0% found this document useful (0 votes)
47 views20 pages

Corrosion Evaluation and Monitoring Practices: Raghuvir Singh

The document discusses various methods for evaluating corrosion, including laboratory tests, field tests, and tests in actual industrial plants. Common evaluation methods described include weight loss tests, salt spray tests, and atmospheric exposure tests. The goal of the tests is to evaluate corrosion resistance of materials, measure corrosion rates, and assess effectiveness of corrosion control measures.

Uploaded by

Nam Phong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views20 pages

Corrosion Evaluation and Monitoring Practices: Raghuvir Singh

The document discusses various methods for evaluating corrosion, including laboratory tests, field tests, and tests in actual industrial plants. Common evaluation methods described include weight loss tests, salt spray tests, and atmospheric exposure tests. The goal of the tests is to evaluate corrosion resistance of materials, measure corrosion rates, and assess effectiveness of corrosion control measures.

Uploaded by

Nam Phong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Industrial Corrosion : Evaluation & Mitigation

CORROSION EVALUATION
AND MONITORING PRACTICES
Raghuvir Singh
Applied Chemistry & Corrosion Division
National Metallurgical Laboratory, Jamshedpur-831007
Email : raghujoggyahoo. co. in

Corrosion tests are aimed at to evaluate and select suitable materials for process,
evaluation of corrosivity of environment, and to check the effectiveness of the applied
corrosion control measures. These tests may be performed in laboratory, in actual process
plant, or in the field such as atmosphere tests. The laboratory tests are generally carried out
using small specimens, small volume of solution (simulated synthetic or from actual process).
These are useful and economic to screen out the most useful or useless materials for the
process or to test further in plant environment. The actual in-plant test needs plant availability
for the desired test and may take certain time and cost. There are several methods being
used for evaluating corrosion. Laboratory test methods may be categorized as an
electrochemical, which are based on the measurements of current evolves from
electrochemical reactions, while non-electrochemical techniques are based on the overall
weight lost by the specimen or surface features due to corrosion such as pit, crevice, crack
or microstructural changes appeared after the test. However, for choosing appropriate
method one needs to know about the type of corrosion against which resistance of materials
is being sought. For instances, to determine the thinning rate of a steel pipe, methodologies
for general/uniform corrosion such as weight loss, polarization resistance etc. will be more
useful than the others. The knowledge of a parameter of concern that defines the resistance
of materials against specific form of corrosion is also important. For example, pitting and
protection potentials (obtained in electrochemical experiments) are characteristic features
(parameters of concern) to illustrate the pitting susceptibility of any passivating alloy in a
corrosive environment. Several methods being practiced to evaluate different types of
corrosion are discussed in forthcoming sections.

GENERAL/ UNIFORM CORROSION


A most common form of corrosion is uniform or general corrosion. The
electrochemical reactions occur uniformly over the large surface exposed to corrosive
environment and results in thinning of the component. For instance, steel or zinc exposed
to the dilute sulfuric acid. This form of corrosion can be accurately predictable by laboratory
or in-plants tests. Various methods (standard or routine) can be used to evaluate general
corrosion; a few such techniques are briefly discussed below:

Weight Loss Test


The weight-loss tests provide data on the resistance of materials against uniform
corrosion and should not be used for predicting localized attack. One need to choose the
corrosion test method judiciously, for instance, this method may be an unsuitable choice if

48
Industrial Corrosion : Evaluation & Mitigation -

selected to asses the -resistance localized corrosion. The latter results into the formation of
minute pinholes on the surface that often lead to failure (perforation and leakage) while
showing insignificant weight loss. The data from uniform corrosion may be converted to
express the corrosion rate in units of mils per year (mpy) or as millimetres per year (mm/y),
etc. in metric units. The test includes specimen preparation 111 (polishing, cleaning, and
degreasing) followed by the dimensional measurements, weighing, and identification of
each specimen (by marking or tagging the specimen) before exposure for the test. The
surface finish of coupons should be nearly the equipment or component in service.
The size of test coupons should be large: enough to give significant mass loss but
should be able to fit into the test chamber. The volume of test solution shall be measured
based on the area of coupon and should also be able to immerse the entire specimen surface.
The exposure time of the coupons shall be planned in a way that the resolvable weight loss
is obtained. The material having high corrosion resistance should be exposed for significantly
long time for obtaining measurable mass loss . Several materials corrode rapidly in the
early stages of exposure to an environment (prior passive film formed) and thereafter corrode
at a much lower rate. The extrapolation of corrosion rate, based on the results obtained in
short durational test, for longer time will be very conservative and should be avoided. It is
always good to design the test for different time periods.
After completion of the test period, corrosion products on the specimen surface
is cleaned mechanically such as by abrasive blasting, brushing, or by chemically (preferably
added with inhibitor), or electrolytic methods. Any corrosion product left on the surface
may cause errors in the final results. The cleaning method itself may produce material loss -
of the base substrate. Such errors in mass loss may be overcome by subjecting the fresh
coupon for cleaning in a number of cycles. After completion of the test, the corrosion rate
may be calculated from the mass loss as follows:
Corrosion Rate = (K x FY) / (A x T x D)
Where
K = Constant
T = time of exposure, h,
A = area, cm2
W = mass loss, g, and
D = density, g/ cm3 (D for steels and stainless steels -7.9 g/cm3,
for copper 8.9 g/cm3 for aluminum =2.7g/cm3).
K = 3.45 x 106 for a corrosion rate in mpy.
Other constants include K= 8.76 x 104 for a corrosion rate in mm/y.
Refer to ASTM G 1 for a complete listing of constants.
Salt (fog) Spray
Salt spray test is an accelerated corrosion test methodology in a controlled
environment . This is most often used to evaluate the effectiveness of coatings or paints or
to rank the various alloys developed for specific corrosive environment . This requires a
fog chamber, a reservoir, air supply system , spray nozzles and specimen support . The salt
solution may be prepared from 5% sodium chloride solution with pH in the range 6.5-7.2

49
Industrial Corrosion : Evaluation & Mitigation
and the exposure chamber should be maintained at 35°C. The time device may be attached
to the cabinet for intermittent spraying of the solution. The exposure period is generally
agreed between the customer and vendor and is advised in multiples of 24 hours. The
detailed methodology is given in the ASTM B 117-03.[21 The environmental conditions
may be varied according to the requirements. In a modified salt spray test methods given in
ASTM G85-02 [31, several environments and test parameters have been suggested. These
includes acetic acid salt spray test which is sodium chloride solution pH: 3.1 - 3.3 added
with glacial acetic acid. The salt fog is sprayed continuously for 16-240 hours. The similar
solution, in a different test procedure, may be sprayed in various cycles with intermittent
drying and humidifying rather than continuous spraying (3/4h spray, 2h dry air purging,
and 3-1 /4h soak at high humidity). The temperature of cabinet should be around 49±1.1 °C.
The synthetic sea salt solution (42 g / litre) is used with periodic sulphur dioxide (SO2) gas
(at flow rate 1 cm3/min.ft3) in another test method. The specimens during and after completion
of the tests are observed and compared for the time at which rust begins to appear, surface
coverage by the rust, pits/ crevice, weight loss etc.

Atmospheric Corrosion
Corrosion resistance of newly developed alloy, paints and coatings can be evaluated
worldwide by conducting the atmospheric corrosion test. For atmospheric corrosion,
selection of exposure sites are important which may be defined as rural, marine, and
industrial. Corrosion in atmosphere mainly depends upon the temperature, humidity, rainfall,
wind speed and direction, chemical species, and solid contents in the air. Rural atmospheres
are least corrosive among all; industrial atmosphere contains various pollutants and corrosive
gases such as sulfur containing gases/ compounds, CO2, NO,,, H2S, and condensate with
low pH that increase the corrosion rate. The marine atmosphere is generally the most severe
one. It contains chloride ions and high humidity. The corrosion rate further depends upon
the distance from the sea.
The test includes test coupons and test panels to fix the specimens on the exposure
site. The coupon size should be sufficiently large to result into significant weight loss.
Commonly used specimen size may be 4 x 6 inch or mutually agreed between vendor and
customer. The identification of specimens needs to be carefully maintained to avoid any
error in the test findings. The concentration and presence of corrosives such as sulfur
compounds, Cl-, humidity, rainfall, temperature etc. record at definite time interval will be
useful to correlate and describe the corrosion rate variations. Cleaning of the specimens
after exposure can be performed as per the ASTM G I and corrosion rate may be determined
as discussed earlier under weight loss section. The detailed test method may be seen from
the ASTM G 50 & 104 [4,51

LOCALIZED CORROSION
Most often premature and catastrophic failure of engineering components occurs due
to localised corrosion such as pitting , crevice , intergranular and intergranular stress corrosion
cracking (IGSCC), SCC, hydrogen assisted damage etc . During localised corrosion , the large
surface of materials remained unattacked , however, only specific locations are attacked at a

50
Industrial Corrosion : Evaluation & Mitigation
relatively higher rate. The test method must be selected depending upon the type of localised
corrosion anticipated from the specific material-environment combination.

Pitting and Crevice Corrosion


Pitting corrosion generally appears in the form of small pinholes, sometimes deep
across the thickness of coupon. The area of pits is extremely small as compared to the
surface of the specimen. Once the pit formation initiates, the solution chemistry inside it
alters to be extremely corrosive as compared to the bulk solution. Presence of certain anions
such as chloride, thiosulphate etc. are responsible for this form of corrosion. The crevice
corrosion generally occurs under the shielded/ occluded regions such as bolted assembly,
under the deposits, gaskets etc. The pits or crevices often become the preferable site for
several other types such as SCC, corrosion fatigue, fretting fatigue etc. These forms of
corrosion can be evaluated by electrochemical as well as by non-electrochemical techniques
described in following sections.

Pitting Tests 16,71


To rank various stainless steels against pitting corrosion in oxidizing chloride media
can be simulated by ferric chloride test. This test method is primarily intended to generate
the environment close to that observed inside the pits. This method includes the exposure
of polished (followed by weighing) coupons of the size 25 x 50 mm in ferric chloride
solution (volume roughly around 5 ml /cm2) at an ambient or 500C temperature. For coupons
larger than the prescribed size, 5 mi/cm2 of ferric chloride solution should be added.
Experimental solution is prepared by dissolving 100g reagent grade FeC 13.61120 in 900 nil
reagent water (10% FeC13 solution). After exposure for about 24-72 hours, clean (by
including ultrasonic cleaner) the specimens for pitting details such as maximum pit depth,
pit density, and average pit depth. Coupons should be weighed to obtain the mass-loss
for corrosion rate analysis. Recommended temperatures for evaluation are 22 ± 2°C
and 50 t 2°C.

Crevice Tests
Crevice corrosion test needs crevice block assembly with `0' rings. The two TFE-
fluorocarbon blocks are fastened on the two sides of test specimen with O-rings or rubber
bands. Finger or hand contact to surfaces during handling should be avoided. The specimen
fastened with crevice block may be placed in the solution as described for pitting in earlier
section. After reasonable test period (24-72 h), specimens may be inspected for the crevice
attack under the contact point 0-ring or rubber bands and under both TFE-fluorocarbon
blocks. After the test is over, the specimen may be cleaned for weight loss and pit analysis
under creviced or occluded locations.

Critical Pitting Temperature (CPT)


Tests can be carried out for obtaining the minimum temperature at which pitting will
be initiated. The solution for this test is more acidic and prepared by adding about 1% HCl
to 6-7 wt% ferric chloride in reagent water. The apparatus need to have condenser to test at
Industrial Corrosion : Evaluation & Mitigation

increasing temperature . This will prevent the decrease in solution level by evaporating.
The start temperature may be obtained from the following formula
CPT(°C)=(2.5 x%Cr)+( 7.6 x % Mo) - (31.9 x % N) - 4 1.0
Maintaining temperatures within t 10C, and test temperature may be increased at
intervals of 5°C. The suggested temperature range for the test is between 0 to 85°C and test
period is 24 hours . After the completion of experiment , check for the pit depth ; if pit depth
is 0.025 mm or higher then pitting corrosion is established . If pit depth is below this, the
experiment should be repeated at a temperature higher by 5°C. If pitting depth greater
than 0 . 025 mm is present , the experiment may be repeated at a temperature lower than
the earlier.

Critical Crevice Temperature (CCT)


The critical crevice temperature (CCT) may be determined in similar solution and
test conditions as for CPT . The multiple crevice assemblies (MCA) with a fastener of Alloy
276 is used for crevice formation . The starting temperature may be obtained by using
following formula
CCT (°C) =(3.2 x % Cr) + ( 7.6 x %Mo) +( 10.5 %Nb) - 81.0

The analysis of pit rating can be made in terms of pit depth, density and size as per
the standard chart given in ASTM G 46 - 94. The pitting can also be represented as `Pitting
Factor' which is the ratio of deepest pit to the average pit depth on the open surface or
under crevice surface. Pitting factor of one indicates general corrosion.

Intergranular Corrosion (IGC) 181


Corrosion propagate along the grain boundary in preference to the grain matrix in
several environment-material combination and is called intergranular corrosion. This
weakens the grain boundaries and reduces the overall strength of materials. The IGC is
prevalent in sensitized stainless steels structures. Sensitization process, which results from
the exposure of stainless steels to the temperature range of 500-750°C, is precipitation of
carbides and depletion of the chromium from nearby grain boundaries. This reduces the
corrosion resistance of grain boundary in several corrosive environments. Various test
methods are available to detect the susceptibility of the stainless steels and nickel-based
alloys to intergranular corrosion (IGC) and are described below 181

Oxalic Acid Etch


The oxalic acid etching is a rapid test method used to screen out specimens which
are free from intergranular corrosion susceptibility. This test method also serves as a basis
for specimens to go for other test as prescribed in this standard, however, rejection of
materials cannot be made based on this test. Solution is prepared by adding 10% oxalic
acid (AR grade H2C204.2H,O) chemical in distilled water (dissolve 100 g oxalic acid in
900 ml distilled water). A carefully polished (from coarse 80 or 120 grit to 4/0 emery paper
or finer) and degreased specimen preferably 1 cm2 area is exposed to the solution. The

52
Industrial Corrosion : Evaluation & Mitigation

specimen should be etched at a current density of lA/cm2 for 90s. The current may be
accurately applied by using a battery or rectifier that can deliver desired current density.
The temperature of solution increases with etching cycles that should be restricted below
500C. Fresh solution is preferred for every etching cycle. Post etch structures are categorized
as step , dual, and ditch as shown in Fig 1. These correspond to no grain boundary attack
(only steps are visible); slight or discontinuous grain boundary attack and continuous ditching
of grain boundaries. The material showing step structure is acceptable or free from IGC for
service and does not require testing by other methods . Stainless steels which contain low
carbon or stabilized types are tested after sensitization at 675°C) for about 1 hour.

Ferric Sulfate-50% Sulfuric Acid Test (Streicher Test)


The specimens which show non-acceptable etch structure (from oxalic acid etching)
are subjected to this test. This test is a quantitative measure of the relative performance of
the material based on mass -loss determinations . The 50% sulphuric acid solution may be
prepared by slowly adding -236 ml H2SO4 (98% by wt.) to 400 ml distilled water. 25 g of
Fe2(SO4)3 is added to the-sulphuric acid solution and dissolved by heating. The test specimen
may be prepared by polishing on coarse grit emery papers (such as 80 or 120) followed by
degreasing. Overheating during polishing or grinding should be avoided. The sharp edges
should be removed before subjecting them for tests. Specimen area and weight should be
measured prior to putting them for the test. The solution is boiled in an Erlenmeyer flask
with proper condensing (of vapours) arrangement. Test coupon may be placed in the solution
after boiling starts . The boiling may be continued for 24 to 120h as desired by the customer.
After the completion of the test, remove the specimen from the flask and rinse in water, dry
and clean with acetone . Weigh the specimen and note down the final weight; calculate the
difference between the initial and final weight - The corrosion rates may be determined in
millimetres of penetration per month, as follows:
Corrosion rate (millimeter per month ) _ (7290 x W)/(A x t x d)
Where: t = time of exposure, h, A = area, cm2
W = weight loss, g, and d= density, g/cm3
(For steels, d = 7.9 g/cm3, for chromium-nickel-molybdenum steels , d = 8.00 g/cm3)

Dual

Fig. I: Microstructures after electrolytic oxalic acid

53
Industrial Corrosion : Evaluation & Mitigation

Nitric Acid Test (Huey Test)


Boiling nitric acid is a strongly oxidizing environment to detect the chromium
depleted regions as well as intermetallic precipitations, like sigma phase in the stainless
steels. The state of the specimens should possibly be close to the one being used in service.
It may be polished up to 80 or 120 grit emery paper. The edges evolved during cutting
should be repolished. The overheating of specimen during preparation needs to be prevented.
The degreased and polished specimens are boiled in a 1L Erlenmeyer flask containing 65%
nitric acid with condenser. Volume of the solution for the test should be at least 20ml/cm2.
Specimen shall be placed after boiling starts. After completion of each period, specimens
are cleaned and weighed after drying. The corrosion rate during each boiling period is
calculated from the difference of weight of the specimens before and after the test and by
using a formula described earlier. This test also may be able to indicate the right heat
treatment and sensitisation state of the specimens. Customer can decide and draw a line for
accepting the materials depending on corrosion rate.

Copper-Copper Sulphate 16% Sulphuric Acid Test (Strauss Test)


This procedure is conducted to determine the susceptibility of austenitic stainless
steel to intergranular attack associated with the precipitation of chromium-rich carbides.
The test solution i.e. copper sulfate-16% sulphuric acid solution may be prepared by
dissolving I OOg copper sulphate in distilled water in a 1000 ml flask. Add 100 ml of sulphuric
acid to it and then dilute further with distilled water to 1000 ml. Place the solution in
Erlenmeyer flask containing Allhin condenser. Sufficient quantity of electrolytic grade copper
shots or grindings should be used along with the solution (8 ml/cm2). The galvanic coupling
between the copper shots and test specimen must be assured. The specimen size may be
specified by the customers. Also the possible dimensions of rod, plate or tube are described
in ASTM A262-Practice E. After surface finishing followed by boiling in the Erlenmeyer
flask containing above solution for 24 - 72 h, samples need to be rinsed and cleaned if
copper is deposited on the specimen surface. The specimen is then subjected to bending
through 180° over a mandrel. In case of weld materials, the HAZ shall lies in the centre of
the bend. The bent location shall be examined under low magnification (5-20X) where the
appearance of fissures or cracks indicates the presence of intergranular corrosion attack as
illustrated in Fig 2. For better clarity the same region may be viewed under higher
magnifications. Crack length and depth may be evaluated and recorded.

Fig. 2 : Surface topographical features after the boiling and bend tests
(A) appearance of IGC fissures (B) sample passed during the test

54
Industrial Corrosion : Evaluation & Mitigation

Copper-Copper Sulphate 50% Sulphuric Acid Test (Modified Strauss test)


This procedure is based on the relative weight loss of specimen subjected to boiling
in copper-copper sulfate-50% sulphuric acid test . The solution may be prepared by adding
236 ml sulphuric acid slowly to 400 ml distilled water and then 72 g of copper sulphate in
the Erlenmeyer flask. Place the copper shots/ chips in the flask. Clean and weigh the specimen
before putting them in boiling copper sulfate-50% sulphuric acid solution. After 24-72
hours of boiling, the specimens are removed and cleaned for any oxide or copper deposition
on specimens followed by weighing . Determining the weight-loss and corrosion rate can be
calculated by using formula mentioned above.

Stress Corrosion Cracking (SCC)


SCC is cracking of materials in the presence of tensile stresses ( residual or
operational) in cracking prone environment . The SCC prone environments including
hydrogen can cause material to fail at stresses much below the yield or design stress. Crack
may propagate along the grain boundary, (intergranular stress corrosion cracking) or across
the boundary (transgranular cracking). Significant numbers of test method have been
developed to evaluate the stress corrosion cracking resistance of engineering materials.
The test methods are broadly categorized as constant strain , static loading , and dynamic
loading. Specimens may be smooth , notched or pre-cracked, based on fracture mechanics
principles . Constant-deformation (strain) tests are conducted by using widely known
geometries of the specimen such as C-ring , O-ring, bent-beam and U-bend.19-13] In all the
bent specimens , state of stress is much more complex than in tensile specimen where it is
almost uniform throughout the cross section . The maximum tensile stress zone in the bent
specimen is at convex surface and reduces to zero at neutral axis . This becomes compressive
and maximum at the concave surface and therefore 50% of surface is under tension and rest
under compression. The crack initiation time and propagation rates are observed under
various environmental and metallurgical conditions.

C-Ring Test 1101


The C-ring specimens may be machined from thick tubes, bars, plates in various
sizes , but minimum outer diameter should be above 16 mm due to difficulties in machining.
Tensile stresses are generated at the exterior (on the circumference) of the ring by tightening
of bolt. A few C ring geometries are shown in Fig 3.

Constant strain Constant load

Fig. 3: C-Ring geometries for SCC test

55
Industrial Corrosion : Evaluation & Mitigation

Tensile stresses on the surface applied by the deformation loading are controlled by
restricting the strain with in the elastic range. The stresses on circumferential and transverse
sections can be accurately calculated and controlled using following formula
6C = E / (1- g2) . (EC + J ET) and

(YT = E / (1- g2). (FT + g8C)


where E = Young modulus of elasticity, g= Poisson's ratio, EE = circumferential
strain and ET = transverse strain. The circumferential and transverse strain can be
measured by strain gages or micrometers.

The final diameter or deflection in the C-ring also can be obtained by the formula
given below
ODF=OD-A
Where A = ficD2/4EtZ
ODF = final outside diameter (mm), OD= outside diameter before stressing (mm),.
desired stress (MPa) within the proportion limit (elastic range), A = changes in the OD
to give desired stresses, t = wall thickness (mm) mean diameter D = OD-t, E = elastic
modulus (MPa), Z = a correction factor for curved beams.

The C-ring typically is under constant-strain till the crack initiate, however, by placing
a calibrated spring on the bolt, a constant load can be applied to it. Details for fabricating C
ring is given in ASTM G 3.8.

Similar to the C-ring, bent beams are another kind of geometry in several
configurations such as two points, three point and four point bent beam. Tensile stress on
the convex side is below the elastic limit and may be calculated precisely. h 11

U -bend Test in Boiling Magnesium Chloride Solution [12,131


Relative resistance of alloys to stress corrosion cracking is frequently assessed by
exposing `U' bend specimens in boiling magnesium chloride solution. This method is
specifically useful for all alloys (sufficiently ductile) susceptible to chloride related stress
corrosion cracking and not for chloride-free SCC. The bent area contains large amount of
plastic and elastic stresses, though the stress conditions are not precisely known. This method
may not be suitable when the effect of small stresses on SCC is the main objective but is
rather useful to see the SCC resistance of one alloy in different metallurgical conditions.
The crack initiation time and growth rate is observed during the experiment. A rectangular
strip of sufficient thickness is bent in `U' shape by about 1800 around a predetermined.
radius. Slow straining in single stage generally by using tensile testing machine or in two
stages may be used. The single stage stressing is more accurate and also useful for thick
sections unlike two stage bending. In two stage bending, specimen is stressed to almost U
shape and then released to eliminate the tensile elastic strain. To maintain the stress, the
parallel legs of the U bend are suitably bolted. The details about the U-bend fabrication are
given elsewhere in ASTM G30, a few are illustrated in the Fig 4.

56
Industrial Corrosion : Evaluation & Mitigation

The test environment i.e. magnesium chloride (MgC12.6H20) solution is prepared


such that it boils at -155 .0 ±1.0 °C (311 .0 t 1.8°F). To prepare about 400 ml of the test
solution, weigh 600 g of reagent grade MgC12 .6H20 and add this to Erlenmeyer flask
containing a thermometer along with 15 ml of reagent water. After the solution boils slowly
add water at the top ofthe condenser to reduce the temperature to 155 °C (311 °F). A solution
of25 weight percent magnesium chloride is required for the trap if the test duration exceeds
seven days without a solution change. Stressed specimens may also be tested for stress
corrosion cracking in alternate immersion method.1141

Welded bend

. Fig. 4: Various U- bend geometries

Slow Strain Rate test [15]


The constant strain by an external means is applied on the gage section of the tensile
or precracked specimen. The low extension rate is such that it allows time to corrosion
processes to occur on the surface and fast enough to produce cracking in reasonably short
time. The slow extension rate produces the strain rate in gage section in the range of 101 to
10-7/s. However, the selection of suitable strain rate depends upon the type of alloy and
environment. Too high a strain rate will result in ductile fracture and too low rate may
prevent corrosion by passive film repair and SCC may not occur. This method requires
tensile testing -machine with calibrated load cell, gripping devices for smooth transfer of
applied load to the specimen and fixtures, displacement gages, environment cell or autoclave
for high temperature test. The test specimen preparation shall be in accordance with the
ASTM E8. The dimensional measurement such as gage length and cross section are made
prior to the test. The data from SSR test can be analyzed for time-to-failure ratio, plastic
elongation ratio, % reduction in area. Each of these parameters shall be normalized with
respect to the controlled environment.

Polythionic Acid Cracking


Polythionic acid is found in petroleum refineries and strongly influences the IGSCC
susceptibility of stainless steels. Stainless steels that have undergone sensitization treatments
are frequently tested in the polythionic acid solution, in laboratory, for determining their
susceptibility to IGSCC. Sensitized stainless steels are fabricated in a U-bend as described

57
Industrial Corrosion : Evaluation & Mitigation
earlier and immersed in the polythionic acid. The initiation of cracking and crack growth
rate can be monitored with time of exposure. The polythionic acid is prepared by bubbling
HZS gas through the sulfurous acid (H3SO3). The latter may be produced by bubbling SO2
gas in distilled water, in accordance with the ASTM specification.[161

Hydrogen Induced Cracking (HIC) and Sulfide Stress Cracking (SSC) [171
Hydrogen damage is common failure mode in the pressure vessels and pipe line
steels exposed to wet sour environments such as in petroleum and natural gas industries.
Hydrogen induced cracking occurs in low strength steels (<550 MPa) during wet hydrogen
sulfide (H2S) exposure. While SSC occurs in the high strength and or/high hardness steels
under the influence of external tensile stress and is caused by absorption of hydrogen from
wet H2S corrosion. HIC is due to the internal pressure build up by accumulated hydrogen
(molecular) even in non-stressed specimens. The HIC test method involves exposure of
unstressed steel coupons to either 5% sodium chloride solution (NaCI) + 0.5 % acetic acid
solution (CH3COOH) or an artificial sea water solution. The test solution shall be deaerated
with argon or nitrogen and then saturated with H2S gas. The detailed test method is available
in NACE TM-02-84. It compares the degree of susceptibility to HIC in each section for
different steels. It is represented in terms of crack length ratio (CLR), crack thickness ratio
(CTR) and crack sensitivity ratio (CSR). The CLR is the sum of crack length of each array
divided by the width of the section and multiplied by 100%. The CTR is the sum of the
crack thickness of each crack array divided by the thickness of the section and multiplied
by 100%. The CSR is the sum of the effective cracked area of each crack array divided by
the area of the section and multiplied by 100%. The standard does not specify pass or fail
values. However, some companies used maximum CLR -'15% to qualify the steels for wet
sour line pipe applications.

Concrete Corrosion
Corrosion of concrete rebar is primarily influenced by the various admixtures used
and chloride ingress from the environment or concrete constituents. Concrete rebar can be
tested for corrosion in laboratory as well as in the atmosphere.[18,191 For this, two rebar of
certain sizes are placed in the mould which then is filled with concrete and admixtures
which are being tested for corrosive effects. A control concrete rebar shall also be prepared
from the concrete not containing the admixtures. Concrete beam are prepared as per the
standard ASTM C192/192M. After curing and drying the specimen in a moist room, an
artificial pond is created with one surface of the concrete as the pond base . This ensures
that one of the rebar is wet while the other is relatively dry. This pond is maintained for two
weeks in 3% NaCI solution at 23+/-3°C; the solution volume should be around 400 ml and
depth 40 mm. The solution is then sucked off and the voltage across the 100-ohm resistor
between the rebar is measured. By cyclically ponding with 3% sodium chloride, the chloride
permeates through the concrete and the upper bar begins to corrode, with the bottom bars
acting as cathodes. The current can be measured as I = V/ 100.
Also measure the corrosion potential of bars against reference electrode and monitor
the current every week for some time. Visual observations of the bars on test completion
will reveal percentage of corroded area and may be recorded.

58
Industrial Corrosion Evaluation & Mitigation

ELECTROCHEMICAL METHODOLOGIES

Electrochemical tests methods need a device for measuring and applying accurate
current and potentials (a Potentiostat/ Galvanostat), an electrochemical cell containing
reference electrode (e.g. saturated calomel, silver-silver chloride), a counter electrode (such
as platinum or graphite) and working electrode ( a test specimen) along with experimental
solution. Reference electrode measures the potential of the specimen-solution interface
and the counter electrode facilitate electrochemical current flow. Electrochemical tests for
corrosion resistance evaluation are preferred due to short experimental time, and can provide
real time (time-corrosion) data on a single specimen. With the advent of advanced
instrumentation, these methods became even easier and attractive. Electrochemical methods
are specifically useful for studying the mechanism of corrosion in the different current-
potential region corresponding to various environmental situations. Various electrochemical
techniques are available to evaluate the different forms of corrosion such as general, pitting,
crevice, IGC, galvanic etc. Regardless of the technique, each relies on the same basic
principles; in each test, a metallic coupon in an electrolyte is subjected to the application of
current or potential from an external source (Potentiostat/ Galvanostat). This current/potential
stimulates the surface corrosion reactions. The voltage or current response of the corroding
coupon is recorded and correlated with the current or potential applied. In either case,
the resultant current is representative of the rate determining mass transfer or charge
transfer rate.

Corrosion Rate Determination


For general corrosion where corrosion rate is of concern, polarization resistance,
Tafel extrapolation, and electrochemical impedance methods are employed. [20-231
Tafel Extrapolation
A relationship is obtained between log current density and applied potential. A
perturbation off 250mV is applied with respect to open circuit potential (E,,0) in cathodic
as well as anodic direction and the resulting current is recorded by potentiostat. However,
such a large over potential may be damaging to the surface particularly during anodic
polarization in which a metal surface gets changed due to corrosion/ passivation processes.
The cathodic polarization is therefore more realistic and surface damage is relatively small.
Corrosion current (i^0 ) may be determined by extrapolating the straight linear region from
either cathodic or anodic curve to the open circuit potential as shown in the Fig 5. For
better accuracy the linear region must be minimum an order of magnitude of current.

Linear Polarization Resistance (LPR) X20.211


The Tafel extrapolation method is dependent on activation controlled electrochemical
reactions. For concentration controlled reactions, however there may be deviations from
linearity for large overpotentials. The LPR technique exploits the linearity that appears
within 5 to 10 mV of the corrosion potential as described by the Stern and Geary, shown
schematically in Fig 6. The potential is scanned at a constant rate (0.6V/h) with a short
potential range. The slope of the resultant current versus potential plot gives the polarization
resistance (inverse of corrosion current density).

59
Industrial Corrosion : Evaluation & Mitigation

icorr = Pa Pc /2.3 Rp (1a + Rc)


where icon is current density, {3a and (3c are anodic and cathodic slope , Rp is polarization
resistance . After obtaining the corrosion current density or the polarization resistance values,
a corrosion rate can be calculated by formula given in ASTM G 102.
Corrosion rate = (K x icon x EW)/(D)
Where
Corrosion rate = mm/y
icorr = corrosion current density, µA/cm2
K =3.27x 10-3, mm g/mA cm yr,
EW = equivalent weight (atomic weight of the base alloying element/number of
electrons involved in the oxidation process),
D= Material density, g/ cm3

+ 0.25 -I

0
z

I-- Anodic

w
Ecorr ... .....................
^s

d
0
C,

.-Cathodic

I
- 0.25 -i-
10-6 1o-4 10-2 10

Current density , (µA/cm2)

Fig. S : Tafel extrapolation

60
Industrial Corrosion : Evaluation & Mitigation

Fig. 6: Linear polarization curve

Electrochemical Impedance Spectroscopy (EIS) 1221


This is another method for determining the corrosion rate and widely used as a
research tool to understand the various corrosion mechanisms. It is also known as AC
impedance method. A small amplitude sinusoidal (AC) potential or current is applied to
the working electrode at various frequencies. The resultant waveform will show a sinusoidal
response which is out of phase with the applied potential or current by certain amount and
with current amplitude that is inversely proportional to the impedance of the interphase. A
corroding system is modeled as an equivalent AC circuit containing elements such as solution
resistance, capacitance, inductance and polarization resistance. The values of various
circuitry elements are obtained by curve fitting procedure using commercial computer
software. By doing so and obtaining the polarization resistance value, corrosion rate can be
calculated using formula given above. The detailed procedures are available in ASTM
G 109. [22]

Localized Corrosion Resistance Evaluation


Electrochemical methods are widely used for evaluating localized corrosion
resistance such as pitting and crevice corrosion susceptibility, galvanic corrosion resistance,
passivity, sensitisation and IGC resistance etc. Potentiodynamic, cyclic polarization,
potentiostatic & galvanostatic, and scratch repassivation tests are useful for pitting corrosion
resistance and to know the passivation/ repassivation state of materials. A few of these are
discussed below

61
Industrial Corrosion : Evaluation & Mitigation

Potentiodynamic and Cyclic Polarization 121,241


Specimen in a electrochemical cell is polarized at a constant scan rate (O.6V/h)
towards more anodic direction from the open circuit potential (OCP). Ideally, both anodic
and cathodic scans should be initiated from the open circuit potential. The specimen is
often polarized till certain predetermined potential or current. Such predetermined potential
may be the vertex (peak), reverse (potential from which the scan is reversed) and final
potential /current. The choice depends upon the type of information required for the particular
material-environment combination. For instance, to know the passive behavior (current
and passive zone) and pitting potential, the specimen must be polarized in the transpassive
zone as shown in the Fig 7. The zone which is independent of the variation in potential is
called the passive zone and end point of this zone followed by an increase in the current
with potential is characterized by breakdown of passive film (pitting potential Ep;t). Higher
is the breakdown potential, higher is the pitting resistance of material. The scanning may
be reversed once a predetermined current or potential is arrived at and then continued till
the final potential or till the reverse scan intersects the forward scan (cyclic polarization).
The potential at which the reverse scan meet forward scan is called the repassivation potential,
Eprateet (potential below which active pits repassivate). In other words, repassivation will
occur at more negative potentials even after localized corrosion initiation. Therefore, the
more positive the potential at which the hysteresis loop is completed (or reverse/backward
scan intersect forward scan), the less likely that localized corrosion will propagate. There
are certain drawbacks associated with this method; the value of E,t and Ep,-df"t are sensitive
to potential scan rate and the value of Eprotect vary with the polarizing (vertex) potential in
the transpassive zone. Higher vertex (potential from which scan is reversed) may result
into lower Epr4,tect• The details about conducting this test is given in ASTM G 61.[2 1, 241

Epit

E Pratt'

r.
Lo rrc I

Fig. 7 : Schematic cyclic anodic polarization curve

62
Industrial Corrosion : Evaluation.;& Mitigation

Potentiostatic and Galvanostatic Methods


The sensitivity of scan rate in evaluating the localized corrosion resistance (using
cyclic potentiodynamic) may be overcome by potentiostatic methods. The Epit can be
obtained by polarizing specimen at potentials above and below the, values of Eprot and Epit
determined from the potentiostatic polarization. The initiation of pitting is indicated by the
increase in current with time. By conducting a series of current versus time curves at an
increment o€50 mV, the Epit is identified as lying between two potentials at which current-
potential curve shows deviation from decreasing or constant trend. For Ep,.ot the pits are
intentionally initiated at a potential higher than the Epit and then quickly shifted to below
the Eprotect for current versus-time curve. The repassivation of pits will be indicated by
decrease in current with time (see ASTM F746 and ASTM G 100 for details). [25, 261

Evaluation of Sensitization
Electrochemical techniques such as single and double loop electrochemical
potentiokinetic reactivation (SL-EPR and DL-EPR, respectively) are only available methods
to quantify the sensitization in stainless steels and nickel based alloys. The SL-EPR and
DL-EPR are based on potentiodynamic and cyclic polarization respectively and quantify
sensitization in terms of degree of sensitization (DOS).1271 Both tests are conducted in 0.5
M H2SO4 + 0.01 M KSCN solution at room temperature at a scan rate of 6V/h. In single
loop technique, sample is allowed to stabilize in the solution at an open circuit potential
typically around -400 mV with respect to SCE. After the sample is stabilized, a potential of
+200 mV (w.r.t. SCE) is applied in order to passivate the steel for about 120 seconds.
The potential is then scanned from +200 mV down to the open circuit potential as
shown in Fig 8.
200 mV

EcoR

Log current density

Fig. 8 : Schematic of single loop EPR polarization curve

63
Industrial Corrosion : Evaluation & Mitigation

With decrease in potential, the sensitized grain boundaries will preferentially activate
while the grain matrix remains passivated. The total anodic current or charge (Q) passed,
during decreasing potential (reverse scan), is proportional to the grain boundary area
activated. This is indicative of the degree of sensitization. The normalized charge (Pa) in
units of coulombs/cm2 is calculated using following equation:
Pa = Q/X
where
Q = charge measured on current integration measuring instrument (coulombs).
Q is normalized for both specimen size and grain,
X = AS [5.1 X 1 0-3 eO35G
AS = specimen area (cm2 ), and
G = Grain Size at I OOX (in accordance with test method ASTM E 112).
In a double loop EPR, the specimen is allowed to stabilize at an open circuit potential.
The specimen is then anodically polarized from the OCP (typically --400 mV SCE) up to
the +300 mV (w. r. t. SCE) and scanned back down to the OCP, schematically shown in Fig
9. The peak current during anodic loop (Ia) is compared with the peak current during
backward scan (I,.).

I,. Ia
Log Current

Fig. 9 Schematic representation of Double loop EPR curv

The current on the return scan is assumed due to the reactivation of the chromium
depleted grain boundaries . The ratio of (I,/Ia) x 100 is known as the percentage degree of
sensitization (% DOS).

64
Industrial Corrosion : Evaluation & Mitigation

Galvanic Corrosion
Galvanic corrosion needs a couple consisting two metals or alloys of interest. The
couple should be in electrical contact of each other and connectivity may be checked before
exposing them to desired environment. Electrical contact of the dissimilar metals should be
checked periodically. The connectivity between the dissimilar metals/ alloys can be made
by pressure contact, soldering or brazing, spot welding, bolting etc. The corrosion at the
joint locations would however be inevitable which, in turn, may affect the electrical contact
between the two candidates of the couple. To prevent the corrosion at such joints, coating
may be a useful solution. The couple should not be in electrical contact with the test chamber
or container. The corrosion or corrosion rate of the couple may be evaluated which would
indicate the corrosion ofthe anodic component ofthe couple. The cathodic member, however,
will be protected cathodically. The exposure time for galvanic corrosion test should be of
sufficient length so that the corrosion processes have reached steady state and intermediate
variations in corrosion reaction would not underestimate or overestimate the corrosion
rate. More detail on galvanic corrosion testing in electrolytes is given in ASTM G 711281

Hydrogen Transport, Diffusion, and Permeation


Among the different form of degradations, hydrogen damage such as hydrogen
embrittlement, hydrogen induced cracking, blistering are quite common to cause premature
failures of industrial components. Hydrogen entry into the material can occur during melting,
electroplating, and in service due to corrosion. The degradation due to hydrogen may vary
with composition, microstructure, and stress levels of the material in service. The
concentration of hydrogen traps in the material determines the level or degree to which the
material can suffer. The concentration is a function of diffusion coefficient, which can be
determined experimentally by different methods such as: electrochemical method, sub-
surface micro hardness profiling, nuclear reaction analysis and nanoindentation
measurements. The method that has greater acceptance in determining the diffusion in
materials is the hydrogen permeation technique. This method can help to recognize how
alloy contents and crystal defects affect the diffusion process. In solid solution, hydrogen
at low concentration in the material does not change the mechanical properties, except
during the application of load. As a consequence of loading , dislocations are generated
with the possibility of becoming hydrogen traps (as these tend to migrate towards areas of
high strain field). The transported hydrogen can eventually cause high local pressure thereby
reducing the stress intensity factor and culminating in brittle fracture. For hydrogen
permeation experiments, a two-cell system based on the Devanathan and Stachurski
technique with some modifications is used.
The hydrogen charging of the sample on the left side (cathodic) cell is controlled
potentiostatically or galvanostatically by a DC power source. Electrolyte used in the charging
cell may be 0.1 M H2SO4 (for steel). Poison such as Na2HAsO4.7H2O may be used to
increase the hydrogen entry rate and subsequent permeation. The exit side (anodic cell) is
controlled by potentiostat in different modes such as potentiostatic, galvanostatic,
potentiodynamic etc. The environment in the exit or anodic side, should be such that high
anodic or background current may be minimized (for example 0.1 M NaOH for steels).

6 1;
Industrial Corrosion : Evaluation & Mitigation

Calculations for such as steady state permeation current, diffusion coefficient etc may be
performed as per the ASTM G148 and ISO: 17081. [29,301

ONLINE CORROSION MONITORING


A few corrosion test methods have been automated to portable corrosion probes
such as LPR (linear polarization resistance ), ER (electrical resistance probes which can be
used to monitor the corrosion rates in-situ as described in ASTM G96J311 Such probes are
widely used in the petrochemical industries, cooling water system, refineries etc. The
developments have been made to provide online real-time monitoring techniques and
progress on corrosion damage can now be seen in a very short interval (within minutes).
These developments could reduce the time and efforts to obtain corrosion data. The LPR
probes are based on the linear polarization resistance as also mentioned in the earlier sections.
The electrical resistance probes are based on the principle that the decreasing cross section
thickness will increase the electrical resistance represented as
R = pl/A, where r is resistivity, I is length of conductor,
and A is area of cross section.

REFERENCES:
1. ASTM G I "Practice for Preparing, Cleaning, and Evaluating Corrosion Test
Specimens
2. ASTM B117: Practice for operating Salt Spray (fog) Apparatus
3. ASTM G85 :Practice or Modified salt spray (fog) test
4. ASTMG50-76(2003) Standard Practice for Conducting Atmospheric Corrosion
Tests on Metals
5. ASTM G104: test method for assessing galvanic corrosion caused by the
atmosphere.
6. ASTM: G 48 - 03 Standard test methods for pitting and crevice corrosion resistance
of stainless Steels and related alloys by use of ferric chloride Solution.
7. ASTM G 46 - 94 Examination and evaluation ofpitting corrosion
8. ASTM 262 A-F: Standard practices for Detecting Susceptibility to Intergranular
Attack in Austenitic Stainless Steels
9. ASTM E8: Test method or tension testing of the metallic materials
10. ASTM G38: Making and using C-ring stress corrosion test specimens
11. ASTM G39: Practice for preparation and use of bent beam stress corrosion test
specimen
12. ASTM G30: Making the U bend stress corrosion test specimen
13. ASTMG36: Practice for performing stress corrosion cracking test in a boiling
magnesium chloride solution

66
Industrial Corrosion : Evaluation & Mitigation

14.. ASTMG44: Practice for evaluating stress corrosion cracking resistance of metals
and alloys by alternate immersion in 3.5 % NaCl solution
15. ASTM G129: Standard practice for slow strain rate testing to evaluate the
susceptibility of metallic materials to environmental assisted cracking.
16. ASTM GG35-88 Standard practice for determining the susceptibility of stainless
steels and related nickel-chromium-iron alloys to stress corrosion cracking in
polythionic acid.
17. NACE TM-0284: Evaluation ofpipe line and pressure vessel steels for resistance
to hydrogen induced cracking.
18. ASTM C192/192M `Practice for making and curing concrete test specimens in
the laboratory
19. ASTM GI 09 `Determining the effects of chemical admixtures on the corrosion of
embedded steel reinforcement in concrete exposed to chloride environments.
20. ASTM G 5, "Standard reference test method for making potentiostatic and
potentiodynamic anodic polarization, measurements
21. ASTM G 59, Practice for Conducting Potentiodynamic Polarization Resistance
Measurements.
22. ASTM G 106: Practice for Verification ofAlgorithm and Equipment for
Electrochemical Impedance Measurements.
23. ASTM G102: Practice for Calculation of Corrosion Rates and Related Information
from Electrochemical Measurements.
24. ASTM G 61 describes a procedure for conduction cyclic potentiodynamic pola-
rization measurements to determine relative susceptibility to localized corrosion.
25. ASTM F 746: Test method for Pitting or Crevice Corrosion of Metallic Surgical
Implant Materials
26. ASTM G 100: Method of Conducting Cyclic Galvanostaircase Polarization.
27. ASTM G 108: Standard test method for electrochemicalpotentiokinetic reactivation
(EPR) for detecting sensitization of AISI type 304 and 304L stainless steels.
28. ASTM G 71 [27], Guide for Conducting and Evaluating Galvanic Corrosion Tests
in Electrolytes.
29. ISO 17081:2004 Method of measurement of hydrogen permeation and determi-
nation of hydrogen uptake and transport in metals by an electrochemical technique
30. ASTM 148-97: Evaluation of hydrogen uptake, permeation and transport in metals
by an electrochemical technique.
31. ASTM G96 Practice of online monitoring of corrosion in pant equipment
(electrochemical and electrical resistance methods)

67

You might also like