Talentum 16591-20
Talentum 16591-20
Talentum 16591-20
Talentum® 16591-20
UV/IR² Flame Detector
The Talentum® Ultra-Violet, dual Infra-Red (UV/IR²) Flame Detector
is designed to protect areas where open fires may be expected and
detects most flames from hydrocarbon fires with 4.3µm emissions
through to invisible fires such as hydrogen.
The UV/IR² Flame Detector is sensitive to flickering, low frequency (1-
15Hz) infra-red radiation along with ultra-violet emitted by flames during
combustion.
This detector has a UV sensor and two IR sensors which respond to
different wavelengths of both the ultra-violet and the infra-red spectrum.
The signals from these sensors are processed by the detector and
checked for characteristics of a flame. The simultaneous detection of
both the UV and the IR light by the sensors will signal an alarm. False
alarms from flickering sunlight, arc welding and lightning are eliminated
by a combination of UV and dual IR signal processing techniques.
Applications
The Talentum® UV/IR² detector has selectable output options of relay
contacts or 4 to 20mA signal as standard. • Refineries • Storage Tanks
• Suitable for indoor and outdoor areas • Fuel Loading Racks • Aircraft Hangars
FM Approved
Visit www.ffeuk.com for up to date approvals information.
Class I, Div. 1, Groups A, B, C, D T4, IP66
www.ffeuk.com
Class I, Zone 1, AEx db IIC Gb T4, IP66
Class II/III, Div. 1, Groups E, F, G T4, IP66
Talentum® 16591-20
Mechanical Specification Approvals
Housing Material Die Cast Zinc Alloy (ZA12) FM Approved Cert. No. 3059453
Housing Colour Blue CPR 0832-CPR-F0584
5.59"H x 4.25"W x 3.23"D LPCB 1204a/12
Dimensions
(142 H x 108 W x 82 D mm)
VdS G212190
Weight 4.41lbs (2kg)
SIL 2 C127_CT001_(2.0)
Cable Gland Entries 2 x .79" (2 x 20mm)
Wiring 1.0 to 4.0mm² Response Characteristics – High Sensitivity
Average
Electrical Specification Flame Size
Fuel Distance m (ft) Response
m (ft)
Supply Voltage 14 to 30Vdc time (seconds)
Quiescent Current 8mA, RL2 energised n-Heptane* 0.3 x 0.3
25 (82) 8
4mA, current loop, RL2 off (Yellow flame) (1 x 1)
3mA, RL2 off Methylated Spirit* 0.5 x 0.5
25 (82) 12
Alarm Current 28mA, RL1 & RL2 energised (Clear flame) (1.6 x 1.6)
20mA, current loop, RL1 & 2 off Hydrogen 0.1 x 0.5
12 (39) 16
9mA, RL1 energised (non-visible flame) (0.3 x 1.6)
Power Up Time 2 seconds max. * has been tested and approved at Class 1
Test Signal Voltage 14 to 30Vdc
Relay Outputs Normally Open or Normally Closed Field of View 0°
15°
-15°
- Programmable Latching or Non-latching -30° 30°
- Ratings: Current 1.0A Max. -45° 45°
Voltage 50Vdc Max.
Power 30W Max. -60° 60°
Storage Temperature -20°C to +65°C To meet the requirements of EN54:10 clause 5.4, where the ratio of the response points Dmax:
Dmin should not exceed 1.41, the horizontal and vertical viewing angles max should not exceed
Relative Humidity 95% Non condensing ±30°.
IP Rating I IP66
Flame Detector Mounting Bracket
Performance 3.54" (90mm)
3.23" (82mm) 4.25" (108mm)
0.1m² n-heptane at 25m
Range - Class 1*
0.1m² n-heptane at 12m
- Class 3
(see EN54:10 for sensitivity settings) FIELD
OF
VIEW
5.59" (142mm)
TERMINAL
COVER GLAND PLUG
2 FIXING HOLES 8 DIA.
Dimensions: inches (mm)
2 x Fixing holes 14 Dia
Installation Recommendations
Please refer to our User Manual for mounting and wiring instructions.
The installation of Talentum® flame detectors should be undertaken in
US Sales and Distribution accordance with the recognised national or international standards and
FFE Limited codes of practice.
Specifications and wiring information are provided for information only and are believed to be accurate. FFE Ltd