Intelligent,
compact and efficient
Basic unit with 1 universal input, 1 analog output, Lock for ’parameter setting’ and ’configuration’ by
2 binary inputs / outputs and 3 relay outputs password or digital input
— Optional second universal input with transmitter supply
Spray-water protected front panel IP 65
Filtering, linearization and square-rooting of the — Brilliant LCD display with color interchange (red/green)
input signal
Plug-in module slot
Ramp rate and high and low limitation for set point — For analog and digital inputs/outputs extension or
and output signal RS 485 interface for Modbus or PROFIBUS DP
4 configurable alarms
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Description Programmer
The industrial controller Digitric 100 is a single channel compact Every unit has a configurable programmer which provides a time
controller used for complementing single control loops for auto dependent set point. Up to 10 programs with 15 segments each
mating small and mediumsized processes in control engineer can be stored in the unit.
ing. It is universally applicable and suitable for accomplishing
simple and special control tasks. Controller outputs (adjustable acc. to configuration list)
Proportioning ON/OFF controller, PID characteristic.
Basic version
Heat/off/cool-control, optionally with two switching or one
1 Universal input for the controlled variable. Without having to continuous and one switching output.
modify the hardware, thermocouples, the resistance thermome
ter Pt 100, teletransmitters and standard signals 0/4...20 mA can Motorized valve control for motor driven valves, butterfly
be connected. If nonlinearized temperature transmitters are valves and gate valves.
used, linearization if effected in the controller. Linearization tables Continuous controller, optionally also splitrange output with
for all standard sensors are stored in the device. two continuous positioning signals.
1 analog output (0/4...20 mA) for the actuating signal or other
values, e.g. for setpoint or actual values. Parameter setting
2 binary inputs/outputs. These inputs and outputs can be After entering a password, the user accesses the parameter set
configured by the user. These can thus not only be used option ting level by means of a menu key. At the parameter setting level
ally as controller or alarm outputs but also as inputs for switching parameters for the available functions, such as PID parameters,
over the controller (e.g. manual/automatic). ramp rates for setpoints and control output, alarm setpoints etc.,
can be set.
3 relays for the actuating signal or alarm outputs and for fault
reporting. Configuration
...a rear interface to connect a parameterisation and configu The menu key accesses the passwordprotected configuration
ration PC. This makes the setting work in connection with com level. There the standard functions are selected from a list
missioning easier. provided in the unit. As an alternative to the user keyboard, the
selection can also be made by way of the PC program IBIS-R.
Hardware extension This especially simplifies the setting procedure if several units
2nd universal input with integrated transmitter power sup- are to be set with the same configuration (see Data Sheet
ply (50 mA) for e. g. external setpoint, feed forward or position 626.70 EN).
feedback for motorized valve control.
1 module slot for extending the input and output levels.
2
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
3
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
4
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Analog inputs
5
Signal resolution
≤ 0.01 % for 20 mA 6
+ 7
B
- 8 1
AE4_MA
2
3
Module 4_MV for thermocouples 4
4 inputs 5
10...80 mV, with electronical isolation
6
Signal resolution
7
20.000 for 10...80 mV
8
Input resistance AE2_MA/MV_TR
approx. 5 MΩ
Permissible common-mode voltage
≤ ± 4 V against device ground Module AE4_PT_2L for RTD 2wires
Permissible differential-mode voltage 4 inputs
50 mVss for Pt100 in 2wire circuit
Destruction proof Range
Voltage at one input ± 10 V 0...400 Ω
Voltage between input and ground ± 50 V
Line resistance
Break monitoring 0...125 Ω per line
configurable reaction
Permissible differential mode voltage
Reference junction compensation 100 mVss
configurable, internal or external 0, 20, 50 or 60 °C
Signal resolution
Linearization configurable like AI01 ≤ 0.01 % for 400 Ω
Measuring current
≤ 1.5 mA
5
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
8
AE4_PT-2L *) Connection example: I = binary inputs; O = binary outputs
5 Module BA4_REL
6 4 relays
7 with NO contact for max. 250 V AC, 1 A resistive load
8 Built-in spark-quenching
AE2_PT-3/4L
0.022 µF + 100 Ω
For max. 250 V, max. 1 A at cosϕ = 0.9
Technical data for Pt100 as module AE4_PT_2_L
Contact material AgCdO
Potentiometer R150
0...150 Ω
T
Series resistance
1
0...500 Ω Rel.1
2
Measuring current
< 1.5 mA 3
Rel.2
Potentiometer R1500 4
0...1500 Ω 5
Rel.3
Series resistance 6
0...1500 Ω
7
Measuring current Rel.4
8
< 0.5 mA BA4_REL
6
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
4
3,4 Rx
5 5,6
H 6
RS-232
9,5 V DC
1 NAMUR
7
9,5 V DC
2 NAMUR
U RS-232
RS-485
3
0/5 V
(+) 4
0/24 V
0/5 V
(+) 5
0/24 V
Module PROFIBUS DP/DPV1 (Slave)
0/5 V
(+) 6
0/24 V Module with the full functional capabilities of DIN 19245, parts 1 to 4.
(+) 7
0/5 V Transmission rate up to 1.5 MBaud.
0/24 V
Bus terminating adapter see accessories on page 10
(-) 8
AE4_F
1)
+ 1
RS-485
Analog outputs CPU
- 2
3
Module AA3_MA
4
Triple current output
0/4...20 mA at 750 Ω 5
6 VCC
Signal resolution
≤ 0.02 % for 20 mA 7
7
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Dimensional drawings
91.5
96
8 136
96
145
21 V int (only available if the controller is equiped with the optional universal input AI02)
1
2 24 Vext
BO01 B01...B02
3
Outputs Inputs +24 V
4
BO02
5
2-wire 6 6 6
6 transmitter
7
7
+
7
7
Thermo-
7
8
couple
Pot.
Pt100-
2-wire
Pt100-
3-wire
AI01
8
mA + - 0
9 - 9 9 9 9 9
B B B B
10 10 10 10
10 2-wire
transmitter 11 11 11
11 +
1
11
Thermo-
Pt100- Pt100- Pt100-
couple
Pot. 2-wire 3-wire 4-wire AI02
12 12
mA + - 0
13 - 13 13 13 13 13
14
mA + AO01 AC L N
15 - DC L+ L- PE 16 17 18 19 20 21
Connection diagram
AI01 Universal input 1
AI02 Universal input 2, optional
B01...B02 Binary inputs or outputs, Function configurable
AO01 Analog output 1 (0/4...20 mA)
21 V Feed for 2wire transmitter and/or binary inputs and outputs, optional
B Jumper required (terminal 9/13) only if power feed to transmitter for AI02 from terminal 1, or if AI02 is used for Pt100
or potentiometer input
BO03...BO05 Relay outputs (NO contact) max. 250 V AC/1 A
8
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Ordering information
Catalog No. EUR Deliv. time
Digitric 100 V61611A- 0
Power supply
115-230 V AC 1 375,00 ** Stock
24 V UC 2 425,00 ** fr. 1.1.02
Basic instrument with
1 universal input 0 - Stock
2 universal inputs with integrated transmitter supply 1 65,00 ** 1 wk.
No extension module 0
Extension module Analog Inputs
4fold thermocouple E 220,00 ** 1 wk.
2fold thermocouple or mA with galvanical isolation B 220,00 ** 1 wk.
4fold Pt100 in 2-wire circuit F 164,00 ** 1 wk.
2fold Pt100 in 3-/4-wire circuit G 164,00 ** 1 wk.
4fold frequency input H 205,00 ** 1 wk.
4fold 0/4…20 mA with electrical isolation A 153,00 ** 1 wk.
Extension module Digital Inputs/Outputs
6fold binary inputs/outputs M 159,00 ** 1 wk.
Extension module Analog Outputs
3fold 0/4...20 mA N 169,00 ** 1 wk.
3fold 0/2...10 V P 159,00 ** 1 wk.
4fold relays T 142,00 ** 1 wk.
Extension module Communication
RS 485 for MODBUS RTU U 175,00 ** 1 wk.
RS 232 for MODBUS RTU Y 175,00 ** 1 wk.
PROFIBUS DP/DPV1 Z 285,00 ** 1 wk.
Adjusted control strategy (factory setting, other strategy configurable)
Continuous control 0 -
Time proportioning ON/OFF control 1 15,00 ** 1 wk.
Heat-Off-Cool-Control 2 15,00 ** 1 wk.
Motorised valve control 3 15,00 ** 1 wk.
Alarm station 4 15,00 ** 1 wk.
Customer specified (as separate item V61675A) 5 - 3 wks.
Approvals
Standard (CE) 0 -
DIN 3440 (in preparation) 1 115,00 ** 1 wk.
VdTÜV water level (in preparation) 2 115,00 ** 1 wk.
Design Front
Black, RAL 9005 with grey keys 0 -
Light grey, RAL 9002 with blue-white keys 1 -
Manual
German D -
English E -
French F -
Notes:
The universal controller Digitric 100 can optionally be pre-adjusted for a basic control strategy at the factory (see Ordering information).
This strategy can be changed or extended to any other function by the user.
Control strategy Control output (other Sensor type for process variable Template-Code (selectable
control outputs configurable) (other sensor types and ranges config.) at the controllers faceplate)
Continuous control Control output 4...20 mA 4...20 mA (0...100 %) 100A0
Time proportioning Control output relay 4...20 mA (0...100 %) 20EA0
ON/OFF control 1 Err-high/low alarm
Heat-Off-Cool- 2 control outputs relay 4...20 mA (0...100 %) 300A0
control
Motorised valve 2 control outputs relay for 4...20 mA (0...100 %) 500A0
control boundless motorized valve con-
trol (without position feedback)
Alarm station 1 PV high and 1 PV low alarm 4...20 mA (0...100 %) 100IA0
9
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Ordering information
The extension modul can also be ordered seperately and plugged in later.
Accessories
Part Designation Catalog No. EUR Deliv. time
GSD Device master data file for PROFIBUS DP, disk 62695-3601109 31,00 * 1 wk.
Bus terminating adapter 62619-0346488 41,00 ** 1 wk.
Ordering information
Catalog No. Code EUR Deliv. time
List configuration V61675A- 0 0 0 0 0
Custumer-specific configuration as separate item
(please enclose task definition in clear text)
List configuration
List configuration 4 199,00 * 3 wks.
Adopted from previous order (see Code No. 302) 5 62,00 * 3 wks.
Delivery
Stored in unit (see Code No. 302) 1 -
3.5 inch. disk 2 36,00
by E-Mail 4
Configuration
Entered at position of current order (clear text) 301 -
Adopted from order number and position
of previous order (clear text) 302 -
Documentation on the configuration is in German (1 copy is provided);
other languages on request!
Special features
Catalog No. Code EUR Deliv. time
Accessories
IBIS-R PC program for setting parameter and configuration
(see Data Sheet 62-6.70 EN)
PC cable with adapter for connection to the serial interface TTL interface 62695-0346270 159,00
Spare parts
Analog input AI02 with integrated transmitter power supply 0346866V 65,00
10
Single-loop process controller D100 10/616.11 EN
Versatile single loop controller for all basic control functions
Applications
TC
TC
T T
N
L1
L2
L3
1 2 3
FFC
FC
F
F M
F
4 5 6
Split range
TC Feed forward
FC
Backup control
Setpoint station
TT T P F Manual station
Alarm station
7 8
11