WP9038ADAM Modbus Extension

The document provides instructions for installing and configuring a Modbus extension module. It connects to burners via connector X22. The module uses Modbus RTU protocol with 19200 baud, 8 data bits, no parity and 1 stop bit. The burner must be configured to Modbus master mode by changing PAR 87 to 2. PAR 86 must match the module ID of 1. Inputs and outputs on the module can then be monitored and controlled via the burner interface.

Uploaded by

Pauls Krūmiņš
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views5 pages

WP9038ADAM Modbus Extension

The document provides instructions for installing and configuring a Modbus extension module. It connects to burners via connector X22. The module uses Modbus RTU protocol with 19200 baud, 8 data bits, no parity and 1 stop bit. The burner must be configured to Modbus master mode by changing PAR 87 to 2. PAR 86 must match the module ID of 1. Inputs and outputs on the module can then be monitored and controlled via the burner interface.

Uploaded by

Pauls Krūmiņš
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Modbus extension module

Instruction manual
WP9038ADAM
Modbus extension module p 2/5

Table of Contents
1 Installation.................................................................................................................................................3

2 Communication protocol...........................................................................................................................3

3 Burner configuration..................................................................................................................................4

4 Module connections..................................................................................................................................4

WP9038ADAM www.pelltech.eu
Modbus extension module p 3/5

1 Installation
Modbus extension module connects to burners connector X22 as shown below

WP9038ADAM

485B
485A
AVcc
AGnd

Figure 1 Modbus extension module connection with connector X22

2 Communication protocol

Baud rate - 19200


Parity – None
Data bits - 8
Stop bits - 1
Handshake – None

WP9038ADAM www.pelltech.eu
Modbus extension module p 4/5

3 Burner configuration

To make burner compatible with Modbus extension module, it's modbus interface must be switched
from slave to master. It can be done by changing PAR 87 MODBUS TYPE from 1 to 2.

PAR 86 MODBUS ID also has to match with the modules id (Default is 1).

In master mode, the burner periodically communicates with modbus extension module, asking
sensor/input data and controlling outputs. All of inputs, both analog and digital can be displayed on
burner's graph in Web.

Modbus extension module is supported from version 2.9.18 and upwards.

4 Module connections

Figure 2 Analog input connection to modbus extension module

WP9038ADAM www.pelltech.eu
Modbus extension module p 5/5

Figure 3 Digital input connection to modbus extension module

Figure 4 Digital output connection to modbus extension module

WP9038ADAM www.pelltech.eu