SIPROTEC 7SA87

Distance protection

www.siemens.com/siprotec

Description
The SIPROTEC 7SA87 distance protection has specifically
been designed for the protection of lines. With its modular
structure, flexibility and the powerful DIGSI 5 engineering
tool, the SIPROTEC 7SA87 device offers future-oriented
system solutions with high investment security and low
operating costs.

Main function Distance Protection

Tripping 1-pole and 3-pole, minimum tripping


time: 9 ms

Inputs and 12 predefined standard variants with 4/4


outputs or 8/8 current/voltage transformers, 5 to
31 binary inputs, 8 to 46 binary outputs Functions
DIGSI 5 permits all functions to be configured and com-
Hardware Flexibly adjustable I/O quantity structure bined as required.
flexibility within the scope of the SIPROTEC 5
modular system • Minimum tripping time: 9 ms
Housing width 1/3 × 19 inch to 2/1 × 19 inch • 6 independent measuring loops (6-system distance
protection)
• Several distance-protection functions can be selected:
Applications
Classic, reactance method (RMD), impedance protec-
• Detection and selective 1-pole and 3-pole tripping of tion for transformers
short circuits in electrical equipment of star networks,
• Directional backup protection and various additional
lines with infeed at one or two ends, parallel lines and
functions
open or closed ring systems of all voltage levels
• Detection of ground faults of any type in isolated or
• Detection of ground faults in isolated or arc- arc-suppression-coil-ground systems using the follow-
suppression-coil-ground power systems in star, ring, ing functions: 3I0>, V0>, fleeting contact, Cos-/SinPhi,
or meshed arrangement harmonic, dir. detection of intermittent ground faults
• Protection data communication over different dis- and admittance
tances and physical media, such as optical fiber, • Ground fault detection using the pulse location
two-wire connections, and communication networks method
• Backup protection for differential protection devices of • Detection of current-transformer saturation for fast
all kind for lines, transformers, generators, motors, tripping with high accuracy
and busbars
• Phasor Measurement Unit (PMU)
Efficient and modular

• Adaptive power-swing blocking, out-of-step protection • Cyber security to NERC CIP and BDWE Whitepaper
requirements
• Arc protection
• Phasor measurement unit (PMU) for synchrophasor
• Automatic frequency relief for load shedding in case
measured values and IEEE C37.118 protocol
of underfrequency, taking account of changed infeed
conditions due to decentralized power generation • Time synchronization using IEEE 1588
• Power protection, configurable as active or reactive • Powerful fault recording (buffer for a max. record time
power protection of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
• Reactive power-undervoltage protection • Auxiliary functions for easy tests and commissioning
(QU protection)
• Flexibly adjustable I/O quantity structure within the
• Detection of current and voltage signals up to the scope of the SIPROTEC 5 modular system
50th harmonic with high accuracy for selected protec-
tion functions (such as thermal overload protection) Benefits
and operational measured values • Compact and cost effective distance protection device
• 3-pole automatic reclosing function • High-performance protection features guarantee
• Control, synchrocheck and switchgear interlocking safety
protection • Data security and transparency throughout the entire
• Graphical logic editor to create powerful automation life cycle of the system save time and reduce costs
functions in the device • Clear and easy-to-use devices and software thanks to
• Single line representation in small or large display user-friendly design

• Integrated electrical Ethernet RJ45 for DIGSI 5 and • Increased quality and reliability of the engineering
IEC 61850 (reporting and GOOSE) process

• Up to 4 optional pluggable communication modules, • High degree of overall safety and security based on
usable for different and redundant protocols thorough implementation
(IEC 61850, IEC 60870-5-103, IEC 60870-5-104, • High-performance communications components
Modbus TCP, DNP3 serial and TCP, PROFINET IO) guarantee safe and effective solutions
• Serial protection data communication via optical fi- • Full compatibility with IEC 61850 Edition 1 and 2
bers, two-wire connections and communication net-
works (IEEE C37.94, and others), including automatic • Future proof system solutions provide high invest-
switchover between ring and chain topology ment security and low operation costs

• Redundancy protocols PRP and HSR

For all products using


security features of
Siemens AG OpenSSL, the
Energy Management Division following shall apply:
Freyeslebenstraße 1 This product includes
91058 Erlangen, Germany software developed
by the OpenSSL
SIPROTEC 7SA87 Profile E7.5.docx Project for use in the
Printed in Germany | © 09.17 Siemens AG OpenSSL Toolkit
(www.openssl.org)
and cryptographic
E-Mail: support.energy@siemens.com software written by
Tel: +49 180 524 70 00 Eric Young
(eay@cryptsoft.com).

You might also like