Contents

Contents

About This Document................................................................................................................ ii


1 Positioning................................................................................................................................ 1
2 Features..................................................................................................................................... 4
3 Typical Application Scenarios and Configurations.......................................................... 6
3.1 Typical Application Scenarios.............................................................................................................................................. 6
3.2 Single-Row Cold and Hot Aisle Containment................................................................................................................6

4 System Architecture................................................................................................................ 8
4.1 Structure System......................................................................................................................................................................8
4.1.1 Cabinet.................................................................................................................................................................................... 8
4.1.2 Converged Cabinet............................................................................................................................................................ 10
4.1.3 Components of Single-Row Cold and Hot Aisle Containment.......................................................................... 12
4.2 Power Supply and Distribution System......................................................................................................................... 14
4.2.1 Technical Specifications................................................................................................................................................... 15
4.2.2 Working Principles............................................................................................................................................................ 16
4.2.3 Hardware Description...................................................................................................................................................... 18
4.2.3.1 Power Distribution Module........................................................................................................................................ 19
4.2.3.2 UPS...................................................................................................................................................................................... 31
4.2.3.2.1 Appearance................................................................................................................................................................... 31
4.2.3.2.2 Product Structure........................................................................................................................................................ 31
4.2.3.2.3 Physical Specifications.............................................................................................................................................. 32
4.2.3.2.4 Environmental Specifications..................................................................................................................................33
4.2.3.2.5 Mains Input Electrical Specifications................................................................................................................... 33
4.2.3.2.6 Bypass Input Electrical Specifications.................................................................................................................. 34
4.2.3.2.7 Output Electrical Specifications............................................................................................................................. 35
4.2.3.2.8 Battery Specifications................................................................................................................................................ 36
4.2.3.2.9 ECO Feature.................................................................................................................................................................. 37
4.2.3.2.10 Parallel Feature......................................................................................................................................................... 37
4.2.3.2.11 Safety Regulations and EMC................................................................................................................................ 38
4.2.3.3 Transformer...................................................................................................................................................................... 38
4.2.3.3.1 Appearance................................................................................................................................................................... 38
4.2.3.3.2 Technical Specifications............................................................................................................................................ 38
4.2.3.4 Battery Cabinet............................................................................................................................................................... 39

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. iv


FusionModule800 Smart Small Data Center
Product Description Contents

4.2.3.4.1 Appearance................................................................................................................................................................... 39
4.2.3.4.2 Technical Specifications............................................................................................................................................ 40
4.2.3.5 Battery Pack..................................................................................................................................................................... 41
4.2.3.5.1 Appearance................................................................................................................................................................... 41
4.2.3.5.2 Technical Specification.............................................................................................................................................. 41
4.2.3.6 rPDU................................................................................................................................................................................... 41
4.2.3.6.1 Basic rPDU.....................................................................................................................................................................41
4.2.3.6.2 (Optional) Monitoring rPDU.................................................................................................................................. 42
4.3 Cooling System...................................................................................................................................................................... 43
4.3.1 Features................................................................................................................................................................................ 43
4.3.2 Product Composition........................................................................................................................................................ 45
4.3.2.1 Indoor Unit....................................................................................................................................................................... 45
4.3.2.2 Outdoor Unit................................................................................................................................................................... 47
4.3.3 Smart Cooling Product Control Unit........................................................................................................................... 49
4.3.4 Application Conditions..................................................................................................................................................... 50
4.3.5 Technical Specifications................................................................................................................................................... 51
4.4 Monitoring System............................................................................................................................................................... 55
4.4.1 Overview............................................................................................................................................................................... 55
4.4.2 System Functions............................................................................................................................................................... 58
4.4.2.1 Monitoring........................................................................................................................................................................ 58
4.4.2.2 App View........................................................................................................................................................................... 58
4.4.2.3 Alarm.................................................................................................................................................................................. 59
4.4.2.4 Historical Data Query................................................................................................................................................... 59
4.4.2.5 Linkage Control...............................................................................................................................................................59
4.4.3 Key Hardware Devices..................................................................................................................................................... 60
4.4.3.1 ECC800-Pro Data Center Controller.........................................................................................................................60
4.4.3.1.1 Product Configuration............................................................................................................................................... 60
4.4.3.1.2 Main Control Module................................................................................................................................................ 61
4.4.3.1.3 Power Module.............................................................................................................................................................. 70
4.4.3.2 PAD..................................................................................................................................................................................... 71
4.4.3.3 Smart ETH Gateway...................................................................................................................................................... 71
4.4.3.4 WiFi Module.....................................................................................................................................................................73
4.4.3.5 ETH Converter................................................................................................................................................................. 74
4.4.3.6 Environment Monitoring System.............................................................................................................................. 76
4.4.3.6.1 WLDS900 Water Sensor (BOM Number: 33010352)..................................................................................... 76
4.4.3.6.2 Electrode Water Sensor (BOM Number: 33010444)...................................................................................... 77
4.4.3.6.3 Temperature Sensor (BOM Number: 33010348).............................................................................................78
4.4.3.6.4 T/H Sensor (BOM Number: 02312PBL).............................................................................................................. 79
4.4.3.6.5 T/H Sensor (BOM Number: 33010516).............................................................................................................. 80
4.4.3.6.6 Smoke Detector........................................................................................................................................................... 81
4.4.3.7 Access Control System.................................................................................................................................................. 82
4.4.3.7.1 Access Actuator........................................................................................................................................................... 82

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. v


FusionModule800 Smart Small Data Center
Product Description Contents

4.4.3.7.2 Cabinet Electronic Clasp Lock.................................................................................................................................86


4.4.3.8 In-Room Access Control............................................................................................................................................... 88
4.4.3.8.1 Fingerprint and Card Reader with a Keypad.....................................................................................................88
4.4.3.8.2 Fingerprint and Card Reader.................................................................................................................................. 90
4.4.3.8.3 Card Reader with a Keypad.....................................................................................................................................91
4.4.3.8.4 Magnetic Lock............................................................................................................................................................. 92
4.4.3.9 Video Management System....................................................................................................................................... 92
4.4.3.9.1 IPC6325 Camera.......................................................................................................................................................... 93
4.4.3.9.2 VCN510.......................................................................................................................................................................... 94
4.4.3.9.3 IVS1800.......................................................................................................................................................................... 95
4.4.3.10 (Optional) eLight......................................................................................................................................................... 97
4.4.3.11 (Optional) iBattery...................................................................................................................................................... 99
4.5 (Optional) NetEco6000 Intelligent Data Center Management System.......................................................... 100
4.5.1 System Overview............................................................................................................................................................. 100
4.5.2 TaiShan 200 Server......................................................................................................................................................... 101
4.5.3 LAN Switch........................................................................................................................................................................ 101
4.6 (Optional) Edge Data Center Management System.............................................................................................. 102
4.7 Surge Protection and Grounding System................................................................................................................... 103
4.7.1 Surge Protection Solution............................................................................................................................................ 103
4.7.2 Grounding Solution........................................................................................................................................................ 103
4.8 Fire Extinguishing System................................................................................................................................................ 104
4.9 Integrated Cabling System.............................................................................................................................................. 104
4.9.1 Integrated Cabling.......................................................................................................................................................... 104
4.9.2 Cables.................................................................................................................................................................................. 105

5 Technical Specifications..................................................................................................... 106


6 Refrigerant Pump Principles.............................................................................................108
7 Equipment Derating Coefficients.................................................................................... 111
8 Acronyms and Abbreviations............................................................................................112

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. vi


FusionModule800 Smart Small Data Center
Product Description 1 Positioning

1 Positioning

The FusionModule800 is a smart small data center solution applied to air cooled
scenarios where the equipment room area is less than 40 m2. This solution mainly
applies to city-, district-, and county-level data centers of the government vertical
industry, small-sized second-level branches and large-sized offices in the financial
industry, and equipment rooms of small- and medium-sized enterprises. The
following figure shows the position of the FusionModule800 in the product family.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 1


FusionModule800 Smart Small Data Center
Product Description 1 Positioning

Figure 1-1 Position of the FusionModule800 in the financial industry

(1) FusionModule5000 (2) FusionModule2000

(3) FusionModule800 (4) FusionModule500

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 2


FusionModule800 Smart Small Data Center
Product Description 1 Positioning

Figure 1-2 Position of the FusionModule800 in the government vertical industry

(1) FusionModule5000 (2) FusionModule2000

(3) FusionModule800 (4) FusionModule500

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 3


FusionModule800 Smart Small Data Center
Product Description 2 Features

2 Features

The FusionModule800 features integration, safety, reliability, small footprint,


energy conservation, easy and quick installation, compatible structure, rapid and
flexible deployment, and comprehensive monitoring. The FusionModule800
represents a new-generation smart module data center. The Converged Cabinet
integrates the uninterruptible power system (UPS), power distribution, smart
cooling product, and management system.

Integration
The smart module integrates the cabinet system, power supply and distribution
system, cooling system, management system, surge protection and grounding
system, integrated cabling system, and fire extinguishing system. It adopts a
modular and integrated design to provide a comprehensive solution.

Safety and Reliability


● Electrical and extra-low voltage (ELV) cables are routed separately to
minimize electromagnetic interference.
● UPSs work in N+1 redundancy mode to improve the system reliability.
● Each UPS is configured with a manual maintenance bypass switch. When the
smart module is working properly, the switch is turned off to prevent
electrical accidents caused by misoperations.
● When the cooling system is faulty due to a power failure, the
FusionModule800 uses the equipment room environment to facilitate heat
dissipation. In this way, the ambient temperature of the equipment can be
maintained in a period of time to avoid abrupt temperature increase. This
ensures the safe operation of servers and equipment until the cooling system
recovers.

Small Footprint and Energy Conservation


● The equipment room can be renovated from an office building room.
● The smart module can be directly installed on a concrete floor in a building,
which simplifies external engineering.
● The delivery cycle is short. The smart module can be installed and
commissioned quickly within three man-days (for a typical 8.5 kW/R3 module
scenario).

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 4


FusionModule800 Smart Small Data Center
Product Description 2 Features

Easy and Quick Installation


● Standard solutions and engineering designs are adopted.
● Cabinets are assembled with the aisle containment for delivery, saving both
space and time.
● The rack-mounted smart cooling product indoor units are prefabricated,
facilitating the redundancy.

Architecture Compatibility
● The FusionModule800 supports T1, T1 low-temperature, and T3 environments.
● The FusionModule800 supports cold and hot aisle containment, saving energy
and reducing noise.
● Modular power distribution and smart cooling products facilitate flexible
expansion.

Fast and Flexible Deployment


● The integrated design supports the relocation of primary equipment with
offices.
● Flexible deployment based on the dimensions of the equipment room and the
power consumption of each cabinet is supported to meet the requirements of
capacity expansion.
● IT cabinets are flexibly configured with servers and storage and network
devices to meet enterprise requirements for web application and internal
services and provide users with more space.

Comprehensive Monitoring
● Various sensors monitor the functional modules in the equipment room in
real time.
● The smart module provides a module-level PAD to easily manage the
functional modules locally.
● A maximum of three smart module cameras and in-room cameras can be
monitored. (Smart module cameras are installed in the smart module and the
in-room cameras are installed in the room.)
● In-room access controllers can be monitored.
● ECC800-Pros in two smart modules can be cascaded.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 5


FusionModule800 Smart Small Data Center
Product Description 3 Typical Application Scenarios and Configurations

3 Typical Application Scenarios and


Configurations

3.1 Typical Application Scenarios


The solution mainly applies to government, education, medical care,
transportation, energy, finance, small- and medium-sized enterprises, and
branches of large companies. It can be sold in:
● Asia, Europe, and Africa: China, Asia Pacific, Africa (including high-
temperature areas in North Africa), Europe, and Middle East. The solution
supports the 380–415 V, 3 Ph+N, 50/60 Hz power systems.
● Latin America: The solution supports the 208–240 V, 3 Ph+N, 50/60 Hz power
systems.

3.2 Single-Row Cold and Hot Aisle Containment


Figure 3-1 Single-row cold and hot aisle containment

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 6


FusionModule800 Smart Small Data Center
Product Description 3 Typical Application Scenarios and Configurations

Figure 3-2 Layout of single-row cold and hot aisle containment

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 7


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4 System Architecture

4.1 Structure System

4.1.1 Cabinet
Cabinets are classified into the Converged Cabinet, battery cabinet, IT cabinet, and
network cabinet.
Cabinets used in the data center comply with the International Electrotechnical
Commission (IEC) 60297-1 standard and provide stable installation space for
servers, thereby ensuring the safe operation of servers.

Figure 4-1 Cabinet

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 8


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-1 Cabinet technical specifications


Item Technical Specifications

Dimensions (H x ● IT cabinet: 2000 mm x 600 mm x 1350 mm


W x D) ● Network cabinet: 2000 mm x 800 mm x 1350 mm
● Battery cabinet (deployed inside the aisle containment):
2000 mm x 600 mm x 1350 mm
● Battery cabinet (deployed outside the aisle containment):
2000 mm x 600 mm x 1100/1200 mm
● Converged Cabinet: 2000 mm x 600 mm x 1350 mm

Color Black

Material High-intensity class A carbon cold rolled steel plate and


zinc-coated steel plate

Air channel Front and rear air channels

Space for ● Each cabinet provides 42 U available space, the position


installing the IT of each U is marked on the vertical mounting bars.
cabinet and ● The maximum depth for installing devices inside the
network cabinet cabinet is 750 mm.
● Positions for vertically installing two rPDUs are provided
in the rear of the cabinet.

Installation mode Installed on a base (concrete floor or ESD floor)

Static load 1500 kg

Dynamic load 1000 kg

Protection level IP20

Figure 4-2 Mounting hole positions at the cabinet bottom

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 9


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-2 Technical specifications of mounting holes at the cabinet bottom


Cabinet Model Mounting Hole (L x W)

2000 mm x 600 mm x 1350 mm 980 mm x 400 mm

2000 mm x 800 mm x 1350 mm 980 mm x 600 mm

4.1.2 Converged Cabinet


The Converged Cabinet consists of the UPS module, input and output power
distribution module, smart cooling product control unit, rack-mounted smart
cooling product module, and monitoring module.

Figure 4-3 Converged Cabinet

NOTE

The figure uses one scenario as an example.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 10


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-4 Converged Cabinet scenario (Asia, Europe, and Africa)

(1) Indicator module (2) Power distribution module (3) UPS2000

(4) ECC800-Pro (5) Smart cooling product (6) Smart cooling product
control unit indoor unit

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 11


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-5 Converged Cabinet scenario (Latin America)

(1) Indicator module (2) Power distribution module (3) UPS2000

(4) Transformer (5) ECC800-Pro (6) Smart cooling product


control unit

(7) Smart cooling product


indoor unit

4.1.3 Components of Single-Row Cold and Hot Aisle


Containment
The components of single-row aisle containment include an enclosed framework,
door components, binding plates, M-shaped cable troughs, and so on.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 12


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-6 Single-row cold and hot aisle containment

(1) IT cabinet (2) Camera mounting kit on (3) Gas spring


the enclosed framework

(4) Side sealing plate (5) Battery cabinet (6) Cabinet electronic clasp
lock

(7) Converged cabinet

Cabinet Door
● In cold and hot aisle containment, a sealed glass door is configured at the
front and a sealed sheet metal door at the rear.
● By default, the front and rear doors of a cabinet are equipped with electronic
clasp locks, which can be unlocked only by using dedicated keys.

Figure 4-7 Front door

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 13


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-8 Rear door

Cable Trough (Optional)


● Cable troughs are clamped one by one to form a whole. A cable trough is
assembled using two side plates, one supporting plate, and one partition
plate (used to separate ELV optical fibers from ELV network cables and
separate electrical route A from electrical route B).
● Signal cables and power cables are routed in different cable troughs to
separate electrical cables from ELV cables.

Figure 4-9 Cable trough

4.2 Power Supply and Distribution System


The Converged Cabinet integrates the rack-mounted UPS, power distribution
module, transformer, smart cooling product indoor unit, and ECC800-Pro.
● The Converged Cabinet houses the UPS input and output, IT load, smart
cooling product power distribution, and management system power
distribution, and supports single and dual power inputs.
● The power distribution module, which is rack-mounted, includes the surge
protective device (SPD), UPS input, output, and maintenance bypass as well
as the power supply to IT loads and smart cooling products.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 14


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● N and N+1 UPS systems are supported, and 10 kVA and 20 kVA UPSs can be
selected to adapt to the actual load power. The power distribution module for
IT loads supports a maximum of 10 cabinets. Choose an appropriate power
distribution module based on the load configuration.
● The air cooled smart cooling product consists of the indoor unit and outdoor
unit and is supplied with mains power.
● The management system consists of the ECC800-Pro, VCN, camera, cabinet
electronic clasp lock, temperature sensor, temperature and humidity sensor
(T/H sensor), smoke detector, iBOX, and water sensor. They are powered by
the power supply and distribution system.
● The power supply and distribution system powers the battery cabinet that
houses the battery tray, battery input switch, and intelligent battery
monitoring system including the iBAT and iBOX and is compatible with 26 Ah,
40 Ah, 65 Ah, and 100 Ah batteries.
● Battery pack: (Optional) 9 Ah battery pack.
● The iBattery (optional) can be used for battery management.

4.2.1 Technical Specifications

Table 4-3 Technical specifications

Item Parameter Specifications

Power supply Input voltage range ● Asia, Europe, and Africa: 342 V –
456 V
● Latin America: 187 V – 264 V

Input frequency 50/60 Hz (±3 Hz)

Power IT load power ● Asia, Europe, and Africa:


consumption – Normal and low temperature
conditions: 8.5 kW/17 kW/25
kW
– High temperature condition: 7
kW/14 kW/21 kW
● Latin America: 7.5 kW/15 kW

Maximum power ● Asia, Europe, and Africa:


consumption of a – Normal and low temperature
single IT cabinet conditions: 7 kW
– High temperature condition: 6
kW
● Latin America: 6 kW

Power supply Single power input Supported


mode
UPS selection UPS2000-10 kVA/UPS2000-20 kVA

Power supply and Normal temperature condition: N/N


distribution mode +1

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 15


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Parameter Specifications

Power system ● Asia, Europe, and Africa: 380


V/400 V/415 V, 50/60 Hz, 3 Ph+N
+PE
● Latin America: 208 V/220 V/230
V/240 V, 50 Hz/60 Hz, 3 Ph+N
+PE

rPDU Input voltage range 187 V AC–264 V AC 1 Ph

Maximum input current 32 A/40 A (Latin America)

4.2.2 Working Principles


Conceptual Diagram for the N Power Distribution System

Figure 4-10 Conceptual diagram for the N power distribution system (Asia, Africa,
and Europe)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 16


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-11 Conceptual diagram for the N power distribution system (Latin
America)

Conceptual Diagram for the N+1 Power Distribution System

Figure 4-12 Conceptual diagram for the N+1 power distribution system (Asia,
Europe, and Africa)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 17


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-13 Conceptual diagram for the N+1 power distribution system (Latin
America)

NOTE

● The 10 kVA UPSs in a parallel system cannot share battery strings or battery packs.
● The 20 kVA UPSs in a parallel system can share battery strings or battery packs.

4.2.3 Hardware Description

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 18


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.1 Power Distribution Module

Table 4-4 Power distribution module specifications


Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power This power 130 mm x 63 A 1x 1x 1x 1x 4x 1x


distribu distribution 442 mm x MCB D63A/ C63A/ C63A/ C40A/ C40A/ C32A/
tion module is 450 mm 1P 1P 1P 1P 1P 4P
module used in the MCB MCB MCB MCB MCB MCB
1 scenario in +1x
which a C25A/
single 1P
input is MCB
provided,
the IT load
power is
less than
or equal to
8.5 kW
module,
and one 10
kV A UPS
and a
maximum
of one
smart
cooling
product are
configured.
The power
distribution
module is
operated
from the
front and
supports
front and
rear
maintenan
ce.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 19


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power This power 263 mm x 100 A 1x 1x 1x 3x 12 x 1x


distribu distribution 442 mm x discon D63A/ C63A/ C63A/ C40A/ C40A/ C32A/
tion module is 450 mm nector 3P 1P 1P 1P 1P 4P
module used in the switch MCB MCB MCB MCB MCB MCB
2 scenario in +3x
which a C25A/
single 1P
input is MCB
provided,
the IT load
power is
less than
or equal to
17 kW, UPS
N
architectur
e is
supported,
and a
maximum
of one 20
kV A UPS
and three
smart
cooling
products
are
configured.
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 20


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power This power 263 mm x 100 A 2x 2x 1x 3x 12 x 1x


distribu distribution 442 mm x discon D63A/ C63A/ C63A/ C40A/ C40A/ C32A/
tion module is 450 mm nector 3P 3P 3P 1P 1P 4P
module used in the switch MCB MCB MCB MCB MCB MCB
3 scenario in +3x
which a C25A/
single 1P
input is MCB
provided,
the IT load
power is
less than
or equal to
8.5 kW or
17 kW, and
UPS N+1
architectur
e is
supported.
If the IT
load power
is less than
or equal to
8.5 kW, a
maximum
of two 10
kVA UPSs
and two
smart
cooling
products
are
configured.
If the IT
load power
is less than
or equal to
17 kW, a
maximum
of two 20
kVA UPSs
and three

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 21


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

smart
cooling
products
are
configured
(two smart
cooling
products
with
humidifiers
and one
only-
refrigeratin
g smart
cooling
product).
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 22


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power This power 130 mm x 125 A 3x 3x 1x 4x 20 x 1x


distribu distribution 442 mm x MCB D63A/ C63A/ C63A/ C40A/ C40A/ C32A/
tion module is 450 3P 3P 3P 1P 1P 4P
module used in the mm/263 MCB MCB MCB MCB MCB MCB
4 scenario in mm x 442 +4x
which a mm x 450 C25A/
single mm 1P
input is MCB
provided,
the IT load
power ≤
25kW, UPS
N/N+1
architectur
e is
supported,
and a
maximum
of three 20
kV A UPSs
and four
smart
cooling
products
are
configured.
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 23


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power ● This 263mm×4 100 A 2x 2x 1x 6x 12 x 1x


distribu module 42mm×45 discon D63A/ C63A/ C63A/ C40A/ C40A/ C32A/
tion supports 0mm/ nector 3P 3P 3P 1P 1P 4P
module intellige 174mm×4 switch MCB MCB MCB MCB MCB MCB
5 nt 42mm×45
detectio 0mm
n of the
total
input
current,
voltage,
and
electric
energy,
and the
IT
branch
current,
voltage,
and
electric
energy
of smart
cooling
product
s.
● This
power
distribut
ion
module
is used
in the
scenario
in which
a single
input is
provide
d, the IT
load
power is
less

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 24


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

than or
equal to
8.5 kW
or 17
kW, and
UPS N
+1
architec
ture is
support
ed. If
the IT
load
power is
less
than or
equal to
8.5 kW,
a
maximu
m of
two 10
kVA
UPSs
and two
smart
cooling
product
s are
configur
ed. If
the IT
load
power is
less
than or
equal to
17 kW,
a
maximu
m of
two 20

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 25


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

kVA
UPSs
and
three
smart
cooling
product
s are
configur
ed (two
smart
cooling
product
s with
humidifi
ers and
one
only-
refrigera
ting
smart
cooling
product
). This
module
can be
operate
d from
the
front
and
maintai
ned
from
the rear
and
front.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 26


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power For Latin 263 mm x / 2x 2x 1x 6x 8x 1x


distribu America. 442 mm x D125A D125A C125A C40A/ C40A/ C32A/
tion This power 450 /2P /2P /2P 2P 1P 4P
module distribution mm/130 MCB MCB MCB MCB MCB MCB
6 module is mm x 442 +8x
used in the mm x 450 C40A/
scenario in mm 2P
which a MCB
single
input is
provided,
the IT load
power is
less than
or equal to
7.5 kW or
15 kW, UPS
N/N+1
architectur
e is
supported,
and a
maximum
of two 10
kV A or 20
kV A UPSs
and three
smart
cooling
products
are
configured
(two smart
cooling
products
with
humidifiers
and one
only-
refrigeratin
g smart
cooling

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 27


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

product).
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 28


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

Power The 352.8 mm / / / / / / /


distribu automatic x 442 mm
tion transfer x 400 mm
module switch
7 (ATS) is
used only
when the
system has
two power
inputs. The
ATS can
work in
any of the
following
modes:
mains-
mains
automatic
switching
back,
mains-
mains
mutual
backup,
mains-
mains not
switching
back,
mains-DG
automatic
switching
back,
mains-DG
mutual
backup,
manual
mode, and
non-
firefighting
power
disconnecti
on. Mains-

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 29


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct

mains
automatic
switching
back is
adopted by
default.

NOTICE

● The preceding table describes the configurations for normal-temperature smart


cooling products. The configurations for high-temperature smart cooling
products are the same.
● The 10 kVA UPS supports single-phase input and single-phase output. The 20
kVA UPS supports single-phase input and single-phase output in Latin America,
and supports three-phase input and three-phase output in Asia, Africa, and
Europe.

Figure 4-14 Power distribution module

NOTICE

The preceding figure is an example.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 30


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.2 UPS
A UPS2000 supports the power systems of 380 V, 400 V, and 415 V, and features
adequate protection, high reliability, intelligence, simplicity, flexible expansion,
high energy efficiency, and environmental protection.

4.2.3.2.1 Appearance

Figure 4-15 UPS2000

4.2.3.2.2 Product Structure

Figure 4-16 Front and rear views of the 10 kVA UPS

(1) Control panel (2) AC input ports (3) AC output ports (4) Parallel ports
(pL and sL)

(5) CAN (6) Optional card slot (7) Battery (8) USB port
communications ports temperature sensor
(MON1 and MON2) port

(9) EPO port (10) Maintenance (11) Input circuit (12) Battery port
bypass port (MBS) breaker

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 31


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-17 Front and rear views of the 20 kVA UPS

(1) Control panel (2) AC input ports (3) Battery terminals (4) EPO port
(mains and bypass)

(5) Maintenance (6) Parallel ports (7) CAN (8) USB port
bypass port (MBS) communications ports
(MON1 and MON2)

(9) Battery (10) Optional card slot (11) AC output ports


temperature sensor (pL and sL)
port

4.2.3.2.3 Physical Specifications

Table 4-5 Item


Item 10 kVA 20 kVA

Dimensions (W x 430 mm x 86 mm x 615 430 mm x 130 mm x 757


H x D) mm mm

Weight 16 kg 32 kg

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 32


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.2.4 Environmental Specifications

Table 4-6 Item


Item 10 kVA 20 kVA

Operating 0–40°C
temperature

Humidity 0%–95% RH (non-condensing)

Altitude < 1000 meters


When the altitude is 1000–4000 meters, see IEC 62040-3 to
check how the UPS power is derated. (The output power
derating by 1% for each additional 100 m.)

Storage and –40°C to +70°C (battery pack: –20°C to +40°C)


transportation
temperature

4.2.3.2.5 Mains Input Electrical Specifications

Table 4-7 Mains input electrical specifications


Item 10 kVA 20 kVA

Input power ● Single-phase (L/N) input ● Single-phase (L/N) input


cable + PE cable + PE cable
● Three-phase (L1/L2/L3/N) ● Three-phase (L1/L2/L3/N)
input + PE cable input + PE cable

Rated input ● 220 V AC, 230 V AC, or ● 220 V AC, 230 V AC, or
voltage 240 V AC (single-phase 240 V AC (single-phase
input) input)
● 380 V AC, 400 V AC, or ● 380 V AC, 400 V AC, or
415 V AC (three-phase 415 V AC (three-phase
input) input)

Input voltage ● 80–280 V AC, single-phase ● 80–280 V AC, single-phase


(When the voltage is 80– (When the voltage is 80–
176 V AC, the load power 176 V AC, the load power
is linearly derated to is linearly derated to
40%–100%.) 40%–100%.)
● 138–485 V AC, three- ● 138–485 V AC, three-
phase (When the voltage phase (When the voltage
is 138–305 V AC, the load is 138–305 V AC, the load
power is linearly derated power is linearly derated
to 40%–100%.) to 40%–100%.)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 33


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item 10 kVA 20 kVA

Input power ● > 0.99 (single-phase > 0.99


factor (100% input)
resistive load) ● > 0.95 (three-phase input)

No-load loss < 90 W < 180 W

Double-power Disabled Enabled


input

Startup voltage 120–280 V AC 120–280 V AC

Diesel generator Minimum 1.5 times the UPS Minimum 1.5 times the UPS
input capacity rated capacity rated capacity

4.2.3.2.6 Bypass Input Electrical Specifications

Table 4-8 Bypass input electrical specifications


Item 10 kVA 20 kVA

Bypass voltage ● Upper threshold: 10%/15%/20%/25%@220 V AC


● Upper threshold: 10%/15%/20%@230 V AC
● Upper threshold: 10%/15%@240 V AC
● Lower threshold: 10%/20%/30%/40%/50%/60%

Bypass frequency Maximum ±6 Hz (configurable on the LCD)


tolerance

Bypass overload ● Load < 125%: continuous in bypass mode


capability ● 125% ≤ load < 150%: 1 minute in bypass mode
● Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.

Input mode One mains input ● One mains input


● Two mains inputs

NOTE

The upper and lower thresholds are configurable on the LCD.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 34


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.2.7 Output Electrical Specifications

Table 4-9 Output electrical specifications


Item 10 kVA 20 kVA

Rated capacity 10 kVA 20 kVA

Output power 0.9


factor (PF)

Rated output 220 V AC, 230 V AC, or 240 ● 220 V AC, 230 V AC, or
voltage V AC (single-phase output; 240 V AC (single-phase
select a voltage system by output; select a voltage
setting a voltage level on system by setting a
the LCD.) voltage level on the LCD.)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)

Output voltage ±1%


tolerance

Total harmonic < 4% (non-linear load)


distortion of
output voltage < 2% (resistive load)
(THDv)

Crest factor A maximum of 3:1

Inverter overload ● 105% ≤ load < 125%: transfer to bypass mode after 5
capability minutes
● 125% ≤ load < 150%: transfer to bypass mode after 1
minute
● Load ≥ 150%: transfer to bypass mode after 100
milliseconds
The UPS stops supplying power if the bypass is abnormal.

Dynamic voltage ±5%


tolerance

Output voltage - ● ±1% (balanced load)


unbalance ● ±3% (unbalanced load)

Average 0.5–2 Hz/s (single UPS) or 0.5–1 Hz/s (parallel system)


frequency
tracking rate

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 35


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item 10 kVA 20 kVA

Power segment ● If overloaded, the UPS disconnects the loads on pL and


(only in single checks whether it is still overloaded.
UPS mode) ● In battery mode, when the battery voltage is less than
the preset value, the UPS disconnects the loads on pL.
● In battery mode, when the battery discharge time
exceeds the preset value, the UPS disconnects the loads
on pL.

4.2.3.2.8 Battery Specifications

Table 4-10 Battery Specifications


Item 10 kVA 20 kVA

Rated battery 240 V DC ±240 V DC


voltage

Number of 16–20, each 12 V DC. If 16–20, respectively in the


batteries the smaller value between positive and negative battery
the numbers of batteries, strings. The rated number is
N, is less than 20, the 20. If the smaller value
battery power is derated between the numbers of
to N/20. batteries in the positive and
negative battery strings, N, is
less than 20, the battery
power is derated to N/20.

Battery string Disabled Enabled


sharing in a
parallel system

Leakage current ≤ 500 µA

Depth of The discharge time is longer than 16 hours (can be set to


discharge (DOD) 0–24 hours, 16 hours by default. If the time is set to 0
protection hours, battery discharge protection is not implemented).

The single-battery voltage drops below 10.8 V in normal


mode.

Standard-UPS 12 V DC VRLA battery


battery type

Standard-UPS 9 Ah -
battery capacity

Backup time > 4 minutes (at full rated load).

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 36


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item 10 kVA 20 kVA

Parallel feature Batter strings can be connected in parallel. If the user


prepares batteries, the maximum number of battery strings
in parallel is specified by the battery manufacturer. A
maximum of four battery strings are recommended.

Charger rated ● 2 A (tolerance ±0.5) for standard models


charge current ● 4 A (tolerance ±0.5) for long backup time models

Charger charge ● Batteries are charged to more than 90% in 3 hours for
time UPS2000-G-10 kVA standard models.
● It depends on battery capacity for UPS2000-G-10 kVA
long backup time models and UPS2000-G-20 kVA.

Charger rated Each cell has an equalized voltage of 2.35 V and a float
charge voltage voltage of 2.25 V. Both are configurable on the LCD.

4.2.3.2.9 ECO Feature

Table 4-11 ECO feature


Item 10 kVA 20kVA

ECO voltage Default value: ±10% (configurable on the LCD)


tolerance The range is ±5% to 10%

ECO frequency Default value: ±2 Hz (configurable on the LCD)


tolerance The range is ±0.5 Hz to ±3 Hz

4.2.3.2.10 Parallel Feature

Table 4-12 Parallel feature


Item 10 kVA 20 kVA

Number of UPSs ≤4
in parallel

NOTE

The UPS2000-G-20 kVA (single-phase input single-phase output) supports 3+1 parallel
systems at most, instead of 4+0 parallel systems.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 37


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.2.11 Safety Regulations and EMC

Table 4-13 Safety regulations and EMC

Item Standards Compliance Remarks

Electromagneti Conducted radiation: IEC/EN -


c compatibility 62040-2

Voltage change, fluctuations, -


and flicker I ≤ 16 A, IEC/EN
61000-3-3; 16 A < I ≤ 75 A,
IEC/EN 61000-3-11

Harmonic interference: 16 A < I -


≤ 75 A, IEC/EN 61000-3-12

Impact current IEC/EN 60240-2 The AC input side meets


(lightning IEC/EN61000-4-5 Level D lightning protection
protection) (differential mode and
YD/T1095-2000 YD/T944-2007 common mode: 5 kA and
8/20 µs).

4.2.3.3 Transformer

4.2.3.3.1 Appearance

Figure 4-18 Transformer appearance

4.2.3.3.2 Technical Specifications

Table 4-14 Transformer technical specifications

Item Specifications

Rated capacity 10 kVA

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 38


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Rated input current 48 A

Rated input voltage Dual-live wire 208 V

input frequency 60 Hz

Output voltage Single-phase 120 V

Output frequency 60 Hz

Efficiency (full load) 96%

Dimensions (W x H x D) 430 mm x 130 mm x 650 mm

Weight 65 kg

4.2.3.4 Battery Cabinet


A battery cabinet provides space for installing batteries and routing battery cables.
The battery cabinet can be deployed inside or outside the Smart Module. A
maximum of two battery cabinets are allowed when deployed inside the Smart
Module.
Battery cabinets are classified into main battery cabinets and auxiliary battery
cabinets. Conversion copper bars are required for the input and output circuit
breakers in the main battery cabinet.
The battery backup time requirement can be 15 minutes and 30 minutes.
The UPSs of 10 kVA can be connected in parallel but cannot share battery strings.
The UPSs of 20 kVA can both be connected in parallel and share battery strings.

4.2.3.4.1 Appearance

Figure 4-19 Battery cabinet exterior

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 39


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.4.2 Technical Specifications

Table 4-15 Battery cabinet technical specifications


Item Specifications

Dimensions (H x W x ● Deployed inside: 2000 mm x 600 mm x 1350 mm


D) ● Deployed outside: 2000 mm x 600 mm x 1100 mm/
1200 mm

Color Black

Material High-intensity class A carbon cold rolled steel sheets


and zinc-coated steel sheets

Ventilation channel Front and rear ventilation channels

Installation space A space of 42 U is available

Installation mode Installed on a concrete floor or ESD floor

Weight (excluding ● Deployed inside: 160 kg


batteries) ● Deployed outside: 140 kg

Static load 1500 kg

Dynamic load 1000 kg

Protection level IP20

Table 4-16 Battery tray specifications


Item Technical Specifications

Dimensions (W x D) 421 mm x 930 mm

Table 4-17 Battery specifications


Battery Battery Vendor Battery Battery Dimensions (H x W
Capacity and Model Weight x D)

26 Ah Shuangdeng 6- 10.0 kg 172 mm x 125 mm x 165


GFM-26 mm

40 Ah Shuangdeng 6- 14.0 kg 172 mm x 165 mm x 197


GFM-40 mm

65 Ah Shuangdeng 6- 22.0 kg 214 mm x 168 mm x 258


GFM-65 mm

100 Ah Shuangdeng 6- 30.0 kg 222 mm x 174 mm x 330


GFM-100 mm

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 40


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.2.3.5 Battery Pack

4.2.3.5.1 Appearance

Figure 4-20 Battery pack

4.2.3.5.2 Technical Specification

Table 4-18 Battery pack specifications

Battery Pack Dimensions (L x W x H) Weight


Specifications

9 Ah 685 mm x 430 mm x 130 69 kg


mm

4.2.3.6 rPDU

4.2.3.6.1 Basic rPDU


By default, IEC sockets are configured for all rPDUs. GB sockets are optional.

Figure 4-21 Full-height rPDU

Figure 4-22 Half-height rPDU

NOTE

Figures provided in this document are for reference only.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 41


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-19 Specifications of the basic rPDU


Type Model Output Port

IEC PDU2000-32-1PH-9/3-B1 9 x C13 + 3 x C19


(half-height)

PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19


(full-height)

PDU2000-40-2PH-20/2-B2 20 x C13 + 2 x C19


(full-height) (Latin
America)

GB PDU2000-32-1PH-9/3-B2 GB 10 A: 9 PCS
(half-height) GB 16 A: 3 PCS

PDU2000-32-1PH-20/4-B2 GB 10 A: 20 PCS
(full-height) GB 16 A: 4 PCS

4.2.3.6.2 (Optional) Monitoring rPDU


The monitoring rPDU accurately and effectively monitors the real-time status
changes of the current, voltage, power, and electric energy of electrical devices in
the data center.
The intelligent rPDU needs to support the following monitoring functions:
● Detect and display the input current.
● Detect and display the total input current.
● Detect and display the input voltage; display the voltage and current
alternately.
● Provide remote input management.
● Remotely query the input voltage, total input current, input power, and input
energy through a serial port.
● Remotely query the rPDU status through a serial port. The status that can be
queried includes normal input power, overcurrent, overvoltage, and
undervoltage, as well as the communication status (normal or abnormal) of
the monitoring board.
● Remotely set the input overcurrent warning threshold, overvoltage alarm
threshold, and undervoltage alarm threshold through a serial port, or locally
set these parameters.
● Working status indicator: The rPDU has a built-in input status indicator, which
indicates the working status of the rPDU.
● Input alarm: If any of input overcurrent, overvoltage, and undervoltage occur,
the working status indicator indicates the fault, and an alarm is reported over
the Modbus port.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 42


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-23 Monitoring rPDU

Table 4-20 Technical specifications of the monitoring rPDU


Item Specifications

Function Supports single-phase 200–240 V AC


power supply, twenty 10 A outputs,
four 16 A outputs

Dimensions (H x W x D) 1732 mm x 50 mm x 45 mm

Output quantity and system 20 x C13 + 4 x C19

Monitoring function Monitors the input power, voltage,


current, power factor, and electric
energy

4.3 Cooling System

4.3.1 Features
The NetCol5000-A features high energy efficiency, high reliability, high
compatibility, multiple power systems, intelligent monitoring, and easy installation
and maintenance.

High Energy Efficiency


● Name-brand efficient DC variable-frequency compressors allow the cooling
capacity of a high-temperature smart cooling product to be adjusted
steplessly in the range of 30% to 100%, the cooling capacity of a normal-
temperature smart cooling product to be adjusted steplessly in the range of
20% to 100%, and the cooling capacity of a low-temperature smart cooling
product to be adjusted steplessly in the range of 20% to 100%. The DC
variable-frequency compressor switches to a fluorine pump for cooling at a
low temperature. This ensures that cooling capacity is delivered as required,
greatly reducing power consumption.
Six EC fans that use the horizontal air supply mode achieve in-cabinet cooling
and support 30%–100% stepless speed adjustment. Precise control can be
implemented over the supply air temperature and direction, thereby reducing
energy consumption.
● Optimal system configurations and efficient refrigeration coil pipes ensure
efficient heat exchange.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 43


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● The variable-frequency temperature control algorithm enables quick response


to load changes and precise temperature control to conserve energy. The
variable-frequency smart cooling product consumes 30% less energy when
compared with a constant-frequency one.
● Fans support variable-frequency start, which lowers the start current and
prevents shock on the power grid and other equipment connecting to the
power grid.
● A wet film humidifier consumes at least 90% less energy when compared
with a conventional humidifier because energy consumption of a wet film
humidifier comes only from the water pump.
● The smart cooling products are connected over the FE port and networked
through the MAC protocol bus to achieve teamwork control, which effectively
saves energy.

High Reliability
● The DC variable-frequency smart cooling product greatly reduces the number
of startup and shutdown times, reducing component failures and extending
the lifespan of key components.
● The electronic expansion valve is used, allowing rapid and precise adjustment
of the refrigerant volume based on the temperature and humidity
requirements and improving system stability. A backup power module is
provided to close the electronic expansion valve when the system experiences
a power failure.
● The Positive Temperature Coefficient (PTC) electric heater provides dual
protection functions: automatic reset and auto-recovery disabling.
● The smart cooling product provides the dehumidification function to maintain
the humidity in cold aisles in the range of 20%–80% at low loads (10% load
at least) in a high humidity environment.
● The smart cooling product features 6 kV surge protection design, providing
high surge protection reliability.

High Compatibility
● The smart cooling product can be rack-mounted, significantly reducing the
footprint required for the cooling system. Only 11 U height space in the
Converged Cabinet is occupied.
● Both the refrigerant pipes and water pipes can be routed from the top or
bottom.
● Heating and humidification functions are optional.

Multiple Power Systems


The smart cooling product is compatible with 208–240 V AC, 1 Ph+N+PE or 2 Ph
+PE, 50 Hz/60 Hz power systems. It supports the voltage range of 187–264 V AC
and the frequency range of 47–53 Hz or 57–63 Hz, which enables the smart
cooling product to be applicable to various countries and regions.

Intelligent Monitoring
● Users can monitor and configure parameters for the cooling system on the
monitoring unit.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 44


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● T/H sensors are cascaded using RJ45 ports, connected to the smart cooling
product control unit, and detect temperature and humidity in real time over
Modbus.

Easy Installation and Maintenance


● The smart cooling product can be easily inserted into a cabinet, facilitating
installation.
● Sealing stop valves are reserved for the end faces of the indoor and outdoor
units. The welding-free design achieves fast maintenance and requires no
open flame.
● The outdoor unit is delivered with refrigerant for 30 m long pipes. The
prefilled refrigerant oil (FV50S) can be used for 80 m long pipes.
● Key components support front and rear maintenance. The entire smart
cooling product can be easily replaced without extra maintenance space.
During the maintenance and replacement of a smart cooling product, other
smart cooling products are not affected.
● The control unit adopts drawer-type maintenance. The power module,
auxiliary module, and main control module embedded in the control unit can
be quickly removed and inserted for maintenance, greatly reducing O&M time
and difficulty.

4.3.2 Product Composition

4.3.2.1 Indoor Unit

Appearance

Figure 4-24 Indoor unit

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 45


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Components
The indoor unit consists of the EC fan, evaporator, electronic expansion valve,
electric heater (optional), wet film humidifier (optional), light load dehumidifier,
and condensate pump.
● EC fan
EC fans that support stepless speed adjustment are used, reducing energy
consumption of loads in overtemperature scenarios.
● Evaporator
The highly efficient V-shaped evaporator and the light load dehumidification
design are used. After entering the light load dehumidification mode, the
smart cooling product automatically closes the dehumidification solenoid
valve to lower the evaporating temperature and increase the dehumidification
capacity. This mode addresses the requirements for effectively controlling the
equipment room temperature and humidity in low load and high humidity
application scenarios.
● Electronic expansion valve
The throttling equipment is a name brand electronic expansion valve. The
system controls the electronic expansion valve to quickly and accurately
adjust the refrigerant volume based on the temperature and humidity
requirements. In this way, system stability and reliability can be ensured, and
balanced temperature and humidity can be achieved in the equipment room.
● Electric heater
The PTC electric heater features quick start, large heating capacity, and
balanced heat dissipation. It automatically adjusts heating capacity and
provides two protection mechanisms to ensure the secure and stable running
of the equipment.
● Wet film humidifier
The wet film evaporation cooling technology is used for cooling to reduce
energy consumption and maintenance costs. Cyclic humidification can save
water.
● Light load dehumidifier
The smart cooling product provides the dehumidification function to maintain
the humidity in cold aisles in the range of 20%–80% at low loads (10% load
at least) in a high humidity environment.
● Condensate pump
The condensate pump uses materials with high temperature resistance to
ensure that condensate water can be drained smoothly in various application
scenarios. The water pump has a lift of 4 meters and uses double liquid level
detectors, providing high reliability. Alarms indicating abnormal water
drainage can be uploaded to the monitoring unit, and audible and visual
alarms can be generated.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 46


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.3.2.2 Outdoor Unit

Exteriors

Figure 4-25 Exterior of the outdoor unit of a normal-temperature model

Figure 4-26 Exterior of the outdoor unit of a high-temperature model

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 47


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-27 Exterior of the outdoor unit of a low-temperature model

Components
The outdoor unit consists of the DC variable-frequency compressor, oil separator,
gas-liquid separator, filter dryer, fan and fluorine pump (only for the low-
temperature outdoor unit).
● Compressor
DC variable-frequency compressors allow the cooling capacity of a high-
temperature smart cooling product to be adjusted steplessly in the range of
30% to 100%, the cooling capacity of a normal-temperature smart cooling
product to be adjusted steplessly in the range of 20% to 100%, and the
cooling capacity of a low-temperature smart cooling product to be adjusted
steplessly in the range of 20% to 100% at the 35°C outdoor temperature.
● Oil separator
Separates the lubricant brought out due to exhaustion of the compressor and
brings back the separated lubricant to the compressor.
● Gas-liquid separator
A gas-liquid separator is installed at the upper end of a compressor to ensure
the compressor reliability.
● Filter dryer
The filter dryer drains the water in the refrigerant pipes and filters out foreign
matter, which reduces the probability of damage to the components and
ensures the efficient and reliable operating. It is installed in the outdoor unit
and easy to maintain.
● Fan
The axial fan is used, which supports stepless speed adjustment.
● Fluorine pump
The fluorine pump uses a special refrigerant pump with low net positive
suction head and good sealing performance. When the outdoor temperature

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 48


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

is low, the compressor does not need to be started. The fluorine pump
pressurization technology is used to implement natural cooling cycle of the
fluorine pump to ensure reliable operation at temperatures as low as –40°C.

4.3.3 Smart Cooling Product Control Unit


The smart cooling product control unit mainly includes the main control board.
The display unit is integrated in the converged cabinet. The controller implements
functions such as logic control, data collection, control signal sending, alarm
reporting, data storage, and teamwork control. The smart cooling product
connects to the ECC over the FE port using the MAC protocol, and the ECC
connects to the NMS to realize remote control.

Main Functions
● Single unit control: When only one unit is running, the controller provides
logic control over components in the unit to meet the indoor temperature and
humidity requirements.
● Teamwork control: When multiple smart cooling products work cooperatively,
the controller optimally distributes the heat load, greatly lowering the power
consumption. Multiple smart cooling products provide backup for higher
reliability.
● Remote management: You can monitor, manage, and upgrade one or more
smart cooling products using the remote management function provided by
Huawei.
● Configuration synchronization: You can synchronize parameters between
smart cooling products on the touchscreen (optional) of the converged
cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
● One-click export: You can export the alarms and logs of a smart cooling
product on the ECC800-Pro WebUI.
● Software upgrade: You can perform a remote upgrade on the touchscreen of
the converged cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
● Alarm details query: You can view the possible causes of alarms and handling
suggestions on the ECC800-Pro WebUI.

Features
● The controller is highly precise and responsive.
● Automatically stores operation logs, 1500 historical alarms, and 30-day
temperature and humidity curves and displays these data on the touchscreen
of the converged cabinet.
● Provides protection functions such as automatic recovery after power failure
and shutdown for protection in the case of abnormal drainage, improving the
system reliability.
● Displays the following information on the touchscreen of the converged
cabinet in real time: operating status of the smart cooling product
components and the corresponding time points.
● Provides RS485 and FE ports that support the MAC-Modbus protocol.
● Uses FE ports for teamwork control networking using the MAC protocol,
offering a higher transmission rate.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 49


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.3.4 Application Conditions


Operating Environment

Table 4-21 Operating Environment


Item Specifications

Indoor unit 0–40°C


operating
temperature

Indoor unit 5%–95% RH (non-condensing)


operating
humidity

Outdoor unit For high-temperature outdoor units: –10°C to +55°C


operating For normal-temperature outdoor units: –20°C to +45°C
temperature
For low-temperature outdoor units: –40°C to +45°C

Storage Without refrigerant: –40°C to +70°C


temperature With refrigerant: –40°C to +55°C

Storage humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m. The smart cooling product performance is


derated when the altitude ranges from 1000 m to 4000 m.
The maximum outdoor operating temperature decreases by
1°C and the nominal cooling capacity decreases by 1% for
each additional 200 m.

Installation Requirements

Table 4-22 Installation Requirements


Installation Mode Rack-mounted

Vertical Difference ● Outdoor unit placed higher than the indoor unit: ≤
Between the Indoor 30 m
and Outdoor Units ● Indoor unit placed higher than the outdoor unit: ≤
8m

Maximum Equivalent 80 m. If the length exceeds 80 m, contact Huawei


Length of One-way technical support.
Pipe

Thermal Insulation ≥ 13 mm
Foam Thickness

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 50


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Water Supply The inlet water pressure should be in the range of


Requirements 0.1–0.7 MPa, and the temperature should be in the
range of 1°C–40°C.
The wet film humidifier should use tap water that
meets the following requirements:
● Non-freezing and nephelometric turbidity units
(NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
For details, refer to the GB 5749-2006 Standards
for Drinking Water Quality.

Drainage The distance between the upper drainage of the


Requirements water pump and the cabinet installation floor should
not exceed 4 m.
(BSPT 1/2 inch drainpipe connectors with external
threads are provided in standard configuration.
Drainpipes and BSPP 1/2 inch connectors with
internal threads should be prepared by the customer.)

Ports

Table 4-23 Ports

Item Specifications

Refrigerant gas ● L ≤ 60 m, reserved port: 5/8 inch (15.9 mm), thread


pipe connection
● 60 m < L ≤ 80 m, reserved port: 7/8 inch (22.2 mm),
thread connection

Refrigerant liquid ● L ≤ 60 m, reserved port: 3/8 inch (9.52 mm), thread


pipe connection
● 60 m < L ≤ 80 m, reserved port: 1/2 inch (12.77 mm),
thread connection

Humidifier water Reserved port: BSPP 1/2 inch, thread connection


inlet pipe

Pipe and cable Top or bottom routing


routing

4.3.5 Technical Specifications


All models (indoor and outdoor units) of this product meet the environmental
protection requirements. The environmental protection mark is as follows.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 51


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-28 Environmental protection mark

Table 4-24 Indoor unit technical specifications


Item NetCol5000-A013HXWE1 NetCol5000-A013HX0E1
(Including Heater and (Excluding Heater and
Humidifier) Humidifier)

Power system 208 V AC–240 V AC 50 Hz/60 Hz 1 Ph+N+PE/2 Ph+PE

Voltage If upstream voltage fluctuation exceeds the rated voltage±10%,


tolerance you are advised to add a voltage regulator. Otherwise, the
smart cooling product may generate alarms frequently and fail
to work properly.

Frequency ±3 Hz
tolerance

Certification Normal-temperature models:


● Asia, Europe, and Africa: REACH, RoHS, CE, CCC, and CQC
● Latin America: REACH, RoHS, and CB
Low-temperature model: REACH, RoHS, CE, CCC, CQC, and EAC
High-temperature models: REACH, RoHS, CE, SASO

Maximum 17.3 A 3.3 A


current

Cooling mode Air cooled Air cooled

Refrigerant R410A R410A

Cooling 12.5 kWa 12.5 kWa


capacity

Humidification Yes No
function

Humidification 1.0 kg/h -


capacity

Heating Yes No
function

Heating 3 kW -
capacity

Air supply Horizontal air supply Horizontal air supply


mode

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 52


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item NetCol5000-A013HXWE1 NetCol5000-A013HX0E1


(Including Heater and (Excluding Heater and
Humidifier) Humidifier)

Maximum 2600 m3/h 2600 m3/h


airflow

Condensate Yes Yes


pump

Power supply Single power supply Single power supply


mode

Dimensions (H 486 mm x 442 mm x 800 mm 486 mm x 442 mm x 800 mm


x W x D)b

Package 710 mm x 610 mm x 1000 710 mm x 610 mm x 1000 mm


dimensions (H mm
x W x D)

Net weight/ 52.6 kg/70 kg 49.4 kg/66.8 kg


Gross weightb

IP rating IP20 IP20

a: The cooling capacity of the smart cooling product is obtained when the
indoor dry bulb temperature is 37.8°C, the indoor wet bulb temperature is
20.8°C, and the outdoor dry bulb temperature is 35°C. The actual cooling
capacity varies depending on the indoor and outdoor ambient temperatures and
relative humidity.
b: The dimensions, net weight, and gross weight of the indoor unit include those
of the control unit.

Table 4-25 Technical specifications of normal-temperature outdoor units

Item NetCol500-A018

Power system Latin America: 208–240 V AC, 50 Hz/60 Hz, 2 PH+PE


Asia, Europe, and Africa: 208–240 V AC, 50 Hz/60 Hz, 1
PH+N+PE

Maximum operating 24 A
current

Number of fans One

Dimensions (H x W 966 mm x 1057 mm x 339 mm


x D)

Package dimensions 1210 mm x 1105 mm x 435 mm


(H x W x D)

Net weight/Gross 83 kg/99 kg


weight

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 53


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item NetCol500-A018

Certification ● Asia, Europe, and Africa: REACH, RoHS, CE, CCC, and
CQC
● Latin America: REACH, RoHS, and CB

Environment type Class B

Protection level IPX4

Table 4-26 Technical specifications of low-temperature outdoor units (Asia,


Europe, and Africa)
Item NetCol500-A021

Power system 220–240 V AC, 50 Hz/60 Hz, 1 PH+N+PE

Maximum 30 A
operating current

Number of fans One

Dimensions (H x W 1350 mm x 1270 mm x 730 mm


x D)

Package dimensions 1530 mm x 1355 mm x 777 mm


(H x W x D)

Net weight/Gross 196 kg/229 kg


weight

Certification REACH, RoHS, CE, CCC, CQC and EAC

Environment type Class B

IP rating IPX5

Table 4-27 Technical specifications of high-temperature outdoor units (Asia,


Europe, and Africa)
Item NetCol500-A020

Power system 220–240 V AC, 50 Hz/60 Hz, 1 PH+N+PE

Maximum operating 30 A
current

Number of fans Two

Dimensions (H x W 1327 mm x 966 mm x 320 mm


x D)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 54


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item NetCol500-A020

Package dimensions 1485 mm x 1082 mm x 435 mm


(H x W x D)

Net weight/Gross 101 kg/114 kg


weight

Certification REACH, RoHS, CE, SASO

Environment type Class B

IP rating IPX4

Outdoor unit application environments are classified by severity as follows:


● Class A (controlled environment): indoor environments where the ambient
temperature and humidity are controlled, including rooms where people live
● Class B (uncontrollable environment): indoor environments where the
ambient temperature and humidity are not controlled or general outdoor
environments with simple shielding measures where the humidity reaches
100% occasionally
● Class C (harsh environment): sea environments, or outdoor land environments
or environments with simple shielding measures, which are within 3.7 km
away from the sea or within 1.2 km away from a pollution source
● Class D (marine environment): environments within 500 m away from the
coast

4.4 Monitoring System

4.4.1 Overview
The management system consists of the management software and other
components. It implements data collection and management for various processes
and infrastructure of the smart module.
The ECC800-Pro manages the real-time status, alarms, and configuration
information about the devices inside the smart module. It also provides a
graphical user interface (GUI) for ease of operating and maintaining devices inside
the smart module.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 55


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-29 Management system network diagram

NOTE

In the figure, RF_Z represents wireless networking, and the iBAT and iBOX communicate
with each other in wireless mode.

Table 4-28 Network diagram description

Device Maximum Quantity Port

Camera 3 FE
NOTE
The total number of room-level cameras
and smart module–level cameras cannot
exceed 3.

VCN 1 FE

Smart ETH gateway 8 FE

Access actuator 2 FE
NOTE
One access actuator connects to at most
one magnetic lock, one access control
device, one exit button, and one
emergency door release button.

NetCol5000-A013 smart 4 FE
cooling product

iBOX (iBattery system) 2 FE

UPS2000 3 CAN

Smoke detector 1 DI

T/H sensor 8 RS485

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 56


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Device Maximum Quantity Port

Temperature sensor 18 AI

Water sensor 1 DI

SPD 1 DI

AC detection board 1 CAN

Electricity meter 1 RS485

Cabinet electronic clasp 24 RS485


lock

WiFi module 1 USB

The management system provides a GUI to implement comprehensive


management functions based on requirements. The system mainly monitors the
following equipment:
● Power equipment: Such as the smart cooling product and UPS
● Environment equipment: such as the smoke detector and water sensor
● Video equipment: camera and VCN. Room-level cameras and smart module-
level cameras can be monitored at the same time.
● Access control equipment: A standard room-level access management system
is integrated to manage and monitor key information such as door status,
card swiping, and permission setting.

Figure 4-30 Layout of the access control system

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 57


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

NOTE

The access actuator should be installed near the door, have a maximum of 3.5 m cabling
distance away from the magnetic lock, and have a maximum of 5 m cabling distance away
from other switches and the access control device.

4.4.2 System Functions

4.4.2.1 Monitoring
● Temperature and humidity monitoring: Detects and collects statistics on the
ambient temperature and humidity inside the smart module.
● Water leakage monitoring: Detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
● Smoke monitoring: Detects smoke in the smart module and provides real-
time alarm signals.
● Power distribution monitoring:
a. (In the intelligent power distribution scenario) Monitors the general
mains input voltage, frequency, current, and power, as well as the UPS
input voltage, frequency, current, switch temperature, and so on.
b. (In the intelligent power distribution scenario) Monitors the current,
electric energy, and switch status of power distribution branches of IT
equipment and smart cooling products, and calculates the load rate.
c. (In the non-intelligent power distribution scenario) Monitors the UPS
input voltage, frequency, current, and so on.
● Smart cooling product monitoring:
a. Monitors the supply and return air temperature and humidity in real
time.
b. Configures the supply air temperature set point in a unified manner,
without the need to separately configure it for each smart cooling
product.
c. Monitors and displays the fan speed, and displays the running
percentage. ECC
d. Displays the cooling load rate.
e. Monitors and displays the compressor running status.
f. Displays the real-time running status of the heating and humidifying.
● Video surveillance: Connects to three cameras and provides PoE power supply;
accesses real-time video images on the WebUI and invokes historical
monitoring data.

4.4.2.2 App View


● Generates a 2.5D layout view that matches the actual layout of the smart
module, including the power distribution module, smart cooling product, IT
cabinet, and temperature and humidity sensor. In addition, the resource usage
rate of electric energy (displayed only when the intelligent power distribution
module is configured), ambient temperature and humidity of the smart
module are displayed on the home screen of the app.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 58


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● Displays the resource usage of the electric energy of the smart module and
each cabinet (displayed only when the intelligent power distribution module
is configured).
● Displays the real-time status and alarms of the aisle temperature and
humidity sensor in the plan view.
● Facial recognition is supported through an app installed on a PAD. After facial
recognition information is added, click Facial Enter to start the facial
recognition. If you do not have facial recognition permission or an error
occurs during facial recognition, you can use the user name and password
login manner.
● After logging in to the app installed on the PAD, you can open the cabinet
door on the corresponding screen.

4.4.2.3 Alarm
● The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
● Alarms can be classified into four severities: critical, major, minor, and
warning. The alarm severities can be user-defined.
● Active alarms can be filtered by device and alarm severity.
● Alarms can be linked with the eLight. The eLight light colors vary with alarm
severities.
● Alarm notifications can be sent by email and SMS.
● A maximum of 500 concurrent active alarms are supported.

4.4.2.4 Historical Data Query


● Historical alarm: You can view the alarms that have been generated in the
system. The historical alarm information includes the device name, alarm
name, alarm severity, alarm generation time, and alarm clearance time.
● Performance data statistics: You can view historical data of devices to help
analyze data or problems.
● Operation log: You can view logs of key operations, such as user login,
parameter modification, data export, device upgrade, and access control
events.
● Data export: You can export historical data of the ECC800-Pro and some
southbound devices.

4.4.2.5 Linkage Control


● Supports the linkage logic of aisle smoke alarms or high temperature alarms.
By default, the IT cabinet doors are opened through linkage by default.
NOTE

The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only
dry contact alarm signals are provided.
● If the protected area of the fire extinguishing system is in the smart module,
when a smoke alarm is generated, the door of the linked cabinet is not
opened. If the door is opened, an alarm (door status alarm) is generated.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 59


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● If the protected area of the fire extinguishing system is outside the smart
module, when a smoke alarm is generated, key hardware devices on the rear
door of the linked cabinet are opened.

4.4.3 Key Hardware Devices

4.4.3.1 ECC800-Pro Data Center Controller

4.4.3.1.1 Product Configuration


The ECC800-Pro data center controller is used to monitor the devices and
environment in the smart module. It consists of the power module and main
control module. You can insert and remove the power module.

Figure 4-31 ECC800-Pro

(1) Power module (2) Main control module

Table 4-29 ECC800-Pro environmental specifications

Item Specifications

Working temperature –20°C to +50°C

Storage temperature –40°C to +70°C

Relative humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m (When the altitude is between 3000 m and


4000 m, the temperature decreases by 1°C for each
additional 200 m.)

Table 4-30 ECC800-Pro structural specifications

Item Specifications

Dimensions (L x W x H) 442 mm x 330 mm x 43.6 mm

Weight 6.3 kg (with a single power module


and a main control module)

Color Black

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 60


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Installation Can be installed in a 1 U space in a


standard 19-inch cabinet

Environmental protection RoHS, REACH, and WEEE

Figure 4-32 ECC800-Pro (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1

(4) AC_INPUT2

Power Ports
The ECC800-Pro provides four power ports, including two AC input ports
(AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUTPUT1 and
DC_OUTPUT2). Table 4-31 provides the power port pin definitions.

Table 4-31 Power port pin definitions


Port Type Pin Description

AC Pin 1 L

Pin 2 PE

Pin 3 N

DC Pin 1 48V+

Pin 2 48VGND

4.4.3.1.2 Main Control Module

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 61


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-33 ECC800-Pro collector main control module

(1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2

(5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE

(9) LAN2/POE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5

(13) AIDI_3 (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN (reserved)

(17) 4G (18) SW button

NOTE

The WLAN port is reserved and cannot be connected to a WLAN antenna for WLAN
communication.

Figure 4-34 ECC800-Pro main control module (side view)

(1) SIM card slot (2) Micro-SD card slot (Reserved)

Specifications

Table 4-32 Technical specifications of the ECC800-Pro main control module

Item Specifications

Power input ● Supports one AC input or two AC inputs


● Rated voltage: 200–240 V AC
● Rated frequency: 50/60 Hz

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 62


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Power output ● Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)


● Output power of two power module supplies: 2000 W (176–
300 V AC); 940 W (linear derating at 85–175 V AC)
● Output power of a single power module supply: 1000 W
(176–300 V AC); 470 W (linear derating at 85–175 V AC)

WAN port ● Supports two WAN ports, which can be connected to the
management systems of two customers. The ports support
autonegotiation of 10/100/1000 Mbit/s communication
rates.
● Connect shielded network cables to the WAN ports.

LAN port ● Supports two LAN ports, which can be connected to


southbound devices. The ports support autonegotiation of
10/100/1000 Mbit/s communication rates.
● Connect shielded network cables to the LAN ports.

RS485 serial ● Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)


port ● Supports four RS485 ports with the default communications
expansion rate of 9600 bit/s.
● COM1–COM3 ports provide 12 V DC power.
● The power supply can be switched on or off and is on by
default.

POE Supports two POE (GE) ports for expansion of the POE bus,
expansion and supports network isolation and ring network.

AIDI ● Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)


expansion ● Provides five universal AIDI ports for connecting to sensors
(RJ45) such as smoke detectors, water sensors, and NTC sensors.
AIDI_1 to AIDI_3 are full-function AIDI ports, and AIDI_4 to
AIDI_5 are simplified AIDI ports without type identification.
● The power supply can be switched on or off and is on by
default.

DO expansion ● Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)


(RJ45) ● One DO port. Supports active DO.
● The power supply can be switched on or off and is on by
default.

Fault isolation There are three groups of 12 V ports. A group has a maximum
current of 660 mA, a route has a maximum current of 800 mA,
and the maximum total current is 2 A.
Group 1: AIDI_1 and DO/12V ports
Group 2: AIDI_2, COM1/AIDI_4, and COM3/12V ports
Group 3: AIDI_3 and COM2/AIDI_5 ports

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 63


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Wireless Supports wireless communication that complies with


communicatio IEEE802.15.4.
n

4G Supports the 4G module. The ECC800-Pro supports short


message service (SMS) message sending and 4G
communication, is compatible with 3G (WCDMA)
communication, and provides a standard SIM card slot.
NOTE
The prerequisite for using a SIM card is that the site has signal
coverage.

USB ● Supports USB 2.0 and 5 V, 1 A power supply.


● After installing the WiFi module, connect the WiFi module
to the ECC800-Pro using the app on the mobile phone or
PAD to view the basic information about the smart module,
such as layout, resources, energy efficiency, environment,
and alarms.
● You can insert a USB flash drive to export historical data
and configuration files and import configuration files.

SW Button ● Restoring the default IP address, factory settings, and user


information.
● RF_Z networking (802.15.4)

Table 4-33 ECC800-Pro RF_Z parameters


Item Specifications

RF_Z Operation 2405–2480 MHz


Frequency

RF_Z EIRP (max.) 8 dBm

Table 4-34 ECC800-Pro 4G parameters


Item Specifications

3G/4G Operation Frequency LTE (FDD): BAND1, BAND2, BAND3,


BAND4, BAND5, BAND7, BAND8,
BAND20
DC-HSPA+/HSPA+/HSPA/UMTS:
850/900/1900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900
MHz

3G/4G EIRP (max.) 23 dBm

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 64


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Communications Port
The ECC800-Pro provides the following communications ports. Figure 4-35 shows
the pins of the RJ45 port.

Figure 4-35 RJ45 port pins

There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN
ports (LAN1/POE and LAN2/POE).

Table 4-35 GE port pin definitions

Item Description

Pin Pin 1 GE1+


sequence
Pin 2 GE1–

Pin 3 GE2+

Pin 4 GE3+

Pin 5 GE3–

Pin 6 GE2–

Pin 7 GE4+

Pin 8 GE4–

Indicator Green Linked, steady on


indicator

Yellow ACT data communication, blinking


indicator

Table 4-36 COM1/AIDI_4, COM2/AIDI_5 port pin definitions

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V DC_OUT

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 65


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Description

Pin 4 RS485+

Pin 5 RS485–

Pin 6 DI–

Pin 7 DI+

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 4-37 COM3/12V port pin definitions

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V DC_OUT

Pin 4 RS485+

Pin 5 RS485–

Pin 6 -

Pin 7 -

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 4-38 COM4/CAN port pin definitions

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 -

Pin 4 RS485+

Pin 5 RS485–

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 66


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Description

Pin 6 -

Pin 7 CAN_H

Pin 8 CAN_L

The following provides the AIDI_1, AIDI_2, and AIDI_3 ports pin definitions.

NOTE

● Pins 1, 2, 4, and 5 identify sensor types.


● Pin 3 and Pin 8 are power output ports.
● Pin 6 and Pin 7 collect sensor data. Pin 7 can detect current type sensors (4–20 mA). Pin
6 and Pin 7 can detect the output status of passive dry contact type sensors. Pin 3 and
Pin 7 can detect temperature sensors.

Table 4-39 AIDI_1, AIDI_2 and AIDI_3 ports pin definitions

Item Description

Pin Pin 1 Type_1


sequence
Pin 2 Type_2

Pin 3 12 V DC

Pin 4 Type_3

Pin 5 Type_4

Pin 6 DI–

Pin 7 DI+

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 4-40 DO/12V port pin definitions

Item Description

Pin Pin 1 -
sequence
Pin 2 -

Pin 3 12 V DC_OUT

Pin 4 -

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 67


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Description

Pin 5 -

Pin 6 DO_OUT+

Pin 7 DO_OUT–

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 4-41 USB port pin definitions

Item Description

Pin sequence Pin 1 5V

Pin 2 DM

Pin 3 DP

Pin 4 GND

Indicators

Table 4-42 Indicators on the ECC800-Pro main control module

Indica Color Name Status Description


tor

RUN Green Running status Steady on The power supply is normal,


indicator the program is being loaded.

Off The power supply is


abnormal.

Blinking at The software runs properly


long (the indicator blinks at 0.5
intervals Hz, on for 1s and then off
for 1s) or the ECC800-Pro
registers with the NetEco
successfully.

Blinking at The ECC800-Pro does not


short register with the NetEco
intervals (the indicator blinks at 5 Hz,
on for 0.125s and then off
for 0.125s).

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 68


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indica Color Name Status Description


tor

ALM Red Alarm indicator Steady on A system failure alarm is


generated.

Off The system is normal.

RF_Z Green Communication Blinking at A network is set up, and no


status indicator long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Blinking at A network is set up, and


super node access is allowed (the
short indicator blinks at 10 Hz, on
intervals for 0.05s and then off for
0.05s).

SW Button

Table 4-43 SW button description

Function Operation Description Indicator Status


Description

Wireless In non-wireless network (802.15.4) The RF_Z indicator is


network RF_Z pairing mode, press and hold down blinking at super
(802.15.4) the button for 3s to 5s to enter the short intervals.
pairing wireless network pairing mode.

In wireless network (802.15.4) The RF_Z indicator is


pairing mode, press and hold down blinking at long
the button for 3s to 5s to exit the intervals.
pairing mode; or the system
automatically exits the pairing mode
after 30 minutes without pressing
the button.

Press and hold down the button for The RF_Z indicator is
more than 8s to 20s to clear blinking at super
network parameters. short intervals.

Turning on Press and hold down the button for None


WLAN 1s to enable WLAN.

Restoring the Hold down for 1 minute. None


default IP
address, factory
settings, and
user information

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 69


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.4.3.1.3 Power Module

Indicator

Table 4-44 PSU indicator description

Indicator Color Name Status Description

Green Power Steady on The converter has a power


indicator input.

Off The converter has no power


input or is faulty.

Blinking at The converter is being


long queried (the indicator blinks
intervals at 0.5 Hz, on for 1s and then
off for 1s).

Blinking at The converter application


short program is being loaded
intervals (the indicator blinks at 4 Hz,
on for 0.125s and then off
for 0.125s).

Yellow Alarm Steady on The converter generates a


indicator forewarning indicating that
power will be limited due to
ambient overtemperature, or
generates a protection
shutdown alarm due to
ambient overtemperature or
undertemperature.

Power input overvoltage or


undervoltage protection

Reverse DC input connection

Slight current imbalance

Output overvoltage

Hibernation

Off The converter generates no


protection alarms.

Blinking at The communication between


long the converter and the
intervals outside is interrupted (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Red Fault Steady on The converter locks out due


indicator to output overvoltage.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 70


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicator Color Name Status Description

The converter delivers no


output due to internal faults.

Off The converter is working


properly.

4.4.3.2 PAD
The PAD, a control panel, allows wireless access to the data center facility
management system. You can monitor the equipment in the data center and
environmental parameters in real time over the app.

Figure 4-36 PAD

The PAD is a capacitive screen which supports multi-touch.

NOTE

If a non-standard PAD is selected, contact technical support.

4.4.3.3 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800-Pro and can be flexibly deployed in a smart
module.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 71


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-37 Smart ETH gateway

(1) PWR_IN cascading (2) FE_1 cascading (3) PoE_1 and PoE_2 (4) PoE_3 and PoE_4
power port signal port ports ports

(5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT
output port output port signal port cascading power port

(9) BLINK button (10) Status indicator

Specifications

Table 4-45 Technical specifications for a smart ETH gateway


Item Specifications

Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC);
power of cascaded smart ETH gateways: max (25 A, 48 V DC)

Power ● PWR_OUT D-type power output terminal, for power


output cascading, output voltage range: 45–55 V DC
● 48V_OUT1 and 48V_OUT2, terminal (1 A,48 V DC), output
voltage range: 45–55 V DC

FE port Two FE ports, RJ45 terminal with an indicator, 10/100M


communication rate, for the cascading between smart ETH
gateways and the communication with the upper computer

POE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at

BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 5 seconds.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 72


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicators

Table 4-46 Indicators on a smart ETH gateway


Indica Color Name Status Description
tor

PWR Green Power Steady on The power input is normal.


input status
indicator Off There is no power input.

RUN Green Module Off The power supply is


running abnormal.
status
indicator Blinking at The smart ETH gateway
long successfully registers with
intervals the ECC800-Pro and the
software runs properly
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).

Blinking at The smart ETH gateway


short has failed to register with
intervals the ECC800-Pro (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).

Blinking The indicator blinks at


super short intervals for
0.5s (blinking at 10 Hz, on
for 0.05s and then off for
0.05s) and then turns off
for 0.5s. The cycle lasts for
10s.

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off No system alarm is


generated.

4.4.3.4 WiFi Module


The WiFi module provides WiFi signals for equipment such as PADs and mobile
phones to interact with the host computer.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 73


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-38 WiFi module

Table 4-47 Technical specifications


Item Specifications

Wireless IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b


standard

Network ● 11n: up to 150 Mbps


bandwidth ● 11g: up to 54 Mbps
● 11b: up to 11 Mbps

Frequency band 2.4-2.4835 GHz

Wireless 20 dBm (MAX EIRP)


transmission
power

Supported Windows 2000/XP/Vista/Linux/Windows 7


operating
system

Ports USB 2.0 Hi-Speed connector

Voltage range 5.0 V DC±5%

Operating -20°C to +70°C


temperature

Storage -40°C to +90°C


temperature

Relative 10%–90% RH (non-condensing)


humidity

Power < 0.8 W

4.4.3.5 ETH Converter


The ETH converter is used to convert the Modbus–RTU protocol or CAN protocol
to the Modbus-MAC protocol for connecting to the POE bus.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 74


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-39 ETH converter

(1) Status indicator (2) BLINK button (3) COM1 communications


port

(4) COM2 communications (5) 48 V power port (6) POE port


port

Specifications

Table 4-48 ETH converter technical specifications

Item Specifications

Power ● DC input: Terminal, with input voltage of 36–60 V DC


input ● PoE power supply: One POE port, 10/100M communication rate,
complying with IEEE802.3at

RS485/CA Provides two RS485/CAN ports. The default communications rate


N for the RS485 port is 9600 bit/s, and that for the CAN port is 125
kbit/s. Both ports match the RJ45 terminal shared by RS485 and
CAN.

BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 10 seconds.

E-label Supported

Indicators

Table 4-49 ETH converter indicators

Indicat Color Name Status Description


or

PWR Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 75


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicat Color Name Status Description


or

RUN Green Operating Off The power supply is


status abnormal.
indicator
Blinking at The ETH converter
long successfully registers with
intervals the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Blinking at The communication has


short failed or the ETH converter
intervals has failed to register with
the ECC800-Pro (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).

Blinking The indicator blinks at super


short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off No system alarm is


generated.

4.4.3.6 Environment Monitoring System

4.4.3.6.1 WLDS900 Water Sensor (BOM Number: 33010352)


The WLDS900 water sensor consists of the water detection cable, water detector,
and conversion cable.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 76


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-40 WLDS900 water sensor

Table 4-50 WLDS900 water sensor specifications


Item Specifications

Operating 12 V DC (9–16 V DC)


voltage

Operating –20°C to +70°C


temperature

Storage –40°C to +85°C


temperature

Humidity 10%–80% RH (non-condensing)

4.4.3.6.2 Electrode Water Sensor (BOM Number: 33010444)


The electrode water sensor consists of electrode probes (liquid level sensor) and
cables.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 77


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-41 Electrode water sensor

Table 4-51 Electrode water sensor technical specifications

Item Specifications

Operating –40°C to +80°C


temperature

Storage –40°C to +80°C


temperature

4.4.3.6.3 Temperature Sensor (BOM Number: 33010348)


The temperature sensor is used for surface temperature measurement, industrial
process control, and measurement instruments.

Figure 4-42 Temperature sensor

Table 4-52 Temperature sensor specifications

Item Specifications

Measurement range –20°C to +70°C

Measurement precision ±1ºC (25ºC)

Operating temperature –10°C to +55°C

Operating voltage 10–16 V DC

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 78


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Storage temperature –40°C to +70°C

4.4.3.6.4 T/H Sensor (BOM Number: 02312PBL)

Figure 4-43 Appearance

(1) RS485-OUT (2) RS485-IN (3) DIP switch (4) Button

(5) NTC1-3 (6) NTC4-6 (7) Display

Table 4-53 Temperature and humidity sensor specifications


Item Temperature Humidity

Measurement range – 40°C to +70°C 1%–99% RH

Precision ≤ ±1°C (25°C) ≤ ±5% RH (25°C, 20%–80%


RH)

Extended temperature Provides two RJ45 ports to connect six NTC


collection port temperature sensors, each RJ45 port connecting to
three NTC temperature sensors.

Signal port RS485

Power supply 5–16 V DC (typical value 12 V DC)

Power consumption < 280 mW

Storage environment – 40°C to +70°C

Weight About 85 g

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 79


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.4.3.6.5 T/H Sensor (BOM Number: 33010516)

Figure 4-44 Appearance

The T/H sensor uses an RJ45 connector.

NOTE

The appearance of the T/H sensor depends on the actual delivery.

Figure 4-45 Pins of an RJ45 connector

Table 4-54 RJ45 port pin definitions


Pin Description

Pin 1 or Pin 4 A

Pin 2 or Pin 5 B

Pin 3 V+

Pin 6 V-

Pin 7 Reserved

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 80


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-55 T/H sensor specifications

Item Specifications

Temperature measuring range –20°C to +80°C

Temperature accuracy ±0.5°C (25°C)


≤±1°C (full measuring range)

Operating temperature –20°C to +80°C

Operating voltage 9–16 V DC

Storage temperature –40°C to +80°C

Output Two RJ45 ports, bidirectional cascading

4.4.3.6.6 Smoke Detector

Figure 4-46 Smoke detector

(1) Wiring terminal (2) Base (3) Indicator

Table 4-56 Technical specifications

Item Specifications

Operating voltage 9–27 V DC

Operating current ● Monitoring status: < 40 μ (12 V


DC), < 60 μA (24 V DC)
● Alarm status: 3–8 mA

Working instruction ● Monitoring status indicator:


blinking once every 46s
● Alarm indicator: steady on

Operating temperature –10ºC to +55ºC

Ambient humidity ≤ 95% RH

Dimensions (H x W x D) 74.8 mm x 58.8 mm x 30.4 mm

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 81


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Weight About 60 g

Installation height ≤ 12 m

4.4.3.7 Access Control System

The access control system applies to the equipment room, aisle containment, and
cabinet doors.

4.4.3.7.1 Access Actuator


The access actuator is the control component for the aisle containment door in a
smart module. It connects to the ECC800-Pro controller over PoE and wireless
networking (802.15.4). It opens the magnetic lock by detecting the card swiping
information of the card reader, door open button information, and fire linkage
information. It has access right management, access event record, and alarm
record functions.

Figure 4-47 Access actuator

(1) 48 V power port (2) POE port (3) RS485 port COM2

(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator

(7) BLINK button (8) WG_2 Wiegand interface (9) WG_1 Wiegand interface

(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM door
(Reserved port for linkage (Reserved port for exit status or magnetic lock port
control or third-party fire button)
extinguishing system dry
contacts)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 82


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Specifications

Table 4-57 Access actuator technical specifications

Item Specifications

Power input ● DC input: Terminal, with input voltage of 36–60 V DC


● POE input: One POE port that complies with IEEE802.3at.

POE port FE communication, 10/100M communications rate

Wireless One wireless communication port that complies with


communicat IEEE802.15.4, mutual backup with FE communication
ion

AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button

DO/DI port ● One 12 V DC power output that controls magnetic locks,


terminal
● One DI input port for connecting to the door status switch

RS485 serial Two RS485 ports (one route) with the default communications
port rate of 9600 bit/s, physical port cascading supported (reserved
expansion function)

Wiegand Two Wiegand interfaces, 12 V DC card reader operating power


interface output; two routes of card readers (non-fingerprint readers) can
operate at the same time.

BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.

Address DIP 4-pin address DIP switch


switch

E-label Supported

Indicators

Table 4-58 Access actuator indicator description

Indicator Color Name Status

PWR Green Power input status ● Steady on: The


indicator power input is
normal.
● Off: There is no
power input.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 83


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicator Color Name Status

RUN Green Communication status ● Off: The power is


indicator abnormal or the
board program is
loading.
● Blinking at long
intervals: The access
actuator
successfully registers
with the ECC800-
Pro and the
software runs
properly (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
● Blinking at short
intervals: The
communication fails
or the access
actuator fails to
register with the
ECC800-Pro (the
indicator blinks at 4
Hz, on for 0.125s
and then off for
0.125s).
● Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then
turns off for 0.5s.
The cycle lasts for
5s.

ALM Red Alarm indicator ● Steady on: A system


failure alarm is
generated.
● Off: No system
alarm is generated.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 84


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicator Color Name Status

RF_Z Green Wireless ● Steady on: No


communication status network parameters
indicator exist, or a network
is to be created.
● Blinking at long
intervals: A network
is set up, and no
node access is
allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
● Blinking at super
short intervals: A
network is set up,
and node access is
allowed (the
indicator blinks at
10 Hz, on for 0.05s
and then off for
0.05s).
● Blinking
intermittently at
super short
intervals: The access
actuator is
searching for a
network (the
indicator blinks at
super short intervals
for 0.5s and then
turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/
COM). Table 4-59 lists the LOCK/GND/GATE/COM port pin definitions.

Table 4-59 LOCK/GND/GATE/COM port pin definitions


Item Description

LOCK/GND LOCK 12V_OUT


(control
magnetic GND GND
locks) pin
sequence

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 85


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Description

GATE/COM GATE DI1


(door
status) pin COM COM
sequence

4.4.3.7.2 Cabinet Electronic Clasp Lock


The cabinet electronic clasp lock can be unlocked automatically or manually.

Figure 4-48 cabinet electronic clasp lock

(1) LED indicator (2) DIP switch (3) RJ45 power port

Table 4-60 RJ45 port definitions

No. Pin Description Description

1 RS485+ RS485+

2 RS485- RS485-

3 +12 V power supply +12 V DC

4 RS485+ RS485+

5 RS485- RS485-

6 / /

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 86


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

No. Pin Description Description

7 / /

8 Ground GND

Table 4-61 LED indicator status


Indicator Color Name Operation Status Description

RUN Green Module / Blinking ● The door


running lock is
indicator paired with
the host,
and the
power
supply is
normal:
The
indicator
blinks at
0.5 Hz (on
for 1s and
then off for
1s).
● The door
lock fails to
pair with
the host:
The
indicator
blinks at 4
Hz (on for
0.125s and
then off for
0.125s).

Steady off The power


supply is
abnormal.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 87


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Indicator Color Name Operation Status Description

Press SW. Blinking ● The


intermittentl indicator
y at super blinks at
short super short
intervals intervals
for 0.5s
and then
off for 0.5s
● The
indicator
blinks at
super short
intervals
(blinking at
10 Hz, on
for 0.05s
and then
off for
0.05s). The
cycle lasts
for 5s.

ALM Red Alarm / Steady on The system is


indicator faulty.

Steady off The system is


normal.

4.4.3.8 In-Room Access Control

4.4.3.8.1 Fingerprint and Card Reader with a Keypad

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 88


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-49 Fingerprint and card reader with a keypad

(1) Fingerprint reader (2) LED indicator

Table 4-62 Specifications for the fingerprint and card reader with a keypad

Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm

Rated operating voltage 12 V DC±15%

Rated operating current 300 mA±15%

Card type supported IC card

Authorized storage A maximum of 3000 authorized users, with a


maximum of 6000 fingerprints

Communications mode RS485 and Wiegand communications ports

Table 4-63 Access control device operating status

Item New Version

Standby LED indicator The indicator is steady


blue.

Fingerprint reader The indicator is off.

Unauthorized fingerprint LED indicator The indicator blinks blue,


collection red, blue, red, and blue
in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds three.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 89


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item New Version

Authorized fingerprint LED indicator The indicator blinks blue,


collection red, and blue in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds once.

Card swiping LED indicator The indicator blinks blue,


red, and blue in order.

Buzzer sounds The buzzer sounds once.

4.4.3.8.2 Fingerprint and Card Reader

Figure 4-50 Fingerprint and card reader

(1) Fingerprint reader (2) LED indicator

Table 4-64 Fingerprint and card reader


Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm

Rated operating voltage 12 V DC±5%

Rated operating current 300 mA±5%

Card type supported IC card

Authorized storage A maximum of 3000 authorized users, with a


maximum of 6000 fingerprints

Communications mode RS485 and Wiegand communications ports

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 90


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-65 Access control device operating status


Item New Version

Standby LED indicator The indicator is steady


blue.

Fingerprint reader The indicator is off.

Unauthorized fingerprint LED indicator The indicator blinks blue,


collection red, blue, red, and blue
in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds three.

Authorized fingerprint LED indicator The indicator blinks blue,


collection red, and blue in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds once.

Card swiping LED indicator The indicator blinks blue,


red, and blue in order.

Buzzer sounds The buzzer sounds once.

4.4.3.8.3 Card Reader with a Keypad

Figure 4-51 Card reader with a keypad

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 91


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-66 Technical specifications of a card reader with a keypad

Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm

Operating voltage Operating voltage range: 10.8–13.2 V DC; rated


voltage: 12 V DC

Operating current Static standby current: 80 mA; dynamic operating


current (card swiping, key pressing): 150 mA;
minimum input current: 12 V DC/300 mA

Communication mode Wiegand communications port

4.4.3.8.4 Magnetic Lock

Figure 4-52 Double door magnetic lock

Figure 4-53 Single door magnetic lock

4.4.3.9 Video Management System


The video surveillance subsystem consists of the camera and network video
recorder and implements real-time monitoring, video storage, and video playback.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 92


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.4.3.9.1 IPC6325 Camera


The IPC6325-WD-VR IP camera (IPC6325 camera for short) is a two-megapixel
wide dynamic infrared zoom dome camera that can be wall-mounted or ceiling-
mounted.
The camera monitors the module interior in real time, records videos, and
implements 24/7 storage.

Figure 4-54 IPC6325 camera

Table 4-67 IPC6325 camera technical specifications


Item Specifications

Image sensor 1/2.7" two-megapixel progressive scan CMOS

Lowest illuminance ● Color: 0.01 lux (F1.4, AGC ON)


● Black and white: 0.004 lux (F1.4, AGC ON)
0 lux (infrared enabled)

Wide dynamic range 120 dB

Focal length 2.8–12 mm manual zoom, 4.3x optical zoom

Video coding format H.265/H.264/MJPEG

Maximum resolution 1920 x 1080

Power supply PoE (802.3at/af), 24 V AC±25%, 24 V DC±25%, 12


V DC±25% (polarity-insensitive DC power supply),
applicable to DC/AC adapter and PoE hot backup

Protection level IP66; complying with IEC 60529

Vandal-proof class IK10; complying with IEC 62262

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 93


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.4.3.9.2 VCN510

Figure 4-55 Appearance

Table 4-68 Performance specifications


Item Specifications

Device access and video storage Supports a maximum of eight video


access channels or 128 Mbit/s video
access bandwidth.

Video forwarding Supports a maximum of 32 video


forwarding channels or 256 Mbit/s
video forwarding bandwidth.

Video playback and download Supports a maximum of eight video


playback and download channels or
128 Mbit/s video playback and
download bandwidth.

Ingress and egress bandwidth The ingress bandwidth does not


exceed 128 Mbit/s.
The egress bandwidth does not exceed
256 Mbit/s.

Table 4-69 Hardware specifications


Item Specifications

Number of disks 2

Whether the hard disk supports hot No


swap

Supported hard disk type 3 TB, 4 TB, 6 TB, or 8 TB SATA disks

CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz

Memory capacity 1 GB

Network port Two GE network ports

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 94


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Power parameters ● One power module


● AC power (100 V AC to 240 V AC;
50 or 60 Hz)

Weight in full configuration (including ≤ 5 kg


disks)

Maximum power consumption < 60 W


(including hard disks)

Dimensions (H x W x D) 43.6 mm x 442 mm x 310 mm (1 U,


excluding the panel)
43.6 mm x 442 mm x 320 mm (1 U,
including the panel)

4.4.3.9.3 IVS1800

Figure 4-56 Appearance

Table 4-70 Performance specifications


Category Item IVS1800-C08-04T IVS1800-C08-04T
(16CH) (64CH)

Device Network 16-channel 1080p, up 64-channel 1080p, up


performance video inputs to 160 Mbit/s access to 320 Mbit/s access
bandwidth bandwidth
Up to 160 Mbit/s
access bandwidth with
intelligent services
enabled

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 95


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Category Item IVS1800-C08-04T IVS1800-C08-04T


(16CH) (64CH)

Video transfer 16-channel 1080p, up 64-channel 1080p, up


to 160 Mbit/s to 320 Mbit/s
forwarding bandwidth forwarding bandwidth
Up to 160 Mbit/s
forwarding bandwidth
with intelligent
services enabled

Playback/ 16-channel 1080p, up 32-channel 1080p, up


Download to 80 Mbit/s playback to 160 Mbit/s
bandwidth playback bandwidth

Platform IP cameras 16 cameras to one 64 cameras to one


performance connected IVS1800 IVS1800

Table 4-71 Hardware specifications


Category Item Specifications

Storage Hard disk 8


capacity quantity

Hard disk port SATA3.0

Hard disk Enterprise-level disks: 4 TB, 6 TB, 8 TB, or 10


type TB
Monitoring-level disks: 4 TB or 6 TB

Controller Processor Hi3559A

Memory 8 GB DDR4

External ports Network port Two 10/100/1000 Mbit/s Ethernet ports

USB ports Three USB ports (two USB 2.0 ports on the
front panel and one USB 3.0 port on the rear
panel)

Audio input 1 channel, RCA port

Audio output 1 channel, RCA port

Alarm port 4-channel alarm input, 2-channel alarm output

Other Power 124 W


specifications consumption
(8 hard disks
included)

Power supply 110–220 V AC

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 96


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Category Item Specifications

Weight (hard 6.6 kg


disks
excluded)

Dimensions 86 mm x 442 mm x 467 mm


(H x W x D)

4.4.3.10 (Optional) eLight


The eLight system consists of the eLight power system, eLight actuator, eLight
strip light, and cables.

Figure 4-57 eLight strip light

Figure 4-58 eLight actuator

NOTE

The appearance of the eLight actuator depends on the product delivered onsite.

Table 4-72 Description of the eLight strip light colors

Scenario Light Color Remarks

Non-associated Blue -
alarm severity NOTE
On the ECC800-Pro WebUI, set
Associated Alarm Severity to None.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 97


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Scenario Light Color Remarks

Associated alarm ● Mapping between smart module Critical and major


severity alarm severities and strip light alarms are
colors: associated by
– Critical: red default. Alarms of
any severity can be
– Major: orange associated manually.
– Minor: yellow Alarms are
– Warning: white associated with the
eLight on both ends.
● No alarm: strip light off If associated alarms
at multiple severities
appear, the strip light
color indicates only
the highest alarm
severity.

eLight fault The eLight disconnects from the -


ECC800-Pro and blinks in red.

Table 4-73 eLight technical specifications


Item Specifications

eLight power supply ● Rated input voltage: 220/230/240 V AC


● Frequency: 50/60 Hz
● Output: ≥ 93 W, 24 V DC
● Certification: CE

eLight actuator ● Rated input voltage: 24 V DC


● Two output channels. The I output is connected to
the RGBW flexible strip light, and supplies different
voltages depending on host instructions so that the
light can be in different colors. The II output
supplies a fixed voltage of 24 V DC.
● Modbus communications protocol, RS485 port, two
RJ45 ports
● Certification: CE

eLight strip light ● Rated input voltage: 24 V DC


● Light type: RGBW LED strip light, in different colors
depending on instructions
● Power: RGB fully on under the maximum working
condition, power P ≤ 12 W/m
● Installation mode: snap-fit in a sheet metal light slot
● Certification: CE and CCC

IP rating ≥ IP20

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 98


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Item Specifications

Environment ● Operating temperature range: 4°C to 40°C


● Humidity range: 5%–95% RH, non-condensing

4.4.3.11 (Optional) iBattery


The iBattery consists of the iBOX and iBAT.
The iBOX is a battery information collection module. It collects battery status data
from a group of downstream iBATs through wireless communication, and sends
the data to the upstream management unit through a COM or PoE port.
The iBAT is a battery monitoring module that supports 12 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.

Appearance

Figure 4-59 iBOX appearance

Figure 4-60 iBAT appearance

iBOX Features
● Each iBOX can manage a maximum of four battery strings composed of 200
batteries in total.
● An external Hall effect sensor is connected to the iBOX to monitor the current
of each battery string. Each iBOX can connect to a maximum of eight Hall
effect sensors.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 99


FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● Calculates the SOC and SOH of batteries and battery strings.


● Accurately identifies batteries with lower voltages in a battery string.
● Identifies loose battery terminals and battery terminal overtemperature, and
controls battery switch tripping.
● Supports WebUI display, and northbound communication over FE and RS485.
● Allows the upstream management unit to upgrade the iBOX and iBAT online.

iBAT Features
● Monitors the voltages, internal resistances, and pole temperatures of
batteries.
● Uploads battery data to the iBOX through wireless communication.
● Has the hibernation function.

4.5 (Optional) NetEco6000 Intelligent Data Center


Management System

4.5.1 System Overview


With a flexible structure and modular design, the NetEco can manage facilities of
one data center or centrally manage facilities of multiple data centers in different
regions.
The management system provides a GUI to implement comprehensive
management functions based on requirements. The system mainly monitors the
following equipment:
● Power equipment: smart cooling product, Power distribution module, UPS,
and so on
● Environment equipment: water sensor, T/H sensor, and so on
● Video equipment: camera, and so on
● Access control equipment: A standard access management system is
integrated to manage and monitor key information such as door status, card
swiping, and permission setting.
● Standard network management interface: The NetEco provides SNMP
interfaces to communicate with third-party NMSs. The system can be
customized to support other protocols for the access from different devices.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 100
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Figure 4-61 Networking diagram

4.5.2 TaiShan 200 Server

Figure 4-62 Appearance

Table 4-74 Technical specifications

Item Specifications

Model 2280

Product form 2U rack server

Processor Kunpeng 920

Memory 4 x 32 GB

Hard disk 2 x 1200 GB + 8 x 1800 GB

4.5.3 LAN Switch


You can select a device model as required.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 101
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

Table 4-75 LAN Switch


Model Maximum Number of Interfaces

S5320-28X-PWR-SI Twenty-four 10/100/1000Base-T Ethernet ports, four


combo 1000Base-X SFP ports, and four 10G SFP+ ports

S5720-28X-PWR-SI Twenty-four 10/100/1000Base-T Ethernet ports, four


combo 1000Base-X SFP ports, and four 10G SFP+ ports

4.6 (Optional) Edge Data Center Management System


The edge data center management system monitors the running status of the
entire network on the GIS home page. After an abnormal site is detected, you can
double-click it to access the site monitoring page. Environment, energy
consumption, key device, alarm, and security monitoring is provided on the site
monitoring page.
● Environment monitoring: Monitors the temperature, humidity, water, and
smoke.
● Key device monitoring: Monitors the UPS, air conditioners, and related power
distribution devices in real time, and displays the energy flow diagram and air
conditioner link diagram.
● Alarm monitoring: Displays site alarm information in real time and quickly
locates device faults.
● Security monitoring: Monitors the cabinet door status and cameras in sites.

Figure 4-63 Networking mode

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 102
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.7 Surge Protection and Grounding System

4.7.1 Surge Protection Solution


The Smart Module is mainly used for building equipment rooms. Its power
distribution system is a subsystem of the building power distribution system. Class
I surge protective devices (SPDs) of the power system are provided by the general
low-voltage power distribution room or cabinet of the building.

4.7.2 Grounding Solution


Equipotential Grounding for Cabinets in the Module
A general ground bar is configured in the Converged Cabinet. The ground
terminals in other cabinets are connected to the general ground bar by cables
with a cross-sectional area no less than 16 mm2. The general ground bar is
connected to the floor ground bar (FEB) or collective ground bar (25 mm x 3 mm
copper bar laid along cable trays or walls) of the equipment room by ground
cables with a cross-sectional area no less than 35 mm2.

NOTE

The AC input power is from the upstream power distribution system. The cross-sectional
areas of ground cables are determined according to IEC 60364-5-54.

Figure 4-64 Equipotential connection of the cabinet system

(1) General ground bar

Cabinet Grounding
● Metal components and parts of cabinets are properly connected. A structural
connection area is protected and applied with antioxidants. An area protected
with painting should ensure proper metal surface contact for two connected
components. The DC resistance is within 0.1 ohm between any two connected
metal components. Use a ground cable to connect two metal components
that cannot be directly connected, such as cabinets and cabinet doors. A cable
for connecting these two metal components has a minimum cross-sectional
area of 6 mm2.
● A ground bar or general ground point is provided in each cabinet for
equipment grounding. These ground bars are not insulated.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 103
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

● A ground terminal is greater than or equal to M8 in dimensions. A yellow

ground label is attached close to the general ground terminal for


cabinets.
● Connect equipotential cables to metal components without carrying currents
in the module, such as metal doors and windows, cable trays, and ESD floor
supports. Each equipotential cable has a minimum cross-sectional area of 6
mm2.

4.8 Fire Extinguishing System


The fire extinguisher system provides only sensors. Other fire extinguishing
components need to be prepared by the customer.

4.9 Integrated Cabling System

4.9.1 Integrated Cabling


Cable troughs are installed on the top of cabinets for routing cables. There are
two types of cable troughs: signal cable troughs and power cable troughs.

Figure 4-65 Cables routes through binding plates

(1) Signal cable (2) Power cable

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 104
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture

4.9.2 Cables
Power Cable
Power cables include the input power cables for the Converged Cabinet, power
cables from the UPS to the battery switch, battery cabinet power cables, smart
cooling product power cables, rPDU power cables, AC power cables (such as the
ECC800-Pro power cables and VCN power cables).

Ground Cable
Ground cables include those for the Converged Cabinet, battery cabinet, IT
cabinet, and smart cooling product.

Monitoring Cable
Monitoring cables include those for the T/H sensor, smart cooling product,
Converged Cabinet, UPS, water sensor, smoke detector, video system, and
intelligent spring lock.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 105
FusionModule800 Smart Small Data Center
Product Description 5 Technical Specifications

5 Technical Specifications

Table 5-1 Key technical specifications


Item Asia, Europe, and Africa Version Latin America
Specifications Version
Specifications

Module Cold and hot aisle containment: 2000 x L x Cold and hot aisle
dimensi 1350, L ≤ 7400 containment: 2000
ons (H x x L x 1350, L ≤ 5000
W x D)
(mm)

Number ≤ 10 (a maximum of one network cabinet) ≤ 6 (including


of IT network cabinets)
cabinets

Number ● The IT power is 8.5 kW or 17 kW: ≤ 8, a ≤ 8, a maximum of


of maximum of two battery cabinets deployed two battery
cabinets inside the aisle containment cabinets deployed
● The IT power is 25 kW: ≤ 12, a maximum of inside the aisle
two battery cabinets deployed inside the containment
aisle containment

Power 380 V/400 V/415 V 3Ph 50 Hz/60 Hz 208 V/220 V/230


system V/240 V 3Ph 50
Hz/60 Hz

Voltage 342–456 V 187–264 V


range

Voltage 50/60 Hz (± 3 Hz)


frequenc
y range

Total IT ≤ 25 kW ≤ 15 kW
equipme
nt
power

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 106
FusionModule800 Smart Small Data Center
Product Description 5 Technical Specifications

Item Asia, Europe, and Africa Version Latin America


Specifications Version
Specifications

Maximu ≤ 7 kW (high temperature condition: ≤ 6 kW) ● 208 V output: ≤


m 6 kW
power ● 120 V output: ≤
of a 3.5 kW
single
cabinet

IP rating IP20

Altitude 0-4000 m (derated when the altitude exceeds 1000 m)

Installati Installed on a concrete floor, a raised floor, or an ESD floor.


on
mode

Cable ● Pipes are routed from the top or bottom.


and pipe ● Input power cables of the Converged Cabinet can be routed in
routing from the top or bottom, and other power cables can be routed
out from the top.
● Signal cables can be routed out from the top or bottom.

Operati Indoor: 0°C to +40°C


ng
tempera Outdoor: Outdoor: – Outdoor: –10°C to Outdoor: –20°C to
ture –20°C to 40°C to +55°C (high +45°C
+45°C +45°C (low temperature
(normal temperature version)
temperat version)
ure
version)

Storage Without refrigerant: –40°C to +70°C


tempera With refrigerant: –40°C to +55°C
ture

Storage ≤ 95% RH (non-condensing)


humidit
y

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 107
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles

6 Refrigerant Pump Principles

Working principles of the refrigerant pump:


● The refrigerant pump is efficient and energy-saving. When the ambient
temperature is lower than –8°C (switches back to the compressor system
when the outdoor temperature is higher than –5°C), the cooling system
automatically switches to the refrigerant pump for circulation through valve
control. The compressor is stopped, and a low-power refrigerant pump is used
for forced convection circulation of refrigerant. In this way, the indoor
evaporator provides cooling and the outdoor condenser dissipates heat
continuously. This mode ensures the cooling capacity equal to that of the
compressor, shortens the compressor runtime, and saves energy.
● The refrigerant pump mode also provides 12.5 kW cooling capacity when the
outdoor temperature (lower than –5°C outdoor) is low. The total power of the
equipment is 2.6 kW when the compressor is running, and it is about 1.2 kW
when the refrigerant pump is running. The cooling capacity in 1.2 kW
refrigerant pump mode is basically equal to that in 2.6 kW compressor mode.

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 108
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles

Figure 6-1 Cooling system layout (with a refrigerant pump)

(1) Compressor (2) High pressure (3) Oil separator (4) High pressure
sensor 1 switch 1

(5) Compressor (6) Condenser (7) Filter dryer (8) Liquid storage
discharge check valve tank

(9) Refrigerant pump (10) High pressure (11) Refrigerant (12) High pressure
bypass check valve sensor 2 pump sensor 3

(13) Fluorine pump (14) Outdoor unit (15) Indoor unit (16) Electronic
outlet solenoid valve liquid pipe stop valve liquid pipe stop valve expansion valve

(17) Evaporator (18) Suction sensor (19) Indoor unit gas (20) Outdoor unit gas
pipe stop valve pipe stop valve

(21) Low pressure (22) Gas-liquid (23) Pre-compressor (24) Compressor


sensor separator solenoid valve bypass check valve

(25) Low pressure


switch

Figure 6-2 Refrigerant flow diagram (compressor mode)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 109
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles

Figure 6-3 Refrigerant flow diagram (refrigerant pump mode)

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 110
FusionModule800 Smart Small Data Center
Product Description 7 Equipment Derating Coefficients

7 Equipment Derating Coefficients

NOTE

The coefficients listed in the Table 7-1 are based on the dry air density being 1.225 kg/m3
(sea level +15ºC).

Table 7-1 Derating coefficients of the UPS2000-G


Altitude (Unit: m) Derating Coefficients

1000 1.0

1500 0.95

2000 0.91

2500 0.86

3000 0.82

3500 0.78

4000 0.74

4500 0.7

5000 0.67

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 111
FusionModule800 Smart Small Data Center
Product Description 8 Acronyms and Abbreviations

8 Acronyms and Abbreviations

A
AC alternate current
ATS Auto Transformer Switch
ATSE Auto Transformer Switch Equipment

B
BIM Battery Interface Module

C
CIM Communication Interface Module

D
DC direct current

I
IEC International Electrotechnical Commission

M
MCB miniature circuit breaker

S
SNMP Simple Network Management Protocol
SPD surge protective device
SOC State Of Charge
SOH State Of Health

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 112
FusionModule800 Smart Small Data Center
Product Description 8 Acronyms and Abbreviations

UPS uninterruptible power system

Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 113