AD 220 (EU)

INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and
continuous duty applications. All generator sets are factory built, and production tested.

POWER 3 Phase,50 Hz, PF 0.8


STANDBY RATING (ESP) PRIME RATING (PRP)
STANDBY
VOLTAGE (V)
kW kVA kW kVA CURRENT (A)

400/231 176.00 220.00 160.00 200.00 317.55

STANDBY RATING (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source.
ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 %
overload capability is available for a period of 1 hour within 12-hour period of operation.

GENERAL CHARACTERISTICS
Model Name AD 220 (EU)
Frequency (Hz) 50
Fuel Type Diesel
Engine Make and Model DOOSAN P086TI
Alternator Make and Model Mecc Alte ECO 38-2S/4 C
Control Panel Model DSE 7320
Canopy AK50 EU (RAL-1015)
Noise Level (@1m./@7m.) (dB(A)) 83.8/74.1

ENGINE SPECIFICATIONS
General Data
Manufacturer DOOSAN
Engine Model P086TI
Number of Cylinders (L) 6 cylinders - in line
Bore (mm.) 111
Stroke (mm.) 139
Displacement (lt.) 8.071
Compression Ratio 16.4:1
Engine Speed (rpm) 1500

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

1/6
AD 220 (EU)

Standby Power (kW/HP) 199/270


Prime Power (kW/HP) 177/240
Block Heater QTY 1
Block Heater Power (Watt) 1500
Governor System Electric
Air Filter Dry Type

Lubrication System
Oil Capacity (Total With Filter) (lt) 15.5
Max. Oil Temperature (ºC) 120

Fuel System
Fuel Type Diesel
Injection Type and System Direct
Type of Fuel Pump Doowon in-line "P" Type

Electrical System
Operating Voltage (Vdc) 24
Battery and Capacity (Qty/Ah) 2x85
Charge Alternator (A) 45

Cooling System
Aspiration Turbo Charged and Intercooled (Air to Air)
Cooling Method Water Cooled
Coolant Capacity (engine only) (lt) 14

Exhaust System
Exhaust Gas Flow (m3/min.) 33.9
Exhaust Back Pressure (kPa) 5,9
Exhaust Gas Temp. (º C) 580
Heat Rejection to Exhaust
º (kW) 170.6

Radiator
Total Coolant Capacity (lt) 35.1
3
Cooling Fan Air Flow (m /min.) 190
External Restriction to Cooling Airflow (Pa) 125

Fuel Consumption
Fuel Cons. Prime With %100 Load (lt/hr) 43.1
Fuel Cons. Prime With %75 Load (lt/hr) 31.7
Fuel Cons. Prime With %50 Load (lt/hr) 21.1

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

2/6
AD 220 (EU)

ALTERNATOR CHARACTERISTICS
Manufacturer Mecc Alte
Alternator Model ECO 38-2S/4 C
Frequency (Hz) 50
Power (kVA) 200
Voltage (V) 400
Phase 3
Regulator DSR
Voltage Regulation (+/-)1%
Insulation System H
Protection IP23
Rated Power Factor 0.8
Weight Complete Generator (kg) 626
Temperature Rise H

CANOPY SPECIFICATIONS
Length (mm) 3402
Width (mm) 1217
Height (mm) 1942
Dry Weight (kg.) 2205
Tank Capacity (lt.) 380

CONTROL PANEL
Manufacturer DSE
Control Module Model DSE 7320
Communication Ports MODBUS

1. Menu navigation buttons


2. Close mains button
3. Main Status and instrumentation display
4. Alarm LED's
5. Close generator button
6. Status LED's
7. Operation selecting buttons

Standard Devices
DSE model 7320, Auto Mains Failure control module, Static battery charger, Emergency stop push button and Fuses for
control circuits

Control Unit
- The DSE 7320 control module is a standard addition to our generator sets from 220 kVA upwards and it has been
designed to start and stop diesel and gas generating sets that include electronic and non electronic engines.
- The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable
for controlling a standby generating set in conjunction with an automatic transfer switch.
- The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and
indicating faults by means of its LCD display on the front panel.

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

3/6
AD 220 (EU)

Construction and Finish


- Components installed in sheet steel enclosure.
- Phosphate chemical, pre-coating of steel provides corrosion resistant surface
- Polyester composite powder topcoat forms high gloss and extremely durable finish
- Lockable hinged panel door provides for easy component access

Installation

Control panel is mounted generating set baseframe on robust steel stand or power module. Located at side of generating
set with properly panel visibility.

Standard Specifications
- Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and Ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manual, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.

Instruments
Engine Shut Downs Warning
- Engine speed - Fail to start - Charge failure
- Oil pressure - Emergency stop - Battery under voltage
- Coolant temperature - Low oil pressure - Fail to stop
- Run time - High engine temperature - Low fuel level (opt.)
- Battery volts - Low coolant level - kW over load
- Engine maintenance due - Under/over speed - Negative phase sequence
- Under/over generator frequency - Loss of speed signal
Generator
- Under/over generator voltage
- Voltage (L-L, L-N)
- Oil pressure sensor open Electrical Trip
- Current (L1-L2-L3)
- Phase rotation - Earth fault
- Frequency
- Earth current - kW over load
Pre-alarms
- kW - Generator over current
- Low oil pressure - Negative phase sequence
- Pf
- High engine temperature
- kVAr
- Low engine temperature
- kWh, kVAh, kVArh Expansion
- Under/over speed
- Phase sequence - Additional LED module (2548)
- Under/over generator frequency
- Expansion relay module (2157)
Mains - Under/over generator voltage
- ECU warning - Expansion input module (2130)
- Voltage (L-L, L-N)
- Frequency

Options Standards

- High oil temperature shut down - Electrical Safety / EMC compatibility


- Low fuel level shut down - BS EN 60950 Electrical business equipment
- Low fuel level alarm - BS EN 61000-6-2 EMC immunity standard
- High fuel level alarm - BS EN 61000-6-4 EMC emission standard

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

4/6
AD 220 (EU)

Static Battery Charger


- Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.
- Battery charger models' output V-I characteristic is very close to square
- 2405 has fully output shot circuit protection and it can be used as a current source.
- 2405 charger has high efficiency, long life, low failure rate, light-weight and low heat radiated in accordance
with linear alternatives.
- The charger is fitted with a protection diode across the output.
- Charge fail output is available.
- Connect charge fail relay coil between positive output and CF output.
- Input: 196-264V.
- Output: 27,6V 5A or 13,8V 5A.

STANDARD EQUIPMENT
- Water cooled, Diesel engine
- Mounted radiator with mechanical fan drive
- Protective grille for rotating and hot parts
- Electric starter and charge alternator
- Lead acid starting battery (with battery switch) including rack and cables
- Engine coolant heater
- Bunded base frame design incorporates an integral fuel tank, anti-vibration isolators and forklift pockets
- Flexible fuel connection hoses
- Single bearing, class H alternator with Anti-condensation Heater
- Industrial exhaust silencer and steel bellows supplied separately (for open sets)
- Static battery charger and battery switch
- Non-ferro plate for anlternator and panel side
- 4P Circuit Breaker
- Manual for application and installation
- Generators Sets’ voltage and frequency regulation comply with ISO 8528-5

OPTIONAL EQUIPMENT

Engine Transfer Switch


- Fuel-Water Separator Filter - Three or four pole contactor
- Oil heater - Three or four pole motor operated circuit breaker

Alternator Auxiliary Equipment

- Over sized alternator - Main Fuel Tank


- Main line circuit breaker - Automatic or manual fuel filling system
- Manual oil drain pump
- Electrical oil drain pump
- Low and high fuel level alarm
Exhaust
- Inlet and outlet motorized louvers
- Residential Silencer - Inlet and outlet acoustic baffles
- Critical Silencer - Tool kit for maintenance
- Silencer Spark Arrester - 1500/3000 hours maintenance kit
- Catalytic Convertor - Supplied with oil and coolant - 30 °C

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

5/6
AD 220 (EU)

Control System Canopy


- Automatic synchronising and power control - ISO Container
system (Multi gen-set Parallel) - Galvanized Coating
- Parallel system with mains. - Marine Grade Paint
- Transition synchronization with mains - Design Option for Hot and Tropical Conditions
- Remote relay output
- Alarm output relays
Optional Alternator and Control Panel Models
- Remote communication with modem
- Earth fault, single set - Please contact to your reseller for additional
- Charge Ammeter Alternator, Control Panel and Breaker Switch options.

AKSA CERTIFICATES

Directives

- 2006/42/EC : Machinery Safety Directive


- 2004/108/EC : Electromagnetic Compatibility Directive
- 2006/95/EC : Low Voltage Directive

Standards

- EN ISO 12100-1:2010 : Safety of machinery -Basic concepts, general principles for design -
Risk Assessment and Risk Reduction
- EN ISO 3744:2010 : Acoustics. Determination of sound power levels of noise sources using
sound pressure. Engineering method in an essentially free field over a reflecting plane

- EN 60204-1:2018 : Safety of machinery-Electrical equipment of machines General Requirements

- EN ISO 8528-13:2016 : Reciprocating internal combustion engine-driven alternating


current generating sets- Part:13: Safety
- BS EN 61000-4-2:2009 : Electromagnetic compatibility (EMC). Testing and Measurement
Techniques-Electrostatic Discharge Immunity Test

- BS EN 61000-4-6 : Electromagnetic Compatibility (EMC). Testing and Measurement


Techniques-Immunity to Conducted Disturbance Induced by Radio - Frequency Fields

- EN 614-1:2006+A1(2009) : Safety of machinery - Ergonomic design principles - Part 1:


Terminology and general principles

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (23.02.2022)

6/6