FusionModule800 Smart Small Data Center V100R001C20 Product Description (HTML)
FusionModule800 Smart Small Data Center V100R001C20 Product Description (HTML)
V100R001C20
Product Description
Issue 04
Date 2022-08-20
and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei
Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope. Unless otherwise
specified in the contract, all statements, information, and recommendations in this document are
provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Futian,Shenzhen 518043
Website: https://e.huawei.com
Purpose
This document describes the FusionModule800 Smart Small Data Center (smart
module for short) in terms of its positioning, features, typical application
scenarios, system architecture, and key technical specifications, helping readers to
systematically understand the FusionModule800.
Intended Audience
This document is intended for:
● Sales engineers
● Technical support engineers
● System engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Symbol Description
Change History
Issue Date Description
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. iii
FusionModule800 Smart Small Data Center
Product Description Contents
Contents
4 System Architecture................................................................................................................ 8
4.1 Structure System......................................................................................................................................................................8
4.1.1 Cabinet.................................................................................................................................................................................... 8
4.1.2 Converged Cabinet............................................................................................................................................................ 10
4.1.3 Components of Single-Row Cold and Hot Aisle Containment.......................................................................... 12
4.2 Power Supply and Distribution System......................................................................................................................... 14
4.2.1 Technical Specifications................................................................................................................................................... 15
4.2.2 Working Principles............................................................................................................................................................ 16
4.2.3 Hardware Description...................................................................................................................................................... 18
4.2.3.1 Power Distribution Module........................................................................................................................................ 19
4.2.3.2 UPS...................................................................................................................................................................................... 31
4.2.3.2.1 Appearance................................................................................................................................................................... 31
4.2.3.2.2 Product Structure........................................................................................................................................................ 31
4.2.3.2.3 Physical Specifications.............................................................................................................................................. 32
4.2.3.2.4 Environmental Specifications..................................................................................................................................33
4.2.3.2.5 Mains Input Electrical Specifications................................................................................................................... 33
4.2.3.2.6 Bypass Input Electrical Specifications.................................................................................................................. 34
4.2.3.2.7 Output Electrical Specifications............................................................................................................................. 35
4.2.3.2.8 Battery Specifications................................................................................................................................................ 36
4.2.3.2.9 ECO Feature.................................................................................................................................................................. 37
4.2.3.2.10 Parallel Feature......................................................................................................................................................... 37
4.2.3.2.11 Safety Regulations and EMC................................................................................................................................ 38
4.2.3.3 Transformer...................................................................................................................................................................... 38
4.2.3.3.1 Appearance................................................................................................................................................................... 38
4.2.3.3.2 Technical Specifications............................................................................................................................................ 38
4.2.3.4 Battery Cabinet............................................................................................................................................................... 39
4.2.3.4.1 Appearance................................................................................................................................................................... 39
4.2.3.4.2 Technical Specifications............................................................................................................................................ 40
4.2.3.5 Battery Pack..................................................................................................................................................................... 41
4.2.3.5.1 Appearance................................................................................................................................................................... 41
4.2.3.5.2 Technical Specification.............................................................................................................................................. 41
4.2.3.6 rPDU................................................................................................................................................................................... 41
4.2.3.6.1 Basic rPDU.....................................................................................................................................................................41
4.2.3.6.2 (Optional) Monitoring rPDU.................................................................................................................................. 42
4.3 Cooling System...................................................................................................................................................................... 43
4.3.1 Features................................................................................................................................................................................ 43
4.3.2 Product Composition........................................................................................................................................................ 45
4.3.2.1 Indoor Unit....................................................................................................................................................................... 45
4.3.2.2 Outdoor Unit................................................................................................................................................................... 47
4.3.3 Smart Cooling Product Control Unit........................................................................................................................... 49
4.3.4 Application Conditions..................................................................................................................................................... 50
4.3.5 Technical Specifications................................................................................................................................................... 51
4.4 Monitoring System............................................................................................................................................................... 55
4.4.1 Overview............................................................................................................................................................................... 55
4.4.2 System Functions............................................................................................................................................................... 58
4.4.2.1 Monitoring........................................................................................................................................................................ 58
4.4.2.2 App View........................................................................................................................................................................... 58
4.4.2.3 Alarm.................................................................................................................................................................................. 59
4.4.2.4 Historical Data Query................................................................................................................................................... 59
4.4.2.5 Linkage Control...............................................................................................................................................................59
4.4.3 Key Hardware Devices..................................................................................................................................................... 60
4.4.3.1 ECC800-Pro Data Center Controller.........................................................................................................................60
4.4.3.1.1 Product Configuration............................................................................................................................................... 60
4.4.3.1.2 Main Control Module................................................................................................................................................ 61
4.4.3.1.3 Power Module.............................................................................................................................................................. 70
4.4.3.2 PAD..................................................................................................................................................................................... 71
4.4.3.3 Smart ETH Gateway...................................................................................................................................................... 71
4.4.3.4 WiFi Module.....................................................................................................................................................................73
4.4.3.5 ETH Converter................................................................................................................................................................. 74
4.4.3.6 Environment Monitoring System.............................................................................................................................. 76
4.4.3.6.1 WLDS900 Water Sensor (BOM Number: 33010352)..................................................................................... 76
4.4.3.6.2 Electrode Water Sensor (BOM Number: 33010444)...................................................................................... 77
4.4.3.6.3 Temperature Sensor (BOM Number: 33010348).............................................................................................78
4.4.3.6.4 T/H Sensor (BOM Number: 02312PBL).............................................................................................................. 79
4.4.3.6.5 T/H Sensor (BOM Number: 33010516).............................................................................................................. 80
4.4.3.6.6 Smoke Detector........................................................................................................................................................... 81
4.4.3.7 Access Control System.................................................................................................................................................. 82
4.4.3.7.1 Access Actuator........................................................................................................................................................... 82
1 Positioning
The FusionModule800 is a smart small data center solution applied to air cooled
scenarios where the equipment room area is less than 40 m2. This solution mainly
applies to city-, district-, and county-level data centers of the government vertical
industry, small-sized second-level branches and large-sized offices in the financial
industry, and equipment rooms of small- and medium-sized enterprises. The
following figure shows the position of the FusionModule800 in the product family.
2 Features
Integration
The smart module integrates the cabinet system, power supply and distribution
system, cooling system, management system, surge protection and grounding
system, integrated cabling system, and fire extinguishing system. It adopts a
modular and integrated design to provide a comprehensive solution.
Architecture Compatibility
● The FusionModule800 supports T1, T1 low-temperature, and T3 environments.
● The FusionModule800 supports cold and hot aisle containment, saving energy
and reducing noise.
● Modular power distribution and smart cooling products facilitate flexible
expansion.
Comprehensive Monitoring
● Various sensors monitor the functional modules in the equipment room in
real time.
● The smart module provides a module-level PAD to easily manage the
functional modules locally.
● A maximum of three smart module cameras and in-room cameras can be
monitored. (Smart module cameras are installed in the smart module and the
in-room cameras are installed in the room.)
● In-room access controllers can be monitored.
● ECC800-Pros in two smart modules can be cascaded.
4 System Architecture
4.1.1 Cabinet
Cabinets are classified into the Converged Cabinet, battery cabinet, IT cabinet, and
network cabinet.
Cabinets used in the data center comply with the International Electrotechnical
Commission (IEC) 60297-1 standard and provide stable installation space for
servers, thereby ensuring the safe operation of servers.
Color Black
NOTE
(4) ECC800-Pro (5) Smart cooling product (6) Smart cooling product
control unit indoor unit
(4) Side sealing plate (5) Battery cabinet (6) Cabinet electronic clasp
lock
Cabinet Door
● In cold and hot aisle containment, a sealed glass door is configured at the
front and a sealed sheet metal door at the rear.
● By default, the front and rear doors of a cabinet are equipped with electronic
clasp locks, which can be unlocked only by using dedicated keys.
● N and N+1 UPS systems are supported, and 10 kVA and 20 kVA UPSs can be
selected to adapt to the actual load power. The power distribution module for
IT loads supports a maximum of 10 cabinets. Choose an appropriate power
distribution module based on the load configuration.
● The air cooled smart cooling product consists of the indoor unit and outdoor
unit and is supplied with mains power.
● The management system consists of the ECC800-Pro, VCN, camera, cabinet
electronic clasp lock, temperature sensor, temperature and humidity sensor
(T/H sensor), smoke detector, iBOX, and water sensor. They are powered by
the power supply and distribution system.
● The power supply and distribution system powers the battery cabinet that
houses the battery tray, battery input switch, and intelligent battery
monitoring system including the iBAT and iBOX and is compatible with 26 Ah,
40 Ah, 65 Ah, and 100 Ah batteries.
● Battery pack: (Optional) 9 Ah battery pack.
● The iBattery (optional) can be used for battery management.
Power supply Input voltage range ● Asia, Europe, and Africa: 342 V –
456 V
● Latin America: 187 V – 264 V
Figure 4-10 Conceptual diagram for the N power distribution system (Asia, Africa,
and Europe)
Figure 4-11 Conceptual diagram for the N power distribution system (Latin
America)
Figure 4-12 Conceptual diagram for the N+1 power distribution system (Asia,
Europe, and Africa)
Figure 4-13 Conceptual diagram for the N+1 power distribution system (Latin
America)
NOTE
● The 10 kVA UPSs in a parallel system cannot share battery strings or battery packs.
● The 20 kVA UPSs in a parallel system can share battery strings or battery packs.
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
smart
cooling
products
are
configured
(two smart
cooling
products
with
humidifiers
and one
only-
refrigeratin
g smart
cooling
product).
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
than or
equal to
8.5 kW
or 17
kW, and
UPS N
+1
architec
ture is
support
ed. If
the IT
load
power is
less
than or
equal to
8.5 kW,
a
maximu
m of
two 10
kVA
UPSs
and two
smart
cooling
product
s are
configur
ed. If
the IT
load
power is
less
than or
equal to
17 kW,
a
maximu
m of
two 20
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
kVA
UPSs
and
three
smart
cooling
product
s are
configur
ed (two
smart
cooling
product
s with
humidifi
ers and
one
only-
refrigera
ting
smart
cooling
product
). This
module
can be
operate
d from
the
front
and
maintai
ned
from
the rear
and
front.
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
product).
This
module
can be
operated
from the
front and
maintained
from the
rear and
front.
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
Name Specificati Dimensio Gener UPS UPS UPS Power Power SPD
ons ns (H x W al Input Outpu Bypas Distri Distri Switc
x D) Input t s butio butio h
n for n for
Smart IT
Coolin Equip
g ment
Produ
ct
mains
automatic
switching
back is
adopted by
default.
NOTICE
NOTICE
4.2.3.2 UPS
A UPS2000 supports the power systems of 380 V, 400 V, and 415 V, and features
adequate protection, high reliability, intelligence, simplicity, flexible expansion,
high energy efficiency, and environmental protection.
4.2.3.2.1 Appearance
(1) Control panel (2) AC input ports (3) AC output ports (4) Parallel ports
(pL and sL)
(5) CAN (6) Optional card slot (7) Battery (8) USB port
communications ports temperature sensor
(MON1 and MON2) port
(9) EPO port (10) Maintenance (11) Input circuit (12) Battery port
bypass port (MBS) breaker
(1) Control panel (2) AC input ports (3) Battery terminals (4) EPO port
(mains and bypass)
(5) Maintenance (6) Parallel ports (7) CAN (8) USB port
bypass port (MBS) communications ports
(MON1 and MON2)
Weight 16 kg 32 kg
Operating 0–40°C
temperature
Rated input ● 220 V AC, 230 V AC, or ● 220 V AC, 230 V AC, or
voltage 240 V AC (single-phase 240 V AC (single-phase
input) input)
● 380 V AC, 400 V AC, or ● 380 V AC, 400 V AC, or
415 V AC (three-phase 415 V AC (three-phase
input) input)
Diesel generator Minimum 1.5 times the UPS Minimum 1.5 times the UPS
input capacity rated capacity rated capacity
NOTE
Rated output 220 V AC, 230 V AC, or 240 ● 220 V AC, 230 V AC, or
voltage V AC (single-phase output; 240 V AC (single-phase
select a voltage system by output; select a voltage
setting a voltage level on system by setting a
the LCD.) voltage level on the LCD.)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)
Inverter overload ● 105% ≤ load < 125%: transfer to bypass mode after 5
capability minutes
● 125% ≤ load < 150%: transfer to bypass mode after 1
minute
● Load ≥ 150%: transfer to bypass mode after 100
milliseconds
The UPS stops supplying power if the bypass is abnormal.
Standard-UPS 9 Ah -
battery capacity
Charger charge ● Batteries are charged to more than 90% in 3 hours for
time UPS2000-G-10 kVA standard models.
● It depends on battery capacity for UPS2000-G-10 kVA
long backup time models and UPS2000-G-20 kVA.
Charger rated Each cell has an equalized voltage of 2.35 V and a float
charge voltage voltage of 2.25 V. Both are configurable on the LCD.
Number of UPSs ≤4
in parallel
NOTE
The UPS2000-G-20 kVA (single-phase input single-phase output) supports 3+1 parallel
systems at most, instead of 4+0 parallel systems.
4.2.3.3 Transformer
4.2.3.3.1 Appearance
Item Specifications
Item Specifications
input frequency 60 Hz
Output frequency 60 Hz
Weight 65 kg
4.2.3.4.1 Appearance
Color Black
4.2.3.5.1 Appearance
4.2.3.6 rPDU
NOTE
GB PDU2000-32-1PH-9/3-B2 GB 10 A: 9 PCS
(half-height) GB 16 A: 3 PCS
PDU2000-32-1PH-20/4-B2 GB 10 A: 20 PCS
(full-height) GB 16 A: 4 PCS
Dimensions (H x W x D) 1732 mm x 50 mm x 45 mm
4.3.1 Features
The NetCol5000-A features high energy efficiency, high reliability, high
compatibility, multiple power systems, intelligent monitoring, and easy installation
and maintenance.
High Reliability
● The DC variable-frequency smart cooling product greatly reduces the number
of startup and shutdown times, reducing component failures and extending
the lifespan of key components.
● The electronic expansion valve is used, allowing rapid and precise adjustment
of the refrigerant volume based on the temperature and humidity
requirements and improving system stability. A backup power module is
provided to close the electronic expansion valve when the system experiences
a power failure.
● The Positive Temperature Coefficient (PTC) electric heater provides dual
protection functions: automatic reset and auto-recovery disabling.
● The smart cooling product provides the dehumidification function to maintain
the humidity in cold aisles in the range of 20%–80% at low loads (10% load
at least) in a high humidity environment.
● The smart cooling product features 6 kV surge protection design, providing
high surge protection reliability.
High Compatibility
● The smart cooling product can be rack-mounted, significantly reducing the
footprint required for the cooling system. Only 11 U height space in the
Converged Cabinet is occupied.
● Both the refrigerant pipes and water pipes can be routed from the top or
bottom.
● Heating and humidification functions are optional.
Intelligent Monitoring
● Users can monitor and configure parameters for the cooling system on the
monitoring unit.
● T/H sensors are cascaded using RJ45 ports, connected to the smart cooling
product control unit, and detect temperature and humidity in real time over
Modbus.
Appearance
Components
The indoor unit consists of the EC fan, evaporator, electronic expansion valve,
electric heater (optional), wet film humidifier (optional), light load dehumidifier,
and condensate pump.
● EC fan
EC fans that support stepless speed adjustment are used, reducing energy
consumption of loads in overtemperature scenarios.
● Evaporator
The highly efficient V-shaped evaporator and the light load dehumidification
design are used. After entering the light load dehumidification mode, the
smart cooling product automatically closes the dehumidification solenoid
valve to lower the evaporating temperature and increase the dehumidification
capacity. This mode addresses the requirements for effectively controlling the
equipment room temperature and humidity in low load and high humidity
application scenarios.
● Electronic expansion valve
The throttling equipment is a name brand electronic expansion valve. The
system controls the electronic expansion valve to quickly and accurately
adjust the refrigerant volume based on the temperature and humidity
requirements. In this way, system stability and reliability can be ensured, and
balanced temperature and humidity can be achieved in the equipment room.
● Electric heater
The PTC electric heater features quick start, large heating capacity, and
balanced heat dissipation. It automatically adjusts heating capacity and
provides two protection mechanisms to ensure the secure and stable running
of the equipment.
● Wet film humidifier
The wet film evaporation cooling technology is used for cooling to reduce
energy consumption and maintenance costs. Cyclic humidification can save
water.
● Light load dehumidifier
The smart cooling product provides the dehumidification function to maintain
the humidity in cold aisles in the range of 20%–80% at low loads (10% load
at least) in a high humidity environment.
● Condensate pump
The condensate pump uses materials with high temperature resistance to
ensure that condensate water can be drained smoothly in various application
scenarios. The water pump has a lift of 4 meters and uses double liquid level
detectors, providing high reliability. Alarms indicating abnormal water
drainage can be uploaded to the monitoring unit, and audible and visual
alarms can be generated.
Exteriors
Components
The outdoor unit consists of the DC variable-frequency compressor, oil separator,
gas-liquid separator, filter dryer, fan and fluorine pump (only for the low-
temperature outdoor unit).
● Compressor
DC variable-frequency compressors allow the cooling capacity of a high-
temperature smart cooling product to be adjusted steplessly in the range of
30% to 100%, the cooling capacity of a normal-temperature smart cooling
product to be adjusted steplessly in the range of 20% to 100%, and the
cooling capacity of a low-temperature smart cooling product to be adjusted
steplessly in the range of 20% to 100% at the 35°C outdoor temperature.
● Oil separator
Separates the lubricant brought out due to exhaustion of the compressor and
brings back the separated lubricant to the compressor.
● Gas-liquid separator
A gas-liquid separator is installed at the upper end of a compressor to ensure
the compressor reliability.
● Filter dryer
The filter dryer drains the water in the refrigerant pipes and filters out foreign
matter, which reduces the probability of damage to the components and
ensures the efficient and reliable operating. It is installed in the outdoor unit
and easy to maintain.
● Fan
The axial fan is used, which supports stepless speed adjustment.
● Fluorine pump
The fluorine pump uses a special refrigerant pump with low net positive
suction head and good sealing performance. When the outdoor temperature
is low, the compressor does not need to be started. The fluorine pump
pressurization technology is used to implement natural cooling cycle of the
fluorine pump to ensure reliable operation at temperatures as low as –40°C.
Main Functions
● Single unit control: When only one unit is running, the controller provides
logic control over components in the unit to meet the indoor temperature and
humidity requirements.
● Teamwork control: When multiple smart cooling products work cooperatively,
the controller optimally distributes the heat load, greatly lowering the power
consumption. Multiple smart cooling products provide backup for higher
reliability.
● Remote management: You can monitor, manage, and upgrade one or more
smart cooling products using the remote management function provided by
Huawei.
● Configuration synchronization: You can synchronize parameters between
smart cooling products on the touchscreen (optional) of the converged
cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
● One-click export: You can export the alarms and logs of a smart cooling
product on the ECC800-Pro WebUI.
● Software upgrade: You can perform a remote upgrade on the touchscreen of
the converged cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
● Alarm details query: You can view the possible causes of alarms and handling
suggestions on the ECC800-Pro WebUI.
Features
● The controller is highly precise and responsive.
● Automatically stores operation logs, 1500 historical alarms, and 30-day
temperature and humidity curves and displays these data on the touchscreen
of the converged cabinet.
● Provides protection functions such as automatic recovery after power failure
and shutdown for protection in the case of abnormal drainage, improving the
system reliability.
● Displays the following information on the touchscreen of the converged
cabinet in real time: operating status of the smart cooling product
components and the corresponding time points.
● Provides RS485 and FE ports that support the MAC-Modbus protocol.
● Uses FE ports for teamwork control networking using the MAC protocol,
offering a higher transmission rate.
Installation Requirements
Vertical Difference ● Outdoor unit placed higher than the indoor unit: ≤
Between the Indoor 30 m
and Outdoor Units ● Indoor unit placed higher than the outdoor unit: ≤
8m
Thermal Insulation ≥ 13 mm
Foam Thickness
Ports
Item Specifications
Frequency ±3 Hz
tolerance
Humidification Yes No
function
Heating Yes No
function
Heating 3 kW -
capacity
a: The cooling capacity of the smart cooling product is obtained when the
indoor dry bulb temperature is 37.8°C, the indoor wet bulb temperature is
20.8°C, and the outdoor dry bulb temperature is 35°C. The actual cooling
capacity varies depending on the indoor and outdoor ambient temperatures and
relative humidity.
b: The dimensions, net weight, and gross weight of the indoor unit include those
of the control unit.
Item NetCol500-A018
Maximum operating 24 A
current
Item NetCol500-A018
Certification ● Asia, Europe, and Africa: REACH, RoHS, CE, CCC, and
CQC
● Latin America: REACH, RoHS, and CB
Maximum 30 A
operating current
IP rating IPX5
Maximum operating 30 A
current
Item NetCol500-A020
IP rating IPX4
4.4.1 Overview
The management system consists of the management software and other
components. It implements data collection and management for various processes
and infrastructure of the smart module.
The ECC800-Pro manages the real-time status, alarms, and configuration
information about the devices inside the smart module. It also provides a
graphical user interface (GUI) for ease of operating and maintaining devices inside
the smart module.
NOTE
In the figure, RF_Z represents wireless networking, and the iBAT and iBOX communicate
with each other in wireless mode.
Camera 3 FE
NOTE
The total number of room-level cameras
and smart module–level cameras cannot
exceed 3.
VCN 1 FE
Access actuator 2 FE
NOTE
One access actuator connects to at most
one magnetic lock, one access control
device, one exit button, and one
emergency door release button.
NetCol5000-A013 smart 4 FE
cooling product
UPS2000 3 CAN
Smoke detector 1 DI
Temperature sensor 18 AI
Water sensor 1 DI
SPD 1 DI
NOTE
The access actuator should be installed near the door, have a maximum of 3.5 m cabling
distance away from the magnetic lock, and have a maximum of 5 m cabling distance away
from other switches and the access control device.
4.4.2.1 Monitoring
● Temperature and humidity monitoring: Detects and collects statistics on the
ambient temperature and humidity inside the smart module.
● Water leakage monitoring: Detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
● Smoke monitoring: Detects smoke in the smart module and provides real-
time alarm signals.
● Power distribution monitoring:
a. (In the intelligent power distribution scenario) Monitors the general
mains input voltage, frequency, current, and power, as well as the UPS
input voltage, frequency, current, switch temperature, and so on.
b. (In the intelligent power distribution scenario) Monitors the current,
electric energy, and switch status of power distribution branches of IT
equipment and smart cooling products, and calculates the load rate.
c. (In the non-intelligent power distribution scenario) Monitors the UPS
input voltage, frequency, current, and so on.
● Smart cooling product monitoring:
a. Monitors the supply and return air temperature and humidity in real
time.
b. Configures the supply air temperature set point in a unified manner,
without the need to separately configure it for each smart cooling
product.
c. Monitors and displays the fan speed, and displays the running
percentage. ECC
d. Displays the cooling load rate.
e. Monitors and displays the compressor running status.
f. Displays the real-time running status of the heating and humidifying.
● Video surveillance: Connects to three cameras and provides PoE power supply;
accesses real-time video images on the WebUI and invokes historical
monitoring data.
● Displays the resource usage of the electric energy of the smart module and
each cabinet (displayed only when the intelligent power distribution module
is configured).
● Displays the real-time status and alarms of the aisle temperature and
humidity sensor in the plan view.
● Facial recognition is supported through an app installed on a PAD. After facial
recognition information is added, click Facial Enter to start the facial
recognition. If you do not have facial recognition permission or an error
occurs during facial recognition, you can use the user name and password
login manner.
● After logging in to the app installed on the PAD, you can open the cabinet
door on the corresponding screen.
4.4.2.3 Alarm
● The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
● Alarms can be classified into four severities: critical, major, minor, and
warning. The alarm severities can be user-defined.
● Active alarms can be filtered by device and alarm severity.
● Alarms can be linked with the eLight. The eLight light colors vary with alarm
severities.
● Alarm notifications can be sent by email and SMS.
● A maximum of 500 concurrent active alarms are supported.
The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only
dry contact alarm signals are provided.
● If the protected area of the fire extinguishing system is in the smart module,
when a smoke alarm is generated, the door of the linked cabinet is not
opened. If the door is opened, an alarm (door status alarm) is generated.
● If the protected area of the fire extinguishing system is outside the smart
module, when a smoke alarm is generated, key hardware devices on the rear
door of the linked cabinet are opened.
Item Specifications
Item Specifications
Color Black
Item Specifications
(4) AC_INPUT2
Power Ports
The ECC800-Pro provides four power ports, including two AC input ports
(AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUTPUT1 and
DC_OUTPUT2). Table 4-31 provides the power port pin definitions.
AC Pin 1 L
Pin 2 PE
Pin 3 N
DC Pin 1 48V+
Pin 2 48VGND
(13) AIDI_3 (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN (reserved)
NOTE
The WLAN port is reserved and cannot be connected to a WLAN antenna for WLAN
communication.
Specifications
Item Specifications
Item Specifications
WAN port ● Supports two WAN ports, which can be connected to the
management systems of two customers. The ports support
autonegotiation of 10/100/1000 Mbit/s communication
rates.
● Connect shielded network cables to the WAN ports.
POE Supports two POE (GE) ports for expansion of the POE bus,
expansion and supports network isolation and ring network.
Fault isolation There are three groups of 12 V ports. A group has a maximum
current of 660 mA, a route has a maximum current of 800 mA,
and the maximum total current is 2 A.
Group 1: AIDI_1 and DO/12V ports
Group 2: AIDI_2, COM1/AIDI_4, and COM3/12V ports
Group 3: AIDI_3 and COM2/AIDI_5 ports
Item Specifications
Communications Port
The ECC800-Pro provides the following communications ports. Figure 4-35 shows
the pins of the RJ45 port.
There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN
ports (LAN1/POE and LAN2/POE).
Item Description
Pin 3 GE2+
Pin 4 GE3+
Pin 5 GE3–
Pin 6 GE2–
Pin 7 GE4+
Pin 8 GE4–
Item Description
Pin 3 12 V DC_OUT
Item Description
Pin 4 RS485+
Pin 5 RS485–
Pin 6 DI–
Pin 7 DI+
Pin 8 GND
Item Description
Pin 3 12 V DC_OUT
Pin 4 RS485+
Pin 5 RS485–
Pin 6 -
Pin 7 -
Pin 8 GND
Item Description
Pin 3 -
Pin 4 RS485+
Pin 5 RS485–
Item Description
Pin 6 -
Pin 7 CAN_H
Pin 8 CAN_L
The following provides the AIDI_1, AIDI_2, and AIDI_3 ports pin definitions.
NOTE
Item Description
Pin 3 12 V DC
Pin 4 Type_3
Pin 5 Type_4
Pin 6 DI–
Pin 7 DI+
Pin 8 GND
Item Description
Pin Pin 1 -
sequence
Pin 2 -
Pin 3 12 V DC_OUT
Pin 4 -
Item Description
Pin 5 -
Pin 6 DO_OUT+
Pin 7 DO_OUT–
Pin 8 GND
Item Description
Pin 2 DM
Pin 3 DP
Pin 4 GND
Indicators
SW Button
Press and hold down the button for The RF_Z indicator is
more than 8s to 20s to clear blinking at super
network parameters. short intervals.
Indicator
Output overvoltage
Hibernation
4.4.3.2 PAD
The PAD, a control panel, allows wireless access to the data center facility
management system. You can monitor the equipment in the data center and
environmental parameters in real time over the app.
NOTE
(1) PWR_IN cascading (2) FE_1 cascading (3) PoE_1 and PoE_2 (4) PoE_3 and PoE_4
power port signal port ports ports
(5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT
output port output port signal port cascading power port
Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC);
power of cascaded smart ETH gateways: max (25 A, 48 V DC)
POE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 5 seconds.
Indicators
Specifications
Item Specifications
BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 10 seconds.
E-label Supported
Indicators
Item Specifications
Item Specifications
Item Specifications
Weight About 85 g
NOTE
Pin 1 or Pin 4 A
Pin 2 or Pin 5 B
Pin 3 V+
Pin 6 V-
Pin 7 Reserved
Item Specifications
Item Specifications
Item Specifications
Weight About 60 g
Installation height ≤ 12 m
The access control system applies to the equipment room, aisle containment, and
cabinet doors.
(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand interface (9) WG_1 Wiegand interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM door
(Reserved port for linkage (Reserved port for exit status or magnetic lock port
control or third-party fire button)
extinguishing system dry
contacts)
Specifications
Item Specifications
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
RS485 serial Two RS485 ports (one route) with the default communications
port rate of 9600 bit/s, physical port cascading supported (reserved
expansion function)
BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
E-label Supported
Indicators
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/
COM). Table 4-59 lists the LOCK/GND/GATE/COM port pin definitions.
Item Description
(1) LED indicator (2) DIP switch (3) RJ45 power port
1 RS485+ RS485+
2 RS485- RS485-
4 RS485+ RS485+
5 RS485- RS485-
6 / /
7 / /
8 Ground GND
Table 4-62 Specifications for the fingerprint and card reader with a keypad
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Item Specifications
Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
4.4.3.9.2 VCN510
Number of disks 2
CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz
Memory capacity 1 GB
Item Specifications
4.4.3.9.3 IVS1800
Memory 8 GB DDR4
USB ports Three USB ports (two USB 2.0 ports on the
front panel and one USB 3.0 port on the rear
panel)
NOTE
The appearance of the eLight actuator depends on the product delivered onsite.
Non-associated Blue -
alarm severity NOTE
On the ECC800-Pro WebUI, set
Associated Alarm Severity to None.
IP rating ≥ IP20
Item Specifications
Appearance
iBOX Features
● Each iBOX can manage a maximum of four battery strings composed of 200
batteries in total.
● An external Hall effect sensor is connected to the iBOX to monitor the current
of each battery string. Each iBOX can connect to a maximum of eight Hall
effect sensors.
iBAT Features
● Monitors the voltages, internal resistances, and pole temperatures of
batteries.
● Uploads battery data to the iBOX through wireless communication.
● Has the hibernation function.
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 100
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture
Item Specifications
Model 2280
Memory 4 x 32 GB
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 101
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 102
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture
NOTE
The AC input power is from the upstream power distribution system. The cross-sectional
areas of ground cables are determined according to IEC 60364-5-54.
Cabinet Grounding
● Metal components and parts of cabinets are properly connected. A structural
connection area is protected and applied with antioxidants. An area protected
with painting should ensure proper metal surface contact for two connected
components. The DC resistance is within 0.1 ohm between any two connected
metal components. Use a ground cable to connect two metal components
that cannot be directly connected, such as cabinets and cabinet doors. A cable
for connecting these two metal components has a minimum cross-sectional
area of 6 mm2.
● A ground bar or general ground point is provided in each cabinet for
equipment grounding. These ground bars are not insulated.
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 103
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 104
FusionModule800 Smart Small Data Center
Product Description 4 System Architecture
4.9.2 Cables
Power Cable
Power cables include the input power cables for the Converged Cabinet, power
cables from the UPS to the battery switch, battery cabinet power cables, smart
cooling product power cables, rPDU power cables, AC power cables (such as the
ECC800-Pro power cables and VCN power cables).
Ground Cable
Ground cables include those for the Converged Cabinet, battery cabinet, IT
cabinet, and smart cooling product.
Monitoring Cable
Monitoring cables include those for the T/H sensor, smart cooling product,
Converged Cabinet, UPS, water sensor, smoke detector, video system, and
intelligent spring lock.
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 105
FusionModule800 Smart Small Data Center
Product Description 5 Technical Specifications
5 Technical Specifications
Module Cold and hot aisle containment: 2000 x L x Cold and hot aisle
dimensi 1350, L ≤ 7400 containment: 2000
ons (H x x L x 1350, L ≤ 5000
W x D)
(mm)
Total IT ≤ 25 kW ≤ 15 kW
equipme
nt
power
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 106
FusionModule800 Smart Small Data Center
Product Description 5 Technical Specifications
IP rating IP20
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 107
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 108
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles
(1) Compressor (2) High pressure (3) Oil separator (4) High pressure
sensor 1 switch 1
(5) Compressor (6) Condenser (7) Filter dryer (8) Liquid storage
discharge check valve tank
(9) Refrigerant pump (10) High pressure (11) Refrigerant (12) High pressure
bypass check valve sensor 2 pump sensor 3
(13) Fluorine pump (14) Outdoor unit (15) Indoor unit (16) Electronic
outlet solenoid valve liquid pipe stop valve liquid pipe stop valve expansion valve
(17) Evaporator (18) Suction sensor (19) Indoor unit gas (20) Outdoor unit gas
pipe stop valve pipe stop valve
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 109
FusionModule800 Smart Small Data Center
Product Description 6 Refrigerant Pump Principles
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 110
FusionModule800 Smart Small Data Center
Product Description 7 Equipment Derating Coefficients
NOTE
The coefficients listed in the Table 7-1 are based on the dry air density being 1.225 kg/m3
(sea level +15ºC).
1000 1.0
1500 0.95
2000 0.91
2500 0.86
3000 0.82
3500 0.78
4000 0.74
4500 0.7
5000 0.67
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 111
FusionModule800 Smart Small Data Center
Product Description 8 Acronyms and Abbreviations
A
AC alternate current
ATS Auto Transformer Switch
ATSE Auto Transformer Switch Equipment
B
BIM Battery Interface Module
C
CIM Communication Interface Module
D
DC direct current
I
IEC International Electrotechnical Commission
M
MCB miniature circuit breaker
S
SNMP Simple Network Management Protocol
SPD surge protective device
SOC State Of Charge
SOH State Of Health
Issue 04 (2022-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 112