21EEE - 2023 - Distribution Systems
21EEE - 2023 - Distribution Systems
Dr. Preetha PK
Course Syllabus
• Unit 1
Introduction-Structure of Electric Power System-Conventional, Deregulated Structure, Grid Structure Micro-grid and
Smart Grid Structure; Methods of electric power generations – Conventional- Renewable Energy based generation,
need for interconnected system- necessity of EHV transmission: EHVAC and HVDC transmission, Variable load on
power system- Load Curve and Load Duration Curve, Tariff-Types, Power factor improvement.
• Unit 2
Introduction to Modeling and performance analysis, Transmission line Models- Line parameter estimation-
symmetrical and unsymmetrical spacing of lines, bundled conductor, double circuit lines- corona- Regulation,
Efficiency, Real and reactive power flow in transmission lines- Harmonics- Effects in power system, THD.
Compensation- shunt and series compensation.
• Unit 3
Insulators and Underground cables -classification and grading. Mechanical design of transmission lines. Distribution
systems –Types and comparison–Ring main- Radial distribution. Representation of power system: Power system
components model, Single line diagram and per unit representation, reactance/impedance diagram, Bus Admittance and
Impedance matrix.
• Lab Practice: Hardware experiments, simulation experiments and field visit – Structure of Electric Power System,
modeling and performance analysis of transmission and distribution systems, power system representation etc.
• Distribution system is that part of power system which distributes power to the consumers for utilization
Primary
2 wire Overhead Radial
distribution
Secondary
3 wire Underground Ring main
distribution
Interconnected
(i) Primary distribution system.
• The most used primary distribution voltages are 11 kV, 6·6 kV and 3·3 kV.
• Due to economic considerations, primary distribution is carried out by 3- phase, 3-wire system.
(ii) Secondary distribution system.
• At each distribution substation, the voltage is stepped down to 400 V and power is delivered by 3-
phase,4-wire a.c. system.
• The single phase domestic loads are connected between any one phase and the neutral, whereas 3-
phase 400 V loads are connected across 3- phase lines directly
• It is a common knowledge that electric power is usually generated, transmitted
and distributed as a.c. However, for certain applications, d.c. supply is
absolutely necessary.
• For instance, d.c. supply is required for the operation of variable speed
machinery (i.e., d.c. motors), for electrochemical work and for congested areas
where storage battery reserves are necessary.
• For this purpose, a.c. power is converted into d.c. power at the substation. The
d.c. supply from the substation may be obtained in the form of
(i) 2-wire or (ii) 3-wire for distribution.
2-wire d.c. system
• This system of distribution consists of two wires. One is the outgoing or positive wire and the
other is the return or negative wire.
• The loads such as lamps, motors etc. are connected in parallel between the two wires as
shown in Fig.
• This system is never used for transmission purposes due to low efficiency but may be
employed for distribution of d.c. power.
3-wire d.c. system.
• Consists of two outers and a middle or neutral wire which is earthed at the substation.
• The voltage between the outers is twice the voltage between either outer and neutral wire as shown
in Fig.
• The principal advantage of this system is that it makes available two voltages at the consumer
terminals viz., V between any outer and the neutral and 2V between the outers.
• Loads requiring high voltage (e.g., motors) are connected across the outers, whereas lamps and
heating circuits requiring less voltage are connected between either outer and the neutral.
• In this system, separate feeders radiate
from a single substation and feed the
distributors at one end only.
• Fig. (i) shows a single line diagram of a radial system for d.c. distribution where a feeder OC
supplies a distributor A B at point A. Obviously, the distributor is fed at one end only i.e., point A
in this case.
• Fig. (ii) shows a single line diagram of radial system for a.c. distribution.
• This is the simplest distribution circuit and has the lowest initial cost.
• The end of the distributor nearest to the
feeding point will be heavily loaded.
• Therefore, any fault on the feeder or distributor cuts off supply to the consumers who are on the side
of the fault away from the substation.
• The consumers at the distant end of the distributor would be subjected to serious voltage
fluctuations when the load on the distributor changes.
• Due to these limitations, this system is used for short distances only.
• In this system, the primaries of distribution
transformers form a loop.
• The loop circuit starts from the substation
bus-bars, makes a loop through the area to
be served, and returns to the substation.
• Substation supplies to the closed feeder
LMNOPQRS.
• The distributors are tapped from different
points M, O and Q of the feeder through
distribution transformers.
• There are less voltage fluctuations at consumer’s
terminals.
ADVANTAGES :
• It increases the service reliability.
• Any area can be fed from any one of the generating station. This reduces reserve
power capacity and increases efficiency of the system.
Requirements of a Distribution system
(i) Proper voltage
• One important requirement of a distribution system is that voltage variations at consumer’s terminals should be
as low as possible.
• The changes in voltage are generally caused due to the variation of load on the system.
• Low voltage causes loss of revenue, inefficient lighting and possible burning out of motors.
• High voltage causes lamps to burn out permanently and may cause failure of other appliances.
• Therefore, a good distribution system should ensure that the voltage variations at consumers terminals are
within permissible limits.
• The statutory limit of voltage variations is ± 6% of the rated value at the consumer’s terminals.
• Thus, if the declared voltage is 230 V, then the highest voltage of the consumer should not exceed 244 V while
the lowest voltage of the consumer should not be less than 216 V.
Requirements of a Distribution system
(ii) Availability of power on demand.
• Power must be available to the consumers in any amount that they may require from time to time.
• For example, motors may be started or shut down, lights may be turned on or off, without advance warning to
the electric supply company.
• As electrical energy cannot be stored, therefore, the distribution system must be capable of supplying load
demands of the consumers.
• This necessitates that operating staff must continuously study load patterns to predict in advance those major
load changes that follow the known schedules.
(iii) Reliability.
• Reliability can be improved to a considerable extent by (a) interconnected system (b) reliable automatic
control system (c) providing additional reserve facilities
Design Considerations in Distribution system
• Good voltage regulation of a distribution network is probably the most
important factor responsible for delivering good service to the consumers.
• For this purpose, design of feeders and distributors requires careful
consideration.
(i) Feeders.
• A feeder is designed from the point of view of its current carrying capacity while the
voltage drop consideration is relatively unimportant.
• It is because voltage drop in a feeder can be compensated by means of voltage
regulating equipment at the substation.
(ii) Distributors.
• A distributor is designed from the point of view of the voltage drop in it.
• It is because a distributor supplies power to the consumers and there is a statutory
limit of voltage variations at the consumer’s terminals (± 6% of rated value).
• The size and length of the distributor should be such that voltage at the consumer’s
terminals is within the permissible limits.