UIC-DX330 Series
Screw Air Compressor Controller
2005-Dec rev. 1
Firmware v2.7b R071116
DOTECH, INC
UIC-DX330 Series User’s Manual Rev 2.0
z Please use with being attached to a dual safety device in case of using for controlling instruments which could be
effective to human life or property (eg: controlling atomic energy, medical instruments, cars, trains, flights, burners,
z Please connect after checking the terminal number when connecting power.
z When connecting wires, please give a good screw on terminal. There is a possibility causing a fire with bad connection.
z Please use in the proper performance zone. If you don’t, there is a possibility making the product life shorter or, causing
a fire accident.
z Do not use a load which is exceeded proper value of opening and shutting capacity of a relay contact. This will cause
z When cleaning, water or liquid including oil are prohibited, only clean with soft and dried cloth.
z Do not use in the place where there is inflammability gas, explosiveness gas, moisture, a direct ray of light, radiation,
z Please prevent from getting a dirt or leftover wire inside of this product.
When connecting a sensor, please connect correctly after checking the polarity.
Some of the setting, size etc. on this manual could be changed without an advance notice.
-2-
UIC-DX330 Series User’s Manual Rev 2.0
. Warranty Information
This is the warranty below for customer who has a license or product from 『Dotech』.
condition of warranty
The warranty period for 『Dotech』 products is a year so that it is provided support of the product during the warranty
period.
『Dotech』 does not have a responsibility for problems of product under the circumstance below.
In the case of using without concerning the proper form mentioned on the manual.
In the case of problems caused from both external artificial and environmental factors.
Please contact 『Dotech』 in advance if there is any problem of product caused during the warranty period.
If the problem of product is informed from customer in the warranty period, it will be checked up in the customer area or sent to
『Dotech』 to check and conduct repair of exchange services directly. If the product is over the warranty period or that is on the
condition that it is not mentioned on manual, customer would be suggested to pay the cost of repair, exchange and delivery.
On the condition that suggestions for ‘Warranty Condition Performance’ below are not against the law, 『Dotech』 is not
responsible for any compensation and guarantee caused by losses or damages by business interruption, loss, return.
The condition of warranty mentioned above is the exclusive customer’s right. Dotech refuses any conditions of warranty for
Warranty Condition Performance does not apply any trouble caused by not following exact direction. It is responsibility for
All the conditions of warranty are actually applied and Nobody has authority to modify or extend.
-3-
UIC-DX330 Series User’s Manual Rev 2.0
Revision Information
-4-
UIC-DX330 Series User’s Manual Rev 2.0
Index
1. OUTLINE ................................................................................................................................................................................. 8
3. CONSTITUTION ................................................................................................................................................................... 17
-5-
UIC-DX330 Series User’s Manual Rev 2.0
-6-
UIC-DX330 Series User’s Manual Rev 2.0
- L Basic Model
Type - M Multi-Function Model
- V VSD Model
- Korean
- E English
Language
- C Chinese
- A Customer Language
-7-
UIC-DX330 Series User’s Manual Rev 2.0
1. OUTLINE
UIC-DX330 is based on Micro Processor and the most advanced equipment for controlling electricity conducting efficient
operation of a screw air compressor. UIC-DX330 is a system managing the compressor’s operation intensively, saving energy
through controlling of timing for capacity adjustment, preventing problems in advance with alarming system and informing the
required preventative and maintenance schedule. In the other word, UIC-DX330 conducts the best operation (control)
according to the condition set up and operating circumstance.
Additionally, UIC-DX330 has VSD and PID function together as an option, so it is possible to reduce more than maximum
30% of energy cost.
Unload pressure : Pressure value under unload operation with closing intake valve on compressor
Load pressure : Pressure value under load operation with opening intake valve on compressor
Load delay : Delay time when compressor starts load operation from starting
Re-load delay : Minimum delay time when compressor start load operation from unload operation
Auto stop delay : Compressor is stopped in case of continuous operation at unload operation during auto stop delay
time.
Manual stop delay : Compressor is stopped after unload operation during manual stop delay time.
-8-
UIC-DX330 Series User’s Manual Rev 2.0
1) Special Advantages
UIC-DX330 is a stable electronic control unit for screw air compressor which can provide users with multi-language
(currently Korean, English, Chinese and Japanese) display and running log for integral control and management of the
equipments. It adopts the method of digital process by high efficiency RISC type microprocessor and occupies enough
installation space and stability by unifying display module and control module. It provides convenience to let users know a
status of operation at once through display.
It is possible for UIC-DX330 to store maximum until 160 events of running log, so it is easy for preventative &
maintenance and trouble-shooting. Additionally, it is possible to verify the operation data at site when trip occurs, so it is
helpful for users to know the reason of trouble and the status of equipment in real-time.
1-4) Display for operation status and/or maintenance information (trip computer)
UIC-DX330 has the display function for operation status, delay time and ready time by counting reversely, so users can
recognize the status of compressor at a glance. Also, it has the basic function to notify parts and oil checking and
exchanging schedule by calculating it automatically according to the information of operation.
1-5) Big Size Graphic LCD (Wide Temperature Range Type : -20 ~ +70℃)
Display part of UIC-DX330 adopts big size graphic LCD for user’s easy operation and recognition. (Currently
applicable for Korean, English, Chinese and Japanese)
1-6) Minimization
It is possible to minimize compressor by occupying a small space due to unifying design of control part and display part.
1-7) Scalability
It provides users with RS485 port, MODBUS RTU standard protocol and MMI software and automatic interface.
-9-
UIC-DX330 Series User’s Manual Rev 2.0
2) Basic Specification
- 10 -
UIC-DX330 Series User’s Manual Rev 2.0
- 11 -
UIC-DX330 Series User’s Manual Rev 2.0
J21.1 N1 -
J21.2 N2 -
J21.3 N3 -
J22.4 N8 -
- 12 -
UIC-DX330 Series User’s Manual Rev 2.0
- 13 -
UIC-DX330 Series User’s Manual Rev 2.0
J6.1 Y1 Inverter Speed Output Signal (in case of VSD Control) 4 ~ 20mA
J6.2 YG1 Inverter Speed Control Output Common (0 ~ 100%)
J6.3 Y2 Delivery Press. Transmission Signal 4 ~ 20mA
J6.4 YG2 Delivery Press. Transmission Signal Common ※ (Range Setup)
J6.5 Y3 Delivery Temp. Transmission Signal 4 ~ 20mA
J6.6 YG3 Delivery Temp. Transmission Signal Common (-10 ~ 150℃)
Î Analogue output signal is application from “V” model.
※ Discharge air press. transmission signal outputs retransmission signal (4~20mA) as the input range of
[configuration, discharge press. low, discharge press. high].
- 14 -
UIC-DX330 Series User’s Manual Rev 2.0
5) Communication Signal
TB1.1 SG -
TB1.2 B SYSTEM BUS TRX- RS-485
TB1.3 A SYSTEM BUS TRX+
TB2.1 SG -
TB2.2 B LOCAL BUS TRX- RS-485
TB2.3 A LOCAL BUS TRX+
- 15 -
UIC
C-DX330 Serries User’s Manual
M Rev 2.0
Pin N
Name Function
n Type
(Power Input
I Wiring Diagram)
D
- 16 -
UIC-DX330 Series User’s Manual Rev 2.0
3. Constitution
1) Operation and Display Part
- 17 -
UIC-DX330 Series User’s Manual Rev 2.0
- 18 -
UIC-DX330 Series User’s Manual Rev 2.0
If you push “ENTER”, it is displayed operation time, loading time, ratio of loading/unloading duty, ambient temp.,
oil reclaimer temp, oil reclamier press. Inverter output and frequency respectively.
Menu It returns to setup and status menu when pushing menu button
- 19 -
UIC-DX330 Series User’s Manual Rev 2.0
No. Status
Operation Status Ramp Alarm Status Ramp
00 Initialization OFF
01 Operation Inhibit OFF
02 Operation Ready OFF
Spot Flickering
Start Delay
03 Load Operation Request Status : High
(Blowdown check)
Speed Flickering
Normal : OFF
04 Start Ready Spot Flickering
Trip : High Speed
Spot Flickering
During Operation Flickering
06 Load Operation Request Status : High
(Y/D transfer delay) Alarm : Low Speed
Speed Flickering
Flickering
Spot Flickering
Maintenance : Spot
07 Load Operation Delay Load Operation Request Status : High
Flickering
Speed Flickering
Start Inhibit : Spot
08 Load Operation ON
Flickering
Spot Flickering
09 Reload Delay Load Operation Request Status : High
Speed Flickering
10 Auto-stop Delay Spot Flickering
11 Manual-stop Delay Low Speed Flickering
99 Shut-down OFF
- 20 -
UIC-DX330 Series User’s Manual Rev 2.0
6) Symbol Explanation
- 21 -
UIC-DX330 Series User’s Manual Rev 2.0
- 22 -
UIC-DX330 Series User’s Manual Rev 2.0
4. Menu Constitution
1) Menu Constitution Type
Main Manu
Sub Menu
Parameter
- 23 -
UIC-DX330 Series User’s Manual Rev 2.0
- 24 -
4) Menu Construction
(Based on ‘M’ model) * mark is applicable for ‘ V ’ model only.
00: Discharge Temp. 00: Unload Pressure 00: Sun : Start ~ Stop 00:Event #1 00: Dust Filter Cleaning 00: Discharge Temp High 00: Discharge Temp High
01: Discharge Press. 01: Load Pressure 01: Mon : Start ~ Stop 01:Event #2 01: Suction Filter Change 01: Discharge Press High 01: Discharge Press High
02: Ambient Temp.* 02: Auto-Stop Delay Time 02: Tue : Start ~ Stop 02:Event #3 02: Oil Filter Change 02: Oil Reclaimer Temp 02: Oil Reclaimer Temp
03: Oil Reclaimer Press. 03: Stop Delay Time 03: Wed : Start ~ Stop | 03: Lub. Oil Change High* High*
04: Oil Reclaimer Temp.* 04: Blowdown Delay 04: Thu : Start ~ Stop 03:Event #160 04: Cooler Cleaning 03: Oil Reclaimer Press 03: Oil Reclaimer Press
05: Differential Press. Time 05: Fri : Start ~ Stop 05: Overhaul High* High
06: Total Run Hours 05: Drain Time [On] 06: Sat : Start ~ Stop 04: Diff-Pressure High 04: Diff- Pressure High
07: Motor Run Hours 06: Drain Interval [Off] 05: Ambient Temp High*
08: Motor On/Off Times 07:Cooling Fan Run
09: Loaded Hours Temp*
10: Loaded On/Off Times 08: Cooling Fan Stop
11: Inverter Control* Temp* CONFIGURE DIAGNOSTIC
12: Discharge Press .
09: LCD Backlight Mode
Retrans. *
13: Discharge Temp. 00: Master Password 00: SELF TEST
Retrans.* VSD MODE* TEST MODE Setup 01: B1 Input
01: Trip/Alarm History 02: B2 Input
Delete 03: B3 Input
00: VSD Control Mode 00: Manual Test Mode
02: Operation History 04: B4 Input
01: Maximum Speed 01: Main Motor MAIN
Delete 05: B5 Input
02: Minimum Speed 02: Main Motor STAR
03: Ambient Temp Sensor 06: B4 4mA
COMPRESSOR 03: Optimum Speed 03: Main Motor DELTA
Use 07: B4 20mA
04: Unloaded Speed 04: Load SOL. Valve
04: Oil Press. Use 08: B5 4mA
00: Y-DELTA Transfer 05: Speed Command(Hz) 05: Multi Function N9
START INHIBIT 05: Oil Temp. Use 09: B5 20mA
Time 06: Speed Command(mA) 06: Multi Function N10
06: Discharge Press 10: Y1 4mA*
01: Load Delay Time 07: Proportional Band(P) 07: Multi Function N11
Correct 11: Y1 20mA*
00: Discharge Temp Low 02: Reload Delay Time 08: Integral Time (I) 08: Multi Function N12
07: Oil Press. Correction 12: Y2 4mA*
01: Oil Reclaimer Press 03: Diff. Press Detect 09: Dead Band 09: Inverter Control*
08: Ambient Temp. 13: Y2 20mA*
High Delay 10: Jerk Control Ratio 10: Discharge Press
Correction* 14: Y3 4mA*
04: Load Command Mode 11: Max. Inverter RPM Retrans.*
12: Max. Inverter Frequency
09: Discharge Temp. 15: Y3 20mA*
05: Starting Command 11: Discharge Temp
Correct 16: ADC F/T
Mode Retrans* 10: Oil Temp. Correction* 17: DAC F/T
06: Power Return Restart 11: Discharge Press Min
07: Network ID 12: Discharge Press Max
08: Network BPS 13: Min. Oil Press.
14: Max. Oil Press.
15: Multi Function N9
16: Multi Function N10
17: Multi Function N11
18: Multi Function N12
UIC-DX330 Series User’s Manual Rev 2.0
① If putting [Menu] on operating display, it shows access code input display below.
(If putting [Menu] during supporting time, it does not ask Access Code.)
② After input Access Code by [Upward]/[Downward] key, put [Enter] and then, convert to Menu display.
③ If Access Level is under [Service] level 1, [Set expanded operation] parameter does not change.
④ When changing lock mode before lasting time, please push [Cancel] button for 3 seconds.
-26-
UIC-DX330 Series User’s Manual Rev 2.0
6) STATUS
- 27 -
UIC-DX330 Series User’s Manual Rev 2.0
7) OPERATION
100 Unload Pressure bar 0.1 4.0 70.0 8.6 bar USER1 SVC1
101 Load Pressure bar 0.1 3.8 65.0 6.5 bar USER1 SVC1
102 Auto-Stop Delay Time S 1 1 3600 300 S USER1 SVC1
103 Stop Delay Time S 1 1 60 30 S USER1 SVC1
104 Blowdown Delay Time S 1 1 600 10 S USER1 SVC1
**
105 Drain Time [On] S 1 1 30 5S USER1 SVC1
106 Drain Inteval** S 1 1 3600 60 S USER1 SVC1
107 Cooling Fan Run Temp*** ℃ 1 0 200 80 ℃ USER1 SVC1
108 Cooling Fan Stop Temp ***
℃ 1 0 200 70 ℃ USER1 SVC1
**
It is displayed only in case of setting [Use]of drain function on [CONFIGURE : Multi Function].
***
It is displayed only in case of setting [Use]of cooling fan function on [CONFIGURE : Multi Function].
① Unload Pressure :
z It cannot be set under +0.2bar of loaded pressure value.
z It cannot be set over -0.2bar of alarm pressure value.
② Load Pressure : It cannot be set over -0.2 bar of unload pressure value.
③ Temperature Sensing Capacity : Control(0.01℃), Display(0.1℃)
④ Pressure Sensing Capacity : Control(0.01bar), Display(0.1bar)
⑤ Cooling Fan Run Temp. : Temperature when cooling fan is under operation. (It is recommended to be set more
than 2℃ than cooling fan stop temperature)
⑥ Cooling Fan Stop Temp. : Temperature when cooling fan stops. (It is recommended to be set less than 2℃ than
cooling fan run temperature.)
- 28 -
UIC-DX330 Series User’s Manual Rev 2.0
8) SCHEDULE
400 SUN 00 : 00 ~ 00 : 00
401 MON 08 : 30 ~ 18 : 30
402 TUE 08 : 30 ~ 18 : 30
403 WED 08 : 30 ~ 18 : 30
404 THU 08 : 30 ~ 18 : 30
405 FRI 08 : 30 ~ 18 : 30
406 SAT 08 : 30 ~ 12 : 30
※ It is applied and displayed only in case of setting of [Schedule Operation] on [Extend Operation] menu.
- 29 -
UIC-DX330 Series User’s Manual Rev 2.0
9) RUNNING LOG
Occur /
Item Date Time Event
Reset
1 YY/MM/DD H H : M M ( X ) Event #1
2 YY/MM/DD H H : M M ( X ) Event #2
3 YY/MM/DD H H : M M ( X ) Event #3
4 YY/MM/DD H H : M M ( X ) Event #4
5 YY/MM/DD H H : M M ( X ) Event #5
| | | | |
160 YY/MM/DD H H : M M ( X ) Event #160
① When trip alarm occurs (resets), date and history of event are stored at non volatile memory.
② The maximum number of storable event is 160EA and it is deleted the earliest event and stored the lastest
one in case of over 160EA.
③ When trip alarm is occurred, [Date, Time and Event] is recorded. Also, when trip alarm is reset, “X” mark is
showed next to [Time].
④ When pushing [Enter] button, you can see operation status code, discharge pressure, discharge temperature
and ambient temperature when trip alarm occurs.
(Screen for Trip Alarm Status)
If pushing [MENU] button, you can see the latest alarm history on screen for [Trip Alarm Status].
Discharge Air Status + Whole Status Oil Reclaimer Status + Whole Status
If pushing [MENU] button, you can see the status of discharge air and oil reclaimer in shifts.
(In case of installation of sensor for oil reclamier pressure or temperature)
- 30 -
UIC-DX330 Series User’s Manual Rev 2.0
Discharge Press. Sensing Discharge Press. [Alarm Mode : Discharge Press. High]
6
High Reset Discharge Press. < [Alarm Mode : Discharge Press. High] - 0.5bar
Discharge Temp. Sensing Discharge Temp. [Alarm Mode : Discharge Temp. High]
7
High Reset Discharge Temp. < [Alarm Mode : Discharge Temp. High] - 5℃
Oil Reclaimer Sensing Oil Reclaimer Press. [Alarm Mode : Oil Reclaimer Press. High]
8
Press. High Reset Oil Reclaimer Press. < [Alarm Mode : Oil Reclaimer Press. High] – 0.5bar
Oil Reclaimer Sensing Oil Reclaimer Temp. [Alarm Mode : Oil Reclaimer Temp. High]
9
Temp. High Reset Oil Reclaimer Temp. < [Alarm Mode : Oil Reclaimer Temp. High] - 5℃
Sensing (Oil Reclaimer Press.–Discharge Press.) [Alarm Mode:Diff. Press. High] &
Browdown Time Oil Reclaimer Press. > [Start Inhibit : Oil Reclaimer Press. High] in case of exceeding of
11
Over [Operation : Blowdown Delay Time] during browdown check sequenc.
Discharge Sensing In case of occurrence of error on discharge press. sensor (disconnection / short)
12
P-Sensor Reset In case of normal condition of discharge press. sensor
Discharge Sensing In case of occurrence of error on discharge temp. sensor (disconnection / short)
13
T-Sensor Reset In case of normal condition of discharge temp. sensor
Sensing In case of occurrence of error on oil reclaimer press. sensor (disconnection / short)
14 Oil P-Sensor Fault
Reset In case of normal condition of oil reclaimer press. sensor
Sensing In case of occurrence of error on oil reclaimer temp. sensor (disconnection / short)
15 Oil T-Sensor Fault
Reset In case of normal condition of oil reclaimer temp. sensor
※ Fault message occurred is reset by pushing [Reset] button after solving related reason.
- 31 -
UIC-DX330 Series User’s Manual Rev 2.0
Oil Filter Sensing [Digital Signal Input : Oil Filter Diff. Press] : ON
1
Diff. Press. Reset [Digital Signal Input : Oil Filter Diff. Press] : OFF
Air Filter Diff. Sensing [Digital Signal Input : Air Filter Diff. Press] : ON
2
Press. Reset [Digital Signal Input : Air Filter Diff. Press] : OFF
Oil Reclaimer Sensing [Digital Signal Input : Oil Reclaimer Diff. Press] : ON
3
Diff. Press. Reset [Digital Signal Input : Oil Reclaimer Diff. Press] : OFF
Discharge Press. Sensing Discharge Press [Alarm Mode : Discharge Press. High]
4
High Reset Discharge Press < [Alarm Mode : Discharge Press. High]-0.5bar
Discharge Temp. Sensing Discharge Temp. [Alarm Mode : Discharge Temp. High]
5
High Reset Discharge Temp. < [Alarm Mode : Discharge Temp. High]-5℃
Oil Reclaimer Sensing Oil Reclaimer Press [Alarm Mode : Oil Reclaimer Press. High]
6
Press. High Reset Oil Reclaimer Press < [Alarm Mode : Oil Reclaimer Press. High]-0.5bar
Oil Reclaimer Sensing Oil Reclaimer Temp. [Alarm Mode : Oil Reclamier Temp. High]
7
Temp. High Reset Oil Reclaimer Temp. < [Alarm Mode : Oil Reclaimer Temp. High]-5℃
Sensing (Oil Reclaimer Press–Discharge Press) [Alarm Mode:Diff. Press High] & Discharge Gas Temp. > 50℃
8 Differential Press
Reset (Oil Reclaimer Press-Discharge Press) < [Alarm Mode:Diff Press. High]-0.1bar
Ambient Temp. Sensing Ambient Temp. [Alarm Mode : Ambient Temp. High]
9
High Reset Ambient Temp. < [Alarm Mode : Ambient Temp. High]-5℃
RTC Function Sensing RTC is not working, (Sensible during scheduled operation)
10
Incapacity Reset RTC is in ordinary operation, (necessary to reset the time)
Discharge Temp. Sensing Discharge Temp. < [Start Inhibit-Discharge Temp. Low]
1
Low Reset Discharge Temp. > [Start Inhibit-Discharge Temp. Low]
Oil Reclaimer Sensing Oil Reclaimer Press > [Start Inhibit-Oil Reclaimer Press High]
2
Press High Reset Oil Reclaimer Press < [Start Inhibit-Oil Reclaimer Press High]
※ The equipment doesn’t operate when start inhibit alarm occurs, and it automatically starts when the alarm is reset..
- 32 -
UIC-DX330 Series User’s Manual Rev 2.0
Initial Power
1 Initial Power Input Time (It cannot be deleted.)
Input
2 Main Power Input Power Input Time, (In case of system recovery by WATCH DOG timer)
Dust Filter
1 In case of exceeding dust filter cleaning cycle
Cleaning
Suction Filter
2 In case of exceeding suction filter change cycle
Change
- 33 -
UIC-DX330 Series User’s Manual Rev 2.0
10) MAINTENANCE
▣ In case of resetting some items, please put cursor on the item and push [RESET] button at till·exceed, pass mode.
▣ You can see cycle, till·exceed, pass mode in order in case of pushing [Menu] button.
- 34 -
UIC-DX330 Series User’s Manual Rev 2.0
11) SHUTDOWN
- 35 -
UIC-DX330 Series User’s Manual Rev 2.0
14) COMPRESSOR
800 Y-DELTA Transfer Time Sec 0.1 0.0 30.0 6.0 Sec USER1 SVC2
801 Load Delay Time Sec 1 5 300 10 Sec USER1 SVC2
802 Reload Delay Time Sec 1 5 300 10 Sec USER1 SVC2
803 Diff. Press Detect Delay Sec 1 1 600 10 Sec USER1 SVC2
804 Load Command Mode - Local / Network / Remote Local USER1 SVC2
805 Starting Command Mode - Local / Network / Remote / Schedule Local USER1 SVC2
806 Power Return Restart - ON/OFF ON USER1 SVC2
807 Network ID** - 1 1 127 1 USER1 SVC2
**
808 Network BPS - 4800, 9600, 19200, 38400 9600 USER1 SVC2
**
It is only displayed in case of installing communication port option.
14-1) Starting Command Mode (Setup of control source for equipment run/stop)
① Local : Run/Stop using keypad on controller itself.
② Network : Run/Stop using system network.
③ Remote : [Stop : Digital Input Signal (ID10) : OFF Æ ON], [Run : Digital Input Signal : ONÆOFF],
Edge Detection Method (It is possbile to run or stop by network or keypad)
④ Schedule : Operation during the setup time on [Schedule] menu
(It is possible to run or stop by network or keypad)
14-2) Load Command Mode (Setup of control source of equipment load run)
① Local : Using press. value from press. sensor.
② Network : Run/Stop using system network
③ Remote : [Load Run : Digital Input Signal (ID9) : ON], [Unload Run : Digital Input Signal : OFF]
14-3) Power Return Restart [Run/Stop Command in case of power return after mains failure
① Power Return Function : ON
- Mains failure during operation Æ Power return : Run
- Mains failure during stop Æ Power return : Stop
② Power Return Function : OFF.
- Mains failure during operation : Power return : Stop
- Mains failure during stop : Power return : Stop
14-4) If Y-DELTA transfer time is set as ‘0.0’sec., the equipment operates direct start mode.
- 36 -
UIC-DX330 Series User’s Manual Rev 2.0
900 VSD Control Mode - OFF / FIX / VSD OFF USER1 SVC2
901 Maximum Speed rpm 10 0 9990 3600 USER1 SVC2
902 Minimum Speed rpm 10 0 9990 1500 USER1 SVC2
903 Optimum Speed rpm 10 0 9990 2700 USER1 SVC2
904 Unloaded Speed rpm 10 0 9990 1800 USER1 SVC2
905 Speed Command(Hz) Hz View only USER1 LOCK
906 Speed Command(mA) mA View only USER1 LOCK
907 Proportional Band (P) % 0.1 0.0 99.9 10.0 USER1 SVC2
908 Integral Time (I) Sec 1 0 3600 10 USER1 SVC2
909 Dead Band (DBand) % 0.1 0.0 20.0 0.7 USER1 SVC2
910 Jerk Control Ratio % 0.1 0.1 99.9 10.0 USER1 SVC2
911 Max Inverter RPM rpm 10 0 9990 3600 USER1 SVC2
912 Max Inverter Frequency Hz 1 0 120 60 USER1 SVC2
VSD controls the speed of main motor according to the change of discharge pressure, so it can maintain
stable required pressure..
Control algorism uses PI control out of PID control.
② Maximum Speed : Put in the speed which limits maximum speed of motor
③ Minimum Speed : Put in the speed which limits minimum speed of motor (Put in 20% of speed range)
④ Optimum Speed : Put in optimum load speed of motor (Put in 70% of speed range)
⑤ Unloaded Speed : Speed of unload operation, In case of error in discharge press. in [Operation:Unload
Pressure]
⑥ Proportional Band (P) : Put in ‘P’ value out of PID invariable number
⑦ Integral Time (I) : Put in ‘I’ value out of PID invariable number
⑧ Dead Band (D.Band) : Dull control of speed change if the difference between discharge press. and target
press. is in dead band
⑨ Jerk Control Ratio : Limit value of motor speed variation. (Jerk Control)
⑩ Max. Inverter RPM : Put in motor speed from inverter when 100% operation.
- 37 -
UIC-DX330 Series User’s Manual Rev 2.0
1010 Discharge Press. Retrans* mA 0.1 4.0 20.0 4.0mA USER1 SVC1
1011 Discharge Temp. Retrans.* mA 0.1 4.0 20.0 4.0mA USER1 SVC1
***
Manual test is available when [Manual Test Mode] is ON only.
*
It is only displayed in case of installing analogue output option.
② Main Motor STAR (Star Magnet) and Main Motor DELTA(Delta Magnet) cannot be turned on at the same time.
③ Manual Test Mode is automatically released after 2 minutes from the final performance of manual test.
- 38 -
UIC-DX330 Series User’s Manual Rev 2.0
17) CONFIGURE
- 39 -
UIC-DX330 Series User’s Manual Rev 2.0
18) DIAGNISTIC
※ It is our initial setup value when shipped out, so you are kindly required to understand it first
- 40 -
UIC-DX330 Series User’s Manual Rev 2.0
Date / Time is used for a point of reference to record system information such as trip/alarm history, operation
history and scheduled operation. It is inevitable when any troubles in equipment occur, so please set it up exactly.
① When you push [MENU] button once at operation screen, access code input window is displayed.
② When you push [MENU] button once again, the following window for setting date/time appears.
③ Please set up date / time by using [ENTER] and [Upward] / [Downward] button, and then return to
operation screen by pushing [CANCEL] button.
④ A day of the week is automatically set.
⑤ If “:” between hour and minute is not flickered per a second, please set it up once again.
- 41 -
UIC-DX330 Series User’s Manual Rev 2.0
5. HOW TO INSTALL
1) Installed Place
Please install this controller in the following place in the same way with other general industrial electronic devices.
2) Installation Method
⊙ Please use shield cable between display part and main board in order to avoid noise.
⊙ Please keep input/output signal line away more than 30cm from power line and do not put at the same lines together.
⊙ Please install fuse additionally in order to protect controller from overvoltage..
⊙ Please wire surge absorber at magnet control coil in parallel in order to improve stability of controller.
⊙ Please install noise filter in order to improve the stability of controller.
⊙ Please use AWG No. 12~28 and fasten terminal screw at 0.3~0.4N•m torque when wiring.
⊙ Please use terminal connected with controller as pen hole terminal (CE007508 standard).
- 42 -
UIC-DX330 Series User’s Manual Rev 2.0
- 43 -
UIC-DX330 Series User’s Manual Rev 2.0
- 44 -
UIC-DX330 Series User’s Manual Rev 2.0
- 45 -