PSV Testing
PSV Testing
OF PRESSURE RELIEF
VALVES PRVs
This article is about Testing, Calibration, Inspection
and POP UP test of PRVs Pressure Relief Valves and
PSVs Pressure Safety Valves and International Codes
and standards used for it. How to make Pressure
Relief Valve Calibration Certificate and what are
testing requirements for PRV and PSV. Here we
explained complete steps for calibration. Question
asked many times for Frequency for Pressure Relief
valve as per ASME Standard.
Table of Contents:
1. SCOPE
2. PURPOSE
3. REFERENCE STANDARD
4. STANDARD EQUIPMENT
5. RESPONSIBILITIES
6. TEST MEDIUM
7. UUC SPECIFICATION
8. PREPARATION OF TEST INSTRUMENT
9. TEST ACTIVITIES / PROCEDURE (INSPECTION &
TESTING)
13. ATTACHMENTS
1. SCOPE
The Scope of this procedure details the visual examination of
pressure relief valve, adjustment of set pressure (pop up) /
seat tightness (if required). This procedure defines steps to
perform testing & inspection of Safety & Pressure Relief
Valves subject to the requirements.
2. PURPOSE
To improve PRVs performance by assuring that pressure relief
devices will open at the specified set pressure within the
tolerances set by the applicable code. To Ensure RVs remain
in good physical condition and comply with all requirements
of this procedure for external condition.
3. REFERENCE STANDARD
API RP 576 Inspection of Pressure-Relieving Devices
SAEP – 319 Pressure Relief Devices – Testing and
Inspection Requirements
SAEP – 1132 Instructions for Using the Relief Valve Test
Stand
SAES-J-600 Pressure Relief Devices.
SATIP-J-600-01 Safety Relief Valve Installation.
SAIC-J-2008 Relief Valve Testing and Calibration
SAEP-318 Pressure Relief Valve Program Authorization for
Installation, Deletion and Changes.
SAEP-1134 Relief Valve Technician Certification.
Construction Safety Manual
Manufacture Instruction Manual.
NBIC Pressure Relief Device (PRD) Inspection Guide.
ABSA (Alberta Boilers Safety Association), AB-524“Pressure
Relief Devices Requirements”, 2016 Edition
NB-501 National Board Certification of Pressure Relief
Devices “Description of Program and Basic Requirements”
4. STANDARD EQUIPMENT
Shut off & Safety Valve Test Stand Pressure Range 0 to 3045
psi (210 bar) / (Air, Nitrogen & Water).
Shut off & Safety Valve Test Bench Pressure Range 0 to 5800
psi (400 bar) / (Air, Nitrogen & Water).
Shut off & Safety Valve Test Bench Pressure Range 0 to 10005
psi (690 bar) / (Water).
Valve Test Bench Pressure Range 0 to 9138 psi ( 630 bar ) /
(Water).
5. RESPONSIBILITIES
Construction Manager
He shall implement HSE requirements for the job and shall
study, analyze and schedule all construction activities with his
department to include manpower and equipment line up as
well as other possible resources required for the successful
implementation of the construction work activities. He shall
study all aspects of work procedure as per Technical Scope of
Work.
Piping Supervisor
He shall be directly reporting to Construction Manager and
responsible for the implementation and control of all activities
as per JGC/DEC Technical Scope of Work and latest approved
for construction drawings. He shall also designate a
responsible staff that shall be in charge for execution of work
to ensure that schedule, plans and allocations shall be
followed and avoid unnecessary delays and obstructions.
QC Piping Inspector
He shall be responsible for inspection and monitoring of the
work and ensure that the work is performed and properly
documented in accordance with Project requirements.
Safety Supervisor
He shall be responsible for monitoring safely aspects and
ensuring that the testing activity is done in accordance with
JGC/DEC Safety Standard Procedure. He shall discuss with
the workers the characteristics of related materials and status
of work area giving reminders as an additional point to work
safely.
6. TEST MEDIUM
Water
Air
Nitrogen
7. UUC SPECIFICATION
Type of Flanges : RF, RTJ, Welded, Grayloc
Threaded Type : 1/4 to 2 inches
Flange Type : 1/2 to Unlimited.
8. PREPARATION OF TEST
INSTRUMENT
8.1 Prior to start the testing, the following instruction to be
made:
Verify that the test instrument is clean and free from obvious
damage, that it would impair its operation.
Check the test instrument comparing between its name plate
details and specification, if available.
Required Compressed Air at 7 bar to run the pumps.
Availability of single phase 220 V & three phase 380 AC.
Hydraulic Oil – 68 grade – 20 liters for Hydraulic clamping
pump.
Clean water – 100 liters for Hydrostatic test.
Size and Pressure rating of the valve to be tested.
Care should be taken for the maximum test pressure
according to size.
Obtain the Clamping pressure from the chart provided.
9.2 TESTING
9.2.1 Test Stand Operation:
Test Configuration
The valve shall be vertically mounted on the test stand, and
the apparatus shall be attached to the valve outlet.
All openings – including but not limited to caps, drain holes,
vents and outlets shall be closed.
Test Pressure
For a valve with set pressure greater than 50 psi, the leakage
rate in bubbles per minute shall be determined with test
pressure at the valve inlet held at 90 % of the set pressure.
For a valve set at 50 psi, the test pressure shall be held at 5
psi less than the set pressure. (Ref: API 527)
Test Configuration
The valve shall be vertically mounted on the water test
stand.
Test Pressure
For a valve with set pressure greater than 50 psi, the leakage
rate in bubbles per minute shall be determined with test
pressure at the valve inlet held at 90 % of the set pressure.
For a valve set at 50 psi, the test pressure shall be held at 5
psi less than the set pressure. (Ref: API 527)
For Oversize Valves: Both side of the valves is fitted with Blind
Flange of relevant rating and required pressure to be applied
from main unit and it’s not required any separate manifold or
relief valve.
For Oversize Valves: Both side of the valves is fitted with Blind
Flange of relevant rating and required pressure to be applied
from main unit and it’s not required any separate manifold or
relief valve.
For Control & Shut off valves: The valve is clamped from the
inlet on the test port and the outlet of the valves is fitted with
Blind flange of relevant rating and it’s not required any
separate manifold or relief valve.
For Oversize Valves: Both side of the valves is fitted with Blind
Flange of relevant rating and required pressure to be applied
from main unit and it’s not required any separate manifold or
relief valve.