ESD3 Manual 2016
ESD3 Manual 2016
1. DESCRIPTION:
E-687 is designed as a controller for refrigerant type compressed air dryers. The controller has 8
temperature sensor inputs. Each channel can be configured for type J, type K thermocouple or Pt-
100 resistance thermometer. These inputs are used to measure the temperatures at various points
in the dryer. The controller has also 8 digital (relay) outputs and 16 digital inputs. The digital
outputs are taken through the normally open contacts of the output relays. The contact rating of
the output relays are 10A at 250 V AC. Digital inputs are activated by 24V DC or AC.
The controller has an RS-485 communication interface that can be used for remotely monitoring
channel temperatures, set points, input and output states. Modbus RTU protocol is used for
communication.
The front panel of the controller contains a four line 20 character LCD display and buttons that are
used in configuration and manual control operations.
The dimensions of the controller are 96 x 192 mm (front panel) with a depth of 110 mm. The panel
cutout should be 90x185 mm. The operating voltage of the controller is 20 - 60V AC or 20 - 85V DC.
2. OPERATION:
The front panel view of E-687 controller is given in Figure 2.1. The front panel of the controller
contains a four line 20 character LCD display, 10 buttons and 2 indicator leds.
button is used to enable or disable the ECO (economy) mode. Pressing this button complements
the state of ECO, i.e. if it is enabled; disables, if it is disabled; enables the ECO mode. The green
led on the left side of the button lights if the ECO mode is enabled. When ECO mode is enabled
and the exchanger temperature is less than or equal to “ECO Start Set point” and this condition is
prevailed more than “ECO Start Delay”, then, the compressor motor is stopped and ECO operation
starts. ECO operation ends when the exchanger temperature reaches to the “ECO end Set point” or
ECO mode is disabled. Disabling ECO mode also resets the ECO Start Delay timer.
button is used for manual control of the drain output. While in normal operation, the drain
output is controlled according to the configured “drain on” and “drain off” periods. When button
is pressed the drain output is activated even if the dryer is in off state.
button is used for alarm acknowledge. The dryer is automatically stopped if an anomaly is
detected. In that case, the alarm output and the alarm indicator led (red) on the front panel
become activated. In order to restart the dryer, alarm should be acknowledged and “restart delay”
period should be timed out. Pressing button acknowledges the alarm and reenergizes the alarm
output and alarm led.
The buttons below the LCD display ( , , and ) are used in screen selection and
configuration operations.
button is used to change the temperature unit from ºC to ºF or vice versa. When this button is
pressed, the control operation stops about 3 seconds and all the temperature values are converted
to the selected unit.
and buttons are used for starting and stopping the dryer respectively. If the dryer is stopped
manually, it can not be started before “restart delay” period is timed out.
, , , , and buttons are disabled during configuration operations.
2. 1. External Connections:
The back panel view and the connection terminals of E-687 controller are given in Figure 2.2.
̓
TABLE 2.1
The digital outputs are taken through the normally open contacts of the output relays. The contact
rating of the output relays are 10A at 250 V AC. The schematic layout of the digital output circuits is
given in Figure 2.3. The terminals 7 and 14 have no internal connection.
Figure 2.3. The Digital Output Circuits.
Digital inputs are activated by 24V DC or AC. Each digital input terminal is internally connected to
the input of an optocoupler. The return terminals of the optocouplers are connected to the common
terminals of the digital inputs (terminals 15, 16 and 17). The schematic layout of the digital input
circuits is given in Figure 2.4. Optocouplers provide galvanic isolation between external and internal
circuits.
Active state of the digital inputs is software configurable, except D.INPUT 1, 2 and 10. For those
digital inputs to be active 24V should be applied to the input.
TABLE 2.2
TERM. N. NAME FUNCTION
1 L
2 N Operation Voltage (20-60V AC/20-85V DC)
3 Ground
4 -P1
Pulse Input 1. (not used in this application)
5 +P1
6 -P2
Pulse Input 2. (not used in this application)
7 +P2
8 +TS
24V Transmitter Supply. (not used in this application)
9 -TS
10 +AO1
Analog Output 1 (4-20 mA)
11 -AO1
12 +AO2
Analog Output 2 (4-20 mA)
13 -AO2
14 GND
15 TRXA RS-485 Communication Line
16 TRXB
17 AIC Analog Input Common. (Internally connected to the (-) terminals of the
18 AIC analog input channels).
19 -AI1
Analog Input Channel 1. (Inlet Air Temperature)
20 +AI1
21 -AI2
Analog Input Channel 2. (Exchanger Temperature)
22 +AI2
23 -AI3
Analog Input Channel 3. (Low Pressure Line Temperature)
24 +AI3
25 -AI4
Analog Input Channel 4. (High Pressure Line Temperature)
26 +AI4
27 -AI5
Analog Input Channel 5. (Ambient Temperature)
28 +AI5
29 -AI6
Analog Input Channel 6. (Condenser Outlet Temperature)
30 +AI6
2. 2. Operation Screens:
2. 2. 1. The Normal Operation Screen:
When the controller is powered on, it displays the type and version message, and then the restart
delay timer is set to 5 seconds. After 5 seconds, the normal operation screen is displayed as shown
NO NAME
in Figure 2.5.
Figure 2.5.
The exchanger temperature (Dew Point) and operation state of the dryer is displayed in this screen.
If there is a situation which will prevent the operation of the dryer then the “READY” message in
the last line will become “DISABLED”. See Figure 2.6.
NO NAME
Figure 2.6.
NO NAME
Figure 2.7.
In the beginning, Digital Output 1 (Compressor Motor), Digital Output 2 (Drain Output) and Digital
Output 3 (Dryer is Running) become active. While in normal operation, the drain output is
controlled according to the configured “drain on” and “drain off” periods. “DRAIN ON” message is
displayed in the end of the last line while the drain output is active.
When the Digital Input 9 (Fan Motor is on) is activated, “FAN MOTOR IS ON” message is displayed
in the second line as shown in Figure 2.8.
NO NAME
FAN MOTOR IS ON
DEW POINT . 16°C
RUNNING
Figure 2.8.
Digital Input 14 (Water Pump is on) activates “WATER PUMP IS ON” message as shown in Figure
NO NAME
WATER PUMP IS ON
DEW POINT . 16°C
RUNNING
2.9.
Figure 2.9.
When ECO mode is enabled and the exchanger temperature is less than or equal to “ECO Start Set
point” and this condition is prevailed more than “ECO Start Delay”, then, the compressor motor is
stopped and ECO operation starts. During the ECO operation the appearance of the display is given
in Figure 2.10. The value at the end of the second row indicates the time in seconds since beginning
NO NAME
ECO(SEC.) : 324
DEW POINT . 1°C
RUNNING
Figure 2.10.
Pressing and keys simultaneously at this page toggles the controller between automatic and
manual mode. In manual mode, the dryer starts and stops manually by using and buttons.
Unlike the manual mode, automatic mode enables the controller start and stop automatically at
pre-programmed times on a daily basis
When running in automatic mode, current scheduling information messages are also activated in the
second line of the displays as show in Figure 2.11. “NOT SCHEDULED” message is displayed when no
schedule exists. “START IN XXX” shows the time to the next scheduled program in minutes and
“STOP IN XXX” message shows the time to the end of current running program in minutes.
Figure 2.11.
If the dryer is stopped manually by using button, or activating Digital Input 2 (Remote Stop) or
deactivating Digital Input 13 (Remote Control), the normal operating screen is displayed as shown in
Figure 2.12. The number at the end of the last line indicates the remaining time in seconds from the
restart delay. If this number becomes zero and there is no anomaly, the dryer can be restarted.
NO NAME
The first line in the normal operation screen (NO NAME) is user configurable.
If the exchanger temperature sensor is broken, dew point temperature will be displayed as 1000ºC.
In Screen2, Screen3 and Screen4, the sensor temperatures are displayed. If the measured
temperatures are between their low and high limits, only the temperature value is displayed,
otherwise “LOW” or “HIGH” message is added in the end of the line. In case of sensor break, only
“SENSOR BREAK” message is displayed.
In screen 5 and 6 the states of the compressor motor, fan motor, the phase sequence, remote
disable and air pressure are displayed. Actually this data is derived from the digital inputs.
The message in the first line of Screen5 is determined by Digital Input 3 and Digital Input 4
(Compressor Fault and Compressor Overload). TABLE 2.4 shows the relation between digital inputs
and the message.
TABLE 2.4
Digital Input 3 Digital Input 4 Message
Not Activated Not Activated COMPRESSOR OK
Activated Not Activated COMPRESSOR FAULT
Not Activated Activated COMP.OVERLOAD
Activated Activated COMP.OVERLOAD
The message in the second line of Screen5 is determined by Digital Input 5 and Digital Input 6 (Fan
Fault and Fan Overload). TABLE 2.5 shows the relation between digital inputs and the message.
TABLE 2.5
Digital Input 5 Digital Input 6 Message
Not Activated Not Activated FAN MOTOR OK
Activated Not Activated FAN MOTOR FAULT
Not Activated Activated FAN MOT.OVERLOAD
Activated Activated FAN MOT.OVERLOAD
The message in the third line of Screen5 is determined by Digital Input 7. If this input is not
activated the message will be “PHASE SEQUENCE OK”, otherwise “PHASE SEQ.ERROR”.
The message in the fourth line of Screen5 is determined by Digital Input 8. If this input is not
activated the message will be “REMOTE CONTROL OK”, otherwise; “REMOTE DISABLE”.
The message in the first line of Screen6 is determined by Digital Input 11 and Digital Input 12 (High
Air Pressure and Low Air Pressure). TABLE 2.6 shows the relation between digital inputs and the
message.
TABLE 2.6
Digital Input 11 Digital Input 12 Message
Not Activated Not Activated PRESSURE OK
Activated Not Activated HIGH PRESSURE
Not Activated Activated LOW PRESSURE
Activated Activated HIGH PRESSURE
The second, the third and the fourth lines of Screen6 are empty.
Screen7 displays the operation durations in hours. In the first two line of Screen7 the total and ECO
operation durations of the dryer are displayed. These values can not be reset. The third line
displays the run time since the last maintenance. The fourth line indicates the filter usage time. If
these durations exceed their set values (general maintenance period and filter change period), a
flashing warning with a message “MAINTENANCE” or “REPLACE FILTER” is displayed in the fourth
line of the display.
IMPORTANT NOTICE:
FILTER CHANGE PERIOD IS 8000 HOURS
GENERAL MAINTENANCE PERIOD IS 20 000 HOURS
NO NAME PRESSURE OK
Figure 2.13.
Screen8 displays the last four events that caused the dryer to be stopped automatically. The
possible alternatives for the messages are given below.
INLET AIR TEMP.LO
INLET AIR TEMP.HI
EXCH.TEMP.LO
EXCH.TEMP.HI
LO.PRES.L.TEMP.LO
LO.PRES.L.TEMP.HI
HI.PRES.L.TEMP.LO
HI.PRES.L.TEMP.HI
AMB.TEMP.LO
AMB.TEMP.HI
COMPRESSOR FAULT
COMP.OVERLOAD
FAN MOTOR FAULT
FAN MOT.OVERLOAD
PHASE SEQ.ERROR
REMOTE DISABLE
PRESSURE HIGH
PRESSURE LOW
CONDENSER FAULT
Screen10 displays the states of the digital inputs and digital outputs. The letters ‘L’ and ‘H’ stands
for ‘not activated’ and ‘activated’ states respectively.
The data in the first line of Screen10 (D.INPUT1), from right to left corresponds to Digital Input 1
to 8.
The data in the second line of Screen10 (D.INPUT2), from right to left corresponds to Digital Input
9 to 16.
The data in the third line of Screen10 (D.OUTPUT), from right to left corresponds to Digital Output
1 to 8.
Secreen11 displays automatic mode scheduling of the day. Please see Section 2.3.3 for scheduling
and see Figure 2.11 for auto/manual selection.
2. 3. Configuration Mode:
In order to enter into configuration mode, button must be pressed at least 3 second duration.
After this operation security code is asked. Security code is adjusted by and buttons. After
adjusting the security code and pressing button, accesses the “General Parameters Page”. Here,
and buttons can be used to select the other pages. When a page is selected, pressing
button accesses the first parameter in that page. Successively pressing button will display the
other parameters in that page. After the last parameter or pressing button more than two
seconds, reverts to the top of that page where a different page can be selected. When a parameter
is selected, its value can be edited by and buttons. In anywhere in the configuration pages,
pressing button quits the configuration mode and reverts to the normal operation screen.
If the entered security code is not correct, all the parameters except “Security Code” parameter in
the “General Parameters Page” can be accessed but no modification is allowed.
The value of the security code is determined by the parameter “Security Code” in the “General
Parameters Page”. The factory setting of the security code is “10”.
The Configuration Pages and the parameters in the configuration pages are given below.
NO NAME _
MESSAGE TEXT
32
Figure 2.14.
The position of the cursor is adjusted by (to the left) and (to the right)
buttons. and buttons are used to edit the number in the last line. ASCII
character corresponding to that number in the last line is displayed in cursor
position. The number in the last line can be adjusted between 32 and 255 to provide
almost all the characters. (32=Space, 33=!, 65=A, etc.) Note: and buttons are
not effective for start and stop while in configuration operation.
6. Power On State: This parameter defines the power on behavior of the dryer. When
set to OFF, the dryer powers on always in off state and when set to ON, the dryer
powers on always in on state. When set to RESUME, the dryer resumes its operation
depending on the state of last power failure instance.
7. Security Code: This parameter determines the value of the security code. It can be
adjusted between 0 and 9999.
8. Load Factory: This parameter loads factory defaults. In order to start loading, first
set to parameter to YES and press key. ‘ARE YOU SURE TO LOAD FACTORY
SETTINGS?’ message appears on the screen for the confirmation. Pressing key
confirms loading and key cancels the operation.
Day
Selection SUN 1 ON 09:00 09:30
2 ON 11:00 12:30
3 ON 13:30 14:00
4 ON 15:00 15:30
Figure 2.15.
3. OPERATION PRINCIPLES:
In order to start the dryer, the following conditions must be satisfied.
1. All the temperatures except the exchanger temperature and condenser outlet temperature
must be between their low and high limits. The low pressure line temperature can be
‘HIGH’.
2. Digital Input 3 (Compressor Fault) is not activated.
3. Digital Input 4 (Compressor Overload) is not activated.
4. Digital Input 5 (Fan Fault) is not activated.
5. Digital Input 6 (Fan Overload) is not activated.
6. Digital Input 7 (Phase Sequence Error) is not activated.
7. Digital Input 8 (Remote Disable) is not activated.
8. Digital Input 11 (High Pressure) is not activated.
9. Digital Input 12 (Low Pressure) is not activated.
If all the above conditions are satisfied, the dryer can be started.
When the dryer is started, Digital Output 1 (Compressor Motor), Digital Output 2 (Drain Output) and
Digital Output 3 (Dryer is Running) become active. Exchanger Temperature Alarm Delay timer and
Low Pressure Line High Alarm Delay timer are set to their configured durations.
The drain output is controlled according to the configured “drain on” and “drain off” periods.
The exchanger temperature is not compared with the configured low and high alarm set points until
the Exchanger Temperature Alarm Delay is timed out. After time out, the exchanger temperature
must be between its low and high limits, otherwise; the dryer is stopped together with the alarm
message “EXCH.TEMP.LO” or “EXCH.TEMP.HI”.
Similarly, the difference between High Pressure Line temperature and Condenser Outlet
temperature is not compared with the Condenser Temp. Dif. Set Point until the Exchanger
Temperature Alarm Delay is timed out. After time out, if the difference is less than the Condenser
Temp. Dif. Set Point, the dryer is stopped together with the alarm message “CONDENSER FAULT”.
The Low Pressure Line temperature is not compared with the configured high alarm set points until
the Low Pressure Line High Alarm Delay is timed out. After time out, the Low Pressure Line
temperature must be between its low and high limits, otherwise; the dryer is stopped together with
the alarm message “LO.PRES.L.TEMP.LO” or “LO.PRES.L.TEMP.HI”.
When ECO mode is enabled and the exchanger temperature is less than or equal to “ECO Start Set
point” and this condition is prevailed more than “ECO Start Delay”, then, the compressor motor is
stopped and ECO operation starts. ECO operation ends when the exchanger temperature reaches to
the “ECO end Set point” or ECO mode is disabled. Disabling ECO mode also resets the ECO Start
Delay timer.
4. MODBUS REGISTERS:
The controller has an RS-485 communication interface that can be used for remotely monitoring channel
temperatures, operation times, the states of digital inputs and outputs. The data format is 8 bit, with no
parity or odd parity or even parity and 1 stop bit. Communication setup is determined by the parameters
Communication Address, Baud Rate and Parity which are in the General Parameters Page. See section
2.3.1. General Parameters Page for the adjustment range of these parameters.
Modbus RTU protocol is used for communication. The Function Codes 03, 06 and 16 are supported. No
parameter is defined for function codes 06 and 16. Modbus register addresses and related explanations are
given in TABLE 4.1.