Ti00392fen 1819
Ti00392fen 1819
Ti00392fen 1819
Technical information
Soliphant M
FTM50, FTM51, FTM52
Vibronic
Application
Soliphant M is a robust point level switch for silos with fine-grained or dusty bulk solids
even with a low bulk weight.
The various designs mean the device has a wide range of applications.
Many certificates are available for use in dust or gas incendive hazard areas.
FTM50:
Compact design for installation in any position. A wide range of applications thanks to
various variations e.g.
• Polished short fork with stainless steel housing (F15) and Tri-Clamp
• Coated standard fork with aluminum housing (F17) and flange
• Standard fork with 280 °C (536 °F) rating and aluminum housing (F13)
FTM51:
With extension pipe up to 4 m (13 ft) for installation in any position
FTM52:
With rope up to 20 m (66 ft) for installation from above
Typical applications:
Cereals, flour, cocoa, sugar, animal feed, detergents, dye powder, chalk, gypsum,
cement, plastic granules, fly ash
Your benefits
• Market leader in the area of level detection of bulk solids
• Functional safety up to SIL 2 as per IEC 61508
• No mechanically moving parts
• Insensitive to external vibrations and build-up
• Various electronic inserts
• Configurable density setting (bulk weight setting) and switching delay
• Process temperature up to 280 °C (536 °F)
• Choice of coated or polished sensor
• Warning in the event of impending device failure due to buildup or abrasion
Soliphant M FTM50, FTM51, FTM52
Table of contents
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Medium temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Thermal shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Limiting medium pressure range . . . . . . . . . . . . . . . . . . . . . . . 16
State of aggregation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Grain size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bulk weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Lateral load (static) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Tensile strength rope FTM52 . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . 17
Housing and process connection . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
A A
t t
L00–FTM5xxxx–15–06–xx–xx–001
A: Amplitude
t: Time
Measuring system The measuring system is available either with compact instrumentation or separate instrumentation
with a switching unit. The following electronic versions are available:
Compact instrumentation 1
FEM51:
• Two-wire AC version
• Switch the load directly into the power supply cir-
cuit via the thyristor
FEM52:
• Three-wire DC version
• Switch the load via the transistor (PNP) and
separate connection
FEM54:
• Universal current version with relay output
• Switch the loads via 2 floating change-over con-
…
tacts (DPDT) L00–FTM5xxxx–15–05–xx–xx–000
1 Electronic version
Endress+Hauser 3
Soliphant M FTM50, FTM51, FTM52
Cable specifications
Within the indicated standards and guidelines to interference immunity (see also "Electromagnetic
compatibility", ä 14) a normal instrument cable is sufficient. If higher interference levels are pre-
sent, a shielded cable must be used.
Immunity to temperature In non-Ex applications the connecting cables must withstand the ambient temperature +5 K.
change of connecting cable For Ex applications, the specifications of the respective certificate (XA) must be observed ä 30
Certificates.
Connecting cables • Electronic inserts: cross-section max. 2.5 mm(13 AWG); strand in ferrule to DIN 46228
• Protective ground in housing: cross-section max. 2.5 mm(13 AWG)
• Equipotential bonding connection on housing: cross-section max. 4 mm(11 AWG)
Input
Measured variable Level (according to the mounting location and the overall length)
Output
Galvanic isolation • FEM51, FEM52, FEM55: Between sensor and power supply
• FEM54: Between sensor, power supply and load
• FEM57, FEM58: See switching unit connected
Switch-on behavior When the power supply is switched on the switching status of the outputs corresponds to "signal on
alarm". The correct switching status is assumed after a maximum of 3 s.
4 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Electronic insert
FEM51 electronic insert Power supply
(AC 2–wire)
• Supply voltage AC: 19 to 253 V
• Power consumption: < 1.0 W
• Residual current consumption (IR): < 4 mA; 5.5 mA for short fork (in switch-off moment < 1 mA for
100 ms)
• Short-circuit protection
• Separation voltage: 3.6 kV
• FEM51 overvoltage protection: overvoltage category II
Two-wire AC connection
Always connect in series with a load!
Check the following:
• the residual current consumption in blocked state.
• that for low voltage
– the voltage drop across the load is such that the minimum termi- 1 2
nal voltage at the electronic insert (19 V) when blocked is not
undershot.
– the voltage drop across the electronics when switched through is
observed (up to 12 V). 19 V
• when selecting the relay, pay attention to the holding power/rated
power (see "Connectable load"). R
*
* External load "R" must be connected F
** AC: Umax. 253 V, 50/60 Hz 1A
L1 N PE
** L00-FTM5xxxx-04-05-xx-xx-024
Endress+Hauser 5
Soliphant M FTM50, FTM51, FTM52
Output signal
IL = load current (switched through) Safety mode Level Output signal LEDs
green yellow red
Instrument failure
IR
1 2
L00–FTM5xxxx–04–05–xx–en–001
Signal on alarm
Output signal on power failure or in the event of device failure: IR
Connectable load
• For relays with a minimum holding power/rated power > 2.5 VA at 253 V (10 mA) or > 0.5 VA at
24 V (20 mA)
• For relays with a maximum holding power/rated power < 89 VA at 253 V or 8.4 VA at 24 V
• Voltage drop across FEM51 max. 12 V
• Residual current with blocked thyristor max. 4 mA (5.5 mA for short fork)
• Load current max. 350 mA (short-circuit proof)
6 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
M12
F 4 3
0.5A R
–
4 3 1
1 2
L+ L – L+ L –
L00-FTM5xxxx-04-05-xx-xx-027a
DC: U 10 V...55 V
A: With cable entry wired by customer (Ordering feature 80, options 2, 3, 4, 7)
B: With M12 plug wired at the factory (Ordering feature 80, option 1)
Output signal
IL = load current (switched through) Safety mode Level Output signal LEDs
green yellow red
Maintenance
required * IL / IR
1 3
Instrument failure
IR
1 3
L00–FTM5xxxx–04–05–xx–en–007
Signal on alarm
Output signal on power failure or in the event of device failure: < 100 μA
Connectable load
• Load switched via transistor and separate PNP connection, max. 55 V
• Load current max. 350 mA (pulsed overload and short-circuit protection)
• Residual current < 100 μA (with transistor blocked)
• Capacitance load max. 0.5 μF at 55 V, max. 1.0 μF at 24 V
• Residual voltage < 3 V (with transistor switched through);
Endress+Hauser 7
Soliphant M FTM50, FTM51, FTM52
Output:
When connecting a device with high inductance, pro- 1 2 3 4 56 7 8
vide a spark arrester to protect the relay contact. A
fine-wire fuse (depending on the load connected)
protects the relay contact on short-circuiting. The
relay contacts switch simultaneously. F
0.5A
* When jumpered, the relay output works *
with NPN logic.
** See "Connectable load"
NO C NC NO C NC
a u r a u r
1 Relay outputs: normally open/closed
L1 N )
(NO, NC) L+ L– ** **
2 AC: U19 to 253 V, DC: U19 to 55 V
2 1
L00-FTM5xxxx-04-05-xx-xx-003
Output signal
= relay energized Safety mode Level Output signal LEDs
green yellow red
= relay de-energized
= lit MAX
3 4 5 6 7 8
= flashes
3 4 5 6 7 8
= unlit
3 4 5 6 7 8
* See also "Operating elements", MIN
ä 25
3 4 5 6 7 8
Maintenance
required *
Instrument failure
3 4 5 6 7 8
L00–FTM5xxxx–04–05–xx–en–008
Signal on alarm
Output signal on power failure or in the event of device failure: relay de-energized
Connectable load
• Loads switched via 2 floating change-over contacts (DPDT)
• AC: I max. 6 A (Ex de 4 A), U max. 253 V; P max. 1500 VA, cos = 1, P max. 750 VA, cos > 0.7
• DC: I max. 6 A (Ex de 4 A) to 30 V, I max. 0.2 A to 125 V
• The following applies when connecting a functional low-voltage circuit with double isolation as per
IEC 1010: Sum of voltages of relay output and power supply max. 300 V
8 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Two-wire connection for separate switching unit with cable entry / M12 plug
For connecting to programmable logic controllers
(PLC), AI modules 4-20 mA to EN 61131-2. FEM55
Output signal jump from high to low current on
point level.
Ex ia
EX
EX
U – 11 V
R R =
16.8 mA
U 11…36 V (DC)
U 11…35 V (DC)
L00-FTM5xxxx-04-05-xx-xx-000
U 11 to 36 e.g. PLC
With cable entry wired by customer (Ordering feature 80,
options 2, 3, 4, 7)
FEM55
1 2 3
M12
4 3
1 2
1 2
– +
L00-FTM5xxxx-04-05-xx-xx-000a
Endress+Hauser 9
Soliphant M FTM50, FTM51, FTM52
Output signal
16 mA = 16 mA ±5 % Safety mode Level Output signal LEDs
green yellow red
8 mA = 8 mA ±6 %
+ ~16 mA
2 1
= lit MAX
+ ~8 mA
= flashes 2 1
= unlit + ~16 mA
2 1
Maintenance
+ 8/16 mA
required *
2 1
MAX OFF
MIN ON
3.6 mA
Instrument failure
+ 3.6 mA
2 1
L00–FTM5xxxx–04–05–xx–en–006
Signal on alarm
Output signal on power failure or in the event of device failure: < 3.6 mA
Connectable load
• R = (U - 11 V) / 16.8 mA
• U = connection DC voltage 11 V to 36 V (in wet location DC 11...35 V)
Power supply
• DC supply voltage: 8.2 V ±20 %
• Power consumption: < 8 mW at I < 1 mA; < 36 mW at I = 2.2 to 4.8 mA
• Separation voltage: 1.9 kV
• Connection data interface: IEC 60947–5–6
10 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Two-wire connection for separate switching unit with cable entry / M12 plug
For connecting to isolating amplifiers FEM58
acc. to NAMUR (IEC 60947-5-6), z.B. FTL325N or
FTL375N from Endress+Hauser.
H-L edge:
Output signal jump from high to low current on point 1 2
level.
Additional function:
Test key on the electronic insert. Ex ia EX
Pressing the key breaks the connection to the isola- H
ting amplifier. I EX
L
Note! – +
• For Ex d applications, the additional function can L00-FTM5xxxx-04-05-xx-xx-005
only be used if the housing is not exposed Isolating amplifier to IEC 60947-5-6 (NAMUR)
With cable entry wired by customer (Ordering feature 80,
to an explosive atmosphere. options 2, 3, 4, 7)
• Connecting to multiplexer:
Set clock time to min. 5 s.
FEM58
1 2 3
M12
4 3
1 2
1 2
– +
L00-FTM5xxxx-04-05-xx-xx-005a
Output signal
= lit Safety mode Level Output signal LEDs
green yellow red
= flashes
2.2 …
+ 4.8 mA
= unlit MAX
2 1
0.4 …
* See also "Operating elements", ä 25 + 1.0 mA
2 1
2.2 …
+ 4.8 mA
2 1
MIN
0.4 …
+ 1.0 mA
2 1
Maintenance 0.4 …
required * + 4.8 mA
2 1
L00–FTM5xxxx–04–05–xx–en–012
Endress+Hauser 11
Soliphant M FTM50, FTM51, FTM52
Signal on alarm
Output signal
in event of device failure: < 1.0 mA
Connectable load
• See "Technical Data" of the isolating amplifier connected according to IEC 60947–5–6 (NAMUR)
• Connection also to safety isolating amplifiers (I = 3 to 4.8 mA)
d4 d2 3: FTL375P (1CH)
z4 z2 4: FTL375P (2CH)
FEM57
1 2 3
M12
4 3
1 2
1 2
– +
L00-FTM5xxxx-04-05-xx-xx-006a
With M12 plug wired at the factory (Ordering feature 80, option 1)
12 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Output signal
= lit Safety mode Level Output signal LEDs
(PFM) green yellow red
= flashes 150 Hz
= unlit
50 Hz
* See also "Operating elements", ä 25
Maintenance 150 Hz
required *
OFF OFF
ON ON
0 Hz
Instrument failure 0 Hz
L00–FTM5xxxx–04–05–xx–en–009
Signal on alarm
Output signal on power failure or in the event of device failure: 0 Hz
Connectable load
• Floating relay contacts in connected switching unit Nivotester (see drawing above)
• For contact load, see the Technical Data of the switching unit
Installation
Installation instructions Orientation FTM50
60 (2.36)
max.
~20°
~250 (9.84)
1
(7.87)
~200
mm (in)
L00-FTM5xxxx-11-06-xx-xx-004
Endress+Hauser 13
Soliphant M FTM50, FTM51, FTM52
Orientation
FTM51, FTM52
1 2 3
L00–FTM5xxxx–11–06–xx–xx–001
1 Sliding sleeve
2 FTM51
3 FTM52
4 FTM51 with supporting tube (not included in the delivery)
A Clearance
B Maximum nozzle length: = L Sensor length – 145 mm (5.71 in) for short fork
= L Sensor length – 200 mm (7.87 in) for standard fork
Environment
Ambient temperature range –50 °C to +70 °C (-58 °F to +158 °F);
With F16 housing: -40 °C to +70 °C (-40 °F to +158 °F)
Climate class Climate protection as per DIN IEC 68, Part 2-38, Fig. 2a
Degree of protection • Housing F15, F16, F17, separate housing: IP66/IP67, NEMA4X
• Housing F13, T13, F27: IP66/IP68, NEMA4X/6P
14 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Process
Medium temperature limits Non-hazardous area and Ex d + DIP certificates
(Ex ia certificates see Seite 30, "Certificates")
NOTICE
Permitted ambient temperature Ta at housing depending on the process temperature Tp in the
container.
Ta Ta FTM52 FTM50/51 **
70 (158)
50 (122)
Tp –40 (–40)
80 (176)
0 (32)
–50 (–58) 0 (32) 50 (122) 100 (212) 150 (302) Tp
90 (194)
L00-FTM5xxxx-05-05-xx-xx-003
Ta
*** **
70 (158)
Ta 50 (122)
Tp
0 (32)
–50 (–58) 0 (32) 50 (122) 230 (446) 280 (536) Tp
190 (374)
L00-FTM5xxxx-05-05-xx-xx-005
Endress+Hauser 15
Soliphant M FTM50, FTM51, FTM52
Lateral load (static) The following graphic shows the maximum permitted lateral load F in N (lbf) in relation to the length
L in mm (in).
A
1000 (224.80)
900 (202.32) F
L
800 (179.84)
B
750 (168.60)
700 (157.36)
650 (146.12)
600 (134.88)
550 (123.64)
C
500 (112.40)
450 (101.16)
F
400 (89.92)
350 (78.68)
300 (67.44)
250 (56.20)
200 (44.96)
150 (33.72)
100 (22.48)
50 (11.24)
0
500 (19.7)
1000 (39.4)
1500 (59.1)
2000 (78.7)
2500 (98.4)
3000 (118)
3500 (138)
4000 (157)
4500 (177)
5000 (197)
5500 (217)
6000 (236)
0
L
L00-FTM5xxxx-05-05-xx-en-001
16 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Mechanical construction
Housing Polyester housing F16
and process connection ø85 (3.35) max. 76 (2.99)
Process connection:
• R 1½
100 (3.94)
• 1½ NPT
• 1¼ NPT
43 (1.69)
22.5 (0.89)
mm (in)
L00–FTM5xxxx–06–05–xx–xx–008
113* (4.45*)
Tri-Clamp
94 (3.7)
28 (1.1)
22,5 (0.9)
105 (4.13)
43 (1.69)
22,5 (0.9)
Endress+Hauser 17
Soliphant M FTM50, FTM51, FTM52
133* (5.24)
118 (4.65)
• 1½ NPT
• 1¼ NPT
Stainless steel housing F27 (Ex d)
(Adaption to sensor threaded.)
Process connection
• Flange
51** (2.01)
53 (2.09)
• R1½
• 1½ NPT
• 1¼ NPT
* Cover with glass insert
(only for aluminum housing F13)
** For Tri-Clamp 36 mm (1.42 in)
22,5 (0,89)
mm (in)
L00-FTM5xxxx-06-05-xx-xx-051
• R1½
135 (5.31)
• 1½ NPT
• 1¼ NPT
With Ex d(e) for FTM51 and FTM52:
for flange and thread dimensions see
the previous graphic
41** (1.61**)
• R 1½
• 1½ NPT
• 1¼ NPT
18 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
(1.69)
ø43
50
L00–FTM5xxxx–06–05–xx–xx–004
(1.42)
ø36
50
L00-FTM5xxxx-06-05-xx-xx-006
(1.42)
ø36
45
L00-FTM5xxxx-06-05-xx-xx-005
L00-FTM5xxxx-06-05-xx-xx-013
available
L00-FTM5xxxx-06-05-xx-xx-014
43 43 36
(1.69) (1.69) (1.42)
(3.94)
(3.94)
100
100
(6.1)
155
15
(0.59) 39 32
(1.54) (1.26)
4 39
(0.16) (1.54)
L00-FTM5xxxx-06-05-xx-xx-030
Endress+Hauser 19
Soliphant M FTM50, FTM51, FTM52
204 (8.03)
D1
D1
140 (5.51)
D2
mm (in)
L00-FTM5xxxx-06-05-xx-xx-015
Versions with FMI51 (pipe): Dimensions depend on process connection and selected pipe extension
extensions FTM52 (rope): Dimensions depend on process connection and selected rope extension
L
X
L
L
X
X
20 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
L
L
L
L
L
L
mm (in) 150 °C (302 °F) 230 °C (446 °F) 280 °C (536 °F)
L: for housing F15, F16, F17 145 (5.71) -- 175 (6.89) 215 (8.46)
L: for housing F13, F27, T13 145 (5.71) 165 (6.5) 165 (6.5) 205 (8.07)
Certificate A, 1, 2, 3, 4, 7, 8, 5, 6, H, Z
Not relevant Not relevant
C, D, F, X
Surface refinement
2
1
L00-FTM5xxxx-06-05-xx-xx-031 L00-FTM5xxxx-06-05-xx-xx-002
‣ In the area of the welding seams, the roughness is not defined due to the production process.
‣ In the area of the fork base a deviation of the surface roughness can occur.
Coating
1
2
3
L00-FTM5xxxx-06-05-xx-xx-032 L00-FTM5xxxx-06-05-xx-xx-003
1: Fork coated
2: Fork and pipe coated as far as welding seam on process connection
3: Fully coated
Endress+Hauser 21
Soliphant M FTM50, FTM51, FTM52
EX
Tp
A
Ta1 Ta2 C
L00-FTM5xxxx-15-06-xx-en-002
Ta1 Ta2 Tp
FTM50/51 70 °C (158 °F) 120 °C (248 °F) Versions: 150 °C (302 °F), 230 °C (446 °F), 280 °C (536 °F)
108 (4.25)2)
1)
H21)
H2
H1
H1
ø34 (1.34)
H3
H3
3)
r
ø21 (0.83)
mm (in)
L00-FTM5xxxx-06-05-xx-xx-023
Dimen- Housing
sions
Polyester Stainless Aluminum Aluminum (F13) Aluminum (T13)
mm (in)
(F16) steel (F15) (F17) Stainless steel Separate connection com-
(F27) partment
H1 155 (6.1) 166 (6.54) 160 (6.3) 243 (9.57) 260 (10.2)
H3 41 (1.61) 62 (2.44)
22 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Weights Depends on type; see last column on "Additional weight" in the ordering information
Surface roughness
NOTICE
‣ In the area of the welding seams, the roughness is not defined due to the production process.
‣ In the area of the fork base a deviation of the surface roughness can occur.
Electropolished for simple cleaning and to avoid build-up and corrosion.
Choice of surface roughness (version => type): Ra < 0.76 m
Endress+Hauser 23
Soliphant M FTM50, FTM51, FTM52
Operability
Display elements
NOTICE
The switch settings in the following graphics are in the as-delivered state.
FEM51
• Green LED lit:
Indicates operational status
• Yellow LED lit: MAX OFF
Indicates switching status
1 MIN ON
• Red LED L1 N 2
FEM51
AC
– flashing: flashes alternately with green LED
if maintenance is required U ~ 19...253V AC
50/60Hz
– lit: indicates device failure I max : 350mA
L00–FTM5xxxx–03–05–xx–xx–001
FEM52
• Green LED lit:
Indicates operational status
• Yellow LED lit: MAX OFF
Indicates switching status
1 MIN ON
• Red LED 3
FEM52
L+ L- DC PNP
– flashing: indicates maintenance is required
– lit: indicates device failure U 10...55V DC
I max : 350mA
L00–FTM5xxxx–03–05–xx–xx–002
FEM54
• Green LED lit:
Indicates operational status
• Yellow LED lit: MAX OFF
Indicates switching status
3 5 MIN ON
U~ –
19... 55V DC
• Red LED 4 3 5 68
19... 253V AC FEM54
L1 N
– flashing: indicates maintenance is required 4 7
L00–FTM5xxxx–03–05–xx–xx–004
FEM55
• Green LED lit:
Indicates operational status
• Yellow LED lit: MAX OFF
Indicates switching status I = 16mA
MIN ON
L00–FTM5xxxx–03–05–xx–xx–005
24 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
FEM57
• Green LED lit:
Indicates operational status
• Yellow LED lit: FEM57
Indicates covered status
• Red LED PFM OFF OFF
- + ON ON
– flashing: indicates maintenance is required
– lit: indicates device failure
L00–FTM5xxxx–03–05–xx–xx–007
FEM58
• Green LED flashing:
Indicates operational status
• Yellow LED lit: FEM58
Indicates switching status NAMUR
• Red LED IEC 60947-5-6
MAX OFF
- + MIN ON
– flashing: flashes alternately with green LED
if maintenance is required
– flashing: indicates device failure > 2,2mA
L00–FTM5xxxx–03–05–xx–xx–008
NOTICE
If the test key is pressed this breaks the cable connection.
MAX OFF
MIN ON
L00-FTM5xxxx-19-05-xx-xx-001
50 g/l standard fork, 200 g/l short fork (high bulk weight)
Endress+Hauser 25
Soliphant M FTM50, FTM51, FTM52
OFF OFF
ON ON
L00–FTM5xxxx–19–05–xx–xx–002
L00-FTM5xxxx-19-05-xx-xx-014
26 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Dust ignition-proof X
X X X X X
(except II 1/2 D)
Ex ia X X X X X X
Ex nA/nL/nC X X X X X X
Ex d – – – X X X
Ex de – – – – X X
IP66/67 X X X – – X
IP66/68 – – – X X –
Recommended in event
of severe external – – – X X X
vibrations
Goretex filter X X X – – –
Other standards and Other standards and guidelines that were taken into consideration in designing and developing
guidelines Soliphant M FTM50, FTM51, FTM52:
• Low Voltage Directive (73/23/EEC)
• DIN EN 61010 Part 1, 2001
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory
Procedures
Part 1: General requirements
• EN 61326
Electrical Equipment for Measurement, Control and Laboratory Use
EMC requirements
Endress+Hauser 27
Soliphant M FTM50, FTM51, FTM52
RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
Pressure Equipment Directive Pressure instruments with permitted pressure ≤ 200 bar (2 900 psi)
2014/68/EU (PED)
Pressure instruments with permitted pressure ≤ 200 bar (2 900 psi) Pressure instruments with a
flange and threaded boss that do not have a pressure-bearing housing do not fall within the scope of
the Pressure Equipment Directive, irrespective of the maximum permitted pressure.
Reason:
According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as
"devices with an operational function and having pressure-bearing housings".
If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber
of its own), there is no pressure accessory present within the meaning of the Directive.
CRN approval CRN-approved devices are fitted with a separate plate bearing the registration number
No.: 0F10907:5C ADD1.
EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines. These are
listed in the corresponding EAC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark.
RoHS The measuring system complies with the substance restrictions of the EU Directive on the restriction
of the use of certain hazardous substances 2011/65/EU (RoHS 2).
ASME B 31.3 Design and materials in accordance with ASME B31.3. The welding seams are through-penetration
welded and comply with ASME Boiler and Pressure Vessel Code Section IX and EN ISO 15614-1.
Process sealing as per ANSI/ North American practice for the installation of process seals.
ISA 12.27.01 Soliphant M instruments are designed by Endress+Hauser according to ANSI/ISA 12.27.01 as single
seal devices with annunciation, allowing the user to waive the use and save the cost of installing exter-
nal secondary process seals in the conduit as required by the process sealing sections of ANSI/NFPA
70 (NEC) and CSA 22.1 (CEC). The instruments comply with the North American installation practice
and provide a very safe and cost-saving installation for pressurized applications with hazardous fluids.
Please refer to the Safety Instructions (XA) of the relevant device for further information ä 30ff.
Other certificates • Material certificate as per EN 10204/3.1 for all wetted parts,
• AD2000 on request
• TSE Certificate of Suitability
The following applies to wetted device components:
– They do not contain any materials derived from animals.
– No additives or operating materials derived from animals are used in production or processing.
Functional safety (SIL valida- Use in safety systems requiring functional safety to SIL2 in accordance with IEC 61508. See "Documen-
tion) tation", ä 30.
28 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com → Click "Corporate"
-> Select country → Click "Products"→ Select product using the filters and search field → Open
product page → The "Configuration" button to the right of the product image opens the Product
Configurator.
• Endress+Hauser Sales Center: www.addresses.endress.com
NOTICE
Product Configurator - the tool for individual product configuration
Accessories
Removing tool For Soliphant M FTM50, FTM51, FTM52.
Order No.: 71026213
(4 10
Order No.: 71040497
)
.33
~1
PA
(4.02)
102
162
(6.3
8)
L00-FTM5xxxx-03-05-xx-xx-009
Endress+Hauser 29
Soliphant M FTM50, FTM51, FTM52
(2.95)
~75
For pressurized containers up to 5 bar (362.5 psi).
C
Sliding sleeve version:
• G2 B
DIN ISO 228/I A
Order No.: 52024631
• 2NPT
ANSI B 1.20.1
D
Order No.: 52024630
NOTICE
Suitable for switch point configuration! E
mm (in)
L00–FTM5xxxx–03–05–xx–xx–002
A G2 (316L)
B 2NPT (316L)
C For G2: 24 mm (0.94 in); for 2NPT: 27.5 mm (1.08 in)
D MWP = 25 bar (362.5 psi)
E Tp = max. 280 °C (536 °F)
L00-FTM5xxxx-00-00-xx-xx-001
Documentation
NOTICE
You can find the following supplementary documentation on our product pages at
www.endress.com.
Certificates ATEX
• ATEX II Ex i 1D, 1/2D, 1G, 1/2G XA00305F
• ATEX II Ex i (X) 1D, 1G XA00319F
30 Endress+Hauser
Soliphant M FTM50, FTM51, FTM52
Endress+Hauser 31
71457236