L-Series Position Controller Rohs Compliant: Product Manual 35154 (Revision - , 07/2019)
L-Series Position Controller Rohs Compliant: Product Manual 35154 (Revision - , 07/2019)
L-Series Position Controller Rohs Compliant: Product Manual 35154 (Revision - , 07/2019)
Read this entire manual and all other publications pertaining to the work to be
performed before installing, operating, or servicing this equipment.
Practice all plant and safety instructions and precautions.
General
Precautions Failure to follow instructions can cause personal injury and/or property damage.
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26455, Customer
Publication Cross Reference and Revision Status & Distribution Restrictions, on
Revisions the publications page of the Woodward website:
www.woodward.com/publications
Revisions— A bold, black line alongside the text identifies changes in this publication since the
last revision.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 35154
Copyright © Woodward, Inc. 2019
All Rights Reserved
Released
Contents
ACRONYMS/ABBREVIATIONS...................................................................... 3
WARNINGS AND NOTICES .......................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ................................................. 5
REGULATORY COMPLIANCE ....................................................................... 6
CHAPTER 1. GENERAL INFORMATION ......................................................... 8
Purpose and Scope ................................................................................................8
How to Use This Manual ........................................................................................8
Intended Applications .............................................................................................8
L-Series Description ...............................................................................................8
Programmable Features .........................................................................................9
Service Tool Software ..........................................................................................10
CHAPTER 2. SYSTEM DESCRIPTION/APPLICATION OVERVIEW .................... 11
System Operation .................................................................................................11
Current Limiting based on Temperature ...............................................................16
Faults ....................................................................................................................16
CHAPTER 3. INSTALLATION ...................................................................... 19
General Installation, Operation Notes and Requirements ....................................20
Unpacking .............................................................................................................20
Mechanical Installation .........................................................................................20
Electrical Installation .............................................................................................26
Description of Electrical I/O ..................................................................................29
CHAPTER 4. SERVICE TOOL ..................................................................... 35
Introduction ...........................................................................................................35
Description ............................................................................................................35
Getting Started .....................................................................................................37
L-Series Configuration ..........................................................................................38
Configuration Parameters.....................................................................................39
Position Calibration and Verification .....................................................................50
Calibration Sequence Overview ...........................................................................51
Position Verification ..............................................................................................51
CHAPTER 5 L-SERIES CONTROL SPECIFICATIONS ..................................... 55
CHAPTER 6. TROUBLESHOOTING ............................................................. 59
Introduction ...........................................................................................................59
General System Troubleshooting Guide ..............................................................60
Engine/Generator Troubleshooting ......................................................................60
CHAPTER 7 PRODUCT SUPPORT AND SERVICE OPTIONS ........................... 63
Product Support Options ......................................................................................63
Product Service Options .......................................................................................63
Returning Equipment for Repair ...........................................................................64
Replacement Parts ...............................................................................................64
Engineering Services ............................................................................................65
Contacting Woodward’s Support Organization ....................................................65
Technical Assistance ............................................................................................66
APPENDIX A. L-SERIES CONFIGURATION SUMMARY .................................. 67
REVISION HISTORY .................................................................................. 68
DECLARATIONS ....................................................................................... 69
Woodward 1
Released
Woodward 2
Released
Acronyms/Abbreviations
AUX auxiliary
EEPROM electrically-erasable programmable read-only memory
EMC electro-magnetic compatibility
GUI graphic user interface
I/O inputs/outputs
Isoch isochronous
ITB integrated throttle body
L-Series Woodward electronic engine governor that contains both a rotary actuator and a
controller circuit board
MPU magnetic pick up
OEM original equipment manufacturer
PWM pulse-width modulated
rpm revolutions per minute
RS-232 a communications standard
TPS throttle position sensor
Woodward 3
Released
DANGER - Indicates a hazardous situation, which if not avoided, will result in death or serious injury.
WARNING - Indicates a hazardous situation, which if not avoided, could result in death or serious
injury.
CAUTION - Indicates a hazardous situation, which if not avoided, could result in minor or moderate
injury.
NOTICE - Indicates a hazard that could result in property damage only (including damage to the
control).
IMPORTANT - Designates an operating tip or maintenance suggestion.
Woodward 4
Released
Woodward 5
Released
Regulatory Compliance
EMC Directive: Declared to Directive 2014/30/EU of the European Parliament and of the Council
of 26 February 2014 on the harmonization of the laws of the Member States
relating to electromagnetic compatibility (EMC)
These listings are limited only to those units bearing the ATEX markings as well as the CE Mark:
CSA: CSA Certified for Class I, Division 2, Groups A, B, C, & D, T3C at 105 °C
Ambient for use in Canada and the United States.
Certificate 1380416
This product is certified as a component for use in other equipment. The final
combination is subject to acceptance by the authority having jurisdiction.
Woodward 6
Released
Woodward 7
Released
Chapter 1.
General Information
Intended Applications
The L-Series control is designed for various industrial applications, including but not limited to generator
sets, welders, portable refrigeration units, irrigation pumps, chipper shredders, and mobile industrial gas
or gasoline reciprocating engines. Key environmental characteristics of these applications include
extended industrial operating temperatures (–40 to +105 °C/–40 to +221 °F), Industrial EMC
Requirements, electrical transients, and lower operating voltages (12/24 V).
L-Series Description
The L-Series provides a building block approach to total engine management. The modular bi-directional
actuator design easily attaches to fuel pumps, mixers, or throttle bodies. For information on Woodward
throttle body applications, refer to manual 35144 (ITB and LC-50).
Woodward also offers L-Series actuator versions for Speed Control and Process Control, like Air/Fuel
Ratio control, applications. Refer to manuals 35141(Speed Control) and 35153 (Process Control).
The L-Series position control accepts a position command and drives the 0–60 degree output shaft to the
commanded position based on an internal shaft position sensor. The high-efficiency torque motor delivers
0.34 Nm (0.25 lb-ft) nominally over 60° travel range to operate fuel or air control devices (see
specifications in Appendix C for torque performance over the full product temperature range).
Woodward 8
Released
For status purposes, a relay driver output is available on the L-Series control which changes state
whenever a fault or error condition is experienced by the
L-Series controller.
If the system so requires, the L-Series provides a direct position output signal in the form of a dc voltage.
The throttle position (TPS) output represents full counterclockwise (ccw) to clockwise (cw) rotation of the
actuator shaft, and thus gives the operator an external position indication after installation and while the
unit is operating.
More detail on the features of the L-Series can be found later in this manual.
When included with an ITB, the actuator depends solely on the return
spring inside the throttle body assembly to drive toward minimum
fuel when not powered, therefore other positive shutdown devices
like fuel shut-off solenoids are recommended to ensure shutdown
upon loss of signal to the control system. Also, separate overspeed
trip devices are always mandatory.
Programmable Features
Control setup and tuning is accomplished through the use of a PC (personal computer), Woodward
Service Tool software, and a programming harness. The features identified below are described in
Chapters 2 and 4. Briefly, the programmable features include:
4 General Setup Parameters
o Position Demand Select (PWM or Analog)
o Fail Direction (ccw or cw)
o Min Position Direction (ccw or cw)
o Actuator Curve Selection (Linear or Non-linear)
PWM Setup Parameters
o PWM Drive Select (Push-Pull, High-Side Drive or Low-Side Drive)
o PWM Offset
4 Valve Position Control Parameters
o Proportional Gain
o Integral Gain
o Derivative Gain
o Friction/Dither Setting
10 Non-Linear Actuator Settings
o Position Request (5 curve input points)
o Actuator Position (5 curve output points)
12 Discrete Output Settings
o Output’s Non-Fault Condition (ON or OFF)
o 11 Selections as Discrete Output Indications
10 Fault Settings
o Latching or Non-Latching Fault Indications
o Position Error Magnitude
o Position Error Delay
o 7 Fault Selections as Alarms or Shutdowns
Woodward 9
Released
The Service Tool is not included, but can be downloaded from the
Woodward Internet website (www.woodward.com/software/).
The actuator must be properly set up using the L-Series Service Tool
prior to starting the engine.
Woodward 10
Released
Chapter 2.
System Description/Application Overview
System Operation
The L-Series actuator is ready for operation immediately (within 0.25 second) when the power supply is
connected. Power may be connected to the control at the same time the engine starter motor is engaged.
Upon power-up, the actuator will immediately go to the commanded position. The actuator will then drive
to maintain the position commanded by the supervisory control.
Optionally, a Run Enable input can be used to activate or de-activate the L-Series output. It can also be
used to reset shutdown fault conditions.
Upon an engine shutdown command, the independent engine shutdown solenoid or solenoid valve in the
fuel supply should be de-activated and the power supply disconnected from the speed control. This
shutdown signal should be sent directly from the engine control panel and should be independent and
separate from the L-Series controller.
Position Demand
(Analog/PWM)
Power Input
(10-32Vdc)
RS-232
Service Tool
The supply voltage failure levels are below 6.25 V and above 33 V. The unit can be configured to either
alarm or shut down upon detection of a supply voltage fault.
Woodward 11
Released
+V
Discrete
Status F (any fault)
Out Logic
(discrete output driver)
24Vdc = ON (status ok) Discrete
Relay
Out
Run Enable
(optional)
Woodward 12
Released
The PWM will function with various types of input sources, including high-side, low-side open collector,
and push-pull—depending on the configuration. It will handle a PWM frequency range from 300 to 1500
Hz at amplitudes ranging from 5 V up to battery voltage. Normal operating range is from 10% to 90% duty
cycle, representing the hard stops in the actuator (Figure 2-1). The input can be optionally set to a non-
linear mode which provides a 5-point curve relationship between position signal and desired position
(Figure 2-2).
The input failure levels are below 3% and above 97% duty cycle. The unit can be configured to either
alarm or shut down on detection of a position command failure. The shutdown failsafe direction is also
user configurable as either clockwise or counterclockwise.
90 failsafe direction
80
70
60
50
40
30
user-defined shutdown
20
failsafe direction
10
0
0 10 20 30 40 50 60 70 80 90 100
90 failsafe direction
80
70
60
50
40
30
20
user-defined points
10
0
0 10 20 30 40 50 60 70 80 90 100
The 0–5 V input uses a different pin in the connector, and it has a usable range of 0.5 to 4.5 V to
command the throttle from minimum to maximum position (Figure 2-3). The input can be optionally set to
Woodward 13
Released
The input failure levels are below 0.2 and above 4.8 V. The unit can be configured to either alarm or shut
down on detection of a position command failure. The shutdown failsafe direction is also user-
configurable as either clockwise or counterclockwise direction.
90 failsafe direction
80
70
60
50
40
30
20 user-defined shutdown
failsafe direction
10
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
90 failsafe direction
80
70
60
50
40
30
20 user-defined points
10
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Discrete Output
A discrete output is provided to serve as a status indicator. This switchable discrete output is a closure to
ground capable of sinking 250 mA with an output voltage rise of less than 1.5 V, and it is available to
power external relays for devices such as alarms or fuel shutoff solenoids. The circuit is protected
internally against overcurrent and inductive spikes, so external clamping is not necessary.
Woodward 14
Released
There are two conditions that will prevent the discrete output from operating correctly. The first is if battery
positive is accidentally connected to it, and the second is if it is shorted to ground. The circuit will protect
itself in the event of a mis-wire, but it will hold the output open (floating) until the fault is removed.
Additional Inputs/Outputs
Auxiliary Inputs—There are four auxiliary inputs on the L-Series controller, all of which are capable of
both analog and discrete functions. They can all be functionally defined for purpose in the software
application. Although they are very flexible, two of them are shared with the serial communications, so will
be unavailable if the L-Series is connected to the Service Tool. More detail concerning the auxiliary inputs
is provided in Chapter 3 (Installation).
5V Output—A 5 Vdc output has been provided on the L-Series actuator to power external sensors, if
necessary. The 5 V output is limited to 10 mA, but this is sufficient for most light-duty ratiometric sensors.
Communications
RS-232 communications are available on the L-Series when used with an external transceiver connected
to pins 4 and 6. Serial communications allow for the use of a service and configuration tool with the L-
Series actuator. The simplest way to establish this interface is to use Woodward kit # 8923-1061.
Functions available through this port include tuning, monitoring, and configuration of the position
controller. Detailed driver status information is also available.
Any RS-232 wiring must meet the requirements in the EIA RS-232 Standard document. The RS-232
standard states that the length of the RS-232 cable between the driver and the PC must be less than 50 ft
(15 m) with a total capacitance less than 2500 pF. The RS-232 data rate is fixed at 19.2 kbps. The
communication port is non-isolated and susceptible to both EMI noise and ground loops related to PC
connections and typical industrial environments.
Woodward 15
Released
The service port is not isolated and is not intended to function while
the prime mover is in normal operation. The service port is provided
for configuration and setup only.
Temperature Sensing
The L-Series has an on-board temperature sensor to monitor board temperatures and protect the unit
from overtemperature. This temperature is monitored and a fault is annunciated if the set point is
exceeded.
Current limiting based on temperature begins when the combined current and temperature environment
causes board temperatures greater than 117 °C. The limit curve is a linear derate from full current at 117
°C down to zero current at 125 °C. At 125 °C, an OverTemp fault is annunciated. Depending on the
current (actuator torque) and ambient operating temperatures, the unit may never reach a reduced level.
Faults
Faults are separated into two categories: Logged Faults and Current Faults. The Current Faults are
volatile and reset every time power is applied. The Current Faults annunciates faults that are presently
active/detected; they may latch or not latch depending on the fault. All latching Current Faults are reset by
a power cycle or Service Tool reset. All logged faults are latched and written to the EEPROM. They must
be cleared through the Service Tool.
A fault can have three effects on the control: change the discrete output state (Alarm), Shutdown–drive to
fail direction and change the discrete output state (Alarm), or Shutdown–go limp and change the discrete
output state (Alarm). A parameter is available to configure the fault to either an alarm or a shutdown. The
shutdown action performed (go limp or drive to fail direction) is fault-dependent. Some faults are
dedicated shutdowns and cannot be configured—they are identified as such below. A "go limp" command
overrides a "drive to fail position" if more than one fault is set.
Faults can be configured as either latching or non-latching. This is a general setting that applies to all
faults, unless otherwise noted. When configured as non-latching, a Reset is not needed. If latching mode
is configured, a Reset or power-cycle is required to clear the fault and resume positioning.
Watchdog Reset
Watchdog Reset is true if a watchdog timer timeout occurred which resulted in a reset of the
microprocessor. This is a hard-coded alarm. If detected, the control will attempt to continue normal
operation.
Brownout Reset
Brownout Reset is true if CPU Voltage drops below 4.2 V but not below 1 V. The brownout detect circuit
will reset the CPU. This is a hard-coded alarm. If detected, the control will attempt to continue normal
operation.
Woodward 16
Released
EEPROM Fail
EEPROM Fail indicates failure or corruption of the internal non-volatile memory. If the CRC is not correct
for the EEPROM data, this fault will be set true. This is a hard-coded internal shutdown. If detected, the
control output will go limp. A power cycle is required to clear this fault.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using current control) if this fault is detected. If configured as an alarm, the control will internally
default to an assumed 32 V power supply voltage (decreased torque at lower actual voltages) and
attempt to continue normal operation if this fault is detected. The value displayed on the Service Tool will
show sensed value, not default.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using position control) if this fault is detected. If configured as an alarm, the control will
internally default to 25 °C and attempt to continue normal operation if this fault is detected. The value
displayed on the Service Tool will show sensed value, not default.
OverTemp
If the on-board temperature sensor reads above 125 °C, this error will be set. Above 125 °C, the
processor can fail in an unpredictable manner, so this fault is recommended as a shutdown. The Current
Limiting based on temperature will effectively make the output "limp" by reducing the drive current to zero.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will go limp if this
fault is detected. If configured as an alarm, the control will attempt to continue normal operation if this
fault is detected.
Woodward 17
Released
Position Error
Position Error detection logic will indicate a difference between commanded position and actual position
exceeded for longer than the set delay. The error magnitude and duration are customer-configurable
parameters.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using position control) if this fault is detected. If configured as an alarm, the control will attempt
to continue normal operation if this fault is detected.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using position control) if this fault is detected. If configured as an alarm, the control will attempt
to continue normal operation if this fault is detected.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using position control) if this fault is detected. If configured as an alarm, the control will attempt
to continue normal operation if this fault is detected.
Can be configured as an alarm or shutdown. If configured as a shutdown, the control will drive to Fail
Direction (using position control) if this fault is detected. If configured as an alarm, the control will attempt
to continue normal operation if this fault is detected.
This is a hard-coded shutdown. The control will go limp if this condition is detected.
Woodward 18
Released
Chapter 3.
Installation
Introduction
This chapter provides instructions on how to mount and connect the L-Series controller into a system.
Hardware dimensions are provided for mounting the device to a specific application.
The surface of this product can become hot enough or cold enough
to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification
section of this manual.
Woodward 19
Released
Unpacking
Be careful when unpacking the actuator. Check the unit for signs of damage, such as bent or dented
panels, scratches, and loose or broken parts. Notify the shipper and Woodward if damage is found.
Mechanical Installation
Mounting Location
Locate the L-Series control a distance from sources of extreme radiant heat, such as exhaust manifolds
or turbochargers. The operating temperature range of the control is –40 to +105 °C (–40 to +221 °F). In
spark-ignited applications, make sure the L-Series is located away from the ignition coil, and that harness
wires are not routed next to the spark plug wires.
Mounting Orientation
While it is not a requirement, it is good practice to orient the connector feature on the control in a
horizontal or downward orientation to minimize fluid accumulation between the enclosure and the mating
connector’s gasket.
Actuator Configuration
The L-Series actuator utilizes a 2” (51 mm) square mounting bolt pattern and is intended to fit within an
envelope of 2.618 x 2.618 x 2.540 (66.50 x 66.50 x 64.52 mm) with the short dimension along the shaft
axis. Two shaft seal configurations are available, an internal lip seal and an external lip seal with spring
backup (Figure 3-2). In addition, six independent output shaft configurations are available (Figure 3-3).
Consult Woodward Applications Engineering for the application appropriate seal and shaft configuration.
Mounting Hardware
Use #10 or M5 fasteners to attach the L-Series control to the mounting bracket. The bracket and
attaching hardware must be designed to hold the weight and to withstand the vibration associated with
prime mover mounting. Use the appropriate fasteners for securing the mounting bracket to the engine.
Woodward 20
Released
The L-Series ITB is not intended to support the inlet or outlet piping.
A suitable bracket must be constructed to support the valve and
piping separately to prevent damage to the throttle body.
Woodward 21
Released
Woodward 22
Released
Woodward 23
Released
Woodward 24
Released
Woodward 25
Released
Electrical Installation
A wiring pinout of the L-Series control, as viewed by looking into the control’s connector feature, is shown
in Figure 3-4. Typical connections to external devices are also shown.
The L-Series has an operating voltage range of 8 to 32 Vdc with nominal voltages of 12 or 24 Vdc. The
power supply is reverse polarity protected, and consumes 32 W maximum power at a peak current of 1 A
(32 V) assuming 4 Ω stator resistance at 25 °C. These assumptions are based on the fact that the
software limits the power to the rotary actuator to 25 W at any given time and input voltage (in the valid
range). The control system should be protected with a 6 A slow-blow fuse in the voltage supply lines.
Typical max average current is 2.1 A, or max 25 W at 12 V. The application should be configured to turn
on power to the actuator when the engine is first cranked.
Woodward 26
Released
Electrical Connections
Prior to installation, refer to the wiring diagrams and the representative I/O interfaces schematic in this
chapter. Also, review the hardware I/O specifications in Appendix C.
The control will only meet ingress protection specifications while the
Deutsch connector is installed in the unit. As such, the unit should
not be exposed to operating environments unless the mating
connector is installed. In addition, if a wire is not used for each of the
12 pins on the control, a Deutsch 114017 plug must be used in place
of each missing wire. Failure to adhere to these guidelines may
result in product failure or decreased life.
Use 1 to 1.5 mm² (16 to 18 AWG) stranded copper wire with insulation
that meets temperature requirements in the harness design. A wiring
harness stress relief within 400 mm (16”) of the control’s connector
is recommended. Limit all I/O and signal lines to less than 30 m (98
ft). Also limit input power (B+/B–) connections to an earth grounded
battery or conditioned power interface to less than 10 m (33 ft) from
the L-Series product.
Dress the harness with wire loom to contain it in a single bundle. Use grommets when passing the
harness through metal panels.
Woodward 27
Released
Connector
The following Deutsch connector components are recommended for harness designs:
Recommended Optional
Mating Connector DT06-12SA-P012 DT06-12SA
Secondary Lock W12S-P012 N/A
Sockets 0462-201-16141 0462-201-16141
Woodward part number 8928-396 is a kit that provides all the necessary Deutsch components.
6A FUSE
+
12/24 Vdc
connector POWER INPUT + 1 -
key
TPS OUTPUT 2 THROTTLE POSITION
12 1 V (0.75 VDC TO 4.25 Vdc )
PWM -/AUX -
3
(SIG. GND)
11 2
AUX3+/RS232 TX 4
10 3 SERIAL COMMUNICATIONS (USE
INPUT POWER GND 5 WOODWARD 8923-1061 TO
9 4 CONNECT TO COMPUTER)
AUX4+/RS232 RX 6
8 5
+5V OUT 7 12 V/24 V OPTIONAL RUN ENABLE DISCRETE
7 6 INPUT (CLOSED TO RUN)
AUX1+ 8
connector 5 Vdc - 32 Vdc, 500 mA max.
key RELAY DRIVER 9
RELAY COIL
CUSTOMER CONTROL
Connector Pinout as Viewed 0.5-4.5 +
AUX2+ 10
Looking Into PWM OR 0.5-4.5 V
L-Series Control PWM + POSITION COMMAND
PWM+ 11
-
POS. CMD COMMON
IGN 12
VIS-168
08/3/4
Woodward 28
Released
Connector
Description Comment
Pin #
1 +12V/24 Vdc Input Power Supply power
2 TPS Signal Output Direct position feedback output indication
Ground for the PWM or AUX command signal
3 PWM – / AUX –
common
4 RS-232 transmit For use with the service tool
5 Input Power Ground Ground for the 12 V/24 V input power
6 RS-232 receive For use with the service tool
7 5 V Out Power for external sensors (10 mA max)
8 Aux Input 1 Optional Run Enable discrete input
9 Relay Driver Output Status signal and fault detection output
10 Aux Input 2 0–5 V command signal input
11 PWM + PWM command signal input
12 Ignition Input Not used—Leave open
Power Supply Input (+12 Vdc/24 Vdc at pin 1, ground at pin 5)—The L-Series is configured for 12 or 24
V nominal operation, although it will handle 8–32 V. The power supply terminals are reverse polarity
protected, and in the case that a reverse polarity condition exists, the L-Series actuator will not power-up
and will remain at the minimum stop if attached to a throttle body with an internal return spring.
Woodward recommends using a 6 A slow-blow fuse on the power supply line feeding pin 1 of the L-Series
actuator.
The input power must be fused. Failure to fuse the L-Series could,
under exceptional circumstances, lead to personal injury, damage to
the control valve, and/or explosion.
PWM Command Input (+PWM at pin 11, PWM ground at pin 3)—This actuator can be configured to
handle a PWM signal from a high-side or low-side open-collector or open-drain source, as well as from a
push-pull (customer pull-up) source. The necessary pull-up and pull-down voltages to accommodate the
open-collector sources are handled within the L-Series actuator. Nominally, the frequency of PWM is 1
kHz, but it will handle the full range of 300 to 1500 Hz. See Figure 3-5 below, which describes the
possible input types and configurations for the PWM input.
RS-232 Connections (pin 4 and pin 6)—These pins are for serial communication with the L-Series
actuator. An external RS-232 transceiver is necessary to make communications possible with the
Woodward L-Series Service Tool. A connectivity kit can be purchased from Woodward to accomplish this.
Further instructions for using this connectivity kit are provided in Chapter 4. See also the description
below on Auxiliary Inputs.
Woodward 29
Released
Do not try to inject signals into the TPS output, as it will negatively
impact the performance of the L-Series actuator. This output is
meant to be used with a high impedance device, such as a voltmeter.
Do not tie pin 2 directly to battery or ground. If the application does
not use this output, leave it open.
Woodward 30
Released
For this type of PWM Source... ...the L-Series PWM Input looks like...
5 - 32 VDC
L-Series
Pin 11
To
PNP (or P-Channel FET) 4 kW 9.5 kW Processor
Internal Clamped to 5V, then
12 kW
Command compared with 2.5V reference.
L-Series 12 kW
NPN (or N-Channel FET) Pin 11
To
Internal 4 kW 9.5 kW Processor
Command
Compared with 2.5V
reference.
L-Series
Pin 11
To
Internal 5 - 32 VDC
Processor
Command OR 13.5 kW
Internal
Command
5 - 32 VDC
OR
Internal
Command
Woodward 31
Released
5-32 VDC,
500mA maximum
Lamp Relay
Indicator Coil
OR Relay Driver
Status back
L-Series
to Processor
Pin 9
Self-Protecting From
.01mF FET Processor
5V Output (pin 7, referenced to pin 3)—The +5 Vdc Power Output is intended to power any external
transducer that depends on a steady 5 V source. The maximum output current is 10 mA.
Auxiliary Inputs (pins 4, 6, 8, and 10)—The L-Series has three dedicated digital inputs (AUX2, AUX3,
and AUX4) used to activate various features of the control. Shorting an auxiliary input pin to battery
voltage activates it. Removing battery voltage from an input pin or shorting the pin to ground deactivates
the input. If it is decided not to use battery voltage with the auxiliary digital inputs, it is recommended that
at least 3 V be present on an input pin in order to change its state from inactive to active. All discrete
inputs will be the same voltage as the system power supply and will be active only while the input is in a
high state. For AUX2, AUX3, and AUX4, greater than 2.5 Vdc is considered high, and less than 0.8 Vdc is
considered low. For the AUX1 discrete input only, the input must exceed 3 V to activate the discrete state.
AUX3 and AUX4 are also used for digital communications such as RS-232 (service tool) or CAN (If the
CAN option was purchased). RS-232 and CAN will NOT run simultaneously.
When used as a position control, AUX1 on the L-Series actuator can be configured as a run enable
discrete input. This configuration must be specified in the configuration of the device using the Service
Tool. If AUX1 is selected to perform the run enable function, then 5 V (5–32 V) applied to pin 8 will allow
the control to run normally. When this input is opened, the actuator will be in stand-by mode. When in
stand-by, the actuator driver will be disabled, and the shaft will be limp.
AUX2 can be used as a 0–5 V command signal for position control. The software must recognize that the
unit is expecting an analog command as opposed to a PWM command. See Figure 3-7 below for typical
usage of AUX1 and AUX2 when the L-Series is configured as a position control.
Woodward 32
Released
This actuator can also be commanded using a PWM signal. See the
description above in the PWM Command Input section. The PWM and
AUX2 input pins should not be tied together.
L-Series
Aux.2 Input
(Pin 10) Clamp to 5V Analog
Command
0.5V to 4.5VDC 10k Signal to
Command Signal Processor
1000pF 499k
** if optional external Run Enable is chosen during L-Series configuration, Aux. 1 can be used to enable or
disable the actuator output shaft torque.
Woodward 33
Released
GROUND
Ground
Junction
JUNCTION
Woodward 34
Released
Chapter 4.
Service Tool
Introduction
This chapter covers the process of tuning, configuring, calibrating, and servicing the control via the L-
Series Service Tool. It is assumed that the control has already been installed on the engine.
Description
The Service Tool software is used to configure, tune, and troubleshoot the L-Series controller. This
chapter describes installation and use of the Service Tool. It identifies the parameters available that can
be viewed. It also provides detailed information on configuring and setting up the L-Series to the
customer-specific field application.
The Service Tool software resides on a PC (personal computer) and communicates to the L-Series
through connector pins 4 and 6. An external
RS-232 transceiver is necessary to make communications possible with the Woodward L-Series service
tool. A connectivity kit (Woodward # 8923-1061) can be purchased from Woodward to accomplish this.
Woodward 35
Released
In addition to the hardware, the following are the distributions of tool software needed to communicate
with the control:
Woodward part number 9927-1222, L-Series Service Tool
Woodward 36
Released
Getting Started
Installation Procedure
The Service Tool software can be downloaded and installed from the Woodward internet site
(www.woodward.com).
What to do next
After the software is installed, connect a serial communications cable between the RS-232 connections
on the L-Series control and an unused serial port on your computer. Run the Service Tool program and
select the appropriate comm port. Once connected to the control, the status bar will display ‘connected’
and the Service Tool screen will populate with monitor parameters.
Woodward 37
Released
Configuration Password
If a password has been saved in the configuration file, the file cannot be opened without first entering the
password. Once a configuration with a password has been loaded into the L-Series driver, the control
configuration cannot be opened without the password. All other service tool functions do not require a
password including: writing over a password protected file configuration, writing over a password
protected control configuration, using the Position Calibration Tool, and using the Edit Position PID.
L-Series Configuration
The L-Series can be configured either on-line or off-line. On-line configuration can only be performed
when the Service Tool is connected to and communicating with the L-Series control. Off-line configuration
can be done at any time, however, settings will not take effect until they are loaded into the control.
The current L-Series control configuration settings can be viewed at any time when connected to the
control by opening the Configuration Editor (File/Open Control Configuration). See Figure 4-3.
Woodward 38
Released
Configuration Parameters
There are three tab sheets that contain all the configuration settings: Overview, Discrete Output, and
Alarm/Shutdown.
A description of each configuration parameter and its adjustment range is also available in the contents of
the Service Tool Help.
Woodward 39
Released
Proportional Gain
Sets the position controller PID’s proportional gain. Increased gain corresponds to increased PID output
(higher proportional = faster response). This setting can also be dynamically adjusted using the PID
Tuning screen. Allowed values: 0–100%.
Integral Gain
Sets the position controller PID’s integral gain. Increased gain corresponds to increased PID output
(higher integral = faster response). This setting can also be dynamically adjusted using the PID Tuning
screen. Allowed values: 0–100%.
Derivative Gain
Sets the position controller PID’s derivative gain. Increased gain corresponds to increased PID output
(higher derivative = faster response). This setting can also be dynamically adjusted using the PID Tuning
screen. Allowed values: 0–100%.
Friction/Dither Setting
Sets the position controller’s friction and dither values. This parameter should be set to zero (no effect)
while tuning the PID and then increased for optimum response. If unsure, a typical value would be 25.
Allowed values: 0–100.
Non-linear Actuator
Selects either a Linear position command, when unchecked, or a Nonlinear 5-point curve command.
Linear/Nonlinear refers to the relationship between the position requested and the position commanded to
the position PID. When this box is checked, additional parameters appear to set up the 5-point demand
curve (Figure 4-4).
Woodward 40
Released
These values must maintain a monotonic increase in their values, in order from lowest to highest. Also,
after the configuration is loaded into the control, power must be cycled on the control before the settings
take effect.
PWM Settings
Two additional configuration parameters appear when the position demand is set to PWM (see Figure 4-5).
PWM Offset
Sets the PWM Duty cycle offset. This setting is provided to compensate for duty cycle variations in PWM
input frequencies, voltages, and types. Allowed values: –5.01 to +5.01%
Woodward 41
Released
Woodward 42
Released
Woodward 43
Released
Each screen displays the position setpoint and actual position values.
Position Setpoint
Displayed value of the position demand, in percent.
Actual Position
Displayed value of the actual position, in percent.
Communication Status
This section of the status bar shows the status of communication between the service tool and the L-
Series Driver. For more information, see Establishing Communication.
Connected—The Service Tool is connected to and communicating with the driver.
Not Connected—The Service Tool is not connected to the driver.
Connecting—The Service Tool is attempting to connect to the driver. This message is displayed
when Connect is selected from the Communications menu or when attempting to re-establish
communication to the driver. If the connection is lost it will continuously attempt to re-connect.
Alarm Status
One or more alarms on the Alarms screen is active.
Shutdown Status
One or more shutdowns on the Shutdowns or Internal Shutdowns screen is active.
Woodward 44
Released
Supply Voltage
Displayed value of the input power, in volts, as read by the processor.
Power Demand
Displayed value of the power demanded, in watts, as read by the processor. This is an indication of the
work output.
Electronics Temperature
Displayed value of the electronics temperature sensor, in degrees Celsius, as read by the processor. The
temperature sensor is physically located between the electronics module and the LAT motor.
AUX2 Input
Displayed value of the analog 0–5 V input, in volts. This indication is displayed only when the position
demand is set to ‘0.5 V’.
Discrete Output
On/Off status of the discrete output command. The indicator is illuminated when the channel is
commanded to ON and grayed-out when the command signal is OFF.
Run Enabled
Open (off) / Closed (on) indication of the Run Enable discrete input.
Woodward 45
Released
An active fault is one that is currently active or latched in the control. The latching/non-latching faults
configuration setting factors into this indication. If the fault is latching, then an active fault could either be
one that is still present or one that occurred but has not been reset. Latched faults can be cleared by
cycling power on the L-Series control or by selecting the ‘Reset Alarms and Shutdowns’ button on any of
the Alarm or Shutdown screens.
A logged fault is one that occurred but is no longer currently active or latched in the control. Logged faults
are permanently cleared by selecting the ‘Reset Logged Alarms and Shutdowns’ button on any of the
Alarm or Shutdown screens.
Alarms Screen
To monitor the alarm conditions, go to the Alarms page on the main window. The values displayed on this
screen dynamically change with the fault configuration. Refer to chapter 2 for a complete listing and
details of all the faults.
Woodward 46
Released
Woodward 47
Released
Identification Screen
To monitor the L-Series product identification, go to the Identification page on the main window.
Woodward 48
Released
The L-Series controller can be put into a manual control mode from this screen by selecting the “Enable
Manual Position Tuning’ checkbox (Figure 4-13). Once in manual mode, the position setpoint box is
highlighted and the value displayed is actively positioning the output. Use this command to create step
changes for the PID and monitor the response using the displayed trend.
Pressing the Properties button pops open the Properties Window (Figure 4-14). From this window the
user can adjust the trending window properties including the update rate and display range.
Woodward 49
Released
There are two methods available to perform a position calibration: Automatic or Manual. If the application
has hard stops that correspond to the actual min/max travel, then either Auto or Manual methods can be
used—although auto is easier. If hard stops are not available, then the auto method will give invalid
results and the manual method must be followed.
The Service Tool can be used to calibrate the control to end user stops (physical or soft) or to verify the
position calibration. To get to the Position Calibration screens select the desired function from Position
Calibration under the Tools menu selection.
Position Calibration is only used when the full travel of the actuator
is constrained or limited such that 0 to 60 degrees of travel is not
used.
Woodward 50
Released
Automatic Mode
1. Select Automatic Position Calibration Mode.
2. Select cw or ccw Direction.
3. L-Series automatically rotates in both cw and ccw directions until the stops are detected. The values
are then captured and stored.
4. When completed, cycle the power on the L-Series.
5. It is recommended that a Position Verification be performed to confirm the calibration is correct. See
Position Verification below.
Manual Mode
1. Determine to rotational travel limits. This can be done by positioning the unit to the minimum and
maximum positions and recording the position settings.
2. Select Manual Position Calibration Mode.
3. Select Direction.
4. Enter the pre-determined rotational travel limits values.
5. When completed, cycle the power on the L-Series.
6. It is recommended that a Position Verification be performed to confirm the calibration is correct. See
Position Verification below.
Position Verification
When the Verify Position screen is entered, the control is put into position control and the position is set to
the position the control was at when the screen was entered. The screen displays the “User” Requested
Position, Actual Position, Minimum Position, and Maximum Position (see figure 4-13). These User
Positions are calculated from the user-calibrated stops.
The Full Travel Actual Position is the full stroke factory position without user stops after software
linearization. The Full Travel Sensor Position is the full stroke factory position without user stops before
software linearization. The Full Travel Sensor Position will match the TPS Output Signal.
The Verify Position screen can be used to check the calibration or to get the minimum and maximum
position values for the manual calibration. If the Enable Requested Position Tuning box is checked the
valve can be positioned anywhere from 0 to 100% of the user minimum and maximum stops by entering a
value into the Requested Position. If the Enable Requested Position Tuning box is unchecked the valve
will go limp and can be physical positioned by hand.
If the full factory position calibration range is not being used (the
Manual or Automatic Calibration has been performed) and the
minimum position direction is changed, the calibration must be run
again for the Verify Position mode to work correctly.
Woodward 51
Released
Manual Calibration
The manual calibration mode is used to set the minimum position and fail direction and to calibrate the
valve to user soft stops (inside of any physical stops). The first screen to appear when entering the
manual mode is used to set the minimum position and fail direction. This setting must be correct before
manually calibrating the valve.
Woodward 52
Released
Automatic Calibration
The automatic calibration mode is used to set the minimum position and fail direction and to calibrate the
valve to user physical stops (mechanical hard stops). Like the manual mode, the first screen to appear is
used to set the minimum position and fail direction. This setting must be correct before automatic
calibration is performed.
After setting minimum position and fail direction the screen below will appear. The control is now moving
first to the ccw stop and then to the cw stop to get the physical minimum and maximum positions.
Woodward 53
Released
Woodward 54
Released
Chapter 5.
L-Series Control Specifications
Specifications
Power Supply 12/24 V systems (10–32 Vdc) reverse polarity protection, 2.5 A max
Power Consumption 32 W maximum
Torque Nominal: 0.34 Nm (0.25 lb-ft) at 25 °C
Maximum Transient (at 105 °C): 0.20 Nm (0.15 lb-ft)
Minimum Continuous (at 105 °C): 0.14 Nm (0.10 lb-ft)
Mass/Weight 425 g (15 oz)
Power-Up to Operation Time <250 ms
Performance
Positioning Accuracy ±2% (analog or PWM command), ±1.0% (CAN)–at 25 °C
±4% (analog), ±3.6% (PWM), ±3% (CAN)–over temperature range
Slew Time 10%–90% 33 ms
Overshoot 1%
Settling Time 10 ms
–6 db Roll-off at ±0.5% Input 32 Hz
–3 db Roll-off at ±2% Input 8 Hz
Environment
Ambient
Operating Temperature –40 to +105 °C (–40 to +221 °F)
Storage Temperature –40 to +125 °C (–40 to +257 °F)
EMC EN61000-6-2: Immunity for Industrial Environments
EN61000-6-4: Emissions for Industrial Environments
SAE J1113-21: Radiated Immunity (100 V/m)
SAE J1113-11: Conducted Transient Immunity – Pulse 5b, Suppressed Load
Dump (45 V)
Humidity US MIL-STD 810E, Method 507.3, Procedure III
Salt Spray US MIL-STD 810E, Method 509.3, Procedure I
Shock MS1-40G 11 ms sawtooth
Random Vibration Random: 0.3 G²/Hz, 10–2000 Hz (22.1 Grms) 3 h/axis
Sine: 5 G 2.5 mm peak-to-peak, 5–2000 Hz, 3 h/axis, 90 min dwells, 1
octave/min
Drop SAE J1211, Paragraph 4.8.3 (modified)
Thermal Shock SAE J1455, Paragraph 4.1.3.2
Ingress Protection IP56 per EN60529
Parameter Value
Input Type 0–5 V, Single-Ended Input
Input Scaling 0.5 V = 0% and 4.5 V = 100% position
Max Input (Full Scale) 5 V ± 1%
Isolation None
Transient Protection According to EMC norm
Input Impedance 499 kΩ
Anti-Aliasing Filter 1 anti-aliasing pole at 0.5 ms (338 Hz)
Resolution 10 bits
±1.3% of full scale over the temperature
Accuracy
range of –40 to +125 °C, including drift
I/O Latency 6.5 ms
Calibration Method 2-point linear software calibration
Out of Range Signal < 0.2 V or > 4.8 V
Input protected against 32 Vdc steady
Overvoltage Protection
state
Woodward 55
Released
Parameter Value
Input Magnitude 5–32 V p-p
Frequency Range 300–1500 Hz
Duty Cycle Scaling 10% = fully closed and 90% = fully open
Isolation None
Input Impedance Push-Pull Mode 44 kΩ–113 kΩ
Input Impedance Open Collector Mode,
15 kΩ
High Side or Low Side.
Resolution 16 bits at 300 Hz, 14 bits at 1.5 kHz
±1% of full scale (duty cycle), over the
Accuracy temperature range of –40 to +125 °C,
including drift
I/O Latency 6.5 ms
Duty cycle offset adjustment is available
Calibration in Service Tool. This will tailor the input
to the signal source
Out of Range Frequency None
Out of Range Duty Cycle < 3% or > 97%
Discrete Input
Parameter Value
Input Current 0.5 mA @ 5 Vdc
Input Type Ground referenced discrete input
Delay Time for Shutdown < 200 ms for system to recognize
shutdown
Delay Time for Reset Detection < 1 s for valves to move to minimum
position
Max Voltage from + Connection 32 V (power input voltage)
Isolation None, Intended for use with external
relay or other dry contact
Input Thresholds > 3.1 Vdc = “ON” < 0.8 Vdc = “OFF”
Input Current 0.5 mA @ 5 Vdc
Discrete Output
Parameter Value
Output Type Low-side output driver
Max Contact Voltage (Open) 32 V
Max Current 0.5 A
Max Contact Voltage at 0.5 A (Closed) 1.5 V
Max Delay Time for Opening Contact 6.5 ms
Default at Power Up Configurable in software
Error Condition Configurable in software
OK Condition Configurable in software
Driving Inductive Loads Yes, internally protected low-side switch
Utilizes circuitry that will open the
contact when output contacts are short-
Protection
circuited. Self-resetting when fault is
removed
Woodward 56
Released
Parameter Value
Output Type 0–5 V, single-ended
0.75 V = full ccw position and
Output Scaling
4.25 V = full cw position
Isolation None
3 db Circuit Bandwidth 350 Hz
Transient Protection According to EMC norm
Output Impedance 2.8 kΩ (±1%)
Accuracy ±10% of full scale, @ 25 °C
Temperature Drift ±0.4% over the full temperature range
I/O Latency n/a–direct from position sensor
Sensor-in-place factory calibration.
Calibration Method
2-point linear
Out of Range Signal < 0.25 V or > 4.75 V
Output protected against 32 Vdc,
steady-state; if >28 V is applied to pin
Overvoltage Protection
2, a position-related error will be
annunciated
Parameter Value
Isolation None
Baud Rate Fixed 19.2 Kbaud
Outputs are TTL level.
Requires external transceiver for
Electrical Interface
conversion to RS-232 levels for proper
communication
Pinout Tx = pin 4, Rx = pin 6, Gnd = pin 3
10 m (33 ft), not meant for permanent
Maximum Cable Length
connection (for service only)
Cable Type Straight-through (no crossover)
Parameter Value
±2 °C at 25 °C ambient
Accuracy
±3 °C over full range (–40 to +125 °C)
I/O Latency 6.5ms
Woodward 57
Released
Woodward 58
Released
Chapter 6.
Troubleshooting
Introduction
This chapter presents several broad categories of application failures typically experienced in the field,
possible causes, and some tests used to verify the causes. Because the exact failure experienced in the
field is the product of the mechanical/electrical failure combined with the configuration file resident in the
control, it is left as the OEM’s responsibility to create a more detailed troubleshooting chart for the end
user. Ideally, this end-user troubleshooting chart will contain information about mechanical, electrical,
engine, and load failures in addition to the possible governor failures. For more detailed information about
governor system failure modes and effects, contact Woodward for a copy of the system DFMEA.
The troubleshooting scenarios listed below assume that the end user has a digital multimeter at his
disposal for testing voltages and checking continuity, and assume that the application has been
engineered and tested thoroughly.
Woodward 59
Released
Engine/Generator Troubleshooting
Table 6-1. Engine/Generator Troubleshooting Chart
Woodward 60
Released
Service Tool not Old version of Service Re-install Service Tool, get the latest version
communicating–‘Error Tool or file corruption or from the Woodward web site
message displayed on bad install. (www.woodward.com)
PC when trying to
connect
Service Tool will not Cap Lock is on. Password is case sensitive, make sure you enter
except password the password correctly using upper and lower
case.
Woodward 61
Released
PWM Input
If the PWM input is not functioning properly, verify the following:
Measure the input voltage, frequency, and duty cycle.
Check the values seen by the L-Series driver using the Service Tool and verify that is matches the
input signal.
Check the wiring. Look for loose connections and disconnected / misconnected cables/connections.
Check the software configuration to ensure that the input is configured properly as the demand
source.
Discrete Output
If the discrete output is not functioning properly, verify the following:
Measure the output voltage on the terminal block. It should be in the range of 10–28 Vdc when the
output is off/false. The voltage will be in this range only if all shutdowns are false. This can be
verified through the Service Tool.
Check the wiring, looking for loose connections or disconnected / misconnected cables.
Verify the configuration of the output.
Service Tool
If the service tool is not functioning properly, review the installation information in Chapter 4. Verify the
following:
Check the wiring, looking for loose connections or disconnected / misconnected cables.
Check that Service Tool is running. Verify the Port setting is correct.
Follow on-screen error messages. Re-install software as needed. The latest version of software is
available for download from the Woodward web site (www.woodward.com).
Woodward 62
Released
Chapter 7.
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are installed into the equipment
system and programmed by an Original Equipment Manufacturer (OEM) or Equipment Packager at their
factory. In some cases, the programming is password-protected by the OEM or packager, and they are the
best source for product service and support. Warranty service for Woodward products shipped with an
equipment system should also be handled through the OEM or Packager. Please review your equipment
system documentation for details.
Woodward Business Partner Support: Woodward works with and supports a global network of
independent business partners whose mission is to serve the users of Woodward controls, as described
here:
A Full-Service Distributor has the primary responsibility for sales, service, system integration
solutions, technical desk support, and aftermarket marketing of standard Woodward products within
a specific geographic area and market segment.
An Authorized Independent Service Facility (AISF) provides authorized service that includes repairs,
repair parts, and warranty service on Woodward's behalf. Service (not new unit sales) is an AISF's
primary mission.
A Recognized Engine Retrofitter (RER) is an independent company that does retrofits and
upgrades on reciprocating gas engines and dual-fuel conversions, and can provide the full line of
Woodward systems and components for the retrofits and overhauls, emission compliance upgrades,
long term service contracts, emergency repairs, etc.
Woodward 63
Released
This option allows you to call your Full-Service Distributor in the event of an unexpected outage, or in
advance of a scheduled outage, to request a replacement control unit. If the unit is available at the time of
the call, it can usually be shipped out within 24 hours. You replace your field control unit with the like-new
replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard mechanical products and some
of the electronic products in the field. This program offers you repair service for your products with the
advantage of knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat Rate Repair option, with
the exception that the unit will be returned to you in “like-new” condition. This option is applicable to
mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
Woodward 64
Released
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our products. For these
services, you can contact the Distributor by telephone or by email.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local Full-Service Distributor,
or from many of Woodward’s worldwide locations, depending upon the product and application. This
service can assist you with technical questions or problem solving during the normal business hours of
the Woodward location you contact.
Product Training is available as standard classes at many Distributor locations. Customized classes are
also available, which can be tailored to your needs and held at one of our Distributor locations or at your
site. This training, conducted by experienced personnel, will assure that you will be able to maintain
system reliability and availability.
Field Service engineering on-site support is available, depending on the product and location, from one
of our Full-Service Distributors. The field engineers are experienced both on Woodward products as well
as on much of the non-Woodward equipment with which our products interface.
For information on these services, please contact one of the Full-Service Distributors listed at
www.woodward.com/directory.
You can also contact the Woodward Customer Service Department at one of the following Woodward
facilities to obtain the address and phone number of the nearest facility at which you can obtain
information and service.
Woodward 65
Released
Technical Assistance
If you need to contact technical assistance, you will need to provide the following information. Please write
it down here before contacting the Engine OEM, the Packager, a Woodward Business Partner, or the
Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or the menu
settings written down and with you at the time of the call.
Woodward 66
Released
Appendix A.
L-Series Configuration Summary
APPLICATION ________________________________________________
Woodward 67
Released
Revision History
New Manual—
Woodward 68
Released
Declarations
Woodward 69
Released
Woodward 70
Released
Woodward 71
Released
ËB35154è:-µºµ¸µ¸Î