iOS Manual - iOSM12BDD-D1
iOS Manual - iOSM12BDD-D1
SPECIFICATIONS
M12BDD-D2 M12BDD-D2
Inputs per Module Sample Time (PLC Min. 20mS - Determined by
4 (1 Common)
(Commons) Update Rate) Configuration
Input Voltage Range 12/24 VDC
Terminal Type Screw Type, Removable
Impedence 4.7k ohms
Peak Voltage 30 VDC
Storage Temp. -40° to 85° Celsius
ON voltage level 10 VDC
OFF voltage level 0-3 VDC Operating Temp. -10° to 60° Celsius
Outputs per Module 8 NPN (Trans) Relative Humidity 5 to 95% Non-condensing
Max Switching 600mA @ 30 VDC 17.5mm x 100mm x 120mm
Dimensions WxHxD
Power per O/P per channel, up to total of 3A. 0.69” x 3.94” x 4.72”
Minimum Load 5 VDC, 10mA
Weight 210g (8.4 oz.)
Maximum Voltage 30VDC
Required Power Modbus/RTU (binary)
45mA @ 24Vdc, typical Communications
(Steady State) RS-485 half duplex
Required Power Default Comms. 38400 baud, N, 8, 1, no h/s
Negligible
(Inrush) Parameters Default Modbus ID 1
2000Vac for 60 seconds Supported Modbus
Isolation 1,2,3,4,5,6,8,15,16
(Input/Power & Input/Comms) Commands
RS-485
12/24Vdc 1 COM+ I/O DC IN
N + - 2 COM-
P + LOAD - 3 OUT0
N + LOAD - 4 OUT1 Pin # 12BDD-D2
O + LOAD - 5 OUT2 1 COM +
2 COM -
U + LOAD - 6 OUT3 3 OUT 0
T + -
LOAD 7 OUT4 4 OUT 1
P
+ - 5 OUT 2
U LOAD 8 OUT5 6 OUT 3
T + - 7 OUT 4
LOAD 9 OUT6
S + - 8 OUT 5
LOAD 10 OUT7 9 OUT 6
10 OUT 7
11 IN 0 11 INPUT 0
12 IN 1 12 INPUT 1
13 INPUT 2
13 IN 2 14 INPUT 3
14 IN 3 15 COM
- + 16 ** Not Connected
15 COM
12/24Vdc
16 N.C.**
D- A I
V-
D+ B V+ J
GND C 10-30Vdc
INIT D
Notes:
Both ends of the RS-485 network should be terminated with a 100Ω, ¼W, 1% resistor. i³ controllers
feature dipswitches or jumpers, which enable appropriate termination if the i³ is located on a network
end.
All configuration parameters listed below (except 40012 Channel Enable) are stored in EPROM and
for this reason they should not be constantly rewritten.
*W.D. = Watchdog
INSTALLATION / SAFETY
Warning: Remove power from the i3 controller, CAN port, and any peripheral equipment connected to
this local system before adding or replacing this or any module.
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields may be terminated at the module terminal strip.
d. In severe applications, shields should be tied directly to the ground block within the panel.
e. Use the following wire type or equivalent: Belden 8441.