CHAPTER 10 - Symmetrical Components Unbalanced Fault

Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

SYMMETRICAL COMPONENTS AND

UNBALANCED FAULT
 Fundamentals of Symmetrical Components

 Sequence Impedances of Y-Connected Loads,


Transmission Lines, Synchronous Machines, and
Transformers.

 Sequence Networks of a Loaded Generator

 Single Line to Ground Fault

 Line to Line Fault

 Double Line to Ground Fault

 Unbalanced Fault Analysis Using Bus Impedance


Matrix
Types of Faults

Balanced Fault:

 3-phase symmetrical fault

Unbalanced Fault:

 Single line-to-ground fault


 Line-to-line fault
 Double line-to-ground fault
Three-phase unbalanced phasors of a three-
phase system can be resolved into three
balanced systems of phasors:

1. Positive-sequence components consisting of a


set of balanced three-phase components with a
phase sequence abc.

2. Negative-sequence components consisting of a


set of balanced three-phase components with a
phase sequence acb.

3. Zero-sequence components consisting of three


single-phase components, all equal in
magnitude and with the same phase angles.
Positive phase Negative phase
sequence: sequence:

Zero phase
sequence:

Based on an operator a that causes a counterclockwise rotation of


120 :
; ;
;
Zero-sequence set

Positive phase Negative phase


sequence: sequence:
Vc1 Va1 Va2

Vb2
Va0
Vb0
Vc0
Vb1 Vc2

3 sets of balanced phasors, which are the symmetrical components


of 3-unbalanced phasors

Graphical addition of the


components of the above 3
sets of balanced phasors
to obtain 3-unbalaced
phasors
Using
Symmetrical component
transformation matrix
where

where

Symmetrical
components
Symmetrical
components

The zero sequence component of current is equal to one-third of


the sum of the phase currents.

When the phase currents sum to zero eg in a 3-phase system with


ungrounded neutral, the zero-sequence current cannot exist.

If the neutral of the power system is grounded, zero-sequence


current flows between the neutral and the ground
One conductor of a 3-phase line
is open. The current flowing to
the -connected load through line
a is 10A. With the current in line a
as reference and assuming that
line c is open, find the
symmetrical components of the
currents.
 Ia = 10∠0 A; Ib = 10 ∠180 A; Ic = 0 A
The Voltages
The unbalanced phase
voltages in terms of
symmetrical components
voltages

in matrix notation

The symmetrical
components in terms of
unbalanced voltages

in matrix notation
10.2
The symmetrical components of a set
of unbalanced 3-phase currents are

Obtain the original unbalanced


phasors.
The 3-phase complex
power

and recall

The total unbalanced power = the sum of symmetrical


component powers
 Analysis of unsymmetrical fault on symmetrical
system consists of finding the symmetrical
components of unbalanced currents that are
flowing.

 Sequence networks carrying the currents:


are interconnected to represent
various unbalanced fault conditions.

 To calculate the effect of a fault by the method of


symmetrical components, it is essential to
determine the sequence impedances an to
combine them to form the sequence networks.
 Z1 – positive sequence impedance
Impedance offered to the flow of positive-
sequence current.

 Z2 – negative sequence impedance


Impedance offered to the flow of negative-
sequence current.

 Z0 – zero sequence impedance


Impedance offered to the flow of zero-
sequence current.
Ia
Zs
+
Ib
Zs }Z
m
Zm

+ In
Va
Ic
Zs
}Z
m

Vb Zn
+
Vc
- - -
In terms of symmetrical components:
- With mutual coupling

- Without mutual coupling, Zm = 0


A balanced 3-phase voltage of 100V line-to-neutral is
applied to a balanced Y-connected load with
ungrounded neutral. The 3-phase load consists of 3
mutually-coupled reactances. Each phase has a series
reactances of Zs = j12 , and the mutual coupling
between phases is Zm = j4 .

a) Determine the line currents


by mesh analysis without
using symmetrical
components.

b) Determine the line currents


using symmetrical
components.
 Applying KVL:

 Applying KCL:

 The equation in matrix form


But, Zn = 0
Static device has no effect on the
impedance, because the voltages and
currents encounter the same geometry
of the line, irrespective of the sequence.

Z1 = Z2; Z0 is different from Z1 and Z2

where

The zero sequence impedance of the transmission line


is >3x larger the +ve or –ve sequence impedance.
 The inductances of a syn. m/c depend on the
phase order of the sequence current relative to
the direction of rotation of the rotor.

 The positive-sequence reactance varies for


balanced 3-phase fault studies:

was used for the balanced 3-phase fault


studies.
 When the negative-sequence currents are
impressed in the stator, the net flux in the air
gap rotates at opposite direction to that of
rotor eg the net flux rotates at twice the syn.
speed relative to the rotor.

 The field wdg. has no influence, but the


damper wdg. produces an effect in the
quadrature axis.

 A set of zero-sequence currents are all


identical.
Where Xl ≡ leakage reactance
 The transformer is modeled with the equivalent series
leakage impedance.

 Transformer is a static device, the leakage impedance


will not change if the phase sequence is changed:

 In - or a - transformer:
- the positive-sequence line VHV leads line VLV by
30º
- the negative-sequence voltage, the corresponding
phase shift is - 30º.

 The zero-sequence impedance depends on the wdg.


connections and also depends on whether the neutral
is grounded or not.

In = 3I0 The neutral impedance appears as 3Zn


Transformer zero-sequence equivalent circuit
Convert to symmetrical components:
- generated emf is balanced

Positive-sequence Negative-sequence Zero-sequence


network network network
Assume that the generator
is initially unloaded.

The boundary conditions at


the fault point:

Recall:
But, and,

While Va = IaZf

Hence, the fault current equals


Assuming that the generator
is initially at no-load.

The boundary conditions at


the fault point:

The symmetrical components


of currents:
Recall:

The phase current:


 The fault current:

In many practical applications, the positive and


negative- sequence impedances are found to be
equal.
For bolted fault, Zf = 0
Assuming that the generator
is initially at no-load.

The boundary conditions at


the fault point:
Recall:
XT10= XT20 = XT30= XT40 = XT50= XT6 0 = j0.1pu

XG10= XG20 = XM30 =j0.4pu

XL10= XL20 = XL30=j0.06pu M3


ZnG1= ZnT1= j1.0pu
T U

T3 T4
T2
T5
R S

M P
L2 L3 V X
G1 T6 G2
T1

N Q L1 W Z
ZnG1 ZnT1
10.5
10.5
Positive sequence network
Zero sequence network
 Sketch the sequence network
connection for a 3-phase balanced
fault.
10.5
Symmetrical components of fault current:

The fault current:


Bus voltages during fault for phase a:

Fault currents in lines for phase a:


Symmetrical components of fault current:

The fault current:


The symmetrical components of bus voltages
during fault:
Bus voltages during fault:
Symmetrical components of fault current in
lines for phase a:
The line fault current:
Symmetrical components of fault current:

The fault current:


The symmetrical components of bus voltages
during fault:
Bus voltages during fault:
Symmetrical components of fault current:
The line fault current:
Symmetrical components of fault current:
The phase current at the faulted bus:
The symmetrical components of bus voltages
during fault:
Bus voltages during fault:
Symmetrical components of fault current:
The line fault current:

You might also like