Indg247 - Electrical Safety For Entertainers
Indg247 - Electrical Safety For Entertainers
Indg247 - Electrical Safety For Entertainers
Executive
Introduction
Who is this leaflet aimed at?
If you are an entertainer who uses electrical equipment for sound, lighting or other
effects, this leaflet is for you. Others who use electrical equipment in the course of
their work, such as wardrobe or scenic artists, may also find this guidance useful. It
sets out basic measures you can take to help control the electrical risks from use of
such equipment.
Entertainers have been injured and even killed from electric shocks while performing
or practising. Make sure your next performance is not your last.
Even a very small electric current flowing through your body can kill you. For example,
50 mA (a 40 W light bulb only takes about 150 mA) can cause pain, paralysis of
chest muscles and, after a few seconds, upset the heartbeat and cause death (see
Figure 1).
The higher the current, the quicker and more dangerous are the effects.
Risks
Faulty, damaged or incorrectly used equipment can injure you. If you damage
electrical equipment, for example a cable, then bare live wires may be exposed.
Apparatus may be wrongly connected so that the outside metal parts become live.
Even equipment which does not have a mains power supply itself can be
dangerous. For example, on some systems audio equipment such as loudspeakers
may have terminals at dangerous voltages.
Electrical equipment that overheats can cause fire (see the advice on this under
‘Extension leads and plugs’ and ‘Ventilation’ later in the leaflet).
Precautions
Ventricular 100 mA
fibrillation,
usually fatal
Respiration is affected, 50 mA
victim dies of
suffocation
Muscles convulse 2 mA
Perception level 1 mA
Use a residual current device (RCD) on the power supply to instruments, audio
equipment and any other equipment which you or your colleagues may handle.
RCDs are relatively inexpensive and widely available from electrical goods retailers.
They should be used because they:
The sockets you use, particularly for audio equipment, should be protected by
RCDs suitable for personal protection. These are commonly referred to as 30 mA
devices, with a disconnection time of no greater than 40 ms. The best place for an
RCD is at the distribution board or at the socket outlet itself (see Figure 2).
You should check with the person responsible for the premises whether the
relevant circuits from the main distribution board are RCD protected. If these are
not already provided, or if the person is unsure about whether this protection is in
place, you can use an RCD-fitted plug or RCD adapter.
Main switchboard
Best place for RCD
To equipment
Remember
Sound equipment
Earth connections
Lack of good earth connections and poorly maintained equipment can cause
electrical safety problems with sound equipment. Any item of equipment which is
mains-powered should either be double-insulated ◘ (see Figure 3) or correctly
fitted with a protective (safety) earth.
If you are in any doubt about the connections of equipment, consult a competent
person. Remember that an audio expert might not be an expert in electrical safety.
When obtaining new equipment, discuss your needs with the supplier. Some
equipment has a facility for disconnecting the ‘signal’ earth from the safety earth
without affecting safety.
Where possible, powering all the sound equipment from the same socket or
distribution panel will go a long way to reducing interference.
Electricity supply
Sometimes it may be necessary to site a mixing desk at some distance from the
power amplifiers, interlinked by multi-core signal cables. Microphones etc may have
their own power supply (not phantom-powered from the mixing desk). If this is not
done, the risk of mains hum will be increased and people may be tempted to
remove the earths from the equipment.
Connections
Amplifier terminals and the wiring and connections to loudspeakers may carry
dangerous voltages. It is essential that wiring with adequate insulation is used, and
that any connectors should be safe for use at the appropriate voltage and current.
The live, neutral and earth wires must be connected correctly (see Figure 4). If they
are not, the apparatus may work but be lethal, perhaps in a way which would not
be detected by a protective device such as a fuse or RCD.
Terminal screw
Earth wire
green/yellow Cartridge fuse
Terminals tightened.
Correctly wired.
Minimum bare wire. Cable cover
(sheath) Put cover back on securely
Correct fuse in use.
One appliance per plug
Note: If the wires are not brown, blue and green/yellow seek
Cable specialist advice: a wrong connection could be very dangerous.
(lead/flex) Make sure all the connections are tight
Only fully extended extension leads are capable of carrying the full current capacity
of the cable without overheating. So fully unwind cable drums or coils to avoid the
risk of fire. Also, do not use multiple adapters plugged into wall sockets, as they
can easily get overloaded.
Ventilation
Make sure your amplifiers are properly ventilated. High-power amplifiers can get
very hot if the ventilation around them is blocked, for example by stacking other
equipment on or near them. This could cause a fire. Most amplifiers are fitted with
thermal protection devices as a precaution against fire and if this protection
operates it will shut the system down (possibly during a performance).
Electrical safety for entertainers Page 5 of 12
Health and Safety
Executive
Fuses
If your equipment is fitted with 13 A (square-pin) plugs, make sure that the correct
fuse is fitted. The rating plate on the equipment or the instruction book will tell you
how much electrical power the equipment needs.
Under no circumstances should you bypass the fuse or replace it by wire, silver
paper, or a nail, all of which are dangerous.
If there is damage to any electrical part or if the equipment causes an RCD to trip, it
should be taken out of service at once and replaced, or repaired by a competent
person.
Typical routine checks for portable apparatus are shown in the checklist at the back
of this leaflet.
Regular electrical tests by a competent person may also be appropriate. These will
detect the faults that cannot be seen at inspection, such as lack of continuous
earth. Electrical testing every month would be reasonable until a suitable interval
can be determined by risk assessment.
Further advice on in-service inspection and testing can be found in the HSE
publication Maintaining portable and transportable electrical equipment (HSG107)1
and an Institution of Engineering and Technology (IET) code of practice.2
One item of equipment can be safely supplied from a safety isolating transformer
which has been manufactured to comply with the British Standard BS EN 61558
(or IEC742). Only one item of equipment should be connected to any one transformer.
Electrical safety for entertainers Page 6 of 12
Health and Safety
Executive
Transformer
If a number of items of equipment are powered from the same transformer, or if the
output of the transformer is connected to long cables (eg across the stage), then
you should use a double-wound isolating transformer, with one side of the
secondary earthed and an RCD (known in America as a ground fault circuit
interruptor) connected into the transformer secondary circuit.
Do not use RCDs designed for UK installations on the output of transformer proving
a 110 V supply as they are not generally designed to operate at such low voltages.
The operating voltage should be marked on the RCD, but if in doubt consult a
competent person.
Do not use two 120 V lamps in series on a 230 V supply unless both of the light
fittings are designed for 230 V operation. It is important that you do not use
standard 230 V plugs on lower-voltage equipment. Accidentally connecting such
equipment to 230 V mains could be dangerous. If in doubt, ask a competent
person which plug you should use.
Lighting
Supports
Unless lighting is specifically intended for use at low level and protected against
inadvertent damage, rig lighting bars and equipment should be out of reach of
performers and the audience.
If cables to lights are run overhead, support them along their length (preferably by a
catenary wire or on truss) unless the cable is the type which has its own strain wire.
Take the strain off the flexible cable of suspended light fittings by supporting them
with support wires or other suitable devices (see Figure 6).
Metal boom
earthed
Double-insulated fittings
marked do not need
to be earthed
Dimmer
Earth metalwork of
dimmer cabinet
If possible, you should take the electrical supply for lighting from sockets which are
protected by a different RCD for that used by the audio equipment. This avoids
problems that may occur with RCDs on lighting circuits. The audio equipment
needs reliable RCD protection.
RCDs may not always be appropriate for lighting circuits. Some types of dimmer
controls have a relatively high electrical leakage which may cause unwanted tripping
when a number of units are fed from one RCD. Other dimmers produce a direct
current which can prevent some types of RCD operating correctly. Some
manufacturers offer RCD protection as an option on the supply side to the dimmer
equipment.
Remember that RCDs should be used for circuits supplying outdoor lighting.
Three-phase supplies
Older lighting installations were typically connected to two or three phases of the
electrical supply, using separate dimmers on different phases to avoid confusion. In
these situations, only a single phase should be connected to any one boom.
Connections
If you have lighting on a bar or boom, connect the individual lights to the boom by
plug and socket. For indoor lighting these can be the ‘old type’ 15 A or 5 A three
(round) pin types which are often used and quite satisfactory for lighting.
Commonly, the industrial type of blue and red connectors are now used for many
lighting circuits, often called Ceeform or Commando plugs. These are available in
ratings from 16 A up to 125 A and can be used outdoors, which the round-pin 15 A
types are not designed for.
These industrial plugs and sockets are manufactured to BS EN 60309 and provide
better protection against damp and rain. They should be used for all new
installations where possible.
The metalwork of individual lights and the bar or boom should be adequately
connected to the protective earth conductor.
Cables
Power cables from the lighting booms to the dimmer cabinet or control cubicle are
often multi-core. You should ensure that such cables are suitably flexible and
protect against abrasion or other mechanical damage.
If there is any risk of the cables getting hot from the lights, they should be of a type
which is sheathed in or protected by heat-resisting material.
■■ Make sure flexible cables are properly secured in a cable grip at the plug or
other termination.
■■ All plugs and sockets should be adequate in terms of voltage and current
ratings and they should be in good condition; the protective earth connection is
particularly important.
■■ Ensure all circuits have their own phase, neutral and protective conductors
which should all be the same size.
Earthing
A dimmer can act as a marshalling point for cables to a lighting boom. All the
exterior metalwork of the dimmer should be adequately earthed. There can
sometimes be separate connections for outgoing earth wires for lights.
Alternatively, you can rely on the earth connection of the outgoing plugs and
sockets. There should be no provision in dimmers for ‘lifting’ (ie disconnecting)
earths.
Special effects
Some lasers, strobes and other high-intensity lighting use high voltages internally so
it is particularly important to ensure they are in good condition and properly earthed
if necessary. Setting up such equipment is a job normally carried out by specialists.
References
1 Maintaining portable and transportable electrical equipment HSG107
(Third edition) HSE Books 2013 www.hse.gov.uk/pubns/books/hsg107.htm
2 IET Code of practice for in-service inspection and testing of electrical equipment
Institution of Engineering and Technology www.theiet.org
Further reading
The health and safety toolbox: How to control risks at work HSG268
HSE Books 2013 www.hse.gov.uk/pubns/books/hsg268.htm
Electrical safety and you: A brief guide Leaflet INDG231(rev1) HSE Books 2012
www.hse.gov.uk/pubns/indg231.htm
Equipment:
2 Mains lead Check for cuts, No inner (coloured brown, blue or green/
splits and crush yellow) insulation visible; no bulges in cable,
damage no kinks or twists or taped up joints
3(b) Equipment Check grommet or No sharp edges on contact with cable. Cable
cable entry clamp still there. clamped securely. No inner insulation visible
Check cable clamp
5 Equipment Check for general No holes (large enough to put a finger in)
housing condition. Check for close to mains cable or switches. No rattles
loose parts inside when you tilt it a quarter of a turn
Further information
For information about health and safety, or to report inconsistencies or inaccuracies
in this guidance, visit www.hse.gov.uk/. You can view HSE guidance online and
order priced publications from the website. HSE priced publications are also
available from bookshops.
This guidance is issued by the Health and Safety Executive. Following the guidance
is not compulsory, unless specifically stated, and you are free to take other action.
But if you do follow the guidance you will normally be doing enough to comply with
the law. Health and safety inspectors seek to secure compliance with the law and
may refer to this guidance.