This user manual intended for use with NP200 VER: 010

or newer controllers. Please check your model number.

NP200
PROGRAMMABLE TEMPERATURE CONTROLLER
User Manual
TABLE OF CONTENTS
1. Safety Cautions 4

2. Model Code 7

3. Wiring 7

4. Dimensions 7

5. Input & Output 8


5-1. Input Signal and Measurement Range 8
5-2. Output Type 8
6. Part Name and Functions 9
6-1. Description of LED Display 9
6-2. Front Panel Key Functions 10
6-3. LCD Displays 11

7. Menu Display 16

8. Setting Guideline 20
8-1. Program Menu 20
8-2. Operation Menu 22
8-3. Function Menu (FUNC) 23
8-4. Setup Menu 25
9. Initial Setting Description 27
9-1.Menu Display 27
9-2. Setting Example 28
10. Menu (Group) Setting Description 35
10-1. Program Menu 35
10-2. Operation Menu 46
10-3. Function Menu 53
10-4. Setting Menu 59

11. Specification 64

12. NP200 Communication Map 68

3
1. Safety Cautions
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality.

Danger Danger DANGER indicates an imminently hazardous situation which,


if not avoided, will result in death or serious injury
Warning Warning Warning indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
Caution Caution used without the safety alert symbol indicates a potentially hazardous
Caution
situation, which, if not avoided, may result in minor or moderate injury, property damage.

Danger
Do not touch or contact the input/output terminals, an electric shock may occur.

Warning
1. If there is a possibility of an accident caused by errors or malfunctions of this product,
install external protection circuit to prevent the accident.
2. This product does not contain an electric switch or fuse, so the user needs to install
a separate electric switch or fuse externally. (Fuse rating : 250 V 0.5A)
3. When setting, “Input type selection number” must be selected in the Group Input(G.In) and also
“Output type selection number” must be selected in the Group Output(G.Out) before moving to other group.
If not, data of other group will be changed to the initial stage.
4. To prevent defection or malfunction of this product, supply proper power voltage in accordance with the rating.
5. To prevent electric shock or devise malfunction of this product, do not supply the power until the wiring is completed.
6. Since this product is not designed with explosion-protective structure, do not use it at any place with
flammable or explosive gas.
7. Do not disassemble, modify, revise or repair this product. This may cause malfunction, electric shock or fire.
8. Installation and removal of this product should be done while the power is off. Or it may cause malfunction or electric shock.
9. If the product is used in a manner not specified by the manufacturer, it may cause injuries or property damages.
10. To avoid an electric shock, the controller is intended to be mounted into an enclosed panel during its operation.

Caution
1. The information in this manual is subject to chage without prior notice.
2. Before using the product you have purchased, check to make sure that it is exactly what you ordered.
3. On receipt of goods, please check for any damage or abnormality that have occurred during shipping
4. Envirionmental Conditions : Operating Temperature Range: 0 to 50 °C
Operating and Storage Humidity: 35 to 85% max. RH non-condensing
5. Do not use this product in the presence of TOXIC, CORROSIVE, FLAMMABLE, and OXIDIZING gases.
6. Do not use this product at any place with direct vibration or impact.
7. Do not use this product in the presence of water, oil, medical substances, moisture, dust, salt or iron contents.
(Use at the Pollution Degree 1~2)
8. Do not use organic solvents such as alcohol or benzene for this prodcts.
The bezel should only be cleaned with a soft cloth and neutral PH detergent.
9. Do not use this product at any place with excessive induction lesion, static electricity or magnetic noise.
10. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation
11. Install this product at place no higher than 2,000m in altitude.
12. Attach the bractets(2pcs) on the holes of the panel and tighten with a screwdriver.
Fixing torque is about 14.7 N·cm (1.5 kg·cm)

4
13. In case of water intrusion, the inspection is required to check the possiblity of electric leakage or fire.
14. Use a compensating cable for connecting thermocouples.
15. The lead wire resistance is small for RTD input use and please use the one which has no resistance
difference to 3 wires.
16. To avoid inductive noise to input wires, seperate from the power and output wires.
17. Keep input wires away from output wires, otherwise using shielded wires recommended.
18. Use non-grounded sensor to R.T.D and thermocouple
19. If there is excessive noise from the power supply, using insulating transformer and
noise filter is recommended. The noise filter must be attached to a panel grounded,
and the wire between the filter output side and power supplyterminal must be as short as possible.
20. It is effective to use a twisted cable for power supply against noise
21. If alarm function is not set correctly, alarm output can not be operated at a trouble.
22. When replacing the sensor, please turn OFF the power supply.
23. Use an extra relay when the frequency of operation is rather high. In this case,
SSR output type is recommended.
•Electromagnetic switch : Proportional cycle time is Min. 20 sec
•SSR : Proportional cycle time is Min. 1 sec
•Contact output life : Mechanically Min.10 million times (no load)
Eletrically Min. 100 thousand times (rated load)
•SSR drive pulse voltage, 4 - 20 mA DC are not insulated with internal circuit
24. The instrument has IP65 protection grade. But to guarantee its grade and specification,
make sure to use rubber seals when installing the instrument to panel.
25. Do not connect anything to the unused terminals.
26. After checking polarity of terminal, connect wires at the correct position.
27. When the product is installed to a panel, use a circuit breaker or switch in conformity with IEC847-1 or IEC947-3.
28. Switches and circuit breakers should be installed nearby the products for prompt and convenient operation.
29. In case of using swtiches and circuit breakers, please display instruction message on the panel e.g.
"Power is disconnected by operating switches or circuit breaker."
30. For the continuous and safe use of this product, the periodical maintenance is recommended.
31. Some parts of this product have limited life span, and others are changed by their usage.
32. The warranty period is 1 year and limited to the product including parts properly and in normal manner used.
33. The heater power supply and the instrument power supply should be connected using the same power
supply when using heater break alarm.
34. After the power is on, the preparation time for contact output is required.
In case of use for signals of external interlock circuit, use with a delay relay.
35. After replacing into new products, make sure that all parameter settings are same as the previous products.

5
● NP200 Series Programmable Temperature Controller
Versatility is a key advantage of NP200 Programmable Temperature
Controller. The following features are incorporated into NP200 to
maximize user benefits. NP200 programs 30 patterns with 300
segments (each pattern can have maximum 99 segments). The
high performance CPU allows great accuracy (+/-0.1%) and
sampling time (100ms). Also, NP200 has multiple inputs (19 types),
multiple outputs (3 types), auto-tuning (2 types), time signal (5),
heat & cooling output, level PID calculation and control, and
emergency output functions. Large back-light display clearly
indicates unit monitored, program running, elapsed time,
temperature, and operation mode.
● Key Features & Benefits
The User can set a parameter that activates the desired control output up to 10
(From U1 through U10).
User Output includes:
① Alarm (ALARM 1~4) ② Time signal (TS1~TS5) ③ Inner signal (IS1~IS5)
④ Pattern end (PTEND) ⑤ Program run (RUN) ⑥ Fixed control mode (FIX)
User Output
⑦ Reset mode (RST) ⑧ Hold (HOLD) ⑨ Wait (WAIT)
⑩ Output during the manual control (MAN) ⑪ Output during the ascending segment
⑫ Output during the descending segment ⑬ Output during the soak segment
(Be sure that U10 is assigned to Cooling Operation Output,
if a controller is the Heating/Cooling model)

Heating/Cooling control outputs the PID operational result in two types of signal, that is, for
heating and for cooling. You can choose either PID control or ON/OFF control for the output
Heating/Cooling PID Control of heating side and cooling side. If you set the proportional value(P) of heating side as 〞
0〟 the ON/OFF control is selected for the heating side, while the fixing of the band(Pc) of
In program control cooling side 〞0〟 chooses the ON/OFF control for cooling side. . Moreover, you can choose
one method among heating side output, cooling side output, relay output, voltage pulse
output and current output and apply the controling function with it.

his controller has two types of auto-tuning as STD(standard type) and LOW
Universal Input/Output
(Low PV type is the value 10% lower than the set value)

2 Type of Auto Tuning Mode This controller has two types of auto-tuning as STD(standard type) and LOW
(Standard/Low PV) (Low PV type is the value 10% lower than the set value)

The input range is divided into four levels and differnt PID group is applied to each level.
If you choose Level function, the PID group is automatically selected by Level irrespective of PID
Level PID Operation number or Set Value Number(SVNO). You can apply different PID data to different range to get
an optimum PID value in wide temperatare range.

6
2. Model Code
Model Number Function
NP200-   Programmable Controller (96 X 96 mm)

0 Universal Type
Control Type
1 Heating/Cooling Type

0 None

1 RS422 / 485 (Communication Function)


Option
2 DI 4 Points(External Signal Input)

3 RS422 / 485(Communication Function), DI 4Points

※ DI 1~3 Standard, DI 4~7 Option

3. Wiring

4. Dimensions
[Unit : mm]
● Dimension ● Panel Cutout
Minimum

7
5. Input & Output
5-1. Input Signal and Measurement Range
Input Signal Input Code Range (℃) Accuracy
K *1 K1 -200.0 ~ 1370.0
K *1 K2 -200.0 ~ 1000.0
±0.10 % of FS
J *1 J -200.0 ~ 1200.0
±1digit
E *1 E -200.0 ~ 1000.0
T *1 T -200.0 ~ 400.0
R R 0 ~ 1700
Thermocouple ±0.15 % of FS
B *2 B 0 ~ 1800
±1digit
S S 0 ~ 1700
L *1 L -200.0 ~ 900.0 ±0.1 % of FS ±1digit
N N -200.0 ~ 1300.0 ±0.2 % of FS ±1digit
U *1 U -200.0 ~ 400.0
W W 0 ~ 2300
PlatinelⅡ Platinel2 0.0 ~ 1300.0
JPt100 JPT100 -200.0 ~ 500.0
R.T.D
Pt100 PT100 -200.0 ~ 640.0 ±0.1 % of FS
Direct 1-5V 1/5 V ±1digit
Range of Scalling
Voltage (V) 0 - 10 V 0/10 V SL-L ~ SL-H = -2000 ~ 14000
*When using current input, use a resistor
Direct -10 - 20 mV -10/20 mV
250 Ω 0.1 % on input terminal (between
Voltage (mV) 0 - 100 mV 0/100 mV No.19 and 20) to convert 4~20mV
Direct 4 - 20 mA d.c. 1/5 V**

※ Display Range : -5 % ~ +105 % of Above Range *1 : 0 ℃bellow : ±0.2 % of FS ±1digit


*2 : 0 ~ 400 ℃의 range : ±5 % of FS ±2digit
5-2. Output Type
Output(OUT) OUT1 OUT2
Classification (Heating/ SSR/SCR
Cooling side) Relay Output SSR/SCR(Current Output) U10
(Current Output)
RLY (Relay) ON-OFF Control
Np200 – 0 SSR SSR OutPut
(U 10) (Retransmission)
(Universal) SCR 4 - 20 mA
RLY (Relay) Relay Output
SSR / SSR SSR Output
SCR / SSR 4 - 20 mA (U 10) SSR Output
Relay / SSR Relay Output (Retransmission)
NP200 – 1 SSR / SCR SSR Output
(Heating/
SCR / SCR 4 - 20 mA (U 10) 4 - 20 mA
Cooling)
Relay / SCR Relay Output (Retransmission)
SSR / Relay SSR Output
SCR / Relay 4 - 20 mA Relay Output (Retransmission)
Relay / Relay Relay Output
8
6. Part Name and Functions

LCD Display

LCD Display

6-1. LED Displays


LED Indication Description
① Lamp This display lights during the ascending ramp segment (UP).

② Lamp This display lights during the soak segment (SOAK).

③ Lamp This display lights during the descending ramp segment (DOWN).
This display lights when the User Output (U1~U10) is activated by
④ U1~U10 Lamp
the prescribed parameter.
⑤ PRG Lamp This display lights during the temperature control program running (Program run).

⑥ RST Lamp This display lights when the controller operation has been paused through RESET.

⑦ FIX Lamp This display lights when the controller operation is controlled through FIX .

⑧ HOLD Lamp This display lights when the program has been paused through HOLD.
This display lights when the Control Output (OUT-1) is activated.
⑨ OUT Lamp
If output is variable, the display lights proportionally.
This display lights during the manual control (MAN).
⑩ MAN/AT Lamp If a controller is in AUTO control mode, this display lights when an
auto-tuning (AT) is in-process.

9
지시치(PV)표시기
6-2. Front Panel Key Functions

CAUTION
LCD 화면
- Push the key until you feel pressure.
- Do not push sharp objects (such as pencil) on key. Otherwise, it may cause damage or malfunction.
Key Descriptions
• Used to activate selected Pattern Number.
• Pressing RUN/HOLD key for at least 1 second activates Segment Hold (pausing).
⑪ (RUN/HOLD)*
• Pressing RUN/HOLD key for at least 1 second deactivates
Segment Hold (pausing) and resume operation (RUN).

• Used to input Parameter.


• Used to input Control Mode.
⑫ (SET) • Used to verify and bypass Parameter settings when in the parameter Group Display.
• Pressing SET key for at least 3 seconds switches between
the Operating Display and Menu Display.
지시값(PV)표시기
• Pressing REST key after a program runs will reset the controller
to STOP mode and end all programs.
⑬ (RESET)*
• Pressing REST key after a program runs will reset the controller
LCD 화면 RESET mode and end all FIXs.

• Used to change Operation mode to FIX mode.


⑭ (FIX)*
• Pressing FIX key after a program runs/or in Stop will reset the controller to FIX mode.

• Pressing STEP key after a program runs will pause the running segment
⑮ (STEP)*
and activate next segment.

• Used to change the Operating Display (LCD: Liquid Crystal Display).


⑯ (DISPLAY) • Used to switch menu display (PROG, OPER, FUNC and STUP).
• Used to return back to the previous display.

•Pressing PTN key will change pattern number.


⑰ (PTN UP/DOWN)
•Pressing SHIFT key will change the digit(s) of Set Value.

• Used to change the value of digits when setting parameters.


⑱ (UP/DOWN) • Used to move between parameter groups.
• Pressing UP/DOWN key activates Key Speed.

• This display indicates the Process Value (PV) while a program is running.
• Temperature display range
(Below zero (-) comes in first place of five digit number.)
⑲ PV DISPLAY

* You may push the key for one second or longer.

10
6-3. LCD Displays

● Operating Display
· Operating display consists of five sub-displays.
· Press for display switching.

●Set Value (SV) Display


1) Program Run

① SV : This display indicates the set value that currently is


being monitored and programmed.
②℃ : This display indicates the temperature unit as below
Direct current (d.c. V) : temperature unit of U.UNIT.
Thermocouple or RTD : temperature unit of UNIT.
③ PT : This display indicates the pattern number.
④ SEGNO : This display indicates the running segment (Now SEG) and total number of programmed segments (Total SEG).
⑤ TIME : This display indicates the remaining time of running segment (hr./Min.:**h** or Min./Sec.:**m**).
⑥ REPEAT : This display indicates the number(s) of repeated and total number of repeats (Now Repeat / Total Repeat).
If Total Repeat is Continue or Now Repeat exceeds 99, the display indicates [∞].

2) Fixed Control (FIX)


[Heating model: SV Display at Fix Mode] [Heating/Cooling model, SV Display at Fix Mode]

① SV: This display indicates the set value that currently is being monitored and programmed.
② ℃: This display indicates the temperature unit as below:
Direct current (d.c. V): temperature unit of U.UNIT;
Thermocouple or RTD: temperature unit of UNIT.
③ ? : This display blink "?" when SV is changed by pressing key during the FIX mode.

11
지시값(PV)표시기

3) Reset
LCD 화면

① SV : This display indicates the minimum value


of setting range.
②℃ : This display indicates the current temperature unit.
③ PT : This display indicate the current Pattern
(Use key to change the required pattern type)
④ SEGNO : This display indicate total number of programmed
segments and END.SEG of the current pattern. (END.SEG / Total SEG)
※ Total SEG and END.SEG
•If the latest programmed SEG is larger than ENG.SEG, Total SEG displays END.SEG.
•If END.SEG is same to/or larger than the latest SEG, Total SEG displays the latest programmed SEG.
【Ex. 1】 If 10SEGs are programmed while END.SEG is 8SEG, then Total SEG is 8SEG.
【Ex. 2】 If 5SEGs are programmed while END.SEG is 7SEG, then Total SEG is 5SEG.
【Ex. 3】 If 5SEGs are programmed while END.SEG is OFF, Total SEG is 5SEG.

● Output (OUT) Display


1) Auto Mode, Heating model 2) Auto Mode, Heating/Cooling model

3) Manual Mode, Heating model 4) Manual Mode, Heating/Cooling model

1) OUT : This display indicates the output value of Heating model.


2) HEAT OUT : This display indicates the heating output value of Heating/Cooling model.
COOL OUT : This display indicates the cooling output value of Heating/Cooling model.
3) SV : This display indicates the set value that currently being monitored and programed during PROG or FIX Mode.
This display indicates the minimum value of setting range during RESET mode.
4) PID : This display indicates PID GROUP number that currently being controlled.
5) AUTO/MAN : This display indicates the output mode that currently being monitored. Use key to change
the required output mode during manual (MAN) mode.

12
● Graph Display
1) SV of selected pattern number (on Display-1: setup)
is shown in the graphic image as below.
2) Maximum 9 segments are displayed.
The current segment is indicated in bold-black bar on x-axis.
However, above bold-black bar disappears during the Fixed
Control or Reset Mode.
3) Use key to change the required segment from 1 through 9.
4) P** indicates the pattern number that currently being selected (FIX, RESET) or operated (PROG).
5) S** indicates the segment number that currently being operated. However, S- - presents during the Fixed Control or Reset Mode.
6) 01 indicates the first segment number among others that currently being displayed.
7) indicates the graph that is not currently being displayed( : right, : left, : both).
8) Vertical bar ① indicates END.SEG.

● User Output Display


1) User Output display indicates programmed parameters from 1 through 10.

【Display below means:】


•U1 is Inner Signal 1 • U7 is Alarm 3
•U2 is Inner Signal 2 • U8 is Pattern End Signal
• U3 is Time Signal 1 • U9 is Pattern Up Signal
• U4 is Time Signal 2
• U5 is Alarm 1 • U10 is inactive.
• U6 is Alarm 2

2) The current User Output Number is heightened.


For instance, above display shows Pattern End Signal is being generated and User Output 8 is being activated.

3) Programmable User Output Display parameters are as below:

• OFF : “ ---- ” • Pattern Soak Signal : “SOAK”


• Alarm 1 ~ 4 : “ALM1” ~ “ALM4” • Program Run : “PROG”
• Time Signal 1 ~ 5 : “TS1” ~ “TS5” • Fix Run : “FIX”
• Inner Signal 1 ~ 5 : “IS1” ~ “IS5” • Reset : “RST”
• Pattern End Signal : “END” • Hold : “HOLD”
• Pattern Up Signal : “UP” • Wait : “WAIT”
• Pattern Down Signal : “DOWN”

13
● Auto & Manual Display
1) uto (AUTO) Output 2) Manual (MAN) Output

① AUTO » MAN indicates that the current output mode is AUTO, MAN » AUTO indicates that the current
output mode is MANUAL.
② If AUTO/MAN is locked, this display is inactive .
※ For instance, if current output mode is AUTO and pressing key will change from output mode to MANUAL
and MAN » AUTO will be displayed.

●Power-On Display
1) PV Display 2) SV Display
D1 D2 D3 D4 D5

① Characters shown in D1 ~ D3 indicate NP200 model. ① Characters in top-left indicate NP200 model,
② Character show in D4 indicates temperature controller controller type and additional information.
type (0: Heating; 1: Heating/Cooling) ② Character in bottom indicates Version number.
③ Character show in D5 indicates additional
information of temperature controller
(0: none, 1: Communication,2 : Four Digital Inputs,
3: Communication/Four Digital Inputs)
● Menu Display
1) Menu displayed on LCD screen consists of groups and sub-groups as blow:
Menu Group Sub-group
G.PRG (Program Group) INFORM (Pattern/Segment Information)
PROG (Program) G.FILE (File Group) PT.EDIT (Pattern Edit)
G.QUICK (Quick Menu Group) SEG.EDIT (Segment Edit)
G.AT (Auto-Tuning Group)
G.PID (PID Group)
OPER (Operation) -
G.SV (Set-up Group)
G.CONTROL (Control Group)
G.IS (Inner Signal)
G.ALARM (Alarm Group)
FUNC (Function) -
G.UO (User Output Group)
G.TRANS (Transfer Group)
G.COMM (Communication group)
G.OUT (Output group)
STUP (Set-up) G.IN (Input Group) -
G.LOCK (Locking group)

14
① Pressing key will alter Menu displays.
② Sub-groups are displayed on left. Use key to change the required sub-group ( indicates the selected
Sub-Group Menu). Pressing key will confirm the selected sub-group.
③ For returning back to Menu display, press key.

2) Menu Display Parameters


① This display indicates the Menu name.
② This display indicates the Group name.
③ This display indicates the full name of Menu.
④ Use key to change the required
sub-group.

3) Group Display Parameters


① This display indicates the Menu name
② This display indicates the Group name.
③ This display indicates the Sub-Group .
④ This display indicates the full name of Parameter.
⑤ This display indicates the Parameter name.
⑥ This display indicates the Parameter value.
⑦ Use key to change the Parameter value.
?-display blinks when the Parameter value is changed.

15
7. Menu Display

2) Menu screen

Power ON
QUICK
1) Operation screen

b
SV screen a
3s
c
k AT.M ARW SVNO LEVEL
s SV1 TIME
AT ALPHA
i SV2 END TIME
d PIDSL SV3 DI
OUT screen SV4 PWR.MD
e

GRAPH screen

PLDSL=1 PLDSL=2 PLDSL=3 PLDSL=4


1.P 2.P 3.P 4.P
1.I 2.I 3.I 4.I
1.D 2.D 3.D 4.D
USER OUT screen 1.MR 2.MR 3.M 4.MR
1.Pc 2.Pc 3.Pc 4.Pc
1.Ic 2.Ic 3.Ic 4.Ic
1.Dc 2.Dc 3.Dc 4.Dc
1.DB 2.DB 3.DB 4.DB
1.LVL 2.LVL LVLD
AUTO/MAN

Caution
* 5th operation screen
Prior to the other group settings, “Input Group (G.IN)”, then “Output
would not be displayed
when LOCK A/M=0. Group (G.OUT)” should be set firstly.
If other groups are set before Input group or Output group setting, the
value should be changed according to the Input / Output setting value.

16
●Menu Setting Screen
CAUTIION - Menu setting is recommended after program operation is off.
- It is to prevent setting value changed according to a certain set-up parameter setting.
- Some parameter may not indicated due to its mode & additional specification of controller,
control type selection etc.

PWD PWD PWD PWD

IS.MD AL.MD U1 TRANS PR-S OUT INP ▽/△


U2 TRANS.H BPS O.ACT UNIT PT.NO
IS1 A1TY
IS1H A1DB
U3 TRANS.L PRI HCT * U.UNIT RUN
U4 ADJ.H STP FR-H
*
IS1L AL-1 CCT A/M
U5 ADJ.L DLN FR-L
IS2 A2TY U6 ADR HYS DP-P PROG
IS2H A2DB U7 RP.T HEO SL-H OPER
IS2L AL-2 U8 SL-L FUNC
CEO
U9 RJC
IS3 A3TY OL-H *
U10 FILT PWD.C
IS3H A3DB OL-L * BIAS
IS3L A3-3 P.INIT
B.OUT
IS4 A4TY
IS4H A4DB
IS4L AL-4

IS5
IS5H
IS5L

● When power is ON
The controller starts from the same operating mode as
when the device was OFF. But if the device was in : OPTION
program mode, will follow ST.MD : H/C TYPE시

• AUTO operation MODE : Starts control from HEO set value * : In ON/OFF (OUT=0) control SKIP
• M A N operation M O D E : S t a r t s c o n t ro l f ro m In MAN control, AT GROUP is
H EO s e t va l u e

17
2) menu screen

Power ON

1) Operation screen

3s
1~30
SV screen PT.NO SEG.NO 0~99
3s

SEG.NO=0 SEG.NO=1 SEG.NO=2 SEG.NO=99

WZ 1.PID 2.PID 99.PID


WTM 1.ALM 2.ALM 99.ALM
OUT - screen 1.SV 2.SV 99.SV
REPEAT 1.TM 2.TM 99.TM
1.TS1 2.TS1 99.TS1
TS.MD 1.TS1 ON 2.TS1 ON 99.TS1 ON
ST.SV 1.TS1 OFF 2.TS1 OFF 99.TS1 OFF
ST.MD 1.TS2 2.TS2 99.TS2
GRAPH screen 1.TS2 ON 2.TS2 ON 99.TS2 ON
END.SEG 1.TS2 OFF 2.TS2 OFF 99.TS2 OFF
END.MD 1.TS3 2.TS3 99.TS3
END.TM 1.TS3 ON 2.TS3 ON 99.TS3 ON
END.PT 1.TS3 OFF 2.TS3 OFF 99.TS3 OFF
1.TS4 2.TS4 99.TS4
1.TS4 ON 2.TS4 ON 99.TS4 ON
USER OUT screen
1.TS4 OFF 2.TS4 OFF 99.TS4 OFF
1.TS5 1.TS5 99.TS5
1.TS5 ON 2.TS5 ON 99.TS5 ON
1.TS5 OFF 2.TS5 OFF 99.TS5 OFF

AUTO/MAN screen

* 5th operation screen


would not be displayed
when LOCK A/M=0.

18
USE *
G.PRG
INFORM PT.EDIT SEG.EDIT
G.FIL
G.AT
G.PID
USED/ PT.NO G.SV
TOTAL G.CTRL
Pattern COPY S INSERT
USED/ DELETE G.IS
COPY D
TOTAL G.ALARM
Segment DELETE G.UO
USED *1 F.INIT G.TRANS
Segment
by Pattern G.COMM
PT.n G.OUT
G.IN
G.LOCK

*If you ON USE menu, display will be


changed as below (Group will be
display only ON menu).

● Operation when Power ON


Starts operation from operation mode before Power off. But in program mode,
operation will be followed by ST.MD.

• AUTO operation MODE: Starts from HEO set value *1 PATTERN number selection (1~3)
• MAN op eration MODE: Star ts from HEO set value by Keys with DIRECT ENTRY

19
8. Setting Guidline
8-1. Program Menu(PROG)
CAUTION
Prior to the other group settings, “Input Group (G.IN)”,
then “Output Group (G.OUT)” should be set firstly.
If other groups are set before Input group or Output group setting, the value should
be changed according to the Input / Output setting value.

● Program Group (G.PRG)


Classification Signal Parameter Set-up range Display Condition Default
PT.NO Pattern Number Selector 1 ~ 30 1
Entry
SEG.NO Segment Number Selector 0 ~ 99 0
WZ Wait Zone OFF, 0 ~ 10 % (EUS) OFF
WTM Wait Time OFF, 0.01 ~ 99.59 (TIME) OFF
REPEAT Repeat Set CONTINUE / 1 ~ 99 1
TS.MD Time Signal Mode NONE, ON/OFF1~5, TIME1~5 Always ON/OFF1
ST.SV Start Set Value 0 ~ 100 % (EU) EU (0 %)
SEG. NO = 0

ST.MD Start Mode SSV, PV1, PV2 SSV


END.SEG Pattern End Segment OFF, 1 ~ 99 OFF
END.MD Pattern End Mode RESET, HOLD, FIX, LINK RESET
END.TM End Signal Time OFF, 0.01 ~ 99.59 (TIME) OFF
LINK.PT Link Pattern 1 ~ 30 END.MD = LINK 1
01. PID 01. PID NO. Select 1~4 Always 1
01. ALM 01. ALM NO.Select OFF, 1 ~ 15 Always OFF
01. SV 01. Set Value 0 ~100 % (EU) EU (0 %)
Always
01. TM 01. Segment Time OFF, 0.00 ~ 99.59 (TIME) OFF
01. TS1 Time Signal 1 OFF, ON Always OFF
TS1 ON 01. TS1 on Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS1 OFF 01. TS1 OFF Time 1.TS1 = ON
01. TS2 Time Signal 2 OFF, ON Always OFF
TS2 ON 01. TS2 on Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS2 OFF 01. TS2 OFF Time 1.TS2 = ON
SEG. NO = 1

01. TS3 Time Signal 3 OFF, ON Always OFF


TS3 ON 01. TS3 on Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS3 OFF 01. TS3 OFF Time 1.TS3 = ON
01. TS4 Time Signal 4 OFF, ON Always OFF
TS4 ON 01. TS4 on Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS4 OFF 01. TS4 OFF Time 1.TS4 = ON
01. TS5 Time Signal 5 OFF, ON Always OFF
TS5 ON 01. TS5 on Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS5 OFF 01. TS5 OFF Time 1.TS5 = ON

20
Classification Signal Parameter Set-up range Display Condition Default
SEG. NO
= 2~98
99. PID PID NO. Select 1~4 PID control level=OFF 1
99.ALM ALM NO.Select OFF, 1~15 Always OFF
99. SV Set Value 1 0 ~ 100 % (EU) Always EU (0 %)
99. TM Segment Time 1 OFF, 0.00 ~ 99.59 (TIME) Always OFF
99. TS1 Time Signal 1 OFF, ON Always OFF
TS1 ON TS1 ON Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS1 OFF TS1 OFF Time 99.TS1 = ON
99. TS2 Time Signal 2 OFF, ON Always OFF
SEG. NO = 99

TS2 ON TS2 ON Time TS.MD = Time


00.00 ~ 99.59 (TIME) 00.00
TS2 OFF TS2 OFF Time 99.TS2 = ON
99. TS3 Time Signal 3 OFF, ON Always OFF
TS3 ON TS3 ON Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS3 OFF TS3 OFF Time 99.TS3 = ON
99. TS4 Time Signal 4 OFF, ON Always OFF
TS4 ON TS4 ON Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS4 OFF TS4 OFF Time 99.TS4 = ON
99. TS5 Time Signal 5 OFF, ON Always OFF
TS5 ON TS5 ON Time TS.MD = Time
00.00 ~ 99.59 (TIME) 00.00
TS5 OFF TS5 OFF Time 99.TS5 = ON

●File Group (G.FILE)


Classification Signal Parameter Setting range Display condition Default
Pattern USED / TOTAL (30) 0 / 30
INFORM Segment USED / TOTAL (300) DISPLAY ONLY Always 0 / 300
PT. n Used Segment by Pattern 0/0
COPY. S Copy Source OFF / 1 ~ 30 Always
OFF
COPY. D Copy Destination Pattern COPY. S ≠ OFF
RESULT Result of File – COPY. S = 1 ~ 30 -
DELETE Delete Pattern Number OFF / 1 ~ 30
COPY. D = 1 ~ 30 OFF
Pattern
PT. EDIT
COPY. S = 1 ~ 30
RESULT Result of File CMD – COPY. D = 1 ~ 30 -
DELETE = 1 ~ 30
F.INIT File All Initialize (Program initializing) OFF
NO, YES Always
CONFIRM Really File Init ? ON
PT. NO Pattern Number Select 1 ~ 30 Pattern Always 1
INSERT Insert Segment Number OFF / 1 ~ 99 seg PT.NO = 1 ~ 30 OFF
SEG.
RESULT Result of File CMD - INSERT = 1 ~ 98 -
EDIT
DELETE Delete Segment Number OFF / 1 ~ 99 seg Always OFF
RESULT Result of File CMD – DELETE = 1 ~ 99 -

21
● Quick Menu Group (G.QUICK)
Default
Menu Code Parameter Setting Range Display Condition
Value
USE Quick menu use or not OFF
G.PRG PRG Group use or not
G.FILE FILE Group use or not
G.AT AT Group use or not
G.PID PID Group use or not
G.SV SV Group use or not
G.CTRL CTRL Group use or not
G.QUICK G.IS IS Group use or not OFF / ON Always
ON
G.ALARM ALARM Group use or not
G.UO UO Group use or not
G.TRANS TRANS Group use or not
G.COMM COMM Group use or not
G.OUT OUT Group use or not
G.IN IN Group use or not
G.LOCK LOCK Group use or not

8-2. Operating Menu (OPER)


● Auto tuning Group (G.AT) : Only display when program operation status
Menu Code Parameter Setting Range Display Condition Default
Value
AT. MD Auto Tuning Mode Selection STD, LOW *1 AUTO & PID STD
AT Auto Tuning OFF, ON, Auto (*2) AUTO & PID제어시 OFF
✽1 ; Low : Auto Tuning Starts as -10% of SV ✽2 Auto is displayed when LEVEL=ON in Control Group
● Using of Auto Tuning
- Please do not use Auto Tuning as following controls
- Quick response controller such as flow control and press control
Caution - Controller output should not be ON /OFF even for a short time.
- Controller should not have big load to the control part
- Fluctuation of set value gives bad effect on product quality
● PID Group (G.PID)
Display Default
Menu Code Parameter Setting Range Condition Value
ARW Anti - Reset Wind up AUTO, 50.0 ~ 200.0 % PID Control 50.0
ALPHA Alpha 0 ~ 100 PID Control 50
PIDSL PID Group Select 0 ~ 4 (Set 1 ~ 4 to move to next parameter) PID Control 0
n.P Proportional band 0.1 (H/C Type : 0.0) ~ 999.9 % PID Control 5.0 %
n.I Integral time 240 s
OFF / 1 ~ 6000 s (Sec.) PID Control
n.D Derivative time 60 s
n.MR Manual reset -0.5 ~ 105.0 % (%) I = OFF 50.0%
n.Pc Proportional band of cooling side 0.0 (ON/OFF control) / 0.1 ~ 999.9 % 5.0 %
n.Ic Integral time of cooling side OFF / 1 ~ 6000 s 240 s
HC TYPE
n.Dc Derivative time of cooling side OFF / 1 ~ 6000 s 60 s
n.DB Dead band of Heating-Cooling side -100.0 ~ 50.0 % 3.0 %
n.LVL PID Level n EU (0) ≤ 1.LVL ≤ 2.LVL ≤ EU (100 %) (EU) LEVEL = ON EU (100%)
LVLD Reference DEV OFF / EUS (0 ~ 100 %) (EU) LEVEL = ON EUS (0.5%)
22
● Set Value Group (G.SV)
Display
Menu Code Parameter Setting Range Default Value
Condition
SVNO Set Value NO, Select 1~4 Always 1
SV1 Set Value 1
FIX SV SV2 Set Value 2
EU (0 ~ 100 %) (EU) Always EU (0 %)
SV3 Set Value 3
SV4 Set Value 4

● Control Group (G.CONTROL)


Display
Menu Code Parameter Setting Range Default Value
Condition
LEVEL Level PID OFF, ON PID OFF
TIME Time Unit HH:MM, MM:SS Always HH.MM
END.TM Time Unit HH:MM, MM:SS Always HH.MM
DI Digital Input Enable OFF / ON DI OPTION시 OFF
PWR. MD Power ON Mode HOT, COOL Always COOL

8-3. Function Menu (FUNC)

● Inner Signal Group (G.IS)


Display
Menu Code Parameter Setting Range Default Value
Condition
IS.MD Inner Signal Mode TSV, NSV, PV TSV
Always
IS1 Inner Signal 1 OFF, ON OFF
IS1 IS1H Inner Signal 1 High IS1L + 1digit + EU (100 %) EU (100 %)
IS1 = ON
IS1L Inner Signal 1 Low EU (0 %) ~ IS1H - 1digit EU (0 %)
IS2 Inner Signal 2 OFF, ON Always OFF
IS2 IS2H Inner Signal 2 High IS2L + 1digit + EU (100 %) EU (100 %)
IS2 = ON
IS2L Inner Signal 2 Low EU (0 %) ~ IS2H - 1digit EU (0 %)
IS3 Inner Signal 3 OFF, ON Always OFF
IS3 IS3H Inner Signal 3 High IS3L + 1digit + EU (100 %) EU (100 %)
IS3 = ON
IS3L Inner Signal 3 Low EU (0 %)~ IS3H - 1digit EU (0 %)
IS4 Inner Signal 4 OFF, ON Always OFF
IS4 IS4H Inner Signal 4 High IS4L + 1digit + EU (100 %) EU (100 %)
IS4 = ON
IS4L Inner Signal 4 Low EU (0 %) ~ IS4H - 1digit EU (0 %)
IS5 Inner Signal 5 OFF, ON Always OFF
IS5 IS5H Inner Signal 5 High IS5L + 1digit + EU (100 %) EU (100 %)
IS5 = ON
IS5L Inner Signal 5 Low EU (0 %) ~ IS5H - 1digit EUS (0 %)

23
● Alarm Group (G.ALARM)
Menu Code Parameter Setting Range Display Condition Default Value
Alarm
AL.MD Alarm Mode ALL, FIX & PROG, FIX, PROG Always ALL
Mode
A1TY Alarm 1 Type 1
OFF, 1 ~ 20 2
Alarm A2TY Alarm 2 Type
※ Please refer to Types of Always
Type A3TY Alarm 3 Type 1
Alarm
A4TY Alarm 4 Type 2
A1DB Alarm 1 Dead Band
Alarm
A2DB Alarm 2 Dead Band
Dead band EUS (0 ~ 100 %) AnTY ≠ OFF EUS (0.5 %)
A3DB Alarm 3 Dead Band
Setting
A4DB Alarm 4 Dead Band
AL-1 Alarm 1 Point EU (100 %)
Alarm EU (0 %)
AL-2 Alarm 2 Point EU (0~100 %)
Set value AnTY ≠ OFF
AL-3 Alarm 3 Point EUS (0~100%) EU (100 %)
Setting
AL-4 Alarm 4 Point EU (0 %)

● User Output Group (G.UO)


Display
Menu Code Parameter Setting Range Default Value
Condition
UO1 User Output 1
UO2 User Output 2
•OFF(----)
UO3 User Output 3 •SGAL
UO4 User Output 4 •Alarm (ALM1~ALM4)
UO5 User Output 5 •Time Signal (TS1~TS5)
•Inner Signal (IS1~IS5) Always 0FF
UO6 User Output 6 •PTEND / PROG / FIX /
UO7 User Output 7 RST / HOLD / WAIT / MAN /
UO8 User Output 8 UP / DOWN / SOAK
UO9 User Output 9
UO10 User Output 10

●Retransmission Group (G.TRANS)


Display
Menu Code Parameter Setting Range Default Value
Condition
TRANS Select Retransmission PV, SV, MV, SPS Always 0FF
High Value of T/C,RTD : FR-H
TRANS.H T/C,RTD : FR-H ~ FR-L
Retransmission RET = PV or mV,V : SL-H
mV, V : SL-H ~ SL-L
Low Value of SV T/C,RTD : FR-L
TRANS.L only, RET.H › RET.L (EU)
Retransmission mV,V : SL-L
Adjust High Value of
ADJ.H 95.0 ~ 105.0 % 100.0
Retransmission
Always
Adjust Low Value of
ADJ.L -5.0 ~ 5.0 % 0.0
Retransmission

24
8-4. Setup Menu (STUP)
● Communication Group (G.COMM)
Display Default
Menu Code Parameter Setting Range
Condition Value
PWD Password 0 ~ 9999 PWD.C 0
RS485, RS422 PC-LINK / PC-LK-S
PR-S PC-LINK
Protocol select / MODBUS ASCII / MODBUS RTU
BPS Baud Rate 600 - 38400 9600
PRI Parity NONE / EVEN / ODD NONE
OPT
STP Stop Bit 1, 2 1
DLN Data Length 7, 8 (Except PC-LIN : 8) 8
ADR Address 1 ~ 99 1
RP.T Response Time 0 ~ 10 0

● Output Group (G.OUT) Caution After setting Input group, Output group, please setup other groups.
Menu Code Parameter Setting Range Display Condition Default Value
PWD Password 0~9999 PWD.C 0
Universal : Relay
OUT Output Type Please refer output type Always Heating/Cooling :
SSR/SSR
REVERSE
O.ACT Output Action Universal REVERSE
DIRECT
RLY or SSR Output
RLY : 30 s
HCT Heat cycle Time 1 ~ 1000 s (Except ON/OFF
SSR : 2 s
control)
Heating/Cooling RLY
RLY : 30 s
CCT Cool cycle Time 1 ~ 1000 s or
SSR : 2 S
SSR output
〔Hysteresis
EUS (0 ~ 100 %) ON/OFF control EUS (0.5 %)
HYS (ON / OFF Control)〕
Heating, Cooling, Normal 0.0 ~ 100.0 % Heating/Cooling 0.5 %
Heat Emergency output -5.0 ~ 105.0 %
HEO Always 0.0 %
Preset Out 1, (Heat) Heating/Cooling : 0.0 ~ 105.0 %
Preset Out 2
CEO 0.0 ~ 105.0 % Heating/Cooling 0.0 %
Cool Emergency output
OL-L + 1digit ~ 105. %
OL-H Output Limit High PID 100.0 %
Heating/Cooling: 0.0 ~ 105.0 %
-0.5 % ~ OL-H - 1digit 0.0 %
OL-L Output Limit Low PID
Heating/Cooling: 0.0 ~ 105.0 % HC : 100.0 %

25
●Input Group (G.IN) Caution After setting Input group, Output group, please setup other groups.

Menu Code Parameter Setting Range Display Condition Default Value


PWD Password 0 ~ 9999 PWD.C 0
INP Input Type Please refer to input type and range Always K1
UNIT Input Unit ℃ T/C, RTD ℃
U.UNIT User Unit ℃, %, %RH, Pa, – (No unit) mV, V ℃
FR-H Full Range High Please refer to 1370.0
input type and range Always
FR-L Full Range Low Notice, FR-H › FR-L -200.0℃
DP-P Dot Point Position 0~3 mV, V 1
SL-H Scale Limit High -2000 ~ 14000 Notice, 100.0
SL-H › SL-L mV, V
SL-L Scale Limit Low Decimal point position sets by DP-P 0.0
Thermocouple
RJC RJC ON / OFF ON, OFF ON
input
FILT PV Input Filter OFF, 1 ~ 120 Always OFF
BIAS PV Input Bias EUS (-100 ~ 100 %) Always EUS (0 %)
B.OUT Burn-out Select OFF, UP, DOWN Always UP

● Lock Group (G.LOCK)


Menu Code Parameter Setting Range Display Condition Default Value
PWD Password 0 ~ 9999 PWD.C 0
▽/△ Down Up Key Lock
PT.NO Pattern Number Lock
RUN Run Key Lock
A/M Auto / Man Lock OFF, ON Always OFF
PROG PROG Menu Lock
OPER OPER Menu Lock
FUNC FUNC Menu Lock
PWD.C Password Chage 0 ~ 9999 Always 0
P.INIT Parameter Initialize NO, YES Always NO

※ If you set password to PWD.C (Password Change), PWD parameter will be displayed.

26
9. Initial Setting Description
This instrument is made up of 5 kinds of operation display and 4 kinds menu display . Please refer to LCD display
and Menu display during the set up process.

9-1. Menu Display

Power Input

Operating Display Menu Display

Press key for 3 seconds or longer

●Program Menu Group :


Program Group: Wait Zone,
Number of Repeat(s), Time Signal
Mode, Start Set Value, Segment value
of each Pattern, Time Signal
File Group : Number of Segment(s) of
each Pattern, Pattern Edit, Segment Edit.
Quick Group: Short-cuts

●Operation Menu Group :


Auto Tuning, PID, Fixed Control,
Control Parameters

●Function Menu Group :


Inner Signal, Alarm, User Output,
Transmit Parameters

●Set-up Menu Group :


Input type (G.IN) and Output type
(G.OUT) needs to be set prior to
other group set-up.

27
9-2. Setting Example

● Input sensor set up


1) K type thermocouple so range is -200.0 ~ 1370 C'.
2) Set-UP group: STUP (Setup menu), G.IN (Input group)
3) Same as default set value so no chagne.

After wiring, power on and operation screen will be display.


If press “Set” key 3 sec, Operating display – Menu display will be screen alternately.

•Menu screen  Push key  STUP  Push key and go G.IN.


 Push key  INP  select K1 type by key.
Select sensor type
• If you want to change input type to PT100Ω, push ▲▼ key and select INP = PT100 and
push SET key. (Each time you push SET key to move the next parameter)
Select input unit • Input Unit select = ˚C
Setup Full Range High • Full Range High FR-H = 1370.0 ˚C
Setup Full Range Low • Full Range LOW FR-L = -200.0 ˚C
Select Cold Junction
• RJC = ON
Compensation (RJC)
Setup PV Input Filter • PV Input Filter = OFF
Setup PV Input Bias • PV Input Bias = 0.0 ˚C
Select Burn Out • Burn Out Select = UP
[Caution] Incorrect setting may cause of overheating or other problems.

● Select Output Type to SSR


1) Use SSR output for heating control output.
2) Setting group: STUP  G.OUT
3) Set as like below

• Menu screen  Push key  STUP  Push key and go G.OUT.


 Push key  OUT  select OUT=RLY by key
Control output type selection
• Push key and select SSR among RLY (PID), SCR(4-20mA),
SSR and ON/OFF(Relay). Push key to select it.
Select Output Action • Output Action O.ACT = REVERSE
Heat Cycle Time • HEAT Cycle Time HCT = 2 Second
Heat Emergency Output • Heat Emergency Output HEO = 0.0%
Output Limit High • Output Limit High OL-H = 100.0%
Output Limit Low • Output Limit Low OL-L = 0.0%

28
● Program
Push SET key at least 3 seconds from Operating Display.
Program from PROG menu  G. PRG.

1) Programming is to the Figure below.


2) Wait Zone: 3.0 ℃, Wait Time: 30Mins.

200.0

100.0

0.0
1H 1H 30M 1H
1SEG 2SEG 3SEG
TS1 ON OFF
TS2 OFF ON OFF
TS3 OFF ON
TS4 OFF ON OFF
TS5 OFF ON OFF

• Menu Display  Push key : OPERFUCNSTUP PROG display sequentially


Select Pattern number • PROG  Push key and go G.PRG  Push SET key
 Select Pattern Number PT.NO = 1. Push SET key to select it.
• Segment Number SEGNO = 0 display. It means 0 segment.
Select Segment number
Push key to select it
• Wait Zone WZ = OFF display. Set WZ=3.0˚C ? by key.
Set Wait Zone
Push key to select it
• Wait Time WTM =OFF display. Set WTM=00h 30m ? by and key.
Set Wait Time
Push key to select it
Set Repeat • Repeat Set REPEAT= 1 display. Push key to select it
• Time Signal Mode TS.MD=ON/OFF 1 display. Set TS.MD=TIME 5 ? by key.
Set Time Signal Mode
Push key to select it
• Start Set Value ST.SV=-200.0’C display. Set ST.SV=50.0’C ?
Set Start Set Value by and key.
Push key to select it
Set Start Mode • Start Mode ST.MD=SSV display. Push key to select it
Set Pattern End Segment • Pattern End Segment END.SEG=OFF display. Push key to select it
•Pattern End Mode END .MD = RESET display. Set END.MD=HOLD ? by key.
Set Pattern End Mode
Push key to select it
•End Signal Time END.TM = OFF display. Push key to select it
Set End Signal Time * Segment Number Seg.NO=0 display.
Setting finish and set segment parameter Seg.NO = 1~3

29
3) PT NO = 1 / SEG NO = 0
Code Parameter SV Display condition
PT NO Pattern No. 1
SEG NO Segment No. 0
WZ Wait Zone 3.0
WTZ Wait Time 00h 30m
REPEAT Repeat 1
TS.MD Time Signal Mode TIME5 Always
ST.SV Start Set Value 50.0
ST.MD Start Mode SSV
END.SEG Pattern End Segment OFF
END.MD Pattern End Mode HOLD
END.TM End Signal Time OFF

4) SEG NO = 1 ~ 3
Segment 1 Segment 2 Segment 3
Code Parameter Display Condition
Set Value Set Value Set Value
PT NO Pattern Number 1 1 1
Always
SEG NO Segment Number 1 2 3
PID control
01.PID PID Group Number 1 1 1
LEVEL = OFF
01.ALM Alarm Number 01 : 0001 01 : 0001 01 : 0001
01.SV temperature setting value 200.0 200.0 50.0 Always
01.TM Segment Time 01h 00m 01h 30m 01h 00m
TS1 Time Signal-1 ON OFF OFF Always
TS1.ON Time Signal-1 ON-Time 00h 00m TS.MD = Time
TS1.OFF Time Signal-1 OFF-Time 01h 00m 1.TS1 = ON
TS2 Time Signal-2 OFF ON OFF Always
TS2.ON Time Signal-2 ON-Time 00h 00m
TS.MD = Time
TS2.OFF Time Signal-2 OFF-Time 01h 30m
TS3 Time Signal-3 OFF OFF ON Always
TS3 ON Time Signal-3 ON-Time 00h 00m TS.MD = Time
TS3 OFF Time Signal-3 OFF-Time 01h 00m 1.TS3 = ON
TS4 Time Signal-4 ON ON OFF Always
TS4 ON Time Signal-4 ON-Time 00h 30m 00h 00m TS.MD = Time
TS4 OFF Time Signal-4 OFF-Time 01h 00m 01h 30m 1.TS4 = ON
TS5 Time Signal-5 OFF ON ON Always
TS5 ON Time Signal-5 ON-Time 01h 00m 00h 00m TS.MD = Time
TS5 OFF Time Signal-5 ON-Time 01h 30m 00h 30m 1.TS5 = ON

30
● G.ALARM
◼ ALARM 1 is set to the High Limit Alarm.
1) If PV is 250.0 ℃ or above, the Alarm is ON.
2) If PV is 230.0 ℃ or below, the Alarm is OFF.

300
250
200
150
100
50
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5
OFF ON OFF

◼ There are four alarm outputs for alarm temperature settings. Set the alarm mode, alarm type, alarm
deadband, temperature alarm settings.
Alarm operation is activated in ALL, FIX & PROG, FIX, PROG according to the parameter of AL.MD in G.ALARM.
Even if each parameter of G.ALARM is set in the program control, alarm selected by alarm parameter(xx.ALM)
in each segment of each pattern is activated.
Ex) in case all alarm number 1, 2, 3, 4 set, the alarm number 1 is only activated if the alarm parameter(01.ALM) is
set with 1 in the segment number 1 of pattern number 1.

•Push Key at least 3 seconds from Operation display > PROG > Push key > FUNC >
Alarm Model Setting Push ▲▼ key and go G.ALARM. > Push key > AL.MD=ALL.
• Push ▲▼ key and select amount ALL, FIX&PROG, FIX or PROG. Push key to select it
Alarm 1 Type Setting • Alarm 1 type A1TY= 1 display. Push key to select it
• Alarm 1 Dead Band A1DB = 7.9˚C display.
Alarm 1 Dead Band Setting
Push ▲▼ key and set IS2H=20.0’C ?. Push key to select it
• Alarm 1 Dead Band A1DB = 7.9˚C display. Push ▲▼ key and set IS2H=20.0˚C ?.
Alarm 1 Temperature Setting
Push key to select it
Alarm 2 Type Setting • Alarm 2 Type A2TY=2 display. Push ▲▼ key and set A2TY=3 ?. Push key to select it
• Alarm 2 Dead Band A2DB=7.9˚C display. Push ▲▼ key and set A2DB=5.0˚C ?.
Alarm 2 Dead Band Setting
Push key to select it
• Alarm 2 Point AL-2=-200.0’C display. Push ▲▼ key and set AL-2=10.0’C ?.
Alarm 2 Temperature Setting
Push key to select it
Alarm 3 Setting • No setting
Alarm 4 Setting • No setting

31
◼ ALARM 2 is set to the High Limit Deviation Alarm.
1) If DEV (Deviation set value)is 10.0 ℃ or above, the Alarm is ON.
2) If DEV is 5.0 ℃ or below, the Alarm is OFF.
3) DEV = PV –SV

30
20
10
0
-10 0 1 2 3 4 5 6 7
-20
-30
-40
-50
-60

ALM1 OFF ON OFF

◼ Setting Group : G.ALARM

Setting is to the Table below.


Alarm Code Default Value Setting Range Default Value
ALL, FIX & PROG,
Alarm Mode AL.MD ALL ALL
FIX, PROG
A1TY 1 OFF, 1 ~ 20 1
A1DB 20.0 ℃ EUS 0 ~100 % 7.9
ALM1
PV : EU (-100 ~ 100 %)
AL-1 250.0 ℃ 1370.0
PV : EUS (-100 ~ 100 %)
A2TY 3 OFF, 1 ~ 20 2
A2DB 5.0 ℃ EUS 0 ~100 % 7.9
ALM2
PV : EU (-100 ~ 100 %)
AL-2 10.0 ℃ -200.0
PV : EUS (-100 ~ 100 %)
A3TY 1
ALM3 A3DB 7.9
AL-3 1370.0
A4TY 2
ALM4 A4DB 7.9
AL-4 -200.0

32
● Inner Signal
IS (Inner Signal) setting is to the Figure below.
1) IS1 Zone is set to 0.0 ~ 100.0 ℃.
2) IS2 Zone is set to 150.0 ~ 250.0 ℃.
3) Inner Signal is active when NSV (current value of the SV) is inside of IS Zone.

(℃)
250.0
200.0 IS2 Zone
150.0
100.0
50.0 IS1 Zone
0.0 T

IS1 ON OFF ON

IS2 OFF ON OFF

IS3
IS4
IS5

Setting is to the Table below.

•Push key  FUCN  Push ▲▼ key and go G.IS  Push key  IS.MD=TSV
Inner Signal Mode Setting
• Push ▲▼ key and set IS.MD=NSV. Push key to select it
Inner Signal 1 Setting • Inner Signal 1 IS1=OFF. Push ▲▼ key and set IS1=ON ?. Push key to select it
• Inner Signal 1High IS1H=1370.0 ˚c display. Push ▲▼ key and set IS1H = 100.0˚C ?.
Inner Signal 1 High Limit Setting
Push key to select it
• Inner Signal 1 Low IS1L=-200.0˚C display. Push ▲▼ key and set IS1L = 000.˚C ?.
Inner Signal 1 Low Limit Setting
Push key to select it (0.0’C setting)
Inner Signal 2 Setting • Inner Signal 2 IS2=OFF. Push ▲▼ key and IS2=ON ?. Push SET key to select it
• Inner Signal 2High IS2H=1370.0 ˚c display. Push ▲▼ key and set IS2H = 250.0˚C ?.
Inner Signal 2 High Limit Setting
Push key to select it
• Inner Signal 2 Low IS2L=-200.0˚C display. Push ▲▼ key and set IS2L = 150.0˚C ?.
Inner Signal 2 Low Limit Setting
Push key to select it (0.0’C setting)
Inner Signal 3 • Inner Signal 3 IS3=OFF display
Inner Signal 4 • Inner Signal 4 IS4=OFF display
Inner Signal 5 • Inner Signal 5 IS5=OFF display

33
● User Output
9 out of 10 User Outputs are to set as below :
1) UO1~UO5 = TS1~TS5
2) UO6~UO7 = ALM1~ALM2
3) UO8~UO9 = IS1~IS2
4) UO10 is inactive.
Operation display  Push key at least 3 seconds  PROG  Push key  FUNC
 Push ▲▼ key and go G.UO  Push key  User Output 1 display U01 = -- (Default value).
Push ▲▼ key and U01=TS1? Push SET key to select it. Set U02~U09 as same ways.

Set as below
Code Parameter Selection Output Selectable output
UO 1 Use output-1 Time Signal Output-1 (TS1) 1) Alarm Output (1~4 contacts)
UO 2 Use output-2 Time Signal Output-2(TS2) 2) Time Signal Output (1~5 contacts)
UO 3 Use output-3 Time Signal Output-3(TS3) 3) Inner Signal Output (1~5 contacts)
4) Pattern End Output (PTEND)
UO 4 Use output-4 Time Signal Output-4(TS4) 5) Program Run Output (PROG)
UO 5 Use output-5 Time Signal Output-5(TS5) 6) Fixed Control Output (FIX)
7) Reset Output (RST)
UO 6 Use output-6 Alarm Output-1 (ALM1) 8) Hold Output (HOLD)
UO 7 Use output-7 Alarm Output-2(ALM2) 9) Wait Output (WAIT)
10) Manual Output (MAN)
UO 8 Use output-8 Inner Signal Output-1 (IS1) 11) Pattern Up Output (UP)
UO 9 Use output-9 Inner Signal Output-2(IS2) 12) Pattern Down Output (Down)
UO 10 Use output-10 No use 13) Pattern Soak Output (SOAK)

Total 10 user output (U1~U10). When heating/ Cooling type and In case of cooling output is relay, U10 is not available.
Regardless U10, cooling output will be applied. Use output cannot be repeated as same content. The SGAL Input is
activated when one of the four alarms is turned ON, if U5 ~ U10 is set to output SGAL.

● AT : Auto Tuning
For the best result, this Setting Example postulates PT NO=1 and SEG NO=2.

1) Activate the Operating Display.


(Pressing SET key for three seconds will change from Menu Display to Operating Display).
2) Activate RESET and then use PTN key to select PT NO-1.
(Pressing RST key for one second will activate RESET)
3) Pressing RUN/HOLD key for one second will initiate programming.
4) Press STEP key for one second to select SEG NO-2
5) Start AT (Auto-Tuning) process. There are two ways to turn ON AT.
Push SET+UP keys together at least 3 seconds in the operating display.
Method-1 AT lame will be blinked and after Auto Tuning AT lamp will be off.
NP200 operate with Auto Turning values.

To turn off Auto Turning during Auto Turning,


Method-2
Push SET+UP keys together at least 3 seconds or off AT from G.AT.

34
10. Menu (Group) Setting Description
10. Program Menu (PROG)

◼ Program Group (G.PRG)


● Pattern Number Select
• NP200 can program 30 patterns and 300 segments.
• NP200 stores a maximum of 300 segments in 10 patterns (maximum 99 segments per pattern).
• Each pattern consists of 99 segments and 0 (SEG=0).

● Segment Number Select


1) Segment (SEG) =0
The pattern of Segment (SEG)=0 is to set:
Start condition (SSV, STC): SSV → Start set Value, STC → Start code
End condition (END.SEG, END.MOD, END.TM, and LINK.PT)
WAIT condition (WTM, WZ)
Time Signal Mode (TS.MD : TIME SIGNAL MODE)
Number of Repeat (REPEAT)

2) Segment (SEG) =1~99


The pattern of Segment (SEG)=1~99 is to set.
Operating PID Group Number (PIDNO), Set Value (SV), Time (TM), Time Signal (TS, TS.ON, and TS.OFF)

● Wait Zone (WZ) Setting


WZ (Wait Zone) : This sets the deviation range of the PV from the SV.

● Wait Zone Time Setting


If PV fails to enter into WZ, the Wait function will infinitely repeat. To avoid this problem, WTM (Wait Time)
needs to be set. The wait function delays the start of the next program segment until the PV reaches
within a specified deviation range from the SP, or until the Wait Time has expired.
It is not guaranteed that there is no deviation between SV and PV before starting the next program
segment. The wait function will be enabled to prevent problems caused by large deviation.
The wait function can be applicable to all program segments.
WAIT ZONE (WZ) sets the deviation value used for the wait function (If WTM=OFF, Wait Time is infinite.)
When set, a running program will not move to the next segment until the PV enters into the WZ.
When OFF, the wait function will not be enabled –a running program will move to the next segment even
the PV fails to enter into the WZ.

35
【Ex.1】 WZ=5 ℃, WTM=1Hr. 【Ex.2】 WZ=10 ℃, WTM=30Min.
During the Soak Segment(2SEG), SV is 90 During the Soak Segment(2SEG), SV is 90 ℃.
℃. Thus, the deviation range is between Thus, the deviation range is between 80 to
85 to 95 ℃. If PV reaches within a 100 ℃. If PV reaches within a specified WZ
specified WZ (wait zone) earlier than WTM (wait zone) later than WTM (30M), the Wait
(1H), the Wait Function is disabled and the Function will delay 30 minutes before starting
running program will move to the next the next program segment.
segment.

【Ex.3】 WZ=OFF, WTM=1Hr.


When WZ is OFF, the Wait Function is disabled.

【Ex.4】 WZ = 10℃, WTM = OFF


When WTM is OFF, the Wait Time is infinite until the PV reaches within a specified WZ (Wait Zone).

● Repeat Set

• Repeat is to set the repeat parameter.


• Repeat set range is either1~99 or infinite (Repeat=1 means no repeat because it is single time operation).

● Time Signal Mode (TS.MD)


① Time Signal Mode is divided into two types. One is ON/FF setting mode
(ON/OFF1, ON/OFF2, ON/OFF3, ON/OFF4, ON/OFF5) and another one is Time setting mode
(Time1, Time2, Time3, Time4, Time5). Time signal output is max 5.
② ON/OFF setting mode: Setting ON or OFF time for Time Signal Output from corresponding segment
③ Time setting mode: Setting ON and OFF time separately for Time Signal Output from corresponding segment
④ Also, when segment number “0” (SEG.NO = 0 from G.PRG, if you set Time Signal Mode (TS.MD)
“ON/OFF2” or “Time3”, Time Signal number will be limited to 2 or 3.

36
3) Example: Time Signal Mode: ON/OFF
【Ex.】In the case Time Signal (TS) is established as below:

Segment 1 2 3 4 5
TS1 ON OFF OFF OFF OFF
TS2 OFF OFF OFF ON ON
TS3 ON OFF OFF ON OFF
TS4 ON ON ON ON ON
TS5 OFF OFF OFF OFF OFF


Time Signal 1 (TS1) : Time Signal is activated (ON) at the beginning of the Segment-1 and deactivated (OFF) at the end of Segment-1.
Time Signal 2 (TS2) : Time Signal is activated (ON) at the beginning of the Segment-4 and continued until the end of the Segment-5.
Time Signal 3 (TS3) : Time Signal is active (ON) during the Segment-1 and Segment-4.
Time Signal 4 (TS4) : Time Signal is active from 1 through 5.
Time Signal 5 (TS5) : Time Signal is inactive. TS is not used.

Operation example when Time Signal Mode is selected to Time.


【Ex.】In the case Time Signal (TS) is established as below :

1SEG 2SEG 3SEG 4SEG 5SEG SEGMENT


300 ℃

200 ℃

100 ℃

Time
1H 1 H 30M 1H 2H 1 H 30 M Time(TM)

TS1
Time Signal

TS2
TS3
TS4
TS5

※ As shown in figure above, ON TM of Time Signal-1 (TS1) is 0. Thus, TS is activated (ON)


at the beginning of the Segment-1 and deactivated after 1 hour of OFF TM
(which is same to Segment Time) at the end of the Segment-1.
Again, Time Signal is activated (ON) after 30 minutes and deactivated (OFF) after 1 hour 30 minutes.
OFF TM is the actual output time.
The length of OFF TM is longer than 1 hour so that the output continues to the next segment.
※ Time Signal-2 (TS2) is activated (ON) at the beginning of the Segmen-3 and deactivated (OFF)
after 30 minutes. Again, Time Signal is activated (ON) after 1 hour from the beginning of the Segment-5.
Regardless of OFF TM length, TS will finish (OFF) when the program ends.

37
※ Time Signal-3 (TS3) is activated (ON) at the beginning of the Segmen-1 and deactivated (OFF)
after 30 minutes. No more segments exist so that TS is inactive (OFF) thereafter.
※ Time Signal-4 (TS4) is activated (ON) after 30 minutes from the beginning of the Segment-3, and deactivated
(OFF) after 4 hours. The length of OFF TM is longer than 1 hour so that the output continues to the next segment.
※ Time Signal 5 (TS5) is inactive (OFF). TS is not used.

● Start Set Value

•The starting conditions of each Start Mode Program Start Behavior


program vary depending on SSV Start from start setting value
Start Mode. PV1 Start from process value and pattern priority
PV2 Start from process value and time priority

1) Start Mode (ST.MD)=SSV: Start at SV


•In SSV mode, the program will begin with at a specified
temperature (Start Set Value) regardless of PV.
•And the program will ramp to the SV1 over the time
designated in Time Segment-1(TM1).

2) Start Mode (ST.MD)= PV1: Start at PV (Pattern)

•PV1 mode, the program will start at the PV but it is related to SSV, PV, Soak and n, TM.
(Refer to the Figures below for additional information.)
•If PV is lower than SSV, the program will start at the SSV.
•Soak Segment is present in the program: If PV is higher than Soak SV, the program will start at the Soak Segment.
•Pattern is reversed during the program running: If PV is higher than SV, the program will start at corresponding segment.
•Program starts at the middle of pattern: Time designated in corresponding segment is ignored.

① First Soak at Segment-2:


•If PV is in a ~ c : Segment-1 is ignored and the program will start
at the beginning of the first soak (segment-2).
•If PV is in d : The program will start at the Segment-1
(D: PV=SV). In this case, the time designated from
E to D in Segment-1 is ignored, and the program
will run for the time designated from D to C.

Starting PV at Program Activation Program Start Point


a C
b C
c C
d D
e E (SSV)

38
② First Soak at Segment-3 :

•If PV is in a : Segment-1 and 2 are ignored and the program


will start at the beginning of the first soak.
•If PV is b ~ d : The program will start at the B, C, and D where
PV is same to SV. In the case where PV is b, the time
designated from E to B is ignored, and the program
will run for the time designated from B to A.
Starting PV at Program Activation Program Start Point
•If, PV is in c : The time designated from E to C is ignored, and the program Starting PV at Program Activation Program Start Point
will run for the time designated from C to A. a A
•If, PV is in c : The time designated from E to D is ignored, and b B
the program will run for the time designated from D to A. c C
•If PV is in e (PV ≤ SSV) : The program will start at SSV. d D
e E (SSV)

③ No Soak Segment in the Program

• If PV is in a : Segment-1 and 2 are ignored and the program will start


at the beginning of the first reverse point (Segment-3).
•If PV is in b~d : The program will start at the B, C, and D where
PV is same to SV. In the case where PV is b,
the time designated from E to B is ignored,
and the program will run for the time designated from
B to A. Starting PV at Program Activation Program Start Point Starting PV at Program Activation Program Start Point
•If PV is in c : The time designated from E to C is ignored, and a A
the program will run for the time designated from C to A. b B
•If PV is in d : The time designated from E to D is ignored, and c C
the program will run for the time designated from D to A. d D
•If PV is in e (PV ≤ SSV) : The program will start at SSV. e E (SSV)

④ Only Ascending Ramp Segments

•If PV is in a : The program will not start.


•If PV is in b~d : The program will start at the B, C, and D where PV is
same to SV. In the case where PV is b, the time
designated from E to B is ignored, and the program
will run for the time designated from B to A.
• If PV is in c : The time designated from E to C is ignored, and
the program will run for the time designated from C to A.
• If PV is in d : The time designated from E to D is ignored, and Starting PV at Program Activation Program Start Point
the program will run for the time designated from D to A. a Program wil NOT start
•If PV is in e (PV ≤ SSV) : The program will start at SSV. b B
c C
d D
e E (SSV)

39
3) Start Mode (ST.MD) = PV2: Start at PV (Time) 4) Pattern Graph
The program will run from PV to SV in the Segment-1 ( SVn- SVn-1 )
during the time designate by the User. Set value (SV) will be changed
TMn
Pattern is determined by the time designated in the
Segment-1.

● Pattern End Segment (END.SEG)


•END.SEG is to set the parameter when the program has to end.
•END.SEG will end the program (segment that programmed to be perform later than END.SEG will be ignored)
•If END. SEG is inactive (OFF), the program will end when the last segment finishes.
【Ex.1】 If a pattern has 10 segments and END.SEG is 5, the pattern will end when the Segment-5 finishes.
【Ex.2】 If a pattern has 10 segments and END.SEG is inactive(OFF0, the pattern will end when the Segment-10 finishes.
【Ex.1】 If a pattern has 10 segments and END.SEG is 15, the pattern will end when the Segment-10 finishes.

● Pattern End Mode (END.MD)


Pattern End Mode (END.MD) consists of Reset (RST), Hold (HOLD), Fixed Control (FIX), and Link (LINK).
If LINK is selected, the pattern number will be displayed on LINK/PT.
1) If Reset is selected (END.MD=RESET);
•Shifting to Reset Mode when a pattern ends.
•Shifting to Reset Mode will activate Pattern End Signal Output (Output Time varies depending on END.TM)

2) If Hold is selected (END.MD=HOLD);


•Shifting to Hold Mode when a pattern ends.
•SV is not changed and the output is normal control.

3) If Fixed Control is selected (END.MD=FIX);


•Shifting to FIX Mode when a pattern ends.
•After shifting, select SV as per SVNO for normal control.

4) If Link is selected (END.MD=LINK);


•Shifting to the designated pattern when a pattern ends.
•Starting condition may vary depending on Start Mode (ST.MD) of respective pattern.

● Pattern End Signal Time (END.TM)


•Program ending will activate Pattern End Signal. The Parameter is to set the End Signal activation (END.TM).
(Unit of time is determined by the Time Unit (TIME) of Control Group)

•If END.TM is inactive (OFF), the End Pattern Time Signal does not occur.

40
●Link Pattern Number (LINK.PT)
•When the program ends and if you want to link another pattern to that, LINK.PT is to set the parameter.
•Pattern number can be identical to itself. In this case, the pattern infinitely repeats (as same REPEAT=CONTINUE)

● Recording and Change of Program (Update Confirm)


•Program Change
Program can be changed when it is completed or it is running.
If the value is changed during the segment process, the original value will be maintained for the duration of the
segment. After segment is complete, the controller will change to the new value.
If the value of next segment is changed, the controller will immediately change to the new value.
•Segment Number from 1 through 99 (SEG.NO=1~99) :
PID Group Number, Target, Run Time, and Time Signal (TS, TS.ON, and TS.OFF).

● PID Number Select (PID NO. Select)


NP200 programs four PID groups. Default is PID GROUP-1. All PID control outputs are user programmable
(and each segment can be controlled by corresponding PID)
•LEVEL PID of Control Group
LEVEL=OFF: Each segment is controlled by corresponding PID Group.
LEVEL=ON: All segments are controlled by LEVEL PID.

● Alarm Number Set (ALM NO. Select)


NP200 programs four Alarm Groups (See. G.ALARM).
As shown in Table below, multiple numbers of Alarm Groups can be selected.

Example) 05 : 0 1 0 1
ALM 1 (Operate) If you select ALM. NO 5, 0101 means ALM3 and ALM1 activate.
ALM 2 (No operate)
ALM 3 (Operate)
ALM 4 (No operate)

No Display ALM4 ALM3 ALM2 ALM1


0 OFF X X X X
1 01 : 0001 X X X O
2 02 : 0010 X X O X
3 03 : 0011 X X O O
4 04 : 0100 X O X X
5 05 : 0101 X O X O
6 06 : 0110 X O O X
7 07 : 0111 X O O O
8 08 : 1000 O X X X
9 09 : 1001 O X X O
10 10 : 1010 O X O X
11 11 : 1011 O X O O
12 12 : 1100 O O X X
13 13 : 1101 O O X O
14 14 : 1110 O O O X
15 15 : 1111 O O O O

41
● Segment Temperature Set Value (Set Value)
This feature is to set the target temperature of each segment.

● Segment Time Set (Segment Time)


This feature is to set the time required to reach to the target temperature of each segment.

● Segment Time Signal-1 (Time Signal 1)


Turn ON Time Signal of each segment, and then set TSx ON and TSx OFF Time.
(Only if, TS.MD is TIMEx)
TS is to set for each pattern (From Segment1 through Segment 99)

● Power Failure during the Running


If the program running is interrupted by power failure, Power Mode (PWR.MD) of Control Group (G.CTL) is activated.

● Program Time Set


For time setting: Segment Time (n, TM) of Program Group
For time unit: Time Unit (TIME) of Control Group (G.CTL)

● Hold (HOLD)
1) Hold during the program running
•Pressing RUN/HOLD key for one second or turning ON Digital Input 2 (DI2) will pause the program process.
•Pressing RUN/HOLD key for one second or turning OFF Digital Input 2 (DI2) will resume the program process.
•Pressing STEP key for one second will turn off HOLD, and force the running program stop / move to the next segment.
•Pressing RESET key for one second will turn off HOLD, and the running program will end.
•While in HOLD, the current value of SV is not changed and the control is normal.

2) Hold after program ends


• End Mode (END.MD) is HOLD: The completed program will be in HOLD mode.

3) Reset after program ends


•Pressing RESET key for one second or turning OFF Digital Input 2 (DI2) will pause turn off HOLD,
and the program process will end.

● Step (STEP)
•Pressing STEP key for one second or turning ON Digital Input (DI3) will force the running segment stop and
move to the next segment.
•Pressing STEP key will turn OFF WAIT or HOLD, and will force the program to the next segment.
•If the running segment is the last, the pressing STEP key will enable END.MD.

42
◼ File Group (G.FILE)
File Group consists of INFORM, PT. EDIT and SEG.EDIT.

● Number of Patterns and Segments Being Used (INFORM)


USED / TOTAL Pattern Number of Patterns that currently being used (NP200 programs a maximum 30 Patterns)
USED TOTAL Segment Number of Segment that currently being used (NP200 programs a maximum 300 Segments)

Number of Segment that currently being used in each Pattern.


Used Segment by Pattern
Pressing key will change the Pattern Number.

● Pattern Edit (PT. EDIT)


Copy Source • To input the pattern number to be copied (Source Pattern).
Copy Destination • To input the pattern number to pasted (Destination Pattern).
Result of File • To verify the result of copy & paste (For more information, See 1-2-4 Edit Error).
Delete Pattern Number • To delete the pattern.
Result of File CMD • To verify the result of pattern delete.
File all Initialize • To initialize all segments (0~99).
Confirm Really File Init • To confirm file initialization. Pressing YES will initialize all patterns.

● Segment Edit (SEG. EDIT)


Pattern Number Select • To input the pattern number to be edited.
• To input the segment number to be added.
• Adding new segment will push back all subsequent segments automatically.
Insert Segment Number
Parameters of the newly added segment are default.
• Insert segment parameter has default value.
Result of File CMD • To verify the result of segment add.

• To input the segment number to be deleted.


Delete Segment Number
• Deleting segment will pull up all subsequent segments automatically.

Result of File CMD • To verify the result of segment delete.

● Edit Error

• Cannot delete because the pattern has no data.


NO PT
• Cannot copy because the pattern has no data.
• Cannot delete because has no data. the segment has no data.
NO SEG
• Cannot add because the segment has no data.

PT USE • Cannot paste because the Destination Pattern already has data.

• Cannot delete because the pattern/segment is running.


PT RUN
• Cannot paste because the pattern/segment is running.

43
● Pattern Graph (PTN-1)
•As shown in graph below, the Patter is at the top while the Time Signal is at the bottom.
•Y-axis: Temperature, X-axis: Time

Pattern Diagram, Time Signal Graph Format

1SEG 2SEG 3SEG 4SEG SEGMENT



300℃

200℃

100℃

Time (TM)
1H 1H 30M 1H 2H 1H 30M Time

TS1
TS2
TS3
TS4
TS5

● Time Signal (TS), Wait, and Hold


Time Signal is being paused in WAIT or HOLD mode.
【Ex.1】 If WAIT is set to as shown in Fig. 1-1;
Time Signal (TS) is being paused during the WAIT as shown in Fig. 1-2 below.

【Fig. 1-1】 【Fig. 1-2】

10Min. 1H 30M Wait 10Min. 1H 30M

● Time Signal (TS) and Start Mode (ST.MD)


In PV START mode, Time Signal (TS) time is deemed passed as much as the program runs.
【Ex.2】 As shown in Fig. 1-3 below, if ST.MD is set to PV (PV START);
As shown in Fig.1-4, Time Signal (TS) time is deemed passed as much as the program runs.

【Fig. 1-3】 【Fig. 1-4】

지시값 (PV)
지시값 (PV)

2시간 30분
1시간 30분
1시간

44
【Ex.3】 As shown in Fig 1-5 below, if ST.MD is set to PV (PV START);
As shown in Fig.1-6, Time Signal (TS) time is deemed passed as much as the program runs.

【Fig. 1-5】 【Fig. 1-6】


Process Value Process Value

2H 30M 1H
1H 30M

● Time Signal (TS) Graph


1) Normal Time Signal (TS) 2) Double Time Signal (TS)
【Ex.1】 Normal Setting :ON TIME is within a specified segment.
【Fig. 1-2】

【Fig. 1-1】
Set TS1 from 1
1SEG 2SEG Segment
Set TS1 from 2 Segment
ON TIME OFF

Actually activated TS1


Set Time Signal from 1 segment

【Ex.2】 If Time Signal (TS) is set to as shown in Fig. 1-3, the actual Time Signal (TS) is as shown in Fig. 1-4

【Fig. 1-3】 【Fig. 1-4】


Link Set-up
Link Set-up

Link Pattern Link Pattern

Time Signal (TS) Remaining Time

● Operation Mode at the error occurrence


• Operation Mode at the error occurrence
① Fatal Error (incl. DC Error)
In the event of fatal error such as a DC error, the controller automatically shifts to RESET mode.
If the Output Mode is AUTO, the Preset-Out (PO) is automatically activated.
② Burn-Out
The Burn-Out does not affect Operation Mode. However, if the Output Mode is AUTO, the Preset-Out (PO) is
automatically activated. The error message will be displayed but the setting will remain unchanged.
In Fixed Control (FIX) mode, the error message will be displayed and the Preset Out (PO) is automatically activated.
In Program Mode, the error message will be displayed and the Preset Out (PO) is automatically activated.
SV and TIME will remain unchanged.
③ Cold Junction Compensation (RJC), OVER, and Communication Error
Cold Junction Compensation (RJC), OVER, and Communication error does affect neither Operation Mode nor
Output. In the case of Cold Junction Compensation error, the error message will be displayed but the RJC
will be turned OFF for normal control. In the case of OVER or Communication error,
the error message will be displayed but the control will be normal.

45
◼ Quick group (G.QUICK)
PROG screen  Push ▲▼ key and go G.QUICK.  Push key  USE=OFF display. Change it to USE=ON?
by ▲▼ key. Push key to select it. Sequentially select other parameter and make up quick menu.

To cancel Quick Menu, PROG screen  Push ▲▼ key and go G.QUICK.  Push key > Set USE=OFF.
 Push key to select it.

10-2. Operation Menu (OPER)


◼ Auto Tuning Group (G.AT)
• What is the Auto-Tuning?
The Auto-Tuning (AT) is used to let the controller measure process characteristics and automatically set the
most appropriate values for the PID parameters. During the default AT process, the control output will function
in an ON/OFF mode, and the controller will use the responses to calculate the needed PID values (For
instance, AT Gain is achieved as shown in Figures below; Cycle is 2.25). There are two types of Auto-Tuning
Mode (AT.MD)- Standard AT (STD) and Low PV AT (LOW PV).

AUTO Tuning Process


Auto Tuning finish AUTO Tuning Process
Set Value - Maximum scale 10%
Set Value

Process Value
Control ON ON ON
Output OFF OFF Control ON ON ON
OFF OFF
Time Output Time
ON / OFF operation PID Control AT = ON ON / OFF operation PID Control
AT = ON

【Standard Auto Tuning 】 【Low PV Auto Tuning】

● Standard Auto-Tuning (AT.MD=STD)


1) LEVEL is OFF :
•Turn ON AT on Auto Tuning Group (G. AT) in Fixed Control (FIX) mode. Referring current SV and SVNO,
the AT is performed and the gain value is assigned in relevant PID GROUP.
【Ex.1】 If SV is 50 ℃ and SVNO is 2;
AT occurs at 50 ℃, and the gain value is assigned to relevant PID GROUP.
• Turn ON AT in Program Control mode.
AT is performed at NSV and the gain value is assigned in relevant PID GROUP.
【Ex.2】 If PID NO is 3 in Segment-3, SV is 20 ℃;
AT is performed in Segment-3 and the gain value is assigned in relevant PID GROUP-3.
2) LEVEL is ON:
• Turn ON AT on Auto Tuning Group (G. AT) in Fixed
Control (FIX) mode. AT is performed at NSV and the gain Maximum
Indicating
value is assigned in relevant PID GROUP. Range
【Ex.1】 If 1.LVL is 100'C, 2.LVL is 200'C, SV is 50'C, SV
3.PID
NO is 2, AT is performed at 50'C and the gain value is 2.LVL
assigned to PID GROUP-1. (SVNO is ignored).
1.LVL 2.PID
•Turn ON AT in Program Control mode. AT is performed
at NSV and the gain value is assigned in Minimum
Indicating 1.PID
relevant PID GROUP. Range TUNING POINT=n.LVL average value

46
【Ex.2】 If 1.LVL is100'C, 2.LVL is 200'C, SV is 20, PID NO is 3 in Segment-3,
AT is performed at 20'C and the gain value is assigned to PID GROUP-1 (PID NO is ignored).
※ Turn AUTO AT in Program Control mode;
(1.LVL – RL) / 2 + RL: The gain value is assigned to PID GROUP-1.
(2.LVL – 1.LVL) / 2 + 1.LVL: The gain value is assigned to PID GROUP-2.
(RH – 2.LVL) / 2 + 2.LVL: The gain value is assigned to PID GROUP-3.

● Low PV Auto-Tuning
The basic process is same to that of Standard Type AT.
However, the Tuning Point is [SV- 10% of Max. Scale].

● Auto-Tuning Description
1) Other Functions during the Auto-Tuning
•If the Auto Tuning is performed during the program running, the TIME and SV will pause.
After Auto-Tuning is complete, the controller will resume.
•Inner Signal, Time Signal, and Alarm will stop during the Auto-Tuning process.
ON/OFF setting of both Inner Signal and Time Signal will remain unchanged because
TIME and SV is being paused during the Auto-Tuning process.

2) AT Running Display
The AT LED will blink at a 500ms time interval.

3) Changing SV during the Auto-Tuning


If the SV is changed during the Auto-Tuning process, the original Tuning Point (TP) will be maintained
for the duration of the AT process. After Auto Tuning is complete, the controller will change to the new SV.

4) Changing PID Parameter during the Auto-Tuning


The PID values can be changed during the Auto Tuning process. After Auto Tuning is complete,
it will then use the auto-tune calculated PID values. Values changed after Auto-Tuning will
remain unchanged until AT runs again.

5) Abnormal Shutdown of the Auto Tuning process


•If the forced AT shutdown occurs, the PID values will remain unchanged.
•If the error (incl. Burn-out, DC error) occurs, the Auto Tuning process will
stop and the PID values will remain unchanged.
•If the second Auto Tuning cycle exceeds 24 hours, the error message will be displayed.
•Shifting to RESET or MANUAL Control Mode will stop the Auto Tuning process.

6) AT Perform/Cancel
• Method-1
To perform: Turn on AT / or select AUTO on the AT Group.
To cancel: Turn off AT on the AT Group.
• Method-2
To perform : Press both SET and UP key simultaneously longer than 3 seconds on the Operating Display.
To cancel : Press both SET and UP key simultaneously longer than 3 seconds on the Operating Display.

47
◼ PID Group (G.PID)

● Anti-Reset Wind Up (ARW)

•When the control outputs reach the high limit value (OLH, OLL), they stop ordinary output action for
integral control and use the Anti-Reset Windup (ARW).
•When the setting is AUTO and the time for integral time (I) is not 0, the ARW is calculated automatically.
1) DV ≥ 0 & High limit output value
2) DV ‹ 0 & Low limit output value

● Control Output Calculation


1) Time Proportional PID Control Control Output Pulse Width =
Control Output Value(%) × Control Output Cycle(CYCLE TIME)

The ON/OFF pulse is proportional to the


control output value (PID calculation). ON
OFF
The width of pulse is calculated by the
Long Cycle Time
control output value multiplying by the
Cycle Time (based on a percentage of ON
ON / OFF
its full scale, default is 100%). User can Time
OFF
select the output mode (Relay Output, Medium Cycle Time ON
Voltage Pulse Output). ON
OFF
The control is better as the Cycle Time OFF
is shorter. Frequent ON/OFF may shorten Short Cycle Time Cycle Time
the Relay lifetime. Generally, 10 to 30
0.0 50.0 100
seconds of Cycle Time is recommended.
【Fig. 2.1】 Time Proportional PID Control

2) Continuous PID Control


The Continuous PID Control will output the current of 4~20mA.
The Cycle is 100ms time interval.

3) ON/OFF Control
ON/OFF Control will output either ON or OFF signal Output ON/OFF Operating
Output as per the deviation between Target SV and Point TSV
PV.(Output Hysteresis setting is available) ON
HYSTERESIS

OFF

PV

【Fig. 2.2】 ON/OFF Control

48
4) Heating/Cooling Control
• Both Heating and Cooling Output can be
calculated by PID For both Heating/Cooling, the HYSTERESIS ON
controller may use either PID Control or ON/OFF
Control. If the Proportional Band of the Heating (P) is
set to 0, the Control Output is ON/OFF. If the OFF(neutral)
Proportional Band of the Cooling (Pc) is set to 0, the
Control Output is ON/OFF. Also, Relay Output, Voltage HYSTERESIS
ON
Pulse Output and Current Output are available.
DEAD BAND
•In Heating/Cooling Control, the Dead Band can be
set from 100 to 50%. The Dead Band of ON/OFF
【Fig. 2-3】+ SV Dead Band
Control is shown in Fig. 2-3
(ON/OFF Control for both Heating and Cooling)

•The Dead Band of PID Control is shown in Fig. 2-4 below.


The –SV Dead Band in PID Control (for both Heating and Cooling) is shown in Fig. 2.5.
In this case, the Heating Output and Cooling Output meet at particular point.

Output (%) Output (%)

Cooling Heating

Cooling 0 Heating 0

DEAD BAND DEAD BAND

【Fig. 2.4】+ SV Dead Band Fig. 2.5】-SV Dead Band


(PID Control for both Heating and Cooling) (PID Control for both Heating and Cooling)

5) PID Control (Heating/Cooling Control)

• PID Select
PID is selected and calculated by the condition 1 and 2 below:
① Output (MV) › 50 % + 0.25%: Select the PID for Heating.
② Output (MV) ‹ 50 % –0.25%: Select the PID for Cooling. In other conditions, the setting remains unchanged.
③ For the first PID calculation, the Output is to set 50 %, and the PID for Heating is used (if P≠0, Pc≠0).
In the Manual Control Mode, the Heating/Cooling Output can be controlled by Key or Communication.
The Manual Control Output is to control the PID Control Output before the Heating/Cooling output calculation.
Although the Cooling PID calculation range is 0 ~ 50%, the output range is adjusted to 0~100%.
Likewise, although the Heating PID calculation range is 50~100%, the output range is adjusted to 0~100%.
• 2-DOF PID Alpha (AP)
Response in a typical closed loop control system
can be divided in response to the disturbance and
Alpha=0
175

the response to the setting change. And the existing PID 155

(1 degree of freedom) algorithm have a limit to optimize 135


Alpha=100
only one response for the two responses. 115
Alpha=50
To overcome this limitation, we applied two degree of 95

freedom PID algorithm and got an optimized response to 75

the setting change and a proper response to 55

the disturbance. 35
0 100 200 300 400 500 600 700 800
Alpha (AP) parameter is used to adjust the response Reference Alpha 0 Alpha 50 Alpha 100

characteristics of the set value (SV) change.


49
◼ Fixed Control Setting Group (G.SV)

● SV (Set Value)
•Four SVs are available in FIX Mode. Selection can be
made by SVNO.
•In FIX Mode, use key to change the
required value on the Display-1(Setup).

●Initialization and Data Change (INITIALIZE & RANGING)


1) F.INIT=ON: All parameters of program group are fully initialized.
2) P.INIT=ON: All parameters (except program group) are initialized.
3) If IN, UNIT, FR-H or FR-L is changed, either EU or EUS Unit parameter is changed.
4) Changing to OUT will initialize all parameters of Output Group.
5) Changing Alarm Type will initialize AnDB and AL-n.

◼ Control Group (G.CTL)

● LEVEL and PID


If LEVEL is ON, LEVEL PID will be used.
1) LEVEL function is OFF :
•In FIX Mode, the program is controlled by PID GROUP assigned by current SV.
【Ex.】 If SVNO=3, and 3.SV is 50.0, the program is controlled by SV=50.0 (equal to the SVNO) and the PID GROUP-3 is selected
•In PROG Mode, the program is controlled by PID GRUP assigned by current SEG.
【Ex.】 If PIDNO-1 of SEG-1 is 3, and PIDNO-2 of SEG-2 is 2, while SEG-1 is running, the PID GROUP-3 is selected
because PIDNO-1 is 3. After SEG-1 is complete, the program moves to SEG-2 and PID GROUP-2 is selected.

2) LEVEL function is ON :
•Four LEVELs within a input range will be assigned to respective PID GROUP.
•If LEVEL is turned ON, the PID GROUP is automatically selected regardless of SVNO or PIDNO.
•The ideal PID control value may vary depending on a range of temperature control.
The LEVEL function assigns each PID data to each range for efficiency and productivity.

3) LEVEL PID Parameters


Code Parameter Description Default Value
1.LVL LEVEL 1 Between PID-1 and PID-2 EU (100 %)
2.LVL LEVEL 2 Between PID-2 and PID-3 EU (100 %)
RDV LEVEL DV Deviation Range of PID-4 OFF

50
【Ex.1】Initial Conditon:1.LVL=2.LVL=FR-H, RDV=OFF 【Ex.2】 LEVEL PID: FR-L‹ 1.LVL ‹ 2.LVL ‹ FR-H,RDV=OFF

FR-H FR-H
PID-3 is selected within a range of 2.LVL~FR-H
2.LVL
PID-1 is selected within a full
range of FR-L~FR-H. PID-2 is selected within a range of 1.LVL~2.LVA
1.LVL
PID-1 is selected within a range of FR-L~1.LVL.
FR-L FR-L
PID-1 Group is selected within a full range of ※ PID 4 is not selected because RDV is turned OFF.
FR-L~FR-H because 1.LVL=2.and LVL=FR-H

【예2】 LEVEL PID : FR-L ‹ 1.LVL ‹ 2.LVL ‹ FR-H, RDV = ON

FR-H
RDV PID3 is selected within a
RDV range of 2.LVL~FR-H.
PID1~3 is selected within a range of
2.LVL
SP-RDV SP-RDV ≤ PV ≤ SP+RDV.
SP PID2 is selected within a
SP+RDV range of 1.LVL~2.LVL
If SP-RDV › PV or SP+RDV ‹ PV,
1.LVL
PID-4 is selected.
PID1 is selected within a
range of FR-L~1.LVL.
FR-L

※ PID4 : If RDV is temporarily out of a specified range, the operation is corrected by PID-4.
If correction fails, the control is made by relevant PID NO.

● Time Unit (TIME)


1) Time unit of NP200 is determined by TIME parameter.
2) hh.mm refers hour(s) and minute(s) respectively while mm.ss refers minute(s) and second(s) respectively.
3) Changing TIME parameter will not affect other parameters.
4) Changing TIME parameter will affect other parameters as below :
•PRG Group: n.WTM, n.TM, nTS ON TM, and n.TS OFF TM
•PTEND Group: END.TM

51
● Digital Input (DI)
1) DI 1, 2, 3
① Functions of DI 1, DI 2, and DI 3

DI Operating Mode ON OFF


DI 1 RESET / FIX / PROG RUN RESET
DI 2 PROG HOLD ON HOLD OFF
PROG STEP ×
DI 3
RESET / FIX PTEND OFF ×

2) DI 4, DI5, DI6, and DI7 (optional)


① Function of DI 4, DI5, DI6, and DI7 (O: Contact ON, X: Contact OFF)

PT.NO 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
DI 4 X ○ X ○ X ○ X ○ X ○ X ○ X ○ X ○
DI 5 X X ○ ○ X X ○ ○ X X ○ ○ X X ○ ○
DI 6 X X X X ○ ○ ○ ○ X X X X ○ ○ ○ ○
DI 7 X X X X X X X X ○ ○ ○ ○ ○ ○ ○ ○

② DI, Function Key and Communication


•If DI parameter of Group Control is turned ON (DI=ON): Pattern number can be changed by
DI 4~7 (Only if, DI is valid)
• If DI parameter of Group Control is turned OFF (DI=OFF) : DI 4~7 is invalid, and the pattern number
can be changed by either Key or Communication.

CAUTION
●DI Wiring
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the DI wiring work.
- Dry Contact (such as Relay) must be used.
- Dry Contact must comply with minimum requirements: Voltage (5V) and Current (1mA) at OFF.
- If any, the Transistor must comply with minimum requirements: Voltage (2V or lower) at ON,
Current (100uA or lower) at OFF

● Modes at the Power Outage and Recovery


The power interruption for a short period of time (less than 2 seconds) will not affect program modes.
When the power is recovered, the program will run again.

Prior to Power-Cut After Power-Recovery


Operation Mode Output Mode Operation Mode Output Mode
RESET MAN MAN
RESET
(PWR.MD = COOL ⇔ HOT) AUTO AUTO
FIX, PROG MAN MAN
RESET
(PWR.MD = COOL) AUTO AUTO
FIX, PROG MAN MAN
FIX, PROG
(PWR.MD = HOT) AUTO AUTO

52
【Ex.】If the controller has a Hot Start (PWR.MD=HOT) in PROG & AUTO Mode, the User may follow as below :

Power Outage Point: Same to TS at ON

2 h 10 m
1SEG 2SEG 3SEG

40m

TS of Power Recovery Point: Same to TS at ON

1) Input the parameters such as PTN NO., SEG NO. (Ex: SEG-2),
Remaining Time (Ex: 2 h 10 m), and REPEAT NO.
2) Input the remaining values of TS (Ex: 40 minutes), if the TS.MD is TIME.
Or, turn on TS, if the TS.MD is ON/OFF.
3) Input the values of HOLD, if the power outage & recovery occurred during the HOLD process.
4) Input the values of WAIT, if the power outage & recovery occurred during the WAIT process.
5) Input the values of MV when the power is recovered.
6) Input the values of Status (incl. IS, ALARM) and check such values again at the starting point.
7) When the controller is powered up and the program starts, STC is not checked.

10-3. Function Menu (FUNC)

◼ Inner Signal Group (G.IS)


•NP200 programs five Inner Signal Groups.
•The Inner Signal is effective in FIX Mode and PROG Mode.
●Inner Signal Mode (IS.MD)

When the Target Set Value (TSV) of current program segment enters into the inner signal
IS.MD=TSV zone, the output set to inner signal will activate. The activation occurs throughout the
current program segment zone.
When the Current Set Value (NSV) of current program segment enters into the inner signal
IS.MD=NSV zone, the output set to inner signal will activate. The activation occurs while NSV remains in
the inner signal activation zone.
If the current indicated value is entered into the inner signal (IS) segment,
IS.MD=PV
it outputs the inner signal (IS).

※ There is no difference between TSV and NSV in FIX Mode.


● Inner signal Parameter Description

Used to set the Inner Signal ON/OFF.


ISn (n = 1〜5)
If OFF, the Inner Signal is immediately turned OFF.

ISnH (n = 1〜5) Used to set the high limit of Inner Signal.

Used to set the low limit of Inner Signal.


ISnL (n = 1〜5)
Inner Signal ranges from ISnH to ISnL.

53
【Ex.1】 IS.MD=TSV, IS5=OFF

3SV = 70 4SV = 70
IS1H = 65
IS4H = 60
IS4 Zone
IS4L = 57
IS3H = 55
1SV = 50 2SV = 50
IS1 Zone IS3 Zone
IS3L = 45

IS2H = 35
IS2 Zone
5SV = 30
IS2L = 25
1SEG 2SEG 3SEG 4SEG 5SEG
IS1H = 0
IS1 ON ON OFF OFF ON
IS2 OFF OFF OFF OFF ON
IS3 ON ON OFF OFF OFF
IS4 OFF OFF OFF OFF OFF
IS5 OFF OFF OFF OFF OFF

• IS1: 1SV(50) is in IS1 Zone(0〜65)  ON


• IS2: 1SV(50) is not in IS2 Zone(25〜35)  OFF
1 SEG • IS3: 1SV(50) in in IS3 Zone(45〜55)  ON
• IS4: 1SV(50) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 2SV(50) is in IS1 Zone (0〜65)  ON
• IS2: 2SV(50) is not in IS2 Zone (25〜35)  OFF
2 SEG • IS3: 2SV(50) is in IS3 Zone(45〜55)  ON
• IS4: 2SV(50) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 3SV(70) is not in IS1 Zone(0〜65)  OFF
• IS2: 3SV(70) is not in IS2 Zone(25〜35)  OFF
3 SEG • IS3: 3SV(70) is not in IS3 Zone(45〜55)  OFF
• IS4: 3SV(70) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 4SV(70) is not in IS1 Zone(0〜65)  OFF
• IS2: 4SV(70) is not in IS2 Zone(25〜35)  OFF
4 SEG • IS3: 4SV(70) is not in IS3 Zone(45〜55)  OFF
• IS4: 4SV(70) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 5SV(30) is in IS1 Zone(0〜65)  ON
• IS2: 5SV(30) is in IS2 Zone(25〜35)  ON
5 SEG • IS3: 5SV(30) is not in IS3 Zone(45〜55)  OFF
• IS4: 5SV(30) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF

54
【Ex.2】 IS.MD=NSV, IS5=OFF

SV = 70
IS1H = 65
IS4H = 60
IS4 Zone
IS4L = 57
IS3H = 55
SV = 50
IS1 Zone IS3 Zone
IS3L = 45

IS2H = 35
IS2 Zone
IS2L = 25
IS1L = 0
IS1 ON OFF ON
IS2 ON OFF ON
IS3 ON OFF ON
IS4 ON OFF ON
IS5 OFF

• IS1: Current SV is in IS1 Zone(0〜65)  ON


• IS2: Current SV is in IS2 Zone(25〜35)  ON
ON Condition • IS3: Current SV is in IS3 Zone(45〜55)  ON
• IS4: Current SV is in IS4 Zone(57〜60)  ON
• IS5: IS5 has no value  OFF
• IS1: Current SV is not in IS1 Zone(0〜65)  OFF
• IS2: Current SV is not in IS2 Zone(25〜35)  OFF
OFF Condition • IS3: Current SV is not in IS3 Zone(45〜55)  OFF
• IS4: Current SV is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF

【Ex.3】 IS.MD=PV, IS5=OFF

PV
IS1H = 65
IS4H = 60
IS4 Zone
IS4L = 57
IS3H = 55

IS1 zone IS3 Zone


IS3L = 45

IS2H = 35
IS2 Zone
IS2L = 25
IS1L = 0
IS1 ON OFF ON
IS2 ON OFF ON
IS3 ON OFF ON
IS4 ON OFF ON
IS5 OFF

• IS1: If the current PV is within the range IS1(0~65), ON


• IS2: If the current PV is within the range IS2(25~35), ON
ON Condition • IS3: If the current PV is within the range IS3(45~55), ON
• IS4: If the current PV is within the range IS4(57~60), ON
• IS5: Because IS5 is not set, OFF
• IS1: If the current PV is not within the range IS1(0~65), ON
• IS2: If the current PV is not within the range IS2(25~35), ON
OFF Condition • IS3: If the current PV is not within the range IS3(45~55), ON
• IS4: If the current PV is not within the range IS4(57~60), ON
• IS5: Because IS5 is not set, OFF

55
◼Alarm Group (G.ALARM)
● Alarm Mode (AL.MD)
The Alarm Parameter is to set Alarm Mode (AL.MD). The types of Alarm are as below :
1) ALL : Alarm will trigger in all modes (incl. Reset (RST), Fixed Control (FIX), and Program (PROG)).
2) FIX & PROG : Alarm will trigger in Fixed Control (FIX) and Program (PROG) mode.
3) FIX : Alarm will trigger only in Fixed Control (FIX) mode.
4) PROG : Alarm will trigger only in Program (PROG) mode.
● The Alarm will not trigger if the alarm condition occurs during the following activities :
1) During the power-up
2) The type of alarm is changed
3) The SV is changed during Fixed Control (FIX) Mode (not applicable to PROG mode)
● Alarm Type
1) Forward Activation of Control Output (When the Alarm triggers : ON)
Alarm Type Code Number ON Condition OFF Condition
High Limit Alarm 1 (11) PV ≥ ALM PV < ALM–HYS
Low Limit Alarm 2 (12) PV ≤ ALM PV > ALM+HYS
High Limit Deviation Alarm 3 (13) DEV ≥ ALM DEV < ALM–HYS
Low Limit Deviation Alarm 4 (14) DEV ≤ –ALM DEV > –ALM+HYS
High and Low Limit DEV ≥ ALM DEV < ALM–HYS
7 (17)
Deviation Alarm (DEV ≤ –ALM) (DEV > –ALM+HYS)
High and Low Limit Range DEV ≤ ALM DEV > ALM–HYS
8 (18)
Deviation Alarm DEV ≥ –ALM (DEV < –ALM+HYS)

※ Code number in bracket refers to the NOT-triggering activity. PV: Process Value, ALM: Alarm Set Value,
DEV : Deviation Set Value (PV-SV)
2) Reverse Activation of Control Output (When the Alarm triggers: OFF)
Alarm Type Code Number ON Condition OFF Condition
High Limit Alarm 9 (19) PV ≥ ALM PV < ALM–HYS
Low Limit Alarm 10 (20) PV ≤ ALM PV > ALM+HYS
High Limit Deviation Alarm 5 (15) DEV ≥ ALM DEV < ALM–HYS
Low Limit Deviation Alarm 6 (16) DEV ≤ –ALM DEV > –ALM+HYS

Code number in bracket refers to the NOT-triggering activity. PV: Process Value, ALM: Alarm Set Value, DEV:
Deviation Set Value (PV-SV)
● Alarm Functions
Alarm Type Figure Alarm Type Figure

PV High Limit
Low Deviation Alarm
Alarm

High and Low


PV Low Limit Alarm
Deviation Alarm

High and Low Limit


High Deviation
Range Deviation
Alarm
Alarm

56
● Types of Alarm
Alarm Code Alarm Type Default Value Set Range
1, 9, 11, 19 High Limit Alarm EU (100 %) EU (0~100 %)
2, 10, 12, 20 Low Limit Alarm EU (0 %) EU (0~100 %)
3, 5, 13, 15 High Limit Deviation Alarm EUS (0 %) EUS (0~100 %)
4, 6, 14, 16 Low Limit Deviation Alarm EUS (0 %) EUS (0~100 %)
High and Low Limit
7, 17 EUS (0 %) EUS (0~100 %)
Deviation Alarm
High and Low Limit Range
8, 18 EUS (0 %) EUS (0~100 %)
Deviation Alarm

※ The Dead Band (DB) value of Alarm Output is default: EUS(0.5 %), Setting Range: EUS(0~100 %).
If AnTY is inactive (OFF), both AL-n and AnDB is not displayed.

CAUTION
● Alarm Output Wiring
•Use a non-voltage contact switch such as relay when the controller supplies the needed voltage
(above 240 V AC) + resistance (above 1A) or voltage (above 30 V DC) + resistance load (above 1A).
•Use a bleeder resistor to draw more infinitesimal current, if required.
•The lifetime of relay is approximately 100,000 operations. If the load inductance is over the controller
specifications, the output may need a RC filter or diode to properly handle frequent relay switching operations.

◼ User Output Group (G.UO)


•The User Output (U1~U10) for terminal ((U1~U10) is selectable.
•The U10 is disabled when the cooling output is a relay, if a controller is the Heating/Cooling model..
•Output will be a cooling regardless of U10. The cooling output has a priority over the U10.
•The setting of User Output (from U1 to U10) can be identical.
•The SGAL Input is activated when one of the four alarms is turned ON, if U5 ~ U10 is set to output SGAL.

● User Output (UO) Parameters

OFF User Output (UO) is inactive (OFF).


ALM1〜4 User Output activates (ON) when the Alarm 1〜4 is active.
TS1〜TS5 User Output activates (ON) when the Time Signal 1〜5 is active.
IS1〜IS5 User Output activates (ON) when the Inner Signal 1〜5 is active.
PTEND User Output activates (ON) when a program ends (if PTEND BIT is ON).
PROG User Output activates (ON) during the program running.
FIX User Output activates (ON) during the fixed control mode.
RESET User Output activates (ON) when the reset mode.
HOLD User Output activates (ON) when the hold mode.
WAIT User Output activates (ON) when the wait mode.
MAN User Output activates (ON) during the manual control mode.
PTUP User Output activates (ON) during the ascending ramp segment.
PTDOWN User Output activates (ON) during the descending ramp segment.
PTSOAK User Output activates (ON) during the soak segment.

57
●The setting and status of UO can be checked in the Display-4 (User Output) as figure below.
【Display below means】
• U1 is IS1 • U6 is ALM2
• U2 is IS2 • U7 is ALM3
• U3 is TS1 • U8 is PTEND Signal
• U4 is TS2 • U9 is PATTERN UP
• U5 is ALM • U10 is inactive

The active (or running) Output No. is highlighted. For instance, the UO-8 is active in Figure above.
The Pattern is completed, and the Pattern End Signal (PTEND SIGNAL) is active.

◼ Retransmission Group (G.TRANS)


● Retransmitting Output (RET)
RET PV SV MV SPS remark
Retransmission Sensor Power Retransmission is invalid when the
PV SV Output (MV OUT)
Output Type Supply OUT is 4, 5, 7 or 8.

CAUTION
●Retransmission Wiring
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the installation/removal of transmitters.
- Use the same terminal for both Retransmission Output and SPS.
Set the parameter to select either Retransmission Output or SPS because both outputs use same terminal.
● Sensor Power Supply Wiring: 24 V DC (20 mA Max.)
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the installation/removal of sensors.
- The Retransmission Output and SPS will be disabled when the output type is Current Output,
if the controller is the Heating/Cooling model..
- The Retransmission Output will be inactive while the SPS is being active.

● Retransmission Range
1) RETH (High Limit), RET=PV, SV Type Retransmission :
The Valid Range is T.C, RTD=RETL+1digit〜FR-H, mV, V=RETL+1digit〜SL-H.
2) RETL (Low Limit), RET=PV, SV Type Retransmission :
The Valid Range is T.C, RTD=FR-L~RETH-1digit, mV, V=SL-L〜RETH-1digit.
● RET Scale

1) PV: 3.2 mA~20.8 mA 2) SV: 4.0 mA~20.0 mA


3.2 mA 4.0 mA 12.0 mA 20.0 mA 20.8 mA 20.0 mA
4.0 mA 12.0 mA

RETL RETH RETH


B.OUT = DOWN & B.OUT B.OUT = UP & B.OUT RETL

3) MVOUT: 3.2 mA~20.8 mA 4) Sensor Power Supply (SPS):


3.2 mA 4.0 mA 12.0 mA 20.0 mA 20.8 mA
Output is 24 V DC 20mA Max.
Select either RET Output or SPS.

MV=0.0 % MV=100.0 %
–5 % 105 %

58
10-4. Set-up Menu (STUP)

◼ Communication Group (G.COMM)


NP200 Series employees either RS485 or RS422 Half-Duplex Communication (2-wire or 4-wire) and links up to 31
computer terminals. The parameters to set the Communication Group and Communication Modes are as below :

Display Default
Code Description Setting
Condition Value
RS485/RS422. Used to set PC LINK(SV:0)/PC LINK SUM(SV:1)
PR-S 0
the communication protocol MODBUS ASCII (SV:2)/MODBUS RTU(SV:3)
600 (SV : 0), 1200 (SV : 1), 2400 (SV : 2),
Used to set the
BPS 4800 (SV : 3), 9600 (SV : 4), 19200 (SV : 5), 4
communication speed (B.P.S)
38400(SV: 6)
Used to set the
PRI NONE(SV:0) / EVEN(SV:1) / ODD(SV:2) 0
communication parity
Used to set the Optional
STP 1-BIT (SV:1) / 2-BIT(SV:2) 1
communication stop bit
Used to set the
DLN 7-BIT(SV:7) / 8-BIT(SV:8) (SV is 8 except PC LINK) 8
communication length
Used to set the
ADR From 1 through 99 (Max. ~31) 1
communication address
Used to set the 0~10. Response Time
RP.T 0
communication response time = (Process Time + Response Time) X 10ms

CAUTION
● PC-LINK Communication/LADER Communication Wiring
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the installation/removal of communication terminal.
- Connect terminating resistors (220Ω1/4W) to slave and master controllers at communication channel ends
- Disconnect SDA from RDA / SBD from RBD when the master controller employees the 2-wire communication

◼ Output Group (G.OUT) CAUTION Set other groups only after both Input and Output group setting is complete

CAUTION
● Control Output Wiring
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the installation/removal of Control Output
- Use shielded wires to Voltage Pulse Output and Current Output connections.

● Output Type
• The output type is determined by the OUT Parameter of OUT GROUP.
※ For more information, see Chapter 5. Input & Output > Control Output Types (see page 8)

● Output Cycle
•The output cycle (HCT, CCT) is valid when the output is either Relay or SSR (Solid State Relay).
•HCT refers the Heating Cycle Time (Output 1).
•CCT refers the Cooling Cycle Time (Output 2).
59
● Output Limit (Limit)
• The OL-H is the High Limit and OL-L is the Low Limit when the OUT is in 1~3.
–5.0 % ≤ OL–L ≤ MVOUT ≤ OL–H ≤ 105.0 %
• The OL-H is the High Limit of Heating Output and OL-L is the High Limit of Cooling Output when
the OUT is 4~12 if a controller is the Heating/Cooling model.
① 0.0 % ≤ H.OUT ≤ OL-H
② 0.0 % ≤ C.OUT ≤ OL-L
● Emergency Output
• The PID calculation stops and the Preset-Out (PO) is activated when the A/D error occurs in AUTO Mode,
or in BURN OUT or RESET Mode.
• The Preset-Out (PO) is activated by HEO Value when the OUT is 0~3. (However, when the OUT is
0; if HEO is 0% or below, the OUT is 0%; if HEO is 0% or above, the OUT is100 %)
• The PO and CEO is responsible for the Preset-Out of Heating and Cooling respectively when the OUT is
4~12, if a controller is the Heating/Cooling model.
• The output is MAN regardless of error event or mode when the controller is in MAN Mode.
● Output Action (Direct/Reverse Action : O.ACT)
• The Direct Action refers an increasing control output when the deviation (PV-SV) is positive (+)
while the Reverse Action refers an increasing control output when the deviation is negative (-).
• O.ACT=DIR: Direct action
• O.ACT=REV: Reverse action
• O.ACT is selectable when the OUT is 0~3 (Except Heating/Cooling model).
• The Heating Output is Reverse Action and the Cooling Output is Direct Action when the OUT is 4~12,
if a controller is the Heating/Cooling model.
● Hysteresis (HYS)
• The HYS is to set the OUT=0 (ON/OFF) or 4〜12 (Heating/Cooling).
• If OUT is 0, the Hysteresis is for ON/OFF operation whereas if OUT is 4~12,
the Hysteresis is for Heating/Cooling operation.
• When the OUT is 0 (ON/OFF), the Hysteresis EUS (0〜100 %).
The Output ON/OFF is {SV-(HYS/2)}〜{SV+(HYS/2)}.
【Ex.】 If, SV=50, HYS=10, O.ACT=REV
• When the OUT is 4~12 (H/C TYPE), 55 = SV+(HYS/2)
the HYS is 0.0~10.0%. The Hysteresis of SV = 50
ON/OFF operation is determined when 45 = SV–(HYS/2)
PV
the Proportional Band of Heating and/or
Cooling (P and/or Pc) is 0.
O/P ON O/P OFF O/P ON

● Auto and Manual Mode (A/M) Use △,▽ Key to change the required control output values
CAUTION in MAN Mode. Do not use SET/ ENT Key.

Use △,▽ Key to change the required control output values in MAN Mode. Do not use SET/ ENT Key.
NP200 employees two functional output modes – Auto Control Mode (AUTO) and Manual Control Mode (MAN).
In AUTO Mode, a controller automatically calculates the required outputs through PID. In MAN Mode, the User
can manually increase/decrease the outputs.

1) Altering AUTO and MAN Mode


① Press DISP key to move to Display-5 (Output Mode Display). Press SET key to alter either AUTO or MAN Mode.
② Altering AUTO and MAN Mode is available in RESET, FIX or PROG Mode.
③ Altering AUTO and MAN Mode is unavailable when the LOCK is ON (also the Display-5 is not available).
60
◼ Input Group (G.IN) CAUTION Set other groups only after both Input and Output group setting is complete.

CAUTION
● Sensor/Probe Input Wiring
- To prevent personal injury or property damage caused by electric shock, please disconnect the controller
device from the external power source during the installation/removal of input (such as sensor or probe).
- Connecting wrong polarity may cause damage or malfunction. Keep the input signal and output wiring
as far as possible away from the power and ground circuit.
- Use shielded wires and ground the shielding to an independent grounding point.

● Input Types: Thermocouple, RTD, Voltage Direct Current (VDC)


• For more information, see Chapter 5. Input & Output > Input Type and Range in this literature (See page 8)
• Changing input type will initialize EU and EUS parameters.

● Input Range Unit


Changing input unit will automatically convert the temperature range.
The Unit is valid in Thermocouple or RTD input type.
Unit : ℃ (Celsius), ℉(Fahrenheit)
● User Unit (U.UNIT)
The User Unit is used to indicate the unit on the operating display.
The unit is valid in the direct voltage input type.
Unit : ℃, %, %RH, Pa, -(N/A)

※ UNIT and U.UNIT


The UNIT is used for temperature input range of Thermocouple or RTD (Resistance Temperature Detector) and it affect all parameters of
EU and EUS. However, the U.UNIT is valid only for the direct current input type and affects the operating display. The U.UNIT is virtual unit
assigned by the User and does not affect parameter of EU or EUS.

● Input Range

Set the Input Range Code for determining input range of Thermocouple/RTD. For the
Input Range Code, see Chapter 5. Input & Output > Input Type and Range (see page 8)
Thermocouple, RTD in this literature. The Input Range is determined by changing FR-H and FR-L within a
specified range. However, the decimal point cannot be changed (DP-P is invalid). SL-H
and SL-L is invalid.
Set the Input Range Code for determining input range of Direct Voltage.
The Input Range is determined by changing FR-H and FR-L within a specified range.
Direct Voltage Input
Also, SL-H and SL-L is to scale the display value.
(DC, V, mV) (Input Command 100% is determined by SL-H, and Input Command 0 % is determined
by SL-L). The decimal point can be changed by DP-P.

1) FR-H, FR-L (T/C, RTD, mV, V)


•Setting Range : Setting is available within a default range of each input type. However, FR-H > FR-L
•Changing FR-H or FR-L will initialize SL-H, SL-L, EU, and EUS parameters.

2) SL-H, SL-L, DP-P (Valid if the input type is mV, V)


•Default Value : SL-H=100.0, SL-L=0.0. (However, the decimal point is determined by DP-P)
Setting Range : Setting is available within a range from -2,000 through 14,000 regardless of FR-H~FR-L setting range. However, SL-H › SL-L
•Changing SL-H or SL-L setting will initialize EU and EUS parameters. (Except FR-H and FR-L)

61
【Example.1】 IN = K1 type

FR-H, FR-L DEFAULT : FR-L :-200.0 800.0 FR-H : 1370.0

change settings : FR-L : 800.0


FR-H : 1370.0

RET.H, RET.L 3.2 mA 4.0 mA 12.0 mA 20.0 mA 20.8 mA

RET.L RET.H
B.OUT = DOWN & B.OUT condition B.OUT = UP & B.OUT condition

【Example.2】 IN = 1/5V type

FR-H, FR-L DEFAULT : FR-L : 1V 3V FR-H : 5V

change settings : FR-L : 1V FR-H : 3V

SL-H, SL-L SL-H : 100.0


DEFAULT : FR-L : 1V 3V

change settings : 0.0 50.0 100.0

SL-H : 150.0
SL-L : -50.0 (3V)
(1V) (2V)

RET.H, RET.L 3.2 mA 4.0 mA 12.0 mA 20.0 mA 20.8 mA

RET.L RET.H
B.OUT = DOWN & B.OUT condition B.OUT = UP & B.OUT condition

● Input Filter
•Remove the noise when noise enters the input
•Setting range FILT: OFF, 1~120s

● Input Correction(BIAS)
• Adjust the deviation of the indicated value(PV) and the display value.
• Displayed Indicated value(PV) = input value + input compensation value(BIAS)
• Setting range of BIAS : EU (-100~100%)

62
● Burn-Out Detection
The Burn-Out (B.OUT) function determines the control outputs including PV up/or down scale, retransmission output and Alarm
when an input disconnection/failure occurs (such as sensor). The Burn-Out is used in the input range of Thermocouple and RTD.
•When the Burn-Out is detected (B.OUT=UP, DOWN), the retransmission and alarm operation is affected and a Control
Output is the Preset-Out.
•When the Burn-Out is not detected (B.OUT=OFF), the PV is rejected and a Control Output is normal (No Preset-Out occurs).

B.OUT (Burn-Out) UP (Up Scale) DOWN (Down Scale) OFF (OFF)

Thermocouple/RTD Detection ◯ ◯ X
(DC, V, mV is invalid)
PV 105 % –5 % Rejected
Remark RTD is +105% temporarily. Up, Down or OFF

● PV Limiter
•-OVR or OVR presents on PV Display when the PV is in either -5% or 105% of the input range.
(a controller runs as per either -5% or 105% of PV)
• PV > EU (105 %): PV=105 %, PV Display= OVR
• EU(-5 %) ≤ PV ≤ EU(105 %): PV= PV
• PV < EU (-5 %): PV= -5 %, PV Display=-OVR

● PV during the A/D Error


•The error message presents on PV Display when an A/D error occurs.
•A controller runs an alarm and retransmission operations as per 105% of PV.

● Reference Conjunction Compensation (RJC)


•The reference conjunction compensation is automatically performed when the input type is a Thermocouple.
•When the RJC error occurs, the error message and PV presents on PV Display and a controller runs as per RJC=0 ℃.

◼ Lock Group (G.LOCK)


● Lock Functions
Key, Menu, and Password locking prevents the accidental or unauthorized change.

Function Code Parameter Description


PWD Password Access is denied if password entry is incorrect.
▽/△ Down Up Key Lock DOWN & UP key is locked and PARAMETER EDIT is disabled.
PT.NO UP and PT.NO DOWN key are locked and PTN NO.
KEY LOCK PT.NO Pattern Number Lock
EDIT is disabled.
RUN Run Key Lock RUN/HOLD key is locked and PROG RUN is disabled.
Display-5 (Output Mode Display) is disabled. Shifting between
A/M Auto / Man Lock
AUTO and MAN Mode is disabled.
PROG PROG Menu Lock PROG Menu is disabled.
Menu OPER OPER Menu Lock OPER Menu is disabled.
FUNC FUNC Menu Lock FUNC Menu is disabled.
PASSWORD PWD.C Password Chage Access to SETUP Menu is denied if password entry is incorrect.
(set-up) P.INIT Parameter Initialize Pattern is initialized.

63
11. Specifications
◼ Input Specification
Input Multi range type (Refer to “Input type Kinds and Range”)
Sampling time 100 ms
Input resolution Basically for the numbers below the decimal point
Input impedance T/C & mV input: 1 MΩ min, DC mV input: approx 1 MΩ
Allowable signal source
T/C: Max 250 Ω, DC mV/V: Less than 2 kΩ
resistance
Allowable wiring resistance RTD input: Less than 150 Ω/ 1 wire
Allowable input voltage DC mV/Thermocouple/RTD: ±10 V, DC V: ±20 V
Noise removal rate NMRR: more than 40 dB (50/60 Hz ±1 %) CMRR: more than 120 dB
Standard Thermocouple/RTD (KS / IEC / DIN)
T/C: Up Scale / Down Scale
Input signal break detection
RTD: Up Scale
(Burn - out) Detected voltage in signal break: Approx. 50 nA
Accuracy Max scale 0.1 %

◼ Output
● Output type
Contact capacity : 240 V AC 3 A, 30 V DC 3 A (registance).
Composition of contac t : 1c
Output operation : time proportioned or ON/OFF
Relay output Time proportion cycle time : 1 ~ 1000 s
Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L). (Trial for MAN / AT is possible).
ON/OFF hysterisis : 0 ~ 100 %
Time resolution : the small one in either 0.1 % or 10 ms
ON voltage : more than 25 V DC (Load resistance more than 600 Ω when cut off happened
there’s limit on electric current of around 30 mA)
OFF voltage : less than 0.1 V DC Output operation: Time proportioned
SSR output
Cycle time : 1 ~ 1000 s
Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L). (Trial for MAN / AT is possible).
Time resolution : the small one in either 0.1 % or 10 ms

Output current range : 4 ~ 2 mA


DC output renewal cycle : 100 ms
Load resistance: less than 600 Ω Output operation : consecutive PID
SCR output Output ripple : less than 0.1 % of FS. (p-p) (150 Hz)
(4~20 mA d.c.) Accuracy : ±0.3% of FS. (range from 4 ~ 20mA DC) Resolution : around 3,000
Output limit : 0.0 ~ 100.0 % Highest value(OL-H) and Lowest value(OL-L).
(Trial for MAN / AT is possible).

Conversion to MANUAL operation is possible at the number 5 of operation screen and


Manual operation communication.
A → M: output tracking M → A: bumpless

◼ Certifications
UL (ongoing)
Certification C-UL (ongoing)
CE (ongoing)

64
● Retransmission output

Current output range: 4 - 20 mA DC Resistance load: less than 600 Ω


Accuracy : ±0. % of FS. (4 - 20 mA DC)
Current output Resolution : Approx. 3,000
Output ripple : Max 0.1 % of FS. (p-p) (150 Hz)
Output renewal cycle time : 100 ms

Retransmission signal: PV (Pro c ess value) / SV (S et value) /


Retransmission output MV (Volume of output) / SPS (Power supply for sensor)
S caling: PV (Pro c ess value) / SV (S et value)

※SPS(Power supply for sensor): Retransmission output of PV/SV/MV can not be used when you use SPS.

◼ Interface
Standard EIA RS485
Number of devices 31. Address setting: 1~99 range
Communication type 2 wire or 4 wire half-duplex
Synchronization Start – stop synchronous mode
Communication order None
Communication distance Max 1.2 km
Communication rate 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 bps
Start Bit 1 Bit
Data length 7 or 8 Bit
Parity None, Even, Odd
Stop Bit 1 or 2 Bit
Protocol PC-LINK, PC-LK-S, MODBUS ASCII, MODBUS RTU
Response time Handling time + (RP.T X 10 ms)

◼ Power Supply
Power supply voltage 100 - 240 V AC (90V ~ 250V)

Frequency 50 - 60 Hz

Power Consumption Max 6.0W / MAX 10 VA

20MΩ min(at 500V DC) : Between primary terminal and secondary terminal
Insulation resistance Between primary terminal and ground
Between ground and secondary terminal

2300V AC 50/60 Hz for 1 minute : Between primary terminal and secondary terminal
Dielectric Strength Between primary terminal and ground
1500V AC 50/60 Hz for 1 minute : Between F.G terminal and secondary terminal

Power supply for sensor 24 V DC 20 mA Max (select between retransmission output or SPS)

65
◼ Function
-100.0 ~ 100.0% for measuring input range.
Bias
Valid setting a correction value
Measuring
Input Scaling According to setting of SL-H, SL-L of measuring range, scaling is available.

Input filter OFF, 1 ~ 120 s

Fix SV 4 kinds

Pattern 30 Patterns, 99 segments are available in each pattern

Segment 300 Segments

PID Group 4 kinds


According to SV, AT is operating.
Auto Tuning
(Select STD or low PV)
Proportional band (P) 0.1% ~ 999.9%

Integral time (I) OFF, 1 ~ 6000sec

Differential time (D) OFF, 1 ~ 6000sec


Control ON/OFF control Select ON/OFF control in output group

PID converter Level PID/Segment PID selectable

Manual reset -0.5 ~ 105.0%. 〔Valid when I=OFF〕

Direct/reverse action Select direct or reverse action in output group

Emergency output -0.5 ~ 105.0% of output value

ON/OFF hysteresis 0.0 ~ 100.0% of range (in case of ON/OFF control, it is up to hysteresis value in output group.)

Heating/cooling hysteresis -100.0 ~ 50.0% of output value

Auto/Man Convert at the 5th operation screen

Anti reset wind up (ARW) AUTO, 50.0 ~ 200.0% at the PID group

Retransmission Retransmission signal PV, SV, MV, SPS (select TRANS in retransmission group)
output Scaling Setting PV, SV

Setting points Max 10 points

Type of alarm High/low alarm, High/low deviation alarm

Alarm Process alarm: 0~100% of range


Setting range Deviation alarm: -100~100% of range

Alarm hysteresis 0.0~100.0% of instrument range

◼ Condition for transportation & storage ◼ Structure


Temperature –25 ~ 70 ℃ Material Plastic case
Humidity 5 ~ 95 %RH (no icing) Weight 696 g (including bracket and box)
Shock Fall from less than 1m Panel cutout 92(W) X 92(H)

66
◼ Operating Environment
Consecutive vibration: vibration width is less than 1.2mm (5 ~14 Hz)
Consecutive vibration: 4.9㎨ (4 ~ 150Hz)
Setting surroundings
Short time vibration: 14.7 ㎨ less than 15 seconds (each 3 directions)
Shock: 147㎨ less than 11ms (3 times at each 3 directions)

Temperature: 0 ~ 50℃
Conditions for normal Humidity: 35 ~ 85%RH (no icing)
operation Magnetic range: less than 400AT/m
Warm Up Time: more than 30 minutes
T/C voltage input: ±1㎶/℃ or ±0.01% of FS/℃
Effects of temperature in the
RTD input: less than ±0.05FS/℃
surrounding environment
Analog output: less than ±0.05% of FS/℃ (consecutive output)
Effects of voltage Analog input: ±1㎶/10V or ±0.01% of FS/10V
fluctuation rate Analog input: less than ±0.05% of FS/10V

◼ Operating indicators
Display process value (5 digit with 7 segment)
Display Set value and parameter display (LCD)
Condition display (Individual LED)
SW1 : RUN / HOLD LED 1 : PROG LED 8 : U2
SW2 : RESET LED 2 : RESET LED 9 : U3
SW3 : STEP LED 3 : FIX LED 10 : U4
SW4 : PT.NO DOWN (▽) LED 4 : HOLD LED 11 : U5
SW5 : PT.NO UP (△) LED 5 : OUT LED 12 : U6
NP200
SW6 : SET LED 6 : MAN / AT LED 13 : U7
SW6 : FIX LED 7 : LED 14 : U8
SW8 : DISP LED 5 : LED 15 : U9
SW9 : DOWN (▽) LED 6 : LED 16 : U10
SW10 : UP (△) LED 7 : U1

◼ Engineering Units
⒜ EU: The value of engineering units according to the range of a material
⒝ EUS: Range of engineering units according to the span of a material

EU (0 %) = -200 ℃ EU (20 %) = 80 ℃ EU (40 %) = 360 ℃


-200 ℃ 80 ℃ 360 ℃ 1200 ℃

EUS (20 %) = 280 ℃ EUS (20 %) = 280 ℃

● As per EU 40% = 360℃,


Total span is 1400 in the range between -200℃ ~ 1200℃.
Therefore 1400 x (40/100) = 560 and 40% of the total span is 360℃ deducting -200℃ from 560.
● As per EU 20% = 280℃,
Total span is 1400 in the range between -200℃ ~ 1200℃.
Therefore 1400 x (20/100) = 280 and 20% of the total span is 80℃ deducting -200℃ from 280.

67
12. NP200 Communication Map (after ver. 011)

● NP200 D Register Mapping Table


Process Control IS SV/PID ALM & UO LOCK OUT & IN
Address 0000 0100 0200 0300 0400 0500 0600
0 CMPT ISMD SVNO A1TY TRANS OUT
1 ✱ NPV COMOP IS1 SV1 A2TY TRANS.H O.ACT
2 ✱ NSV CMAM IS1H SV2 A3TY TRANS.L HCT
3 CMMOUT IS1L SV3 A4TY ADJ.H CTC
4 ✱ SSV LEVEL IS2 SV4 A1DB ADJ.L HYS
5 ✱ MVOUT IS2H ATMD A2DB HEO
6 ✱ HOUT ARW IS2L ✓ AT A3DB CEO
7 ✱ COUT TMU IS3 A4DB OL-H
8 ✱ PIDNO DI IS3H AL-1 OL-L
9 PWR.MD IS3L ALPHA AL-2
10 IS4 1.P AL-3 PRS INP
11 IS4H 1.I AL-4 BPS UNIT
12 IS4L 1.D ALMD PRI FR-H
13 ✱ ALMSTS IS5 1.MR STP FR-L
14 ✱ UOSTS IS5H 1.PC DLN DP-P
15 ✱ DISTS IS5L 1.IC ADR SL-H
16 1.DC RPT SL-L
17 ✱ ERRSTS 1.DB FILT
18 ✱ NOWSTS 1.LVL BIAS
19 ✱ COMOP ENDTIME B.OUT
20 ✱ CPTNO 2.P UO1 UPDN RJC
21 ✱ CSGNO 2.I UO2 PT.NO U.UNIT
22 ✱ CSGSV 2.D UO3 RUN
23 ✱ CSGTM 2.MR UO4 A/M
24 ✱ RSGTM 2.PC UO5 PROG
25 ✱ BRSGTM 2.IC UO6 OPER
26 ✱BWRSGTM 2.DC UO7 FUNC
27 ✱ CRPT 2.DB UO8 P.INIT
28 ✱ TRPT 2.LVL UO9 F.INIT
29 ✱ PTSTS UO10 FCFIRM
30 3.P PWD
31 3.I
32 3.D
33 3.MR
34 3.PC
35 3.IC
36 3.DC
37 3.DB
38
39
40 4.P
41 4.I
42 4.D
43 4.MR
44 4.PC
45 ✱ INFO.SYS 4.IC
46 ✱INFO.OPT 4.DC
47 ✱ INFO.SP1 4.DB
48 ✱ INFO.SP2 LVLD
49 ✱ INFO.HW
50 ✱ INFO.FW
68
✱ READ ONLY READ / WRITE
✓ Out of control due to communication READ / WRITE (Abnormal communication after Write)

COMM CTL PT SET PT INFO SV INFO TM INFO


Address 0700 0800 0900 1000 1050 1100 1150
0 CPTNO_S WZ TUPT
1 CPTNO_D WTM NPT1 MSV1 MSV51 MTM1 MTM51
2 CSEGNO REPEAT NPT2 MSV2 MSV52 MTM2 MTM52
3 CFCMD TS.MD NPT3 MSV3 MSV53 MTM3 MTM53
4 CFANS ST.SV NPT4 MSV4 MSV54 MTM4 MTM54
5 ST.MD NPT5 MSV5 MSV55 MTM5 MTM55
6 END.SEG NPT6 MSV6 MSV56 MTM6 MTM56
7 END.MOD NPT7 MSV7 MSV57 MTM7 MTM57
8 END.TM NPT8 MSV8 MSV58 MTM8 MTM58
9 LINK.PT NPT9 MSV9 MSV59 MTM9 MTM59
10 PTFSUM NPT10 MSV10 MSV60 MTM10 MTM60
11 NPT11 MSV11 MSV61 MTM11 MTM61
12 NPT12 MSV12 MSV62 MTM12 MTM62
13 NPT13 MSV13 MSV63 MTM13 MTM63
14 NPT14 MSV14 MSV64 MTM14 MTM64
15 NPT15 MSV15 MSV65 MTM15 MTM65
16 NPT16 MSV16 MSV66 MTM16 MTM66
17 NPT17 MSV17 MSV67 MTM17 MTM67
18 NPT18 MSV18 MSV68 MTM18 MTM68
19 NPT19 MSV19 MSV69 MTM19 MTM69
20 NPT NPT20 MSV20 MSV70 MTM20 MTM70
21 PID NPT21 MSV21 MSV71 MTM21 MTM71
22 ALM NPT22 MSV22 MSV72 MTM22 MTM72
23 SV NPT23 MSV23 MSV73 MTM23 MTM73
24 TM NPT24 MSV24 MSV74 MTM24 MTM74
25 TS1 NPT25 MSV25 MSV75 MTM25 MTM75
26 TS1ON NPT26 MSV26 MSV76 MTM26 MTM76
27 TS1OFF NPT27 MSV27 MSV77 MTM27 MTM77
28 TS2 NPT28 MSV28 MSV78 MTM28 MTM78
29 TS2ON NPT29 MSV29 MSV79 MTM29 MTM79
30 TS2OFF NPT30 MSV30 MSV80 MTM30 MTM80
31 TS3 TUSEG MSV31 MSV81 MTM31 MTM81
32 TS3ON MSV32 MSV82 MTM32 MTM82
33 TS3OFF MSV33 MSV83 MTM33 MTM83
34 TS4 MSV34 MSV84 MTM34 MTM84
35 TS4ON MSV35 MSV85 MTM35 MTM85
36 TS4OFF MSV36 MSV86 MTM36 MTM86
37 TS5 MSV37 MSV87 MTM37 MTM87
38 TS5ON MSV38 MSV88 MTM38 MTM88
39 TS5OFF MSV39 MSV89 MTM39 MTM89
40 SUM MSV40 MSV90 MTM40 MTM90
41 MSV41 MSV91 MTM41 MTM91
42 MSV42 MSV92 MTM42 MTM92
43 MSV43 MSV93 MTM43 MTM93
44 MSV44 MSV94 MTM44 MTM94
45 MSV45 MSV95 MTM45 MTM95
46 MSV46 MSV96 MTM46 MTM96
47 MSV47 MSV97 MTM47 MTM97
48 MSV48 MSV98 MTM48 MTM98
49 MSV49 MSV99 MTM49 MTM99
50 MSV50 MTM50

69
● Read and Write Register Area
Address Address
0001 ~ 0050
0145 ~ 0150 Read Only
0900 ~ 1199
0100 ~ 0144
Read & Write
0200 ~ 0899

● NP_200 Bit Map Information


Data ALMSTS UOSTS DISTS ERRSTS NOWSTS PTSTS
Address 0013 0014 0015 0017 0018 0029
0 ALM1 UO1 DI1 RESET PT_UP
1 ALM2 UO2 DI2 CALL_ERR FIX PT_SOAK
2 ALM3 UO3 DI3 PV_POVR PROG PT_DOWN
3 ALM4 UO4 DI4 PV_MOVR HOLD
4 UO5 DI5 BOUT WAIT
5 UO6 DI6 RJC_ERR AT
6 UO7 DI7 ADC_ERR MAN
7 UO8 FERR
Bit
8 UO9 AT_ERR
9 UO10 SYS_ERR
10
11
12
13
14 COM_ERR
15

● Terms Description
D REGISTER Description
0001 NPV Current PV
0002 NSV Current SV
0004 SSV Start SV (Read the value when programing is running)
0005 MVOUT Current output amount
0006 HOUT Heating output amount
0007 COUT Cooling output amount
0008 PIDNO Current PID No.
0013 ALMSTS Alarm Status (Refer to Bit Map Information)
0014 UOSTS User Output Status (Refer to Bit Map Information)
0015 DISTS DI Status (Refer to Bit Map Information)
0017 ERRSTS ERROR Status (Refer to Bit Map Information)
0018 NOWSTS MODE Status (Refer to Bit Map Information)
0019 COMOP MODE SET (1:RUN/2:HOLD/3:STEP/4:RESET/5:FIX)
0020 CPTNOY Currently running Pattern Number
0021 CSGNO Currently running Segment Number
0022 CSGSV Currently running target value in segment
0023 CSGTM Currently running set time in segment
0024 RSGTM Elapsed time
0025 BRSGTM Remaining time
0026 BWRSGTM Waited time
0027 CRPT Current repetition number
0028 TRPT Repetition number in the current running pattern
0029 PTSTS Pattern Status (Refer to Bit Map Information)
0100 CMPT Operating Pattern Number
0101 COMOP MODE SET (1:RUN/2:HOLD/3:STEP/4:RESET/5:FIX)
0102 CMAM AUTO/MAN Switch (1:AUTO/2:MAN)
0103 CMMOUT Output by Manual

70
D REGISTER Description
0104 LEVEL Level PID G.Control
0106 ARW Anti-Reset Wind up G.PID
0107 TMU Time Unit G.Control
0108 DI Digital Input Enable G.Control
0109 PWR.MD Power ON Mode G.Control
0200 ISMD Inner Signal Mode G.IS
ISx Inner Signal x (X is the symbol that represents the IS number) G.IS
0201~0215 ISxH Inner Signal x High (X is the symbol that represents the IS number) G.IS
ISxL Inner Signal x Low (X is the symbol that represents the IS number) G.IS
0219 ENDTIME Time Unit G.Control
0300 SVNO Set Value No Select G.SV
0301~0304 SVx Set Value x (X is the symbol that represents the SV number) G.SV
0305 ATMD Auto Tuning Mode select G.AT
0306 AT Auto Tuning G.AT
0309 ALPHA Alpha G.PID
x.P proportional band (X is the symbol that represents the PID number) G.PID
x.I integration time (X is the symbol that represents the PID number) G.PID
x.D derivative time (X is the symbol that represents the PID number) G.PID
x.MR Manual reset (X is the symbol that represents the PID number) G.PID
0310~0347
x.PC Cooling proportional band (X is the symbol that represents the PID number) G.PID
x.IC Cooling integration time (X is the symbol that represents the PID number) G.PID
x.DC Cooling derivative time (X is the symbol that represents the PID number) G.PID
x.DB Heating/Cooling dead band (X is the symbol that represents the PID number) G.PID
0318 1.LVL PID Lecel 1 G.PID
0328 2.LVL PID Lecel 2 G.PID
0348 LVLD Reference DEV G.PID
AxTY Alarm Type (X is the symbol that represents the ALARM number) G.ALARM
0400~0411 AxDB Alarm Dead Band (X is the symbol that represents the ALARM number) G.ALARM
AL-x Alarm Point (X is the symbol that represents the ALARM number) G.ALARM
0412 ALMD Alarm Mode G.ALARM
0420~0429 UOx User Output (X is the symbol that represents the UO number) G.UO
0500 TRANS Transmission output selection G.TRANS
0501 TRANS.H Transmission output high value G.TRANS
0502 TRANS.L Transmission output low value G.TRANS
0503 ADJ.H Transmission output high correction value G.TRANS
0504 ADJ.L Transmission output low correction value G.TRANS
0510 PRS RS485, RS422 Protocol selection G.COMM
0511 BPS Baud Rate G.COMM
0512 PRI Parity G.COMM
0513 STP Stop Bit G.COMM
0514 DLN Data Length G.COMM
0515 ADR Address G.COMM
0516 RPT Response Time G.COMM
0520 UPDN Down/Up Key Lock G.LOCK
0521 PT.NO Pattern Number Lock G.LOCK
0522 RUN Run Key Lock G.LOCK
0523 A/M Auto/MAN Lcok G.LOCK
0524 PROG PROG Menu Lock G.LOCK
0525 OPER OPER Menu Lock G.LOCK
0526 FUNC FUNC Menu Lock G.LOCK
0527 P.INIT Parameter initialization G.LOCK
0528 F.INIT Program initialization G.FILE
0530 PWD Password Change G.LOCK
0600 OUT Output selection G.OUT
0601 O.ACT Direct/reverse action G.OUT
0602 HCT Heat cycle time G.OUT
0603 CTC Cool cycle time G.OUT

71
D REGISTER Description
0604 HYS Dead band (Hysteresis (ON/OFF control)) G.OUT
0605 HEO Heat Emergency Output G.OUT
0606 CEO Cool Emergency Output G.OUT
0607 OL-H Output high limit G.OUT
0608 OL-L Output low limit G.OUT
0610 INP Input type selection G.IN
0611 UNIT Input range unit selection G.IN
0612 FR-H Upper range G.IN
0613 FR-L Lower range G.IN
0614 DP-P Decimal point input G.IN
0615 SL-H High scale G.IN
0616 SL-L Low scale G.IN
0617 FILT PV bias G.IN
0618 BIAS PV bias G.IN
0619 B.OUT Show PV during input (sensor) disconnection G.IN
0620 RJC RJC ON/OFF G.IN
0621 U.UNIT User unit selection G.IN
0700 CPTNO_S Pattern number to edit or pattern number source to copy
0701 CPTNO_D Pattern number destination to copy
0702 CSEGNO Segment number to edit
0703 CFCMD Edit command [see below]
0704 CFANS Edit result [see below]
0800~0840 SEG value to edit (see program parameter)
0900 TUPT Total number of used patterns
0901~0930 NPTx Quantity of used segment in each pattern (X is the symbol that represents the pattern number)
0931 TUSEG Total number of used segments
1001~1099 MSVxx SV per each segment of the running pattern (xx is the symbol that represents the segment number)
1101~1199 MTMxx TM per each segment of the running pattern (xx is the symbol that represents the segment number)

● [see] CFCMD (D0703) : Edit command


Value command Description
1 INIT D0700~D0704 Init
2 FREAD After reading the CSEGNO of the CPTNO_S display it under the D0800
3 FWRITE Write the content under the D0800 in the CSEGN of the CPTNO_S
4 CPYPTF Copy the PT content of the CPTNO_S into the PT of the CPTNO_D
5 DELPTF Delete the PT of the CPTNO_S
6 INSSEG Insert in the CSEGNO of the CPTNO_S
7 DELSEG Delete the CSEGNO content of the CPTNO_S
8 PTUPLOAD After uploading the PT content of the CPTNO_S, show under the D1000

● [see] CFANS (D0704) : CFANS result


Value command Description
1 DONE Execution OK
2 NO PT No corresponding pattern (No SEG or Range Out)
3 NO SEG No corresponding pattern (No SEG content or Range Out)
4 PT RUN Correspondent Pattern running
5 PAR ERR Other command error

72
◼ Communication example (PC-LINK STD)
The example below is about the Pattern reading and writing after using the PC-LINK_STD protocol.
For the LINK-SUM, MODBUS RTU/ASCII please change the example below according to the protocol.
● READ EXAMPLE
1) Check the Seg quantity saved in each pattern of the NP200
Sender (STX) 01DRS,30,0901 (CR) (LF)
(STX) 01DRS,OK,0005,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,
Receiver
0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000 (CR) (LF)
2) Read PT=1, SEG=0 (execution command)
Sender (STX) 01DWR,03,0700,0001,0702,0000,0703,0002 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
3) Result check (execution result)
Sender (STX) 01DRR,01,0704 (CR) (LF)
Receiver (STX) 01DRR,OK,0001 (CR) (LF)
4) Check PT=1, SEG=0 content (result value)
Sender (STX) 01DRS,11,0800 (CR) (LF)
Receiver (STX) 01DRS,OK,0000,0000,0001,0000,F830,0000,000A,0000,0000,0001,000C (CR) (LF)
5) Read PT=1, SEG=1 (execution command)
Sender (STX) 01DWR,03,0700,0001,0702,0001,0703,0002 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
6) Result check (execution result)
Sender (STX) 01DRR,01,0704 (CR) (LF)
Receiver (STX) 01DRR,OK,0001 (CR) (LF)
7) Check PT=1, SEG=1 content (result value)
Sender (STX) 01DRS,21,0820 (CR) (LF)
(STX) 01DRS,OK,0000,0001,0000,0
Receiver
7D0,0005,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0064 (CR) (LF)

● WRITE EXAMPLE
1) Write PT=1, SEG=0 (PT=1, SEG=0 content deletion, command execution)
Sender (STX) 01DWR,03,0700,0001,0702,0000,0703,0005 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
2) Result check (execution result)
Sender (STX) 01DRR,01,0704 (CR) (LF)
Receiver (STX) 01DRR,OK,0001 (CR) (LF)
3) PT=1, SEG=0 selection
Sender (STX) 01DWR,02,0700,0001,0702,0000 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
4) Write to 800 address (write SEG0 value)
Sender (STX) 01DWS,10,0800,0000,0000,0001,0000,F830,0000,000A,0000,0000,0001 (CR) (LF)
Receiver (STX) 01DWS,OK (CR) (LF)
5) Write PT=1, SEG=0 (execution command)
Sender (STX) 01DWR,01,0703,0003 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
6) Check result (execution result)
Sender (STX) 01DRR,01,0704 (CR) (LF)
Receiver (STX) 01DRR,OK,0001 (CR) (LF)
7) PT=1, SEG=1 selection
Sender (STX) 01DWR,02,0700,0001,0702,0001 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
8) Write to 821 address (write SEGx value)
(STX) 01DWS,19,0821,0001,0000,0
Sender
7D0,0005,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000,0000 (CR) (LF)
Receiver (STX) 01DWS,OK (CR) (LF)
9) Write PT=1, SEG=1 (execution command)
Sender (STX) 01DWR,01,0703,0003 (CR) (LF)
Receiver (STX) 01DWR,OK (CR) (LF)
10) Result check (execution result)
Sender (STX) 01DRR,01,0704 (CR) (LF)
Receiver (STX) 01DRR,OK,0001 (CR) (LF)

73
MA0101E161020

www.hynux.com
HANYOUNG NUX CO.,LTD.
28, Gilpa-ro 71 beon-gil, Nam-gu, Incheon, Korea
Tel : +82-32-876-4697 Fax : +82-32-876-4696
E-mail : [email protected]