P14169 Formosa2 Protection V4
P14169 Formosa2 Protection V4
settings
P14169
prepared for:
Released by:
Peter Lilje, Ph. D.
Tel.: +49 7071 13879-17
Email.: [email protected]
2
P14169 – Wind farm Formosa 2 – Protection settings
Table of contents
1 Introduction .................................................................................................................................. 5
2 69kV Cable strings (CBs 610, 620, 630 and 640) ....................................................................... 7
2.1 Phase overcurrent protection (50/51/46) ................................................................................. 7
2.2 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 11
2.3 Breaker fail protection (50BF)................................................................................................ 13
3 69kV Shunt reactors (CBs 910, 920, 930 and 940) .................................................................. 15
3.1 Phase overcurrent protection (50/51) .................................................................................... 15
3.2 Reactor restricted earth fault protection (87N) ...................................................................... 17
3.3 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 17
3.4 Breaker fail protection (50BF)................................................................................................ 19
4 69kV Filters (CBs 810, 820) ....................................................................................................... 20
4.1 Phase overcurrent protection (50/51/46) ............................................................................... 20
4.2 Delay before energising protection (37 and 62) .................................................................... 21
4.3 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 22
4.4 Breaker fail protection (50BF)................................................................................................ 22
5 69/25kV Substation auxiliary transformer (CBs 590, 210)...................................................... 24
5.1 Transformer differential protection (87T) ............................................................................... 24
5.2 Transformer restricted earth fault protection (87N) ............................................................... 25
5.3 Phase overcurrent protection at 69kV (50/51) ....................................................................... 26
5.4 Phase-to-ground overcurrent protection at 69kV (50N/51N) ................................................. 28
5.5 Phase overcurrent protection at 23kV (50/51/46).................................................................. 29
5.6 Phase-to-ground overcurrent protection at 23kV (50N/51N) ................................................. 30
5.7 Breaker fail protection (50BF)................................................................................................ 30
6 23/0.40kV Substation LV transformer (CB 220) ....................................................................... 31
6.1 Phase overcurrent protection at 23kV (50/51) ....................................................................... 31
6.2 Phase-to-ground overcurrent protection at 23kV (50N/51N) ................................................. 32
7 69kV Busbars .............................................................................................................................. 34
7.1 Busbar differential protection (87B) ....................................................................................... 34
7.2 69kV Bus coupler (CB 600) ................................................................................................... 37
7.2.1 Phase overcurrent protection at 69kV (50/51) ............................................................... 37
7.2.2 Breaker fail protection (50BF) ........................................................................................ 37
8 161/69kV Wind farm transformers (CBs 710/20/30 and 1650/60/70) ...................................... 38
8.1 Transformer differential protection (87T) ............................................................................... 38
8.2 Transformer restricted earth fault protection (87N) ............................................................... 41
8.3 Phase overcurrent protection at 69kV (50/51/46).................................................................. 42
8.4 Phase-to-ground overcurrent protection at 69kV (50N/51N) ................................................. 45
3
P14169 – Wind farm Formosa 2 – Protection settings
4
P14169 – Wind farm Formosa 2 – Protection settings
1 Introduction
The company Fortune Electric Co., Ltd. (Fortune Electric) is planning the construction of the onshore
parts of the nearshore wind farm Formosa 2 in Taiwan, together with all required power system
studies. The wind farm will have 47 wind turbine generators of the type Siemens SG 8.0-167 DD;
60Hz. It will be connected to the 161kV transmission system. The wind farm voltage will be 69kV.
This document presents the proposed settings of the electrical protection relays. The protection
functions have been provided by Fortune Electric [1]. The settings are stated in terms of primary
voltages and currents. The values that must be entered into the relay may be secondary, % or per unit
values. These may depend on the specific version of the relay to be installed and must be derived by
the protection commissioning engineer from the primary values.
All current transformers have rated secondary currents of 5A [2]. It is recommended to ensure that the
burdens of all relay circuits do not lead to excessive saturation.
Figure 1 shows the topology of the onshore electrical system, including the circuit breakers (CBs) that
were considered in this study (numbers in red).
The symbol Apri is used throughout this document to mean Amperes on the primary side of the current
transformer.
5
P14169 – Wind farm Formosa 2 – Protection settings
Figure 1: Topology of onshore wind farm power system incl. circuit breaker numbers
6
P14169 – Wind farm Formosa 2 – Protection settings
The pickup current is set to approximately 110-120% of the cable rating, which allows temporary
operation at of the WTGs at 8.4MW and 1.08p.u. voltage. The current contribution from the WTGs will
be within 110% for their rated currents during fault conditions (944A for 12 WTGs).
The protection acts as a backup for the WTG transformer protection. It is noted that this backup
function has a limitation, because 2-ph faults on the secondary side of the last WTG in a string could
lead to faults currents in the order of the load currents i.e., they would not cause the overcurrent
protection in the CBs 610, 620, 630 or 640 to operate.
At currents above approximately 130% of the instantaneous phase overcurrent protection of the
WTGs, the tripping time is reduced to 200ms. This reduces the operating time compared to the IDMT-
characteristic at high fault currents.
The protection is also set to grade with that of the 10Mvar shunt reactors.
A negative-sequence definite-time overcurrent function is set to back up the protection on the HV side
of the WTG transformers in the event of unbalanced faults in the WTG transformers, leading to fault
currents that are not detected by the normal phase overcurrent protection. It is noted that the WTGs
control their negative sequence currents to zero during fault conditions. Table 4 shows that the
negative phase sequence overcurrent protection is slower than the phase overcurrent protection,
which ensures that the string is not disconnected prior to the WTG protection having had time to clear
WTG faults. The negative phase sequence protection also provides a backup to earth faults on the
690V side of the WTG transformers.
Description Setting
Definite time overcurrent, I> (7SR45) 102Apri
Time delay, I> (7SR45) 190ms
Instantaneous overcurrent, I>> (7SR45) 1443Apri
Definite time overcurrent, I> (7SJ82) 98Apri
Time delay, I> (7SJ82) 190ms
Instantaneous overcurrent, I>> (7SJ82) 1393Apri
Harmonic blocking Enabled
7
P14169 – Wind farm Formosa 2 – Protection settings
Table 2: Rated, operating and sub-transient fault currents at CBs 610, 620, 630 and 640
8
P14169 – Wind farm Formosa 2 – Protection settings
Table 3: Phase overcurrent protection at CBs 610, 620, 630 and 640 (7SJ85)
Description Setting
610 620 630 640
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT current pick-up 1032 Apri 1032 Apri 1032 Apri 1032 Apri
IDMT time multiplier 1.00 1.00 1.00 1.00
Stage 1-definite time overcurrent, I> 1800 Apri 1800 Apri 1800 Apri 1800 Apri
Stage 1-time delay, I> 200ms 200ms 200ms 200ms
Negative sequence, Stage 1-definite time 180 Apri 180 Apri 180 Apri 180 Apri
overcurrent, I2>
Negative sequence, Stage 1-time delay, I2> 500ms 500ms 500ms 500ms
Harmonic blocking (both +ve and -ve Enabled Enabled Enabled Enabled
sequence)
Figure 2: Phase overcurrent protection at 69kV CBs 610, 620, 630 and 640 and cable capabilities
9
P14169 – Wind farm Formosa 2 – Protection settings
Table 4: Calculated operating times for phase overcurrent and negative sequence overcurrent
protection
Description
Phase Operating Negative Operating
current time sequence time
current
(Apri) (s) (s)
(Apri)
Minimum 2-ph short-circuit current at most 3801 0.20 2195 0.50
remote WTG (69kV), with fault impedance 0%
of WTG transformer impedance, string interlink
closed, one 161/69kV wind farm transformer in
service, one 161kV cable in service
Minimum 2-ph short-circuit current at most 1121 None 647 0.50
remote WTG (69kV), with fault impedance 80%
of WTG transformer impedance, string interlink
closed, one 161/69kV wind farm transformer in
service, one 161kV cable in service
Maximum 3-ph short-circuit current at first WTG 16255 0.20 0 None
(69kV), all 161/69kV wind farm transformers in
service, all 161kV cables in service
Minimum short-circuit current for phase-to- 595 None 297 0.50
phase fault at most remote WTG (690V
terminals), string interlink closed, two 161/69kV
wind farm transformers in service, two 161kV
cables in service
Maximum short-circuit current for three-phase 23793 0.20 0 None
fault at terminals of reactor (69kV), three
161/69kV wind farm transformers in service,
two 161kV cables in service
Maximum short-circuit current for phase-to- 19169 0.20 11288 0.50
phase fault at terminals of reactor (69kV), three
161/69kV wind farm transformers in service,
two 161kV cables in service
Maximum 2-ph short-circuit current at terminals 19110 0.20 11288 0.50
of reactor (69kV), three 161/69kV wind farm
transformers in service, two 161kV cables in
service
10
P14169 – Wind farm Formosa 2 – Protection settings
An earth fault current in the offshore network leads to a residual current at all four string CBs in the
substation (610, 620, 630 and 640). Selective protection is achieved using time-grading of time-
dependent overcurrent protection.
The current measurement is set to measure the fundamental frequency component (standard, as
recommended by Siemens [4]).
Table 5 summarises the earth-fault protection settings of the WTG transformers [3] and Figure 3
shows them diagrammatically.
Description Setting
Instantaneous overcurrent, IG>> (7SR45) 24 Apri
Instantaneous overcurrent, IG>> (7SJ82) 12 Apri
Table 6 shows the fault currents through the bays 610-640 for various fault locations and operating
conditions. Both the residual currents (3Io) and the negative-sequence currents (I2) are shown.
Table 7 and Figure 3 show the proposed settings for the phase-to-ground protection.
11
P14169 – Wind farm Formosa 2 – Protection settings
Table 6: Sub-transient fault currents at CBs 610, 620, 630 and 640 for different operating and fault
conditions
12
P14169 – Wind farm Formosa 2 – Protection settings
Table 7: Phase-to-ground overcurrent protection at CBs 610, 620, 630 and 640 (7SJ85)
Description Setting
610 620 630 640
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT current pick-up, 3Io 180 Apri 180 Apri 180 Apri 180 Apri
IDMT time multiplier 0.05 0.05 0.05 0.05
Instantaneous overcurrent, 3Io>> 4608 Apri 4608 Apri 4608 Apri 4608 Apri
Figure 3: Phase-to-ground overcurrent protection, 69kV CBs 610, 620, 630, 640
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
13
P14169 – Wind farm Formosa 2 – Protection settings
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Table 8: Breaker fail protection at CBs 610, 620, 630 and 640 (7SJ85)
Description Setting
610 620 630 640
Phase current threshold for breaker closed 300 Apri 300 Apri 300 Apri 300 Apri
detection
14
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
910 920 930 940
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT current pick-up 120 Apri 120 Apri 120 Apri 120 Apri
IDMT time multiplier 0.09 0.09 0.09 0.09
Instantaneous overcurrent, I>> 500 Apri 500 Apri 500 Apri 500 Apri
Harmonic blocking Enabled Enabled Enabled Enabled
15
P14169 – Wind farm Formosa 2 – Protection settings
Figure 4: Overcurrent protection, 69kV CB 910 (shunt reactor, purple) and CB 610 (string cable, blue)
16
P14169 – Wind farm Formosa 2 – Protection settings
• The differential current is given by 𝐼𝐷𝑖𝑓𝑓,𝑅𝐸𝐹 = |𝐼𝑌∗ + 3𝐼𝑜∗ | , where 𝐼𝑌∗ refers to the star-point
current, 3𝐼𝑜∗ refers to the sum of the phase currents and * means that the ratios of the current
transformers have been considered.
• A minimum possible setting for the threshold current is specified (5% of the current
transformer rating). Using the current transformer primary current of 1200A, the minimum
threshold in Ampere is 0.05*1200A = 60A. Since the reactor rated current is 83.7A (based on
10MVA and 69kV), the minimum threshold in percentage of the reactor’s rated current is 72%.
Based on that, the threshold has been set at 75%.
• In the case of a shunt reactor, the sloped section can be set to the minimum value of 0.05. A
sensitive setting is possible because faults external to the reactor do not lead to saturation of
the reactor’s current transformers.
• The protection relay uses the phase angles of the currents to provide security against
maloperation whilst allowing sensitive settings to be used.
In the case of a single-phase to ground fault, the lowest fault current at the terminals of the reactor
occurs if only one of the 200MVA transformers is in service and amounts to 1100A. The fault current
reduces to 3Io=60A if the fault impedance is approximately 650Ω. This impedance exceeds the
reactors winding reactance of 476Ω, meaning that the restricted earth fault protection would cover the
entire winding.
Table 10: Shunt reactor restricted earth fault protection at CBs 610, 620, 630 and 640 (7SJ82)
Description Setting
Threshold 60 Apri
0.75 I/Irated,S
Intersection of the two straight lines 250 Apri
Slope 0.05
The current measurement is set to measure the fundamental frequency component (standard, as
recommended by Siemens [4]).
17
P14169 – Wind farm Formosa 2 – Protection settings
The pickup current is set to approximately 10% of the CT rated current. Very high currents, which can
only occur for faults in the respective shunt reactor, can be cleared instantaneously.
Table 11: Sub-transient currents at selected CBs for different operating and 1ph-ground short-circuit
conditions
Description Current at CB
640 910, 920,
930, 940
Maximum residual current 3Io for fault at terminals of shunt reactor 3453 Apri 282 - 3662
SR-1 Apri
Minimum residual current 3Io for earth fault at end of string D, one 1169 Apri 237 Apri
161/69kV wind farm transformer in service, strings A-D connected
Maximum residual current 3Io for earth fault at end of string D, string 2293 Apri 187 Apri
D interlink closed, three 161/69kV wind farm transformers in service,
strings A-D connected
Table 12 summarises the proposed settings and Figure 5 shows them diagrammatically.
Table 12: Phase-to-ground overcurrent protection at CBs 910, 920, 930 and 940 (7SJ82)
Description Setting
910, 920, 930, 940
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up, 3Io 30 Apri
IDMT time multiplier 0.10
Instantaneous overcurrent, I>> 500 Apri
18
P14169 – Wind farm Formosa 2 – Protection settings
Figure 5: Phase-to-ground overcurrent protection, 69kV CBs 910, 920, 930 and 940
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Table 13: Breaker fail protection at CBs 910, 920, 930 and 940 (7SJ82)
Description Setting
910 920 930 940
Phase current threshold for breaker closed 50 Apri 50 Apri 50 Apri 50 Apri
detection
19
P14169 – Wind farm Formosa 2 – Protection settings
Further protection is provided at component level. For example, the current unbalance between
capacitor groups is measured to detect capacitor failures. It must be ensured that the settings of any
thermal overload, additional overcurrent, overvoltage or current unbalance protection is not activated
during grid disturbances, which the wind farm has to ride through. For example, the filter should not
trip during temporary overvoltages (which lead to currents beyond the rated current) that occur due to
increases in the grid voltage. Such voltage increases will be corrected by the action of the wind farm
transformer tap changers (see also section 8.8).
Table 14: Phase overcurrent protection at CBs 810 and 820 (7SJ85)
Description Setting
810, 820
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up 150 Apri
IDMT time multiplier 0.10
Instantaneous overcurrent, I>> 750 Apri
20
P14169 – Wind farm Formosa 2 – Protection settings
Based on the specified discharge time of 10 minutes, as specified in [7], it is proposed to set the delay
to 15 minutes.
1 As an additional precaution, the filters can be discharged through their earth switches (after having discharged
through their built-in resistances) prior to re-energisation.
21
P14169 – Wind farm Formosa 2 – Protection settings
Table 15: Delay before re-energising at CBs 810 and 820 (7SJ85)
Description Setting
810, 820
Under-current to detect de-energisation, <I 60 Apri
Delay to detect energisation 3s
Delay before re-energisation 15 minutes
The pickup current of the relay is set to measure RMS currents and respond to the lowest possible
current, subject to the recommendation in [4] that for RMS current measurements the setting should
not be less than 10% of the secondary rated current. It is assumed that the multi-ratio current
transformer will be set at 300/5A.
Table 16 summarises the proposed settings and Figure 14 shows them diagrammatically, together
with the protection characteristics for the other 69kV substation bays.
Table 16: Phase-to-ground overcurrent protection at CBs 810 and 820 (7SJ85)
Description Setting
810, 820
Stage 1-definite time overcurrent, 3Io> 30 Apri
Stage 1-time delay, 3Io> 150ms
Instantaneous overcurrent, 3Io>> 120 Apri
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
22
P14169 – Wind farm Formosa 2 – Protection settings
Table 17: Breaker fail protection at CBs 810 and 820 (7SJ85)
Description Setting
810, 820
Phase current threshold for breaker closed detection 60 Apri
23
P14169 – Wind farm Formosa 2 – Protection settings
• The characteristic of the differential protection relay is shown in Figure 11, where the current
difference is given by Idiff = | I1 + I2 | and the restraint current by Irest. = Max (| I1|, | I2|), with I1
and I2 being the currents on either side of the transformer.
• The star-point of the 22.8kV-side is solidly grounded. The measurement of the CT in the star-
point connection is used by the differential protection. This improves the accuracy of
distinguishing between internal and external earth faults.
• The threshold setting is chosen based on the assumption that the setting of the tap setting is
not fed back to the relay. This leads to a tap changer correction value of kStS = 0.1 [6] and a
threshold setting of at least 0.27.
• The slope has been set assuming that the tap setting is not fed back to the relay and in
accordance with the recommendation in [6], leading to Slope 1 ≈ 2*1.2* kStS = 0.24.
• Current transformer errors can cause a non-zero current difference during normal operation.
Errors up to 10% have been considered.
• The setting for I-diff-unconstrained was set above the maximum expected inrush current,
using figure 6-48 in [6]. A further consideration was the maximum current on the 69kV-side of
the transformer, for a fault on 22.8kV-side. Currents higher than this must, therefore, be due to
faults inside the protected zone.
The main parameters of the transformers are shown in Table 18. The proposed settings are shown in
Table 19.
24
P14169 – Wind farm Formosa 2 – Protection settings
Parameter Value
Rated power (base for values below) 6 MVA
Rated voltage HV side 69kV ± 8*1.25%
Rated voltage LV side 22.8 kV
Rated current HV side at 69kV 50.2 A
Rated current LV side at 22.8kV 152 A
Short circuit voltage uk 10 %
Description Setting
• The differential current is given by 𝐼𝐷𝑖𝑓𝑓,𝑅𝐸𝐹 = |𝐼𝑌∗ + 3𝐼𝑜∗ | , where 𝐼𝑌∗ refers to the star-point
current, 3𝐼𝑜∗ refers to the sum of the phase currents and * means that the ratios of the current
transformers have been considered.
• A minimum possible setting for the threshold current is specified (5% of the current
transformer rating). Using the current transformer primary current of 200A, the minimum
25
P14169 – Wind farm Formosa 2 – Protection settings
threshold in Ampere is 0.05*200A = 10A. Since the transformer rated current is 152A, the
minimum threshold in per centage of the transformer rated current is 6.5%. Based on that, the
threshold has been set at a value higher than 0.065.
• The sloped section of the characteristic is typically set to start at a restraint current of 3 times
the rated current (in this case, 456 A). The slope is set at the threshold setting / 3.
• The protection relay uses the phase angles of the currents to provide security against
maloperation whilst allowing sensitive settings to be used.
Table 20: Substation auxiliary transformer restricted earth fault protection LV side at CB 590 (7UT85)
Description Setting
Description Current
26
P14169 – Wind farm Formosa 2 – Protection settings
Table 22 lists the proposed settings and Figure 7 shows the relay characteristics diagrammatically.
Description Setting
590
CT ratio 300 / 5
IDMT characteristic (IEC) Extremely
inverse
IDMT current pick-up 75 Apri
IDMT time multiplier 0.40
Instantaneous overcurrent, I>> 699 Apri
Harmonic blocking Enabled
Figure 7: Overcurrent protection at 69kV CBs 210 (red), 220 (blue), 590 (black) and 710 (purple), and
capability of 6MVA substation transformer TR-4
27
P14169 – Wind farm Formosa 2 – Protection settings
The current measurement is set to measure the fundamental frequency component (standard, as
recommended by Siemens [4]).
Description Setting
590
Stage 1-definite time overcurrent, 3Io> 30 Apri
Stage 1-time delay, 3Io> 150ms
Instantaneous overcurrent, 3Io>> 120 Apri
28
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 25 lists the proposed settings and Figure 8 shows the relay characteristics diagrammatically,
together with the characteristics of the upstream protection.
Table 25: Phase overcurrent protection at CB 210 (7SJ82)
Description Setting
210
CT ratio 200 / 5
IDMT characteristic (IEC) Extremely
inverse
IDMT current pick-up 168 Apri
IDMT time multiplier 0.30
Harmonic blocking Enabled
29
P14169 – Wind farm Formosa 2 – Protection settings
The protection should grade with that in CB 220 i.e., the protection of the 500kVA transformer.
The current measurement is set to measure the fundamental frequency component (standard, as
recommended by Siemens [4]).
Description Setting
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Description Setting
590
Phase current threshold for breaker closed detection 250 Apri
30
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 29 lists the proposed settings and Figure 8 shows the relay characteristics diagrammatically.
Description Setting
220
CT ratio 50 / 5
IDMT characteristic (IEC) Extremely
inverse
IDMT current pick-up 16 Apri
IDMT time multiplier 0.08
Instantaneous overcurrent, I>> 300 Apri
Harmonic blocking Enabled
31
P14169 – Wind farm Formosa 2 – Protection settings
Figure 8: Overcurrent protection at CB 210 (red), 220 (blue) and 590 (black), and capability of 500kVA
substation transformer Trf_Station
The pickup current is set to approximately 10% of the CT rated current. Very high currents, which can
only occur for faults in the respective shunt reactor, can be cleared instantaneously.
Table 30 summarises the proposed settings. The grading with the protection at CB 210 is shown in
Figure 9.
Description Setting
220
Definite time overcurrent, 3Io>> 5 Apri
Time delay, 3Io> 150ms
Instantaneous overcurrent, 3Io>> 25 Apri
32
P14169 – Wind farm Formosa 2 – Protection settings
33
P14169 – Wind farm Formosa 2 – Protection settings
7 69kV Busbars
7.1 Busbar differential protection (87B)
The busbar differential protection includes two zones, each of which includes one busbar and the bus
coupler. A check zone should be enabled for extra security, using the standard logic provided by
Siemens to prevent overstabilisation [8].
The settings have been determined using the recommendations provided by Siemens in [8], the main
considerations of which are as follows:
• The characteristic of the differential protection relay is shown in Figure 10, where the current
difference is given by Idiff = | I1 + I2 + …| and the restraint current by Irest. = | I1| + | I2 | + …,
with I1 and I2 etc. being the currents through the individual CBs.
• The rated current must be selected to exceed a tenth of the largest nominal current. In this
case the largest nominal current would be that of the bus coupler i.e., 2500A, so that the rated
current must exceed 250A. It can be set to equal the actual rated busbar current i.e., 2500A.
• The threshold Idiff determines the sensitivity of the protection in the case of low fault currents.
It should be set not higher than 80% of the lowest steady-state fault current and not lower than
130% of the highest operating current of all the feeders.
• The stabilisation factor k improves the stability in case of faults outside of the protected zone
but reduces the sensitivity of the detection of internal faults. Its setting considers measurement
errors of the current transformers. The manual includes a formula to calculate its setting,
based on the burden of the secondary circuit. These can be measured once the construction
has been completed.
• The single-phase-to-ground short-circuit currents can be lower than the load currents.
Therefore, it is recommended to use the additional sensitive characteristic at low values of
load current. Stability should be ensured by using additional criteria, such as under-voltage.
Such criteria have already been foreseen by Fortune Electric [1].
• The threshold Id for the sensitive characteristic should be set to the lowest fault current with a
20% margin. The sensitive characteristic ends at the setting Is, which should be set to the sum
of the magnitudes of the maximum load currents plus the single-phase to earth fault current
(plus 20% margin).
34
P14169 – Wind farm Formosa 2 – Protection settings
The following table summarises the currents used to determine suitable settings for the busbar
differential protection.
Table 31: Sub-transient fault currents used to determine setting for 69kV busbar protection
Description Current
Minimum busbar fault current (2-phase fault); one 161kV cable, one 5981 Apri
161/69kV transformer and no 69kV strings in service
80% of above minimum fault current 4785 Apri
Minimum busbar fault current (1-phase fault); one 161kV cable, one 983 Apri
161/69kV transformer and no 69kV strings in service
80% of above minimum fault current 786 Apri
Current through transformer, operating at 200MVA, 69kV 1673 Apri
130% of above current 2174 Apri
The following table shows the proposed settings. The relay settings (in %) depend on the selection of
rated current.
35
P14169 – Wind farm Formosa 2 – Protection settings
The setting for the stabilisation factor should be reviewed on site using measurements of the CT
burden.
The “area of higher sensitivity” should be activated based on the zero-sequence voltage Uo.
The threshold Id of the sensitive characteristic was set to about 50% of the single-phase fault current
with only one transformer in service. The threshold Is was selected to ensure that the area of higher
sensitivity can be activated over the entire operating range. Is was set at 120% of the maximum total
current, being the sum of the maximum individual feeder currents and the earth-fault current.
Table 32: 69kV busbar differential protection (7SS85)
Description Setting
36
P14169 – Wind farm Formosa 2 – Protection settings
The coupler has a continuous current rating of 2500A. The overcurrent protection is set marginally
below this to allow for CT errors.
Table 33 provides the proposed settings. These must be confirmed once the short-term capability of
the bus coupler is known.
Description Setting
600
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up 2400 Apri
IDMT time multiplier 0.40
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Description Setting
600
Phase current threshold for breaker closed detection 500 Apri
37
P14169 – Wind farm Formosa 2 – Protection settings
• The characteristic of the differential protection relay is shown in Figure 11, where the current
difference is given by Idiff = | I1 + I2 | and the restraint current by Irest. = Max (| I1|, | I2|), with I1
and I2 being the currents on either side of the transformer.
• The star-point of the 69kV-side is grounded via an NER. It is recommended to use the
measurement of the CT in the star-point connection to the NER. This improves the accuracy
of distinguishing between internal and external earth faults.
• The transformer tap changer can cause a non-zero current difference during normal operation.
The tap changer setting should be fed to the relay to allow relatively sensitive settings to be
used. This leads to a recommended threshold setting of 0.20.
• For slope 1, Siemens [6] recommends a minimum value of 0.30. For slope 2, at least twice
this value is recommended.
• Current transformer errors can cause a non-zero current difference during normal operation.
Errors up to 10% have been considered.
• The setting for I-diff-unconstrained was set above the maximum expected inrush current,
using figure 6-48 in [6]. A further consideration was the maximum current on the 161kV-side of
the transformer, for a fault on 69kV-side, which is approximately 3200A. Currents higher than
this must, therefore, be due to faults inside the protected zone.
The recommended settings are shown in Table 36.
38
P14169 – Wind farm Formosa 2 – Protection settings
Parameter Value
Rated power (base for impedances in this table) (ODAN) 120 MVA
Rated power with forced cooling (ODAF) 200 MVA
Primary side current at 200MVA, 161kV 717 A
Primary side current at 200MVA, 0.9 x 161kV 797 A
Secondary side current at 200MVA, 69kV 1673.5 A
Voltage HV side 161 kV
Voltage LV side 69 kV
Short circuit voltage uk range at nominal tap position 12 % @120MVA
Copper losses plus auxiliary losses 296 kW
Zero sequence impedance-Short circuit voltage uk0 12 % assumed
No load current 0.1% assumed
No load losses 105 kW
Vector group Dyn1
Additional voltage per tap 1.25 %
Minimum position -8
Maximum position 8
39
P14169 – Wind farm Formosa 2 – Protection settings
40
P14169 – Wind farm Formosa 2 – Protection settings
Table 36: Wind farm transformer differential protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
• The differential current is given by 𝐼𝐷𝑖𝑓𝑓,𝑅𝐸𝐹 = |𝐼𝑌∗ + 3𝐼𝑜∗ | , where 𝐼𝑌∗ refers to the star-point
current, 3𝐼𝑜∗ refers to the sum of the phase currents and * means that the ratios of the current
transformers have been considered.
• A minimum possible setting for the threshold current is specified (5% of the current
transformer rating). Using the current transformer primary current of 2000A, the minimum
threshold in Ampere is 0.05*2000A = 100A. Since the transformer rated current is 1673.5A
(based on 200MVA and 69kV), the minimum threshold in per centage of the transformer rated
current is 5.9%. Based on that, the threshold has been set at 6%.
• The sloped section of the characteristic is typically set to start at a restraint current of 3 times
the rated current (in this case, 5020 A). Based on that, the slope is set to 0.06/3 = 0.02.
• The protection relay uses the phase angles of the currents to provide security against
maloperation whilst allowing sensitive settings to be used.
41
P14169 – Wind farm Formosa 2 – Protection settings
The proportion of the secondary transformer winding, which is covered by the restricted earth fault
protection, can be estimated from the threshold current and the differential current that would flow
through the star point in the event of a single-phase to ground fault at the transformer terminals. For a
fault at the terminals, the differential current would amount to approximately 69kV*√3/40Ω = 1kA.
Therefore, the protection will cover approximately 90% of the winding.
Table 37: Wind farm transformer restricted earth fault protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
1650, 1660, 1670
Threshold 0.06 I/Irated,S
i.e., 100 Apri
Intersection of the two straight lines 5020 Apri
Slope 0.02
42
P14169 – Wind farm Formosa 2 – Protection settings
The fault current through the circuit breakers at 710, 720 and 730 for faults in the 69kV offshore
system depend highly on the number of wind farm transformers in service and on the distance of the
fault from the substation. Some faults lead to currents close to the maximum load currents, so that the
phase overcurrent protection cannot always back up the protection at 610 – 640, or the operating
times of the backup phase current protection are very high. To achieve reasonable operating times for
the backup protection function, it is recommended to make use of definite-time overcurrent protection.
To ensure that the backup protection provides extensive coverage, a relatively low current pickup
setting is proposed. The recommended settings are shown in Table 39 and Figure 13. The backup
protection extends up to about the second last 69kV-node in the strings under worst-case conditions
(minimum phase-to-phase fault). Such a fault is likely to develop into one includes an earth current,
which is covered by further protection and backup protection.
If a short-current through the circuit breaker exceeds the maximum value that it could reach in the
event of a 69kV busbar fault, then the short-circuit must be on the transformer side of the circuit
breaker (being fed through the 69kV system from remaining transformers as well as the WTGs). In this
case, the circuit breaker can be tripped with minimal delay.
Table 38: Rated currents and sub-transient fault currents at CBs 710, 720 and 730 for different
operating and fault conditions
Description Current
43
P14169 – Wind farm Formosa 2 – Protection settings
Table 39: Phase overcurrent protection at CBs 710, 720 and 730 (7SJ85)
Description Setting
Figure 13: Overcurrent protection, 69kV CBs 710, 720 and 730 (wind farm transformers, purple)
44
P14169 – Wind farm Formosa 2 – Protection settings
Table 40 summarises the proposed settings and Figure 14 shows them diagrammatically.
Table 40: Phase-to-ground overcurrent protection at CBs 710, 720 and 730 (7SJ85)
Description Setting
710, 720, 730
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up 300 Apri
IDMT time multiplier 0.12
45
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 42: Phase overcurrent protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
1650, 1660, 1670
IDMT characteristic (IEC) IEC standard
inverse
IDMT current pick-up 990 Apri
IDMT time multiplier 0.25s
Stage 1-definite time overcurrent, I> 2100 Apri
Stage 1-time delay, I> 0.65 s
Instantaneous overcurrent, I>> 5250 Apri
Harmonic blocking Enabled
46
P14169 – Wind farm Formosa 2 – Protection settings
Figure 15: Overcurrent protection at 161kV CBs 1650, 1660 and 1670 and 69kV CBs 710, 720 and
730
The pickup current is set to approximately 10% of the CT rated current. An instantaneous element is
added for the case of very high fault currents.
Table 43 summarises the proposed settings and Figure 16 show the protection characteristic
graphically.
Table 43: Phase-to-ground overcurrent protection at CBs 1650, 1660, 1670 (7UT85)
Description Setting
1650, 1660, 1670
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up, 3Io 150 Apri
IDMT time multiplier 0.05
Instantaneous overcurrent 3000 Apri
47
P14169 – Wind farm Formosa 2 – Protection settings
Figure 16: Phase-to-ground overcurrent protection, 161kV CBs 1650 and 1660
Table 43 summarises the proposed settings and the characteristic is shown in Figure 17.
Description Setting
48
P14169 – Wind farm Formosa 2 – Protection settings
49
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
710, 720, 730
Undervoltage, U< 62.1 kV (90% of 69kV)
Time delay, U< 30s
Phase overvoltage, U> 72.5 kV
(100% of rated voltage,
105% of 69kV)
Time delay, U> 60s
50
P14169 – Wind farm Formosa 2 – Protection settings
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Table 46: Breaker fail protection at CBs 710, 720 and 730 (7SJ85)
Description Setting
710, 720,
730
Phase current threshold for breaker closed detection 500 Apri
Table 47: Breaker fail protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
1650, 1660,
1670
Phase current threshold for breaker closed detection 1200 Apri
51
P14169 – Wind farm Formosa 2 – Protection settings
9 161kV Busbars
9.1 Busbar differential protection (87B)
The busbar differential protection includes two zones, each of which includes one busbar and the bus
coupler.
The settings have been determined using the recommendations provided by Siemens in [8], the main
considerations of which are as follows:
• The characteristic of the differential protection relay is shown in Figure 10, where the current
difference is given by Idiff = | I1 + I2 + …| and the restraint current by Irest. = | I1| + | I2 | + …,
with I1 and I2 etc. being the currents through the individual CBs.
• The rated current must be selected to exceed a tenth of the largest nominal current. In this
case the largest nominal current would be that of an export cable, which is around 1400A. The
rated current has to exceed 140A. It can be set to the actual rated current of the busbar i.e.,
2000A.
• The threshold Idiff determines the sensitivity of the protection in the case of low fault currents.
It should be set not higher than 80% of the lowest steady-state fault current and not lower than
130% of the highest operating current of all the feeders.
• The stabilisation factor k improves the stability in case of faults outside of the protected zone
but reduces the sensitivity of the detection of internal faults. Its setting considers measurement
errors of the current transformers. The manual includes a formula to calculate its setting,
based on the burden of the secondary circuit. These can be measured once the construction
has been completed.
• Since the minimum fault current is not in the range of the load current, no additional sensitive
characteristic is foreseen.
The following table summarises the currents used to determine suitable settings for the busbar
differential protection.
Table 48: Fault currents used to determine setting for 161kV busbar protection
Description Current
52
P14169 – Wind farm Formosa 2 – Protection settings
The setting for the stabilisation factor should be reviewed on site using measurements of the CT
burden.
Description Setting
53
P14169 – Wind farm Formosa 2 – Protection settings
According to [14], the ratios of the multi-ratio current transformers have been selected at 3000A:5A.
The rated current of the cable could be set according to 1485 A (Table 57). The threshold I-DIFF is set
approximately 20% of the rated current (note that the use of the special charging compensation
function would allow a lower setting [13]). The fast stage I-DIFF fast 2 is set to approximately twice the
rated current of the cable.
A relay trip signal shall lead to the tripping of all three phases.
54
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
The first zone of the distance protection shall act as a backup to the cable differential protection (87L).
It is set to approximately 80% of the cable length so as not to risk tripping prior to the tripping of
downstream protection.
The distance relays shall be set up for direct inter-tripping i.e., if either of the relays at Ying-Pan end
sees a fault in its zone 1, it shall send tripping signals to both the local-end and remote-end circuit
breaker of the faulted line.
A second zone is set to reach into the wind farm, thereby acting as a backup to the 200MVA wind farm
transformer protection. It shall be time-delayed and reach into, but not beyond the wind farm
transformers.
The relays at the Ying-Pan end should trip the breakers at Ying-Pan immediately if the fault is seen in
the overreaching zone (zone 2) and the remote circuit breaker is open. This is typically done using the
echo logic i.e., the relays at F2 shall be set up to send an echo signal.
Distance relays typically require a source-to-line impedance ratio (SIR) of at most 50 to estimate the
impedance with sufficient accuracy. The fault current from the wind farm depends on the number of
WTGs in operation. With all WTGs in operation, the fault current is limited to approximately 110% of
rated wind farm current (1.5kA). This relates to a source impedance of 63Ω. The cable impedance is
around 0.86Ω, so that the SIR is around 73. With half the number of WTGs in operation, this increases
to 126. Therefore, it cannot be assumed that a distance relay at F2 would always measure the
impedance to the fault correctly, especially if the fault is close to F2. It is, therefore, proposed to make
use of the weak infeed logic.
If the relays at Ying-Pan see the fault in zone 2, and no blocking signal is received from the relays at
F2, then they shall trip the circuit breakers at the Ying-Pan end. The blocking signal shall be generated
by the relays at F2 if they see the fault in their reverse zone i.e., behind them, such as in the wind farm
transformers.
The weak infeed logic should be set up to make use of a voltage measurement at F2. They shall trip
the breakers at F2 with minimal delay if they receive a permissive signal from the relays at Ying-Pan
and do not see the fault in their reverse zones e.g., in the wind farm transformers.
55
P14169 – Wind farm Formosa 2 – Protection settings
If the relays at F2 see the fault in their reverse zone (zone 3), they send a blocking signal to the relays
at Ying-Pan.
It is recommended that the weak infeed logic is always operational i.e., not to make it dependent on
the operating state of the wind farm.
The reverse-looking zone 3 at F2 shall reach beyond the overreaching zone at Ying-Pan to prevent a
mal-operation of the weak infeed logic.
The proposed relay (Siemens SIPROTEC 7SL86) allows the setting of many possible impedance
shapes – see Figure 19. It is proposed to use quadrilaterals. The inclination characteristic defined by
the angle α is not used.
The resistive reach depends mainly on the resistance of the cable. Some allowance is made for the
resistance of an arc, which could occur at the cable termination.
56
P14169 – Wind farm Formosa 2 – Protection settings
Table 51: System data and currents at CBs 1550, 1560, 1610 and 1620 for different operating and
fault conditions
Description Value
VT ratio 161000V/√3:115V/√3
CT ratio 3000/5
Positive-sequence resistance of 161kV cables [12] 0.04852Ωpri
Positive-sequence reactance of 161kV cables [12] 0.8573 Ωpri
Positive-sequence impedance of 161kV cables 0.86 Ωpri, 86.8°
Zero-sequence impedance of 161kV cables [12] 1.95 Ωpri, 58.8°
Rated current of cable, n-1 [15] 1485 Apri
Impedance of one 200MVA transformers at 161kV 25.9Ω
Half of impedance of three parallel 200MVA transformers at 161kV 4.3Ω
Minimum short circuit current at Ying-Pan for 2-phase fault at 69kV-side of 3060 Apri
transformer, one 161kV cable and one 200MVA transformer in service
Minimum short circuit current at Ying-Pan for 2-phase fault at 161kV- 5036 Apri
terminals of transformer with 8Ω fault reactance, both 161kV cables in
service
Maximum short-circuit current at Ying-Pan, three-phase fault at 161kV/F2 30 000 Apri
and one 161kV cable in service
Minimum short circuit current at Ying-Pan, 2-phase fault with 5Ω reactance 11 615 Apri
at the 161kV-terminals of a 200MVA transformer, other two transformers
out of service, one 161kV cable and one 200MVA transformer in service
Impedance seen at POC for worst-case loading (including some margin):
R+jX as seen at the POC at 161kV, 400MW, 0Mvar 64.8+j0 Ωpri
R+jX as seen at the POC at 161kV, 400MW, 0.9 power factor 52.5±j25.4 Ωpri
57
P14169 – Wind farm Formosa 2 – Protection settings
Table 52: 161kV cable distance protection at CBs 1550, 1560, 1610 and 1620 (7SL86)
Description Setting
General
Characteristic Quadrilateral, forward
Relay characteristic angle, 𝜑𝐷𝑖𝑠𝑡 86°
Pickup method Impedance
Minimum current to enable pickup 150Apri
Other • Direct intertripping from Yin-Pan
• Weak infeed logic at F2
58
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
1610, 1620
Description Setting
CT ratio 3000 / 5
Stage 1-definite time overcurrent, directional I> 2000 Apri
Stage 1-time delay, directional I> 0.15s
59
P14169 – Wind farm Formosa 2 – Protection settings
The settings are summarised in Table 43 and shown in and Figure 21.
Table 55: Sub-transient fault currents at CBs 1610 and 1620 for different operating and fault
conditions (7SL86)
Description Current
Minimum current 3Io for single phase to ground short circuit at 161kV busbar 10685 Apri
of F2, both 161kV cables in service
Minimum current 3Io for single phase to ground short circuit at 161kV busbar 18798 Apri
of F2, one 161kV cables in service
Table 56: Phase-to-ground directional overcurrent protection at CBs 1610, 1620 (7SL86)
Description Setting
1610, 1620
IDMT characteristic (IEC) Standard
inverse
IDMT current pick-up, directional 3Io 420 Apri
IDMT time multiplier 0.10
60
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
61
P14169 – Wind farm Formosa 2 – Protection settings
Table 58: Phase overcurrent protection at CBs 1550 and 1560 (7SL86)
Description Setting
1550, 1560
CT ratio 3000 / 5
IDMT characteristic (IEC) Standard inverse
IDMT current pick-up 1650 Apri
IDMT time multiplier 0.22
Stage 1-overcurrent, I> 6300 Apri
Stage 1-time delay, I> 250 ms
Harmonic blocking Enabled
Figure 20: Overcurrent protection, 161kV CBs at Yin-Pan and F2 substations (purple, 1550, 1560,
1610, 1620) and transformer bays at F2 (green, 1650, 1660 and 1670)
62
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
1650, 1660,
1670
IDMT characteristic (IEC) Standard
inverse
IDMT current pick-up, 3Io 420 Apri
IDMT time multiplier 0.10
Figure 21: Phase to ground overcurrent protection, 161kV CBs at Yin-Pan substation bays (1550,
1560 in red), F2 substation bays (1610 and 1620 in blue) and transformer bays at F2 (1650, 1660 and
1670 in green)
63
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
64
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
1550, 1560
Underfrequency, <f (81L) 58Hz
Time delay, <f 2s
Overfrequency, >f (81H) 61Hz
Time delay, >f 2s
The circuit breaker shall be considered closed if any phase current exceeds approximately half of the
minimum fault current. It is not required to make use of separate current thresholds such as 3Io or I2.
In the event of a breaker failure detection, the protection function shall issue a second trip signal to the
circuit breaker. If the breaker failure condition persists, remote circuit breakers shall be tripped
according to the logic specified in the protection philosophy [5].
Table 62: Breaker fail protection at CBs 1610 and 1620 (7SL86)
Description Setting
1610, 1620
Phase current threshold for breaker closed detection 5000 Apri
65
P14169 – Wind farm Formosa 2 – Protection settings
66
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
1550, 1560
Undervoltage, U< 144.9kV (90%)
Time delay, U< 3.5s
Phase overvoltage, U> 177.1kV (110%)
Time delay, U> 2.0s
Residual overvoltage, 3Vo 30%
Time delay, U> 2s
67
P14169 – Wind farm Formosa 2 – Protection settings
The settings have already been agreed with TPC. These are shown in Table 64.
Description Setting
68
P14169 – Wind farm Formosa 2 – Protection settings
12 References
[1] Fortune Electric, “Formosa 2 On Shore Work Detailed design meeting No. 12th, Presentation,”
10. Dec. 2019.
[3] Siemens, “D8 60Hz 66kV Relay Settings; Fortune Electric Document F2-WTG-CON-SGR-SP-
EL-00002[00],” 06.08.2019.
[4] Siemens, “SIPROTEC 5, Version 8.01 and higher, Overcurrent Protection 7SJ82, 7SJ85, Manual
C53000-G5040-C017-B”.
[6] Siemens, “SIPROTEC 5, Version 8.01 and higher, Transformer Differential Protection 7UT82,
7UT85, 7UT86, 7UT87, Manual C53000-G5040-C016-C”.
[8] Siemens, “SIPROTEC 5, Version 8.30 and higher, Low-Impedance Busbar Protection, 7SS85,”
Manual C53000-G5040-C019-A.
[10] FORTUNE ELECTRIC CO., LTD., SPECIFICATION FOR TRANSFORMER TR19025; F2-ONS-
CON-FOR-LY-EL-00002-002, 2019/10/18.
[11] Email from Fortune Electrical (Breeze Yeh), “Re: URGENT - TPC SLD & Protection Settings
Agreed Strategy,” 12.05.2021.
[12] MPE GmbH, “Wind farm Formosa 2; Load flow and short-circuit report, Version 5,” 28.01.2021.
[13] Siemens, “SIPROTEC 5, Version 8.30 and higher, Distance Protection, Line Differential
Protection, and Overcurrent Protection for 3-Pole Tripping, 7SL86 etc.,” C53000-G5040-C010-D.
[14] Fortune Electric Co., “Formosa 2 Offshore Wind Farm Project, Protection Philosophy; F2-ONS-
CON-FOR-ST-EL-00021; Version 5,” 28 January 2021.
[15] MPE, “Wind farm Formosa 2: Cable sizing study; Version 2,” 15.04.2021.
[16] TPC, Taiwan Power Company's Technical Guidelines for the Parallel Connection of Renewable
Energy Power Generation Systems.
69
P14169 – Wind farm Formosa 2 – Protection settings
[17] Siemens Wind Power, “D12 Wind Turbine Voltage and Frequency Limits, Type 3; F2 document
number F2-WTG-CON-F2-CD-EL-00013,” 07.03.2019.
70