Dimensi Busbar
Dimensi Busbar
Dimensi Busbar
Busbar
Bus bar
A bus bar (also spelled busbar, buss bar or busbar), is a strip or bar of copper, brass or aluminum that cond
Busbars are typically either flat strips or hollow tubes as these shapes allow heat to dissipate more efficient
A busbar may either be supported on insulators, or else insulation may completely surround it. Busbars are
Busbars may be connected to each other and to electrical apparatus by bolted, clamp, or welded connection
Busbars are typically contained inside switchgear, panel boards, or busway. Distribution boards split the el
Advantag
es
Following are some advantages of Bus bar trunking system over normal cabling system:-
1. On-site installation times are reduced compared to hard-wired systems, thus leading to cost savings.
2. It provides increased flexibility in design and versatility with regard to future modifications.
3. Greater safety and peace of mind for specifiers, contractors and end-users.
4. Because of the simplicity of busbar, it is easy to estimate costs from the design/estimating stage throug
5. It is short sighted to compare the cost of busbar against that of a length of cable — and not the real cos
6. Distribution busbar distributes power along its length through tap-off points along the busbar at typical
7. Installed vertically the same systems can be used for rising-mains applications, with tap-offs feeding in
8. Very compact so provides space savings.
9. Where aesthetics have to be considered, busbar trunking can be installed with natural galvanized, alum
10. Busbar trunking has several key advantages over conventional forms of power distribution including: -
11. (a) Reduced, onsite installation times when compared to hard-wired systems thus leading to cost saving
a. Increased flexibility in design and versatility with regard to future modifications.
b. Increased safety features brought about by the use of high quality, manufactured components, which p
12. Uneven distribution of current takes place where multiple runs of cables are used in parallel.
13. Busbar trunking has tap-off points at regular intervals along each length to allow power to be taken off
14. For higher ratings of power distribution we need to have multiple runs of cable. In such conditions unb
15. When multiple runs of cables are used it often leads to improper end connections thereby causing overh
Current carrying capacity
The current-carrying capacity of a busbar is usually determined by the maximum temperature at which the
BS 159 stipulates a maximum temperature rise of 50°C above a 24 hour mean ambient temperature of up to
ANSI C37.20 alternatively permits a temperature rise of 65°C above a maximum ambient of 40°C, provide
A very approximate method of estimating the current carrying capacity of a copper busbar is to assume a cu
The more popular thumb rule being followed in India is to assume current density of 1.0 Amps / Sq.mm fo
Standard size of bus bar
Sr. Application area Cable
One circuit per floor. Hence for a 20-floor building,
1 Number of circuits
you need 20 circuits.
CONSIDERATION
Enclosure size: 1400 mm. wide X 400mm. height
Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.
Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)
The minimum cross section needed in sqmm for busbar in various common cases can be listed as below-
35 285
Copper
Copper 50 407
65 528
2) Copper busbar for 2000A, 35 kA for 1 sec withstand – From the table the minimum cross-section need
Thus, by using the above formula and table, we can easily select busbars for our switchboards.
12X2 24 0.209
15X2 30 0.262
15X3 75 0.396
20X2 40 0.351
20X3 60 0.529
25X3 75 0.663
30X3 90 0.796
Temperature rise
During the short circuiting, the bus bar should be able to withstand the thermal as well as mechanical stress
Typical calculation
ling system:-
hus leading to cost savings.
uture modifications.
design/estimating stage through to installation on site. This is because the technical characteristics and price of each component
f cable — and not the real cost of a cable installation to include multiple runs of cable, tray and fixing, let alone the protracted tim
ints along the busbar at typically at 0.5 or 1 m centers. Tap-off units are plugged in along the length of the busbar to supply a loa
ations, with tap-offs feeding individual floors. Certified fire barriers are available at points where the busbar passes through a flo
with natural galvanized, aluminium, or painted finish. Special colours to match switchboards or a specific colour scheme are als
power distribution including: -
ems thus leading to cost savings.
ufactured components, which provide greater safety and peace of mind for specifies, contractors and end-users.
are used in parallel.
to allow power to be taken off and distributed to where it is needed. Because it is fully self-contained it needs only to be mechan
f cable. In such conditions unbalanced distribution of current takes place and causing overheating of some cable. This is complet
nections thereby causing overheating of contacts, burning of cables ends, and is a major cause of fire. This is completely avoided
mum temperature at which the bar is permitted to operate, as defined by national and international standards such as British Stand
n ambient temperature of up to 35°C, and a peak ambient temperature of 40°C.
mum ambient of 40°C, provided that silver-plated (or acceptable alternative) bolted terminations are used. If not, a temperature ri
copper busbar is to assume a current density of 2 A/mm2 (1250 A/in2) in still air. This method should only be used to estimate a
ensity of 1.0 Amps / Sq.mm for Aluminium and 1.6 Amps for Copper for any standard rectangular conductor profile.
busbar
Just one circuit can cover all floors.
time as well as internal material handling costs. Various conductors are terminated at customer specified locations to eliminate th
The reduction of wiring errors results in fewer reworks, lower service costs and lower quality costs.
will ultimately lead to greater effective signal suppression and noise elimination. Keeping the dielectrics thin and using dielectrics
s-wirings is eliminated. Wiring harnesses have high failure rates relative to bus bars, which have virtually none. These problems
use of thin parallel conductors with a thin dielectric laminated together minimizes the effect of inductance on electrical circuits. M
or in eliminating noise. Keeping the dielectric thickness to a minimum will accomplish the highly desired low impedance.
requirements. Laminated bus bars have helped decrease total system size and cost.
ion styles to choose from. Bushings, embossments, and fasten tabs are most commonly used.
ms. As package sizes decrease, the cost of removing heat from systems has greatly increased. A bus bar cannot only reduce the o
oxygen free copper.
Copper + Silver 99.90% min.
Withstand time
200 msec. 40 ms. 10 ms.
198 89 44
283 127 63
368 165 82
127 57 28
182 81 41
236 106 53
le the minimum cross-section needed would be 443 mm2. Thus we can select a 100mm x 5mm busbar as the minimum cross-sec
e minimum cross-section needed would be 285 mm2. Thus we can select a 60mm x 5mm busbar as the minimum cross-section.
our switchboards.
current carrying capacity in amp ( copper ) at 35 deg.C
AC ( no. of bus) DC ( no. of bus)
I II III II II I II
mal as well as mechanical stress. When a sort circuiting takes place, the temperature rise is directly proportional to the squire of th
is being calculated.
bank or other electrical apparatus. Its main purpose is to conduct electricity, not to function as a structural member.
on has higher stiffness than a solid rod of equivalent current-carrying capacity, which allows a greater span between busbar supp
elevation out of normal reach. Power Neutral busbars may also be insulated. Earth (safety grounding) busbars are typically bare
at are silver-plated to reduce the contact resistance. At extra-high voltages (more than 300 kV) in outdoor buses, corona around t
are long busbars with a protective cover. Rather than branching the main supply at one location, they allow new circuits to branc
s such as British Standard BS 159, American Standard ANSI C37.20, etc. These standards give maximum temperature rises as w
none. These problems are very costly to repair. Adding bus bars to your systems is effective insurance.
on electrical circuits. Magnetic flux cancellation is maximized when opposing potentials are laminated together. Laminated bus b
low impedance.
nnot only reduce the overall size required, but it can also improve airflow with its sleek design.
he minimum cross-section. Considering a current density of 1A/ mm 2 by considering temperature as well as skin effect, we shal
nimum cross-section. Considering a current density of 1.6A/ mm2 by considering temperature as well as skin effect, we shall req
DC ( no. of bus)
III II II
2000
1750
2500
1900 2500
2800 3600
2500 3200
3700 4800
3150 4050
4500 5800
5200 6700
6900 9000
8500 10000
onal to the squire of the rms value of the fault current. The duration of short circuiting is very small i.e. one second till the breake
an between busbar supports in outdoor switch yards.
sbars are typically bare and bolted directly onto any metal chassis of their enclosure. Busbars may be enclosed in a metal housin
r buses, corona around the connections becomes a source of radio-frequency interference and power loss, so connection fittings d
ow new circuits to branch off anywhere along the route of the busway.
ap-offs can normally be added or removed with busbar live, eliminating production down time.
d along the busbar run, reducing the need for large distribution boards and the large quantities of distribution cables running to a
skin effect, we shall require 4 x 60mm x 5mm busbars for this case.
one second till the breakers opens and clears the fault. The heat dissipation through convection and radiation during this short dur
closed in a metal housing, in the form of bus duct or busway, segregated-phase bus, or isolated-phase bus.
s, so connection fittings designed for these voltages are used.