Ozone Demand Effect
Ozone Demand Effect
Paul Overbeck
GDT Corporation
Phoenix, Arizona, USA
ABSTRACT
Mass Transfer Efficiency (MTE) and Ozone Demand are critical factors in
In-Line Contactor system design. The MTE is the percentage of the applied
Ozone that actually goes into solution under a given set of operating
conditions. Ozone Demand is the amount of ozone consumed by oxidizable
material in the water. Both the MTE and Ozone Demand must be taken into
account for prediction of Dissolved Ozone concentration, and hence CT
Value, during In-Line Contacting system design.
Presented in this paper is a computer program that facilitates the design of In-
Line Contactors which utilize side stream ozone injection via High
Efficiency Venturi's and Radial Mixing Nozzles. The predicted transfer
efficiencies are based on extensive empirical test results. The effect of Ozone
Demand on both the MTE and the resulting Dissolved Ozone concentration
are automatically calculated by the program.
Introduction:
The Mass Transfer Efficiency of a side stream injection system that utilizes
high efficiency venturis and mixing nozzles has been studied in detail (2,3).
The data collected has been used to develop a spreadsheet that facilitates in-
line contactor design. The spreadsheet uses empirical Ozone Demand data,
contactor vessel volume and ozone generator output values to calculate the
dissolved ozone residual and CT Value. In addition, the proper venturi
injector(s) is specified, and based on operating cost data the overall cost of
operation is calculated. Table 1 is an example of this spreadsheet.
Figures 1 & 2 depict the thorough mixing of the side stream and main flows in
the test apparatus used in the Mass Transfer Efficiency testing.
Figure 1
Figure 2
Mass Transfer Efficiency is defined as the portion of applied ozone that goes
into solution in the water. The MTE is calculated from the mass of applied
ozone and the mass of ozone in the off gas as follows (2,3):
((O3 Conc. in x Gas Vol. in) - (O3 Conc. out x Gas Vol. out))
MTE = __________________________________________________ x 100
(O3 Con in x Gas Vol. in)
Operating parameters that affect MTE are water temperature, gas/liquid ratio
(Vg/Vl) and contactor pressure (1,2,3). Ozone is more soluble in cold water
than hot water. Low Vg/Vl’s promote high mass transfer efficiency, while high
Vg/Vl’s result in low mass transfer efficiency (2,3). High concentration ozone
generators facilitate low Vg/Vl’s even at high-applied ozone doses. Figure 3
demonstrates the affect of gas/liquid ratio on MTE.
Figure 3
95
90
85
80
Operating Conditions
120 GPM, 3 ft/s, 20 PSI
75
Applied Ozone Dose 2.26-7.04 mg/l
70
Ozone Conc. 27.9-134.2 g/m3
65
Contact Time 30 Seconds
60
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
High contactor operating pressures force more ozone into solution resulting in
increased MTE (1,2,3). Figure 4 demonstrates the affect of contactor pressure
on the MTE.
Figure 4
90
85
80
Vg/Vl 0.069-0.077
Ozone Dose 2.86-9.32 mg/l
75
80 GPM, 2 ft/s, 45 Second Contact Time
Ozone Conc. 39.6-131.0 g/m3
70
0 5 10 15 20 25 30 35 40
Ozone Demand:
Figure 5 demonstrates the ozone demand relative to applied dose for the well
water used in the mass transfer testing (3).
The slope of the ozone demand curve for the well water used in the Mass
Transfer testing was 0.36/1. This value was used in the system design
spreadsheet to correct the Observed MTE back to what the MTE would have
been if there were no demand in the test water.
It must be noted that this Observed MTE is not the same as the mass transfer
efficiency that would be calculated from the mass of dissolved ozone after the
demand has been met, divided by the mass of applied ozone.
Figure 5
The mathematical formula for correction of the No-demand MTE (ND MTE) to
the Observed MTE (Ob MTE) under a given set of operating conditions
follows:
Figure 4 shows that the ozone demand has a relatively greater effect on the
Observed MTE when the No-Demand MTE is low as compared to when it is
high. In addition, it makes sense that if the demand is 100% then all of the
applied ozone will have been consumed, and 100% of nothing will have to be
transferred.
90
Observed Ozone MTE
No-Demand
MTE = 95%
80
No-Demand
MTE = 75%
70
No-Demand
60
MTE = 50%
50
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Ozone Demand Ratio
It must be noted that the Observed MTE is not the same as the mass transfer
efficiency that could be calculated from the mass of dissolved ozone (after the
demand has been met) divided by the mass of applied ozone. Mass transfer
efficiency calculated from the dissolved ozone residual will always be less due
to the ozone demand.
Following are instructions on the use of the “In-line Ozone Contactor with
Side Stream Injection” spreadsheet. Table 1 is an example of the actual
spreadsheet, which can be referred to while working through the instructions.
Operating Parameters Section:
The Main Flow Volume is the total volume of water with which the ozone is to
be contacted. Units are GPM.
The Contactor Operating Pressure is the pressure in the main flow contactor
conduit. Units are PSI.
The Applied Ozone Dose is the dose of ozone required to meet the ozone
residual for the specified CT Value after the ozone demand and mass transfer
efficiency have been met. Units are mg/l. This value is typically determined
empirically by pilot testing.
The Ozone Demand Ratio is the amount of ozone that will be consumed by
the ozone demand of the water. The value to be entered is the ratio of ozone
consumed relative to the applied ozone dose. This value is a ratio, not an
absolute mass of ozone consumed. For example, if 2.0 mg/l of ozone are
applied, and after the demand of the water has been met, the residual is 1.0
mg/l, the demand ratio is 1.0/2.0 or 0.5. This value must be determined
empirically by pilot testing.
Contactor Volume:
Calculations Section:
The spreadsheet calculates the following values from the values entered in the
Operating Parameters section.
Required Ozone Injection Rate:
The Required Ozone Gas Flow is the volume of ozone gas in units of SCFM
that must be injected. This value is calculated from the Required Ozone
Injection Rate and the Ozone Gas Concentration from the ozone generator.
The volumetric Gas/Liquid Ratio (Vg/Vl) calculated from the Required Ozone
Gas Flow and the Main Flow Volume (in units of CFM). The Vg/Vl value is
used along with the Contactor Operating Pressure to determine the Mass
Transfer Efficiency.
Contact Time:
The Contact Time (residence time) is based on the Main Flow Volume and the
Contactor Volume.
CT Value:
In the this section, an appropriate injector(s) will be suggested to meet the side
stream injection requirements dictated by the Required Ozone Gas Flow and
contactor operating pressure conditions. The injector(s) suggestion is for the
minimum required to inject the Required Ozone Gas Flow. The ozone mass
transfer testing documented that the percent side stream has relatively little
affect on the MTE (3). However, it is suggested that the minimum percent side
stream be about 10%.
The Ozone Gas Pressure is the pressure of the ozone gas from the ozone
generator that is available at the suction port of the injector(s). Head losses in
the conduit from the generator to the injector must be taken into account. Units
are gauge pressure, PSIG. Pressures less than one atmosphere absolute are
entered in units of negative gauge pressure. For example, if the Ozone Gas
Pressure were 0.5 atmospheres absolute (or 15” Hg vacuum), the value
entered would be –7.35 PSI ((14.7*0.5)-14.7).
Once a valid Required Suction Per Injector has been displayed, the injector(s)
Model is specified. The Boost Pressure Required (pressure added to the
Contactor Operating Pressure for injector operation), Total Side Stream
volume and Percent Side Stream are calculated.
Pump Requirement:
Operating Costs:
The Total Operating Cost for the side stream injection system is estimated
from the costs for operating the ozone generator and the side stream pumping
requirements.
CONCLUSIONS:
REFERENCES
Key Words