Service: Residential/Commercial Generator Sets
Service: Residential/Commercial Generator Sets
Service: Residential/Commercial Generator Sets
Models:
15/30RYG
15/30RES
Controller:
Advanced Digital Control
TP-6198 10/04a
Table of Contents
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPower.com. Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product. Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444.
(91) 80 3366231
D Outside the US and Canada, call the nearest regional Fax: (91) 80 3315972
office. Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Fax: (813) 3440-2727
3 rue de Brennus
93200 Saint Denis Latin America
France Latin America Regional Office
Phone: (33) 1 49 178300 Lakeland, Florida, USA
Fax: (33) 1 49 178301 Phone: (863) 619-7568
Fax: (863) 701-7131
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
15RES 30RES
and and
Alternator Specification 15RYG 15RYG 30RYG 30RYG 30RYG 30RYG
Alternator model 4H7 4J7 2F5 2G5 2F7 2G7
Stator leads, qty. 4 12 4 12 4 12
Phase 1 3 1 3 1 3
Rotor resistance, ohms, cold 3.0 3.0 4.2 4.2 5.6 5.6
Stator resistance, ohms,* cold
Main winding: 1-2, 3-4 0.07 — 0.03 — 0.02 —
Main winding: 1-2, 3-4, 5-6, 7-8, 9-10, 11-12 — 0.04 — 0.09 — 0.06
Aux. winding: 55-66 1.26 1.3 0.53 0.19 0.44 0.18
Stator output AC voltage with separately excited rotor using 12-volt battery, minimum
Main winding: 1-2, 3-4 105 — 105 — 88 —
Main winding: 1-2, 3-4, 5-6, 7-8, 9-10, 11-12 — 120 — 140 — 112
Aux. winding: 55-66 130 150 140 190 117 150
Rotor field DC voltage/current readings at rated output voltage, hot
No load 16V/4.5A 16V/4.5A 16V/3.9A 12V/2.5A 19V/3.9A 15V/2.2A
Full load 36V/8.6A 40V/9.5A 46V/7.6A 63V/9.8A 53V/7.4A 69V/9.6A
* Most ohmmeters do not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance
reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with
a reading indicating a shorted winding.
7 9 10 11
6
5 Service-Side View 12
8
4
3
13
14
1 15
24 23 22 21 20 19 18 17 16
27
28
32
GM32850D-J
31 30 29
1. Fuses (F1, F2, and F3) 17. Coolant overflow bottle (daily coolant check/fill location)
2. Generator set master switch (RUN\OFF/RESET\AUTO) 18. Secondary fuel regulator
3. Advanced Digital Control (ADC 2100) 19. Fuel solenoid valve
4. Runtime hour display 20. Oil drain valve
5. Nameplate 21. Positive (+) battery connection point
6. Air cleaner 22. Fuel inlet
7. Oil check 23. Engine control module (ECM)
8. Oil fill (on valve cover) 24. AC line circuit breaker panel
9. Coolant temperature sender 25. Exhaust connection
10. Fuel/air mixer 26. Spark plugs
11. Pressure cap (engine water fill) 27. Remote customer interface connector
12. Coolant overflow tube 28. Customer load lead access
13. Radiator 29. Oil filter
14. Belt guard 30. Negative (--) battery connection point
15. Battery charging alternator 31. Coolant drain
16. Low oil pressure switch 32. Cooling air inlet
Servicing the exhaust system. Hot parts can cause 2.1 Service Schedule
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely Perform the items listed in the service schedule at the
hot during operation. designated intervals for the life of the generator set. For
example, an item serviced every 100 hours or 3 months
WARNING must also be serviced after 200 hours or 6 months,
300 hours or 9 months, etc.
Note: The generator set will not start and circuit board
damage may result if the battery is connected in
reverse.
Sulfuric acid in batteries.
Can cause severe injury or death.
1 2
Wear protective goggles and
clothing. Battery acid may cause
blindness and burn skin.
Troubleshooting Chart
Problem Possible Cause Corrective Action Reference
Generator Weak or dead battery Recharge or replace battery. O/M
set does not If battery is weak or dead, check battery charger fuse, power
crank supply, and operation.
Battery connections Check for reversed or poor battery connections. —
Open circuit in engine/ Check for loose connections. Section 6
controller connections Check the wire harness continuity.
Blown fuse F3, controller Replace fuse; if fuse blows again, check circuit and Section 5.12
components. Section 6
Blown fuse F2, relay Replace fuse. Section 5.12
interface board (RIB) If fuse blows again, disconnect the board leads one at a time to Section 6
identify the cause of the blown fuse:
Lead 70A at the fuel valve
Lead 71A at P30
Leads FP and FN at the rotor
Repair or replace the component causing the blown fuse.
Engine S/M: Engine Service Manual I/M: Generator Set Installation Manual O/M: Generator Set Operation Manual
4.1 Introduction A relay interface board (RIB) is used with the controller.
Section 4.6 describes the standard and optional RIBs.
This section describes the operation and replacement of
the ADC 2100 controller. Controller configuration and A silicon controlled rectifier (SCR) module works with
adjustment are explained Section 4.9. See Section 3 for the controller to regulate the output voltage. See
troubleshooting procedures. Section 4.7.
1
4 6 8
2 5
GM32850B-
4
GM28707A-C
1. LED display
2. Select button (for setup and adjustment only)
3. Up and down arrow buttons (for setup and adjustment only)
4. Generator set master switch
Item Description
Crank Displays CC_1, CC_2, or CC_3 to
indication indicate the first, second, or third
attempt to start the engine. The last
digit flashes during the crank cycle rest
periods. tp6196
AUTO
5 4 3
RUN
VBAT
4.5.1 Warnings
The fault conditions listed in Figure 4-5 will cause the
controller to display a fault code but will not shut down
the generator set.
4.5.2 Shutdowns
7
Under the fault conditions listed in Figure 4-8, the 1 4
controller displays a fault code and the generator set 3 1
COMMON AUX
shuts down. K1 FAULT K4 RUN
2
D1
5
shutdown before restarting the generator set. Refer to
K2
CRANK P14 K5
Section 3, Troubleshooting, for instructions to identify
D6
D7
RUN
D2
3
Move the generator set master switch to the OFF/ 9 7
R1
shutdown. Then move the switch to the AUTO or RUN T1
R2
R3
FN LED1
RUN
VBAT LED2
position. FLASH R
R
LED3
K3 FLASH FP CRANK
D4
D5
T2 R
Required equipment:
AC1
D Ohmmeter
D 12-volt test lamp (or voltmeter) (+) AC2
(--)
D 12-volt DC power source
D 100--500 ohm resistor G2
tp6198
D Jumper
1. Place the generator set master switch in the OFF 10. Reconnect the engine starting battery, negative (--)
position. lead last.
2. Disconnect power to the battery charger. 11. Reconnect power to the battery charger, if
equipped.
3. Disconnect the generator set engine starting
battery, negative (--) lead first. 12. Follow the instructions in Section 4.9 to change the
new controller’s configuration settings to match the
4. Remove four mounting screws from the front of the generator set system voltage and frequency, unit
controller. configuration, engine type, engine data input
types, battery voltage, and communications
5. Carefully pull the controller forward, angling it so settings.
that the P1 connector on the right side clears the
opening in the mounting plate.
4.9 Controller Configuration and Note: Be sure to save your settings before exiting the
Adjustment configuration mode.
This section contains instructions for using the Voltage changes are lost if they are not saved before the
controller’s password-protected menus to check and generator set shuts down. The generator set continues
adjust the generator output and controller configuration. to run with the new settings until it shuts down but then
The controller configuration and generator set output reverts to the previous settings at the next startup if the
are factory-set and should not require field adjustment changes have not been saved.
under normal circumstances. Check and adjust the
configuration and/or output in the following cases: Pressing the Select button when SAVE is displayed
returns to the first parameter, voltage adjust (1P).
D Check and adjust the controller configuration and
generator output after generator set reconnection to a Note: Refer to the flowcharts in Figure 4-13 and
different voltage. Figure 4-14 during the voltage adjustment
procedure.
D Check controller configuration when troubleshooting
generator set problems. Voltage Adjustment Procedure
D Check and adjust the generator set output after 1. With the generator set off, connect a digital
installation if the voltage requires adjustment for a multimeter to the output leads or an electrical outlet
particular application. on the load side of the generator set. Set the meter
to measure AC voltage.
4.9.1 Voltage Adjustments 2. Start the generator set by moving the generator set
master switch to the RUN position.
WARNING
3. Use the ADC controller to adjust the voltage
(parameter 1P) until the output voltage reaches the
desired value. See Figure 4-12 for the
approximate change in voltage per step in
Hazardous voltage. Moving parts.
parameter 1P.
Can cause severe injury or death.
Voltage Change per Step, VAC
Operate the generator set only when Measured
all guards and electrical enclosures Voltage, VAC Coarse Adjust Fine Adjust
are in place. 85--132 5 0.5
180--251 7 0.7
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury Figure 4-12 Voltage Adjustment (approximate)
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or 4. Adjust the voltage stability (gain, parameter 2P) to
repairs. Remove all jewelry before servicing the equipment. minimize light flicker.
The controller’s adjustment mode allows adjustment of 5. Readjust the voltage, if necessary.
the output voltage, if necessary. Have adjustments
performed by an authorized distributor/dealer or service 6. Stop the generator set.
technician.
Press:
or
To raise or lower the voltage in large increments 1 P x x
(approximately 5--7 volts per step).
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
To save changes. Y E S
or
To discard changes without saving. n o
“Yes”or “no” flashes when the up or down arrow is pressed and then the
controller exits the configuration mode. The display returns to the x x x x
runtime hours.
* X in the examples above denotes any number from 0 to 9. The actual values
may vary from model-to-model.
Parameter Low Coolant Level Sensor Pressure Sensor Temperature Sensor Magnetic Pickup
Ed00 Digital Switch Digital Switch Digital Switch No
Ed01 Digital Switch Digital Switch Analog Sender No
Ed02 Digital Switch Analog Sender Digital Switch No
Ed03 Digital Switch Analog Sender Analog Sender No
Ed04 Digital Switch Digital Switch Digital Switch Yes
Ed05 * Digital Switch Digital Switch Analog Sender Yes
Ed06 Digital Switch Analog Sender Digital Switch Yes
Ed07 Digital Switch Analog Sender Analog Sender Yes
Ed08 Analog Sender Digital Switch Digital Switch No
Ed09 Analog Sender Digital Switch Analog Sender No
Ed10 Analog Sender Analog Sender Digital Switch No
Ed11 Analog Sender Analog Sender Analog Sender No
Ed12 Analog Sender Digital Switch Digital Switch Yes
Ed13 Analog Sender Digital Switch Analog Sender Yes
Ed14 Analog Sender Analog Sender Digital Switch Yes
Ed15 Analog Sender Analog Sender Analog Sender Yes
* Factory setting for replacement controllers. See Figure 4-15 for the default settings for certain models. The installation of optional sender
kits (available for some models) may require a different Ed setting.
Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
To enter advanced configuration mode. E d 0 1
Go to Figure 4-18.
or
or To proceed to the save mode without
entering the advanced configuration mode. S AV E
Go to Figure 4-19.
Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed.
Figure 4-17 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts
to the last saved settings when the master switch is moved to the OFF/RESET position.
Figure 4-18 Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)
To save changes. Y E S
or
To discard changes without saving. n o
“Yes”or “no” flashes when the up or down arrow is pressed and then
the controller exits the configuration mode. The display returns to
the runtime hours.
x x x x
Note: The jumper must be connected for continuous 10. Reconnect power to the battery charger, if
power if the optional Remote Digital Gauge is equipped.
used.
11. Place the generator set master switch in the AUTO
Use the following procedure to disconnect the jumper, if position.
desired.
2
Procedure to disconnect the continuous power
mode jumper (optional). 1
1. Prevent the generator set from starting.
4. Check for AC output across the stator leads; see Hazardous voltage. Moving parts.
Section 5.3, Stator. Compare the readings to the Can cause severe injury or death.
AC output values shown in Section 1,
Operate the generator set only when
Specifications. If the readings vary considerably, a
all guards and electrical enclosures
faulty stator is likely. Refer to Section 5.3, Stator, are in place.
for further information.
High voltage test. Hazardous voltage can cause severe
5. If this test shows that the rotor and stator are in
injury or death. Follow the instructions of the test equipment
good condition, check the wiring and fuses. Check manufacturer when performing high-voltage tests on the rotor
the SCR module. See Section 4.7, Silicon or stator. An improper test procedure can damage equipment
Controlled Rectifier (SCR) Module. Check the or lead to generator set failure.
controller settings and connections. See
Section 4, Controller.
4. Disconnect all stator leads before performing all Note: For three-phase models, leads 1--12 are the
stator tests. generator output leads. Leads V7, V8, V9, 55,
and 66 are the controller and SCR module
5. To check for stator continuity, set the ohmmeter on sensing and supply leads. Refer to the schematic
R x 1 scale. First set the ohmmeter zero by holding in Figure 5-6 when performing the following
the red and black meter leads together and setting steps.
the ohmmeter reading to zero. Then check the
stator continuity by connecting the meter leads to
the stator leads as shown in Figure 5-4.
R14807-14 tp6198
7 5
Side View
6
8 9
3
New 1.9 cm (0.75 in.)
2 2
3
TP5867
1. Brush holders (2) 7. Brush holder
2. Slip ring 8. Correctly positioned
3. Brush brush
4. Retainer wire 9. Incorrectly positioned
5. Shim brush
6. Spring
The factory sets the voltage for correct generator Grounding electrical equipment. Hazardous voltage can
operation under a variety of load conditions. Usually, the cause severe injury or death. Electrocution is possible
voltage needs no further adjustment. Adjust the voltage whenever electricity is present. Ensure you comply with all
when necessary according to the following procedure. applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
The adjustment procedure requires a meter that can
power sources before servicing the equipment. Never
measure voltage and frequency. contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk
Use the ADC controller to adjust the voltage, gain, and of electrocution.
volts/hertz (Hz). Refer to Section 4.9.2 for instructions to
adjust each parameter and save changes using
Voltage Adjustment Procedure
controller keypad.
1. Connect a digital voltmeter from one side of the
Note: The ADC controller will time out and exit the circuit breaker to the L0 terminal on the end bracket
adjustment mode after approximately 1 minute if casting. See Figure 5-11. Set the meter to
no buttons are pressed. Any unsaved changes measure voltage.
are discarded if the controller times out before the
settings are saved. Refer to Section 4.9.2 for
instructions to save your settings.
Note: The controller will revert to the previous 3. Stop the generator set.
settings at the next startup if the changes are
not saved.
5.8 Voltage Reconnection
7. Stop the generator set.
Voltage Reconnection is covered in the generator set
Installation Manual. See the List of Related Materials for
Volts per Hertz Adjustments
the document number.
The cut-in frequency is set at 57.5 Hz (60 Hz system) or
47.5 Hz (50 Hz system) and is not adjustable. When the
frequency falls below the cut-in, output voltage is 5.9 Governor System
reduced to relieve the engine. The amount of the
The frequency of the alternator output is determined by
voltage reduction is set by the 3P parameter. Monitor
the speed of the engine. A four-pole alternator must be
engine speed and output voltage as loads are applied.
driven at 1800 rpm to provide 60 Hz. A two-pole
D If there is excessive droop in engine speed and little
alternator must be driven at 3600 rpm to provide 60 Hz.
droop in voltage, increase the 3P value. The engine speed is maintained by the Engine Control
Module (ECM). See the engine documentation for ECM
D If there is little engine speed droop but excessive information.
voltage droop, decrease the 3P value.
WARNING
1
tp6198
1. Coolant temperature sensor (CTS) The fuel supplier provides and maintains manual
shut-off valves and the primary regulator. Verify that the
Figure 5-14 Coolant Temperature Sensor (CTS) fuel system capacity is adequate to supply the generator
set plus all other gas appliances.
Low Oil Pressure (LOP) Switch A factory-installed secondary regulator and 12 VDC
solenoid valve are located in the front inlet air
Remove the LOP switch and install an oil pressure
compartment. The controller energizes the fuel
gauge to verify that the engine oil pressure is within the
solenoid valve to open at startup and deenergizes the
range specified in Section 1, Specifications, before
valve to close at shutdown. The secondary fuel
testing or replacing the LOP switch. See Figure 5-15.
regulator reduces fuel pressure for delivery to the fuel
To test the LOP switch, reinstall the switch and start the
block. The fuel flows from the fuel block to the
generator set. If the unit shuts down, disconnect lead 13
carburetor in a gaseous state. The carburetor mixes the
from the LOP switch and reset the controller. Restart the
fuel with intake air for consumption by the engine.
generator set and verify that it does not shut down. A
successful restart indicates a bad LOP switch. Replace
the switch.
tp6198
COM
RUN
AUTO
5.13 Continuity Checks Zero ohms (continuity) across
COM and AUTO terminals
WARNING
3 2 1
Master Switch in
AUTO Position
COM
RUN
AUTO
Hazardous voltage. Moving parts.
Can cause severe injury or death. tp6196
Operate the generator set only when Figure 5-19 Generator Set Master Switch Continuity
all guards and electrical enclosures
Checks (back view of switch)
are in place.
Use the information below and on the following pages to Steps for common hardware application:
identify proper fastening techniques when no specific
reference for reassembly is made. 1. Determine entry hole type: round or slotted.
Bolt/Screw Length: When bolt/screw length is not given, 2. Determine exit hole type: fixed female thread
use Figure 1 as a guide. As a general rule, a minimum (weld nut), round, or slotted.
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is For round and slotted exit holes, determine if
the preferred method. hardware is greater than 1/2 inch in diameter, or
1/2 inch in diameter or less. Hardware that is
Washers and Nuts: Use split lock washers as a bolt greater than 1/2 inch in diameter takes a standard
locking device where specified. Use SAE flat washers nut and SAE washer. Hardware 1/2 inch or less in
with whiz nuts, spiralock nuts, or standard nuts and diameter can take a properly torqued whiz nut or
preloading (torque) of the bolt in all other applications. spiralock nut. See Figure 2.
See Appendix C, General Torque Specifications, and 3. Follow these SAE washer rules after determining
other torque specifications in the service literature. exit hole type:
3 2
1
3
G-585
5
4
6
G-585
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
Notes:
1. The torque values above are general guidelines. Always use the torque values specified in the service manuals and/or assembly
drawings when they differ from the above torque values.
2. The torque values above are based on new plated threads. Increase torque values by 15% if non-plated threads are used.
3. Hardware threaded into aluminum must have either two diameters of thread engagement or a 30% or more reduction in the torque to
prevent stripped threads.
4. Torque values are calculated as equivalent stress loading on American hardware with an approximate preload of 90% of the yield strength
and a friction coefficient of 0.125.
Drive Styles
External Tooth Lock
Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillipsr
Slotted
Hex Socket
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts) Plain Washers
1/4-20 x 1 9/32 x 5/8 x 1/16
Length In Inches (Screws and Bolts) Thickness
Threads Per Inch External Dimension
Major Thread Diameter In Fractional Inches Or Screw Number Size Internal Dimension
Metric (Screws, Bolts, Studs, and
Nuts)
M8-1.25 x 20 Lock Washers
Length In Millimeters (Screws and Bolts) 5/8
Distance Between Threads In Millimeters Internal Dimension
Major Thread Diameter In Millimeters
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No. Dimensions Part No. Dimensions Part No. Dimensions Type
Hex Head Bolts (Grade 5) Hex Head Bolts, cont. Hex Nuts
X-465-17 1/4-20 x .38 X-6238-14 3/8-24 x .75 X-6009-1 1-8 Standard
X-465-6 1/4-20 x .50 X-6238-16 3/8-24 x 1.25
X-465-2 1/4-20 x .62 X-6238-21 3/8-24 x 4.00 X-6210-3 6-32 Whiz
X-465-16 1/4-20 x .75 X-6238-22 3/8-24 x 4.50 X-6210-4 8-32 Whiz
X-465-18 1/4-20 x .88 X-6210-5 10-24 Whiz
X-465-7 1/4-20 x 1.00 X-6024-5 7/16-14 x .75
X-6024-2 7/16-14 x 1.00 X-6210-1 10-32 Whiz
X-465-8 1/4-20 x 1.25
X-465-9 1/4-20 x 1.50 X-6024-8 7/16-14 x 1.25 X-6210-2 1/4-20 Spiralock
X-465-10 1/4-20 x 1.75 X-6024-3 7/16-14 x 1.50 X-6210-6 1/4-28 Spiralock
X-465-11 1/4-20 x 2.00 X-6024-4 7/16-14 x 2.00 X-6210-7 5/16-18 Spiralock
X-465-12 1/4-20 x 2.25 X-6024-11 7/16-14 x 2.75 X-6210-8 5/16-24 Spiralock
X-465-14 1/4-20 x 2.75 X-6024-12 7/16-14 x 6.50
X-6210-9 3/8-16 Spiralock
X-465-21 1/4-20 x 5.00 X-129-15 1/2-13 x .75 X-6210-10 3/8-24 Spiralock
X-465-25 1/4-28 x .38 X-129-17 1/2-13 x 1.00 X-6210-11 7/16-14 Spiralock
X-465-20 1/4-28 x 1.00 X-129-18 1/2-13 x 1.25 X-6210-12 1/2-13 Spiralock
X-125-33 5/16-18 x .50 X-129-19 1/2-13 x 1.50 X-6210-15 7/16-20 Spiralock
X-125-23 5/16-18 x .62 X-129-20 1/2-13 x 1.75 X-6210-14 1/2-20 Spiralock
X-125-3 5/16-18 x .75 X-129-21 1/2-13 x 2.00
X-129-22 1/2-13 x 2.25 X-85-3 5/8-11 Standard
X-125-31 5/16-18 x .88 X-88-12 3/4-10 Standard
X-125-5 5/16-18 x 1.00 X-129-23 1/2-13 x 2.50
X-129-24 1/2-13 x 2.75 X-89-2 1/2-20 Standard
X-125-24 5/16-18 x 1.25
X-125-34 5/16-18 x 1.50 X-129-25 1/2-13 x 3.00
X-125-25 5/16-18 x 1.75 X-129-27 1/2-13 x 3.50
X-125-26 5/16-18 x 2.00 X-129-29 1/2-13 x 4.00 Washers
230578 5/16-18 x 2.25 X-129-30 1/2-13 x 4.50 Bolt/
X-125-29 5/16-18 x 2.50 X-463-9 1/2-13 x 5.50
X-129-44 1/2-13 x 6.00 Part No. ID OD Thick. Screw
X-125-27 5/16-18 x 2.75
X-125-28 5/16-18 x 3.00 X-129-51 1/2-20 x .75 X-25-46 .125 .250 .022 #4
X-125-22 5/16-18 x 4.50 X-129-45 1/2-20 x 1.25 X-25-9 .156 .375 .049 #6
X-125-32 5/16-18 x 5.00 X-129-52 1/2-20 x 1.50 X-25-48 .188 .438 .049 #8
X-125-35 5/16-18 x 5.50 X-25-36 .219 .500 .049 #10
X-125-36 5/16-18 x 6.00 X-6021-3 5/8-11 x 1.00 X-25-40 .281 .625 .065 1/4
X-125-40 5/16-18 x 6.50 X-6021-4 5/8-11 x 1.25 X-25-85 .344 .687 .065 5/16
X-6021-2 5/8-11 x 1.50 X-25-37 .406 .812 .065 3/8
X-125-43 5/16-24 x 1.75 X-6021-1 5/8-11 x 1.75 X-25-34 .469 .922 .065 7/16
X-125-44 5/16-24 x 2.50 273049 5/8-11 x 2.00
X-125-30 5/16-24 x .75 X-25-26 .531 1.062 .095 1/2
X-6021-5 5/8-11 x 2.25 X-25-15 .656 1.312 .095 5/8
X-125-39 5/16-24 x 2.00 X-6021-6 5/8-11 x 2.50
X-125-38 5/16-24 x 2.75 X-25-29 .812 1.469 .134 3/4
X-6021-7 5/8-11 x 2.75
X-25-127 1.062 2.000 .134 1
X-6238-2 3/8-16 x .62 X-6021-12 5/8-11 x 3.75
X-6238-10 3/8-16 x .75 X-6021-11 5/8-11 x 4.50
X-6238-3 3/8-16 x .88 X-6021-10 5/8-11 x 6.00
X-6238-11 3/8-16 x 1.00 X-6021-9 5/8-18 x 2.50
X-6238-4 3/8-16 x 1.25
X-6238-5 3/8-16 x 1.50 X-6239-1 3/4-10 x 1.00
X-6238-1 3/8-16 x 1.75 X-6239-8 3/4-10 x 1.25
X-6238-6 3/8-16 x 2.00 X-6239-2 3/4-10 x 1.50
X-6238-17 3/8-16 x 2.25 X-6239-3 3/4-10 x 2.00
X-6238-7 3/8-16 x 2.50 X-6239-4 3/4-10 x 2.50
X-6238-8 3/8-16 x 2.75 X-6239-5 3/4-10 x 3.00
X-6238-9 3/8-16 x 3.00 X-6239-6 3/4-10 x 3.50
X-6238-19 3/8-16 x 3.25 X-792-1 1-8 x 2.25
X-6238-12 3/8-16 x 3.50 X-792-5 1-8 x 3.00
X-6238-20 3/8-16 x 3.75 X-792-8 1-8 x 5.00
X-6238-13 3/8-16 x 4.50
X-6238-18 3/8-16 x 5.50
X-6238-25 3/8-16 x 6.50
Washers
Bolt/
Part No. ID OD Thick. Screw
M125A-03-80 3.2 7.0 0.5 M3
M125A-04-80 4.3 9.0 0.8 M4
M125A-05-80 5.3 10.0 1.0 M5
M125A-06-80 6.4 12.0 1.6 M6
M125A-08-80 8.4 16.0 1.6 M8
M125A-10-80 10.5 20.0 2.0 M10
M125A-12-80 13.0 24.0 2.5 M12
M125A-14-80 15.0 28.0 2.5 M14
M125A-16-80 17.0 30.0 3.0 M16
M125A-18-80 19.0 34.0 3.0 M18
M125A-20-80 21.0 37.0 3.0 M20
M125A-24-80 25.0 44.0 4.0 M24
TP-6198 10/04 69
Notes
70 TP-6198 10/04
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
TP-6198 10/04a 7 Jurong Pier Road
Singapore 619159
E 2004, 2009 by Kohler Co. All rights reserved. Phone (65) 6264-6422, Fax (65) 6264-6455