0% found this document useful (0 votes)
107 views6 pages

RHSDW - Model

The document summarizes a screw module chiller model RHSDW series. Key points: 1) The chiller uses microprocessors to control up to 8 modules for large capacities and flexible design. It displays operating conditions for easy management. 2) The chiller uses HFC-407C refrigerant which has zero ozone depletion potential. Hermetic compressors provide a leakless and reliable design. 3) Module chillers are compact and easy to replace, providing high reliability. They save space compared to older centrifugal chillers.

Uploaded by

IMRAN WAHEED
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views6 pages

RHSDW - Model

The document summarizes a screw module chiller model RHSDW series. Key points: 1) The chiller uses microprocessors to control up to 8 modules for large capacities and flexible design. It displays operating conditions for easy management. 2) The chiller uses HFC-407C refrigerant which has zero ozone depletion potential. Hermetic compressors provide a leakless and reliable design. 3) Module chillers are compact and easy to replace, providing high reliability. They save space compared to older centrifugal chillers.

Uploaded by

IMRAN WAHEED
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

HFC 407C REFRIGERANT MODEL(Water-Cooled)

EBARA
SCREW MODULE CHILLER
MODEL RHSDW Series
※MODEL - XXX in this catalog is our model code
APPLY for NEW MICROPROCESSOR,
ACHIEVE & COVER LARGE CAPACITY
Apply for New Microprocessor,
FEATURE Becomes Easy Chiller Operation
◆Microprocessor; Controls up to 8 modules for large capacity, Enables flexible building design.
(applicable from 207kW to 3360kW)

◆Microprocessor; Indicate operating ref. cycle condition on display for easy chiller management &
maintenance.
◆Microprocessor; 6 points of Operating status (D/O) selected from total 30 points and 3 signals
(A/O) selected from 15 i.e. chilled water, cooling water, refrigerant temperature or pressure are able to send to DCS.
◆Microprocessor; Able to control each chilled & cooling water pumps, which is installed in each
modular chillers for energy saving. Standard system to install one chilled & one cooling water for one chiller (a few modules
up to 8 modules)

Zero ODP* REFRIGERANT HFC-407C is applied for Module chiller


Hermetic type leakless compressor is applied and easy to add a few modules for increasing capacity. Module chiller has
many modules, it means high reliability design                       *ODP: Ozone Depletion Potential

OUR PROPOSAL for RENEWAL PROJECT

For Replacement, Compact modules chiller is easy to install in the machine room.
For Save Energy, Chilled & Cooling water pumps are installed each by each modules. Operating cost is easy to save at
partial load condition.
Our Recommendation Fig. 1 Comparison for Replace job Hotel in Japan
1,400 47% Energy saving vs.
Pattern a b c d Centrifugal Chiller
1,200
Screw Module Screw Module Screw Module chiller
Machine Centrifugal
chiller model chiller model model DW402MV5
Type Chiller
Power Consumption(MW)

1,000
DW402M5 DW402M5 with Inverter
800

600

Setting
Flow 400

200

Operating One Pump for One pump for Each Module Each Module a b c d
Pump Style chiller 5 modules has one pump has one pump Centrifugal
chiller
Std. model DW402M5
Unit Control Non Control Control Control Model DW402M4 with each pump

Comparison Condition: Inveter model DW402MV5 with each pump


Design capacity 1800kW, Load condition Hotel in Japan Chilled & cooling water Chiller's power
Chilled water pump head & cooling water pump head: 20mH2O and 30 degC pump power consumption consumption

1
New Microprocessor panel can control modules up to 8 modules.
Module chillers are easy to replace and good for reliability.

◆Skip back up feature: If one module is failed, other module starts for back up.
◆Rotation feature: Keep constant operation hours for rotating modules.
◆Optimum Operation Feature: Control optimum operation modules under partial load condition
 (Pumps interlocking operation expect more energy saving)

Save Space: Chiller's foot print becomes smaller


Compared with 20 years old Comparison between Module chiller and 20 years old centrifugal chiller under same capacity
model, Module chiller's
installation space becomes
44% save space
smaller. Also tube removal space including maintenance space.

is not required, such space can


蒸発器
3310mm
3020mm

1175mm
凝縮器

be used for other purpose. Tube removal space

操作盤
Maintenance space for 20 years
old centrifugal chiller
Maintenance space for Model RHSDW402M5
3000mm

4500mm
6310mm

Several

Not only compact design but also separate


module by module, even if narrow installation
passage, we can carry it into the machine
room. As model DW202M1 module's weight
is less than 1000kg, using conventional Lift
is able to carry it into the machine room.
Also Module chiller can be carried by
overturned installation.

Image picture of Lift instalation. Overturned installation (Option)

2
Model RHSDW202MV with Inverter Standard performance
  
  MODEL: RHSDW 202MV1 202MV2 202MV3 202MV4 202MV5 202MV6 202MV7 202MV8
Cycle Hz 50 60 50 60 50 60 50 60 50 60 50 60 50 60 50 60

Capacity kW 211 422 633 844 1055 1266 1477 1688

Number of Modules 1 2 3 4 5 6 7 8

Leaving Temperature ℃        7

Flow rate(*) L/min 600 1210 1810 2420 3030 3630 4230 4840
Chilled water

Pressure drop(*) kPa     59

Connection Size(**) mm     65

Header Size(***) mm ー 80 100 125 125 150 150 200

Flow rate(*) L/min 730 1460 2180 2910 3640 4370 5100 5830
Cooling water

Pressure drop(*) kPa     35

Connection Size(**) mm     65

Header Size(***) mm ー 100 125 125 150 200 200 200


Electrical Data(*)

Power Consumption kW 42.2 84.4 126.6 168.8 211 253.2 295.4 337.6

Current Data A 64 128 192 256 320 384 448 513

Power Factor %     95

Power Source       200/400V 3Phase 50/60Hz

Type    Semi-Hermetic Type Screw

Model number RHSB045J RHSB045J × 2 RHSB045J × 3 RHSB045J × 4 RHSB045J × 5 RHSB045J × 6 RHSB045J × 7 RHSB045J × 8
Compressor

Motor Power & (Pole) kW 45


(2) 45
(2)× 2 45
(2)× 3 45
(2)× 4 45
(2)× 5 45
(2)× 6 45
(2)× 7 45
(2)× 8

Starting Method    Star-Delta

Turn down % 100~33 100~17 100~11 100~8 100~7 100~6 100~5 100~5

Type Blazing Type Plate Heat Exchanger


Evapo
rator

Containing Water Volume L 25 25 × 2 25 × 3 25 × 4 25 × 5 25 × 6 25 × 7 25 × 8

Type Blazing Type Plate Heat Exchanger


enser
Cond

Containing Water Volume L 42 42 × 2 42 × 3 42 × 4 42 × 5 42 × 6 42 × 7 42 × 8

Safety device Motor High Temperature, Discharge Temperature High, Compressor Over load, Refrigerant High & Low pressure,
            
Chilled water low temperature, Fusible plug and Safety relief valve
Inter lock for Chilled & cooling water Pumps, Indication (Operating hours , Number of start & stop, Chilled water leaving temperature), Chilled water temperature
Standard feature
dual set points, Local/Remote, Auto-Restart feature within 10 min (adjustable) power Failure, No. of unit(s) start/stop control by load condition and Module Rotation.

Brand    HFC407C
gerant
Refri

Charge volume kg 28 28 × 2 28 × 3 28 × 4 28 × 5 28 × 6 28 × 7 28 × 8
Dimensions Lube Oil

Brand        UX300

Charge volume L 7 7×2 7×3 7×4 7×5 7×6 7×7 7×8

Width mm 700 1400 2100 2800 3500 4200 4900 5600

Height mm        1695

Length mm        1320

Dry Weight kg 1014 2028 3042 4056 5070 6084 7098 8112

Operating Weight kg 1236 2472 3708 4944 6180 7416 8652 9888

Paint Color (Mansel #)    N4

Sound Level (50Hz/60Hz)(****) dB


(A) 69 72 74 75 76 77 78 79

Standard Accessory     Vibration Isolation Pad


*Indicate data is based on JIS condition (Chilled water 12/7 ℃, cooling water 30/35 ℃ and Electrical data 400V motor).Design fouling factor is 0.086 m2K/kW.
**Indicate each modules connection size.
***Indicate recommended connection size of header.
****Indicate sound data is based on JIS condition monitored at 1m from casing and 1.5m from grand level.Sound value will be changed at actual site condition.

4
Model RHSDW402MV Inverter model Standard performance
  MODEL: RHSDW
  402MV1 402MV2 402MV3 402MV4 402MV5 402MV6 402MV7 402MV8
Cycle Hz 50 60 50 60 50 60 50 60 50 60 50 60 50 60 50 60

Capacity kW 400 800 1200 1600 2000 2400 2800 3200

Number of Modules 1 2 3 4 5 6 7 8

Leaving Temperature ℃        7

Flow rate(*) L/min 1140 2290 3430 4580 5720 6880 8030 9170
Chilled water

Pressure drop(*) kPa        50

Connection Size(**) mm        100

Header Size(***) mm ー 125 150 150 200 200 250 250

Flow rate(*) L/min 1370 2740 4110 5480 6850 8190 9550 10920
Cooling water

Pressure drop(*) kPa     30

Connection Size(**) mm     100

Header Size(***) mm ー 125 150 200 200 250 250 250


Electrical Data(*)

Power Consumption kW 73.7 147.4 221.1 294.8 368.5 442.2 515.9 589.6

Current Data A 112 224 336 448 560 673 784 896

Power Factor %     95

Power Source       200/400V 3Phase 50/60Hz

Type    Semi-Hermetic Type Screw

Model number RHSB090J RHSB090J × 2 RHSB090J × 3 RHSB090J × 4 RHSB090J × 5 RHSB090J × 6 RHSB090J × 7 RHSB090J × 8
Compressor

Motor Power & (Pole) kW 90


(2) 90
(2)× 2 90
(2)× 3 90
(2)× 4 90
(2)× 5 90
(2)× 6 90
(2)× 7 90
(2)× 8

Starting Method    Star-Delta

Turn down % 100~33 100~17 100~11 100~8 100~7 100~6 100~5 100~5

Type Blazing Type Plate Heat Exchanger


Evapo
rator

Containing Water Volume L 50 50 × 2 50 × 3 50 × 4 50 × 5 50 × 6 50 × 7 50 × 8

Type Blazing Type Plate Heat Exchanger


enser
Cond

Containing Water Volume L 124 248 372 496 726 850 974 1098

Safety device Motor High Temperature, Discharge Temperature High, Compressor Over load, Refrigerant High & Low pressure,
            
Chilled water low temperature, Fusible plug and Safety relief valve
Inter lock for Chilled & cooling water Pumps, Indication (Operating hours , Number of start & stop, Chilled water leaving temperature), Chilled water temperature
Standard feature
dual set points, Local/Remote, Auto-Restart feature within 10 min (adjustable) power Failure, No. of unit(s) start/stop control by load condition and Module Rotation.

Brand    HFC407C
gerant
Refri

Charge volume kg 49 49 × 2 49 × 3 49 × 4 49 × 5 49 × 6 49 × 7 49 × 8

       UX300
Dimensions Lube Oil

Brand

Charge volume L 7 7×2 7×3 7×4 7×5 7×6 7×7 7×8

Width mm 960 1920 2880 3840 4800 5760 6720 7680

Height mm        2100

Length mm        1710

Dry Weight kg 1980 3960 5940 7920 9900 11880 13860 15840

Operating Weight kg 2210 4420 6630 8840 11050 13260 15470 17680

Paint Color (Mansel #)    N4

Sound Level (50Hz/60Hz)(****) dB


(A) 73 76 78 79 80 81 82 83

Standard Accessory     Vibration Isolation Pad


*Indicate data is based on JIS condition (Chilled water 12/7 ℃, cooling water 30/35 ℃ and Electrical data 400V motor).Design fouling factor is 0.086 m2K/kW.
**Indicate each modules connection size.
***Indicate recommended connection size of header.
****Indicate sound data is based on JIS condition monitored at 1m from casing and 1.5m from grand level.Sound value will be changed at actual site condition.

6
ERS Group supply Following Chillers, Cooling Towers & Pumps

Consider Other Chillers ....... Looking For Cooling Tower .....

Centrifugal Chillers

Direct Fired
Absorption Chillers Cross Flow Type Tower Counter Flow Type Tower

Looking for Pumps & Fans .......

Steam Driven
Absorption Chillers

Products produced byEbara Ref. Equip. & Systems Co., Ltd. Products from Ebara Corporation

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO., LTD.


http://www.ers.ebara.com/en/
Head Office & Sales Department
3-2-16 Ohmorikita, Ohta-ku, Tokyo143-0016, JAPAN
Phone: +81-3-6384-8145 Fax: +81-3-5493-0716

EBARA CORPORATION
Head Office:
11-1, Haneda Asahi cho, Ohta-ku, Tokyo, 144-8510 Japan
Phone: +81-3-3743-6111 Fax: +81-3-3745-3356
Cable: EBARAMAIN TOKYO
lnt'I Telex: J22988 EBARA TYO

○ Liaison Offices & Distributors

ITALY THAILAND
○Dynamis Sistemi Diclimatizzazione ○Asia Shinwa Engineering Co., Ltd. - ERS Unit
 Phone: +39-032145-7643  Phone: +66-2-612-9357~9
○Ebara(Thailand)Limited Head Office
HUNGARY  Phone: +66-2-216-4935~6, +66-2-612-0322~30
○Regale Klimatechnika Kft.
 Phone: +36-1-212-2099 PAKISTAN
○Arshad Amjad&Abid(Pte)Ltd.
PEOPLE'S REPUBLIC OF CHINA  Phone: +92-21-454-2112
○Yantai Ebara Air Conditioning Equipment Co., Ltd.
 Phone: +86-535-630-3890 EGYPT
○The Egyptian Co. for Refrigeration
TAIWAN  by Natural Gas(GASCOOL)
 Phone: +20-2-2270-6390, 2275-2478
○Ebara Corporation Taipei Office
 Phone: +886-2-2567-1310
KOREA
○Ming Kung lnd. Co., Ltd.
 Phone: +886-2-2816-1230 ○Hanseo Air Conditioning Co., Ltd.
 Phone: +82-2-3412-1270
SINGAPORE MALAYSIA
○Ebara Engineering Singapore Pte., Ltd. ○Ebara Pumps Malaysia Sdn Bhd
 Phone: +65-6862-3536  Phone: +60-3-8023-6622
INDONESIA
○PT. Ebara lndonesia
 Phone: +62-21-874-0852

“Model: XXX” in this catalog is our model code.


AIl specifications are subject to change without notice.
28-084-E02A
2014/12

You might also like