Acceleration Measurements: Operation and Maintenance Manual
Acceleration Measurements: Operation and Maintenance Manual
Acceleration Measurements: Operation and Maintenance Manual
Acceleration Measurements
* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Com-
pany.
Bently Nevada, Keyphasor, Velomitor
Contact Information
The following contact information is provided for those times when you cannot contact your
local representative:
ii
Additional Information
NOTE
This manual does not contain all the information required to operate and maintain the monitoring system. The
following is a complete list of the 3500 ENCORE manuals. Refer to these manuals for other required information.
3500 Thrust & Diff Expansion Measurement Manual (part number 287553-01)
3500 Valve Position Measurement Manual (part number 288622-01)
3500 Velocity Measurement Manual (part number 287551-01)
iii
Acceleration Measurement
iv
Contents
1. General Information 1
1.1 ENCORE Acceleration 2 Screen Displays 2
1.1.1 Display Components 4
2. Acceleration 2 Configuration 5
2.1 Transducer Filtering and Configuration 5
2.1.1 Transducer Selection 5
2.1.1.1 Type 5
2.1.1.2 Customize Button 6
2.1.1.3 I/O Module Attached - Jumper Position 8
2.1.1.4 Take Input From Channel 1 (3) Transducer 8
2.1.2 Barriers 8
2.1.3 Corner Frequencies 8
2.1.4 High-Pass Filter 9
2.1.5 Low-Pass Filter 9
2.2 Variables and Alarms Configuration 9
2.2.1 Enable 10
2.2.1.1 Enable Check Boxes 10
2.2.1.2 Direct 10
2.2.1.3 Bias Voltage 10
2.2.1.4 1X Ampl 10
2.2.1.5 1X Phase Lag 10
2.2.1.6 2X Ampl 10
2.2.1.7 2X Phase Lag 10
2.2.1.8 Full-Scale Range 10
2.2.1.9 Clamp Value 14
2.2.1.10 RMS 14
2.2.1.11 Integrate 14
2.2.2 Delay 14
2.2.2.1 Alert Delay 14
2.2.2.2 Danger Delay 14
2.2.2.3 100 ms Option 14
2.2.3 Alarm Mode 15
2.2.3.1 Latching 15
v
Acceleration Measurement
2.2.3.2 Non-latching 15
2.2.3.3 Timed OK Channel Defeat 15
2.2.3.4 Monitor Danger Relay Voting 16
2.2.4 OK Mode 16
2.2.5 Trip Multiply 16
2.2.6 Recorder Output 17
2.2.6.1 Two mA Clamp 17
2.3 Alarm Setpoints 17
2.3.1 Alarm Setpoint Dialog 18
2.3.2 Available Setpoints 18
2.3.3 Alarm Hysteresis 19
2.4 General Parameters and Buttons 19
2.4.1 Set Defaults Button 19
2.4.2 CP Mod 19
2.4.3 Print Form Button 20
2.4.4 Point Names Button 20
2.5 Configuration Considerations 20
3. Acceleration Verification 23
3.1 Test Equipment and Software Setup 23
3.1.1 Test Equipment Setup 23
3.1.2 Verification Screen Setup 24
3.2 Test Alarms 25
3.2.1 Direct 25
3.2.2 1X Amplitude (1X Amp) 26
3.2.3 1X Phase 27
3.2.4 2X Amplitude (2X Amp) 28
3.2.5 2X Phase 30
3.3 Verify Channel Values 31
3.3.1 Direct 31
3.3.2 1X Amplitude (1X Ampl) 32
3.3.3 1X Phase 33
3.3.3.1 If Your Test Equipment Cannot Change the 1X Phase Output 33
3.3.3.2 If Your Test Equipment Can Change the 1X Phase Output 34
3.3.4 2X Amplitude (2X Ampl) 35
3.3.5 2X Phase 35
3.3.5.1 If Your Test Equipment Cannot Change the 2X Phase Output 36
vi
3.3.5.2 If Your Test Equipment Can Change the 2X Phase Output 37
3.3.6 Calculating Verification Frequency 37
3.3.7 Calculating the Input Voltage for Full Scale 38
3.3.7.1 Full Scale Formulas With Integration 38
3.3.7.2 Full Scale Equations Without Integration 39
3.4 Test OK Limits 40
3.4.1 Acceleration OK Limits 41
4. Acceleration Configuration 43
4.1 Configuration Options 43
4.1.1 Direct 43
4.1.1.1 Full-Scale Range 43
4.1.1.2 Clamp Value 47
4.1.1.3 Recorder Output 47
Two mA Clamp 47
4.1.2 Trip Multiply 47
4.1.3 Type 48
4.1.4 Customize Button 48
4.1.5 I/O Module Attached - Jumper Position 50
4.1.6 Take Input From Channel 1 (3) Transducer 50
4.1.7 Corner Frequencies 50
4.1.8 High-Pass Filter 51
4.1.9 Low-Pass Filter 51
4.1.10 Delay 51
4.1.10.1 Alert Delay 51
4.1.10.2 Danger Delay 51
4.1.10.3 100 ms Option 51
4.1.11 Alarm Mode 52
4.1.11.1 Latching 52
4.1.11.2 Non-latching 52
4.1.11.3 Timed OK Channel Defeat 52
4.1.11.4 Monitor Danger Relay Voting 52
4.1.12 Barriers 53
4.1.13 OK Mode 53
4.1.14 CP Mod 53
4.2 Alarm Setpoints 53
4.2.1 Alarm Setpoint Dialog 54
vii
Acceleration Measurement
viii
1. General Information
1. General Information
Acceleration measurements are generally made with an Accelerometer. You typically use these
measurements to evaluate the high frequency vibration of a machine casing or bearing housing
that is due to blade passage, gear mesh, cavitation, rolling element bearing defects, and other
conditions. For harmonic motion, acceleration is often expressed as g or a. Typical units for accel-
eration are feet per second per second peak (ft/s2 pk), meters per second per second peak (m/s2
pk), or more commonly g pk (acceleration of gravity = 386.1 in/s2 pk = 32.17 ft/s2 pk = 9.81 m/s2 pk).
Note
Acceleration, as well as velocity, are zero-to-peak (pk) measurements.
You program Acceleration channels in pairs. These channels, depending on configuration, typ-
ically condition the input signals into various parameters called "œstatic values" . You can con-
figure Alert setpoints for each active static value and Danger setpoints for any 2 of the active
static values.
Advisory
If you plan to use housing measurements for overall machine protection, you should consider the usefulness of
the measurement for each application. Most common machine malfunctions (imbalance, misalignment, etc.) orig-
inate at the rotor and increase (or at least change) rotor vibration. For any housing measurement alone to be
effective for overall machine protection, the system must faithfully transmit a significant amount of rotor vibra-
tion to the bearing housing or machine casing, or more specifically, to the mounting location of the transducer.
In addition, you should exercise care in the physical installation of the transducer. Improper installation can
decrease the transducer amplitude and frequency response and/or generate signals which do not represent
actual machine vibration.
Upon request, Bently Nevada, Inc can provide engineering services to determine whether housing meas-
urements are appropriate for the machine in question and/or to provide installation assistance.
There are 2 different channel types, Acceleration and Acceleration 2, which support the meas-
urement of acceleration. The Acceleration channel type supports only the Direct measurement
and works with the 3500/42 and 3500/42M. The Acceleration 2 channel type, which is an
enhanced version of the Acceleration channel type, supports Direct, 1X Amplitude 1X Phase, 2X
Amplitude, and 2X Phase. The Acceleration 2 channel type is available on 3500/42E monitors and
on 3500/42M monitors with revision 2.1 or higher firmware. The Acceleration 2 channel type
requires version 3.2 of the 3500 System Configuration software.
Advisory
When upgrading from an Acceleration to an Acceleration 2 channel type you must take care with any DCS or PLC
programming that uses data from the Communications Gateway. The order and the number of values differ for
the Acceleration and Acceleration 2 static data and alarm status data. This may require you to change your DCS
or PLC programming. If this is undesirable you should use the Acceleration channel type.
1
Acceleration Measurement
Alert
A sudden mechanical impact can over-range velocity, acceleration, or Velomitor* sensors. If you enable Timed
OK Channel Defeat on the monitor and the over-range signal exceeds the OK limits, the monitor may not annun-
ciate an alarm. This may result in a missed alarm and temporary loss of machine protection. You can disable
Timed OK Channel Defeat on velocity and acceleration channel types.
Alert
Mechanical impacts will occur on reciprocating compressors. Disable Timed OK Channel Defeat when using veloc-
ity, acceleration, or Velomitor sensors to monitor crankcase or crosshead vibration.
Advisory
We do not recommend 3500/42M or 3500/42E monitors for acceleration measurements on reciprocating com-
pressors. Consider using the Bently Nevada* 3500/70M monitor for acceleration measurements on reciprocating
compressors.
2
1. General Information
3
Acceleration Measurement
1. Display Title
2. Upper Full Scale Range (FSR)
3. Upper Danger Setpoint (Red Solid Line)
4. Upper Alert Setpoint (Amber Solid Line)
5. Channel Bar
6. Lower Alert Setpoint (Amber Dashed Line)
7. Lower Danger Setpoint (Red Dashed Line)
8. Lower Full Scale Range
9. Channel Measured Value
10. Channel Units
11. Phase Danger Area (Red)
12. Phase Alert Area (Amber)
13. Channel Indicator
14. Zero Point (Black Solid Line)
15. Page Number Sequence
4
2. Acceleration 2 Configuration
2. Acceleration 2 Configuration
This section discusses the configuration considerations and the 3500 Rack Configuration Soft-
ware screens that are associated with the Acceleration 2 Channel Type.
5
Acceleration Measurement
l If you select a Non-standard transducer, the software sets the setpoint OK limits to±1 volt
from the Upper and Lower OK Limits that are selected.
6
2. Acceleration 2 Configuration
7
Acceleration Measurement
Upper OK Limits (V) Lower OK Limits (V) Center Bias Voltage (V)
Transducer
Type Without Bar- With Bar- Without Bar- With Bar- Without Bar- With Bar-
riers riers riers riers riers riers
(-15.05) (-2.75) (-8.90)
Not Sup- Not Sup- Not Sup-
24145-02 -15.05 -2.75 -8.90
ported ported ported
-13.85 -3.10 -8.475
330400 -15.05 -2.75 -8.90
(-15.05) (-2.75) (-8.90)
-10.86 -5.34 -8.10
330425 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
-10.86 -5.34 -8.10
49578-01 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
Not Sup- Not Sup- Not Sup-
155023-01 -11.37 -5.63 -8.50
ported ported ported
3300450 HT -22.00 ? -1.00 ? -12.5 ?
Note: The values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules.
2.1.1.3 I/O Module Attached - Jumper Position
This option returns the position of the transducer jumper on the I/O Module in 3500 systems.
Note
In the 3500 ENCORE systems, the jumper is located on the monitor.
2.1.2 Barriers
Barriers are devices that restrict the amount of energy that can flow into a hazardous area. Select
the MTL 796(-) Zener External option or Galvanic Isolators if you will connect external safety bar-
riers between the monitor and the transducer. If your application uses an internal barrier I/O mod-
ule, select the internal option.
8
2. Acceleration 2 Configuration
l If you enable integration, software will configure the monitor with a 10 Hz HPF and a 20 kHz
LPF.
9
Acceleration Measurement
2.2.1 Enable
The following items are found within the Enable group on the dialog.
2.2.1.1 Enable Check Boxes
Click the checkbox next to the static value to specify that the channel will provide that value.
2.2.1.2 Direct
Direct data represents the overall peak-to-peak vibration. This static value includes all frequen-
cies within the selected Direct Frequency Response.
2.2.1.3 Bias Voltage
Bias voltage is the dc voltage that the system uses as a bias for the transducer. You can use this
value as a diagnostic tool for evaluating system integrity.
This measurement contains no information about the condition of the machinery being mon-
itored. It has been provided only for monitoring system diagnostics.
2.2.1.4 1X Ampl
In a complex vibration signal, 1X Ampl is the notation for the amplitude component that occurs at
the rotative speed frequency.
2.2.1.5 1X Phase Lag
In a complex vibration signal, 1X Phase Lag is the notation for the phase lag component that
occurs at the rotative speed frequency.
2.2.1.6 2X Ampl
In a complex vibration signal, 2X Ampl is the notation for the amplitude component having a
frequency equal to twice the shaft rotative speed.
10
2. Acceleration 2 Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-10 g pk
0-20 g pk
0-25 g pk
0-10 g rms
0-40 g pk
0-20 g rms 0-4 in/s pk
0-45 g pk
0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-20 m/s2 pk
0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk Custom
0-100 m/s2 rms 0-100 mm/s pk
0-100 m/s2 pk Custom
0-200 m/s2 rms
0-200 m/s2 pk
Custom
0-250 m/s2 pk
0-400 m/s2 pk
Custom
0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 rms Custom
0-100 m/s2 pk 0-100 mm/s pk
Custom Custom
0-200 m/s2 pk
Custom
11
Acceleration Measurement
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-50 m/s2 rms
Custom
12
2. Acceleration 2 Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-700 m/s2
Custom
0-25 g rms
0-40 g rms
Custom
0-5 g pk
0-10 g pk
0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 pk 0-100 m/s2 rms 0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk Custom Custom
0-200 m/s2 pk
0-400 m/s2 pk
0-450 m/s2pk
Custom
Note
Whenever you modify a full-scale range, you should readjust the setpoints that are associated with this static
value.
13
Acceleration Measurement
2.2.2 Delay
Delay is the time for which a static value must remain at or above an over alarm level, or below an
under alarm level, before the monitor declares an alarm as active.
2.2.2.1 Alert Delay
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all available
static values. Alert is the first level alarm that occurs when the transducer signal level exceeds the
selected Alert/Alarm 1 setpoint. You can set this setpoint on the Setpoint screen.
2.2.2.2 Danger Delay
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds. Danger is
the second level alarm that occurs when the transducer signal level exceeds the selected
Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
2.2.2.3 100 ms Option
The 100 ms (typical) option applies only to the Danger time delay and has the following effects:
14
2. Acceleration 2 Configuration
2.2.3.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value drops
below the configured setpoint level.
2.2.3.3 Timed OK Channel Defeat
Timed OK Channel Defeat is an option that prevents a channel from returning to an OK status
until that channel's transducer has remained in an OK state for the specified period of time. If you
enable the option, the software sets the time to 30 seconds. This option prevents false trips that
intermittent transducers can cause.
Alert
A sudden mechanical impact can over-range velocity, acceleration, or Velomitor* sensors. If you enable Timed OK
15
Acceleration Measurement
Alert
Channel Defeat on the monitor and the over-range signal exceeds the OK limits, the monitor may not annunciate
an alarm. This may result in a missed alarm and temporary loss of machine protection. You can disable Timed OK
Channel Defeat on velocity and acceleration channel types.
2.2.4 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK the status
will stay Not OK until you use one of the following methods to issue a reset:
l Pressing the reset switch on the front of the System Module
l Closing the contact on the Power Input Module (PIM)
l Issuing the reset command over Modbus
l Issuing the reset command through the 3500 Display Interface Module
l Issuing the reset command in the 3500 Rack Configuration Software
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track the
defined OK status of the transducer.
16
2. Acceleration 2 Configuration
l Issuing the Trip Multiply command over an industrial protocol (example: Modbus)
l Issuing the Trip Multiply command in the 3500 Rack Configuration Software
Note
You can place the setpoint Over and Under limits only within the OK limits of the specified transducer.
17
Acceleration Measurement
18
2. Acceleration 2 Configuration
Advisory
The older Acceleration channel type had only 2 setpoints. Setpoint Number 2 was the Danger setpoint. The equiv-
alent Acceleration 2 setpoint is now Setpoint Number 10.
Note
Clicking on Set Defaults returns the settings on all screens at levels below the current screen to their default set-
tings even if the changes at lower levels were confirmed by clicking on the OK button at the lower level screen.
2.4.2 CP Mod
Selecting the CP Mod button in the Channel Options Dialog Box allows you to download a Cus-
tom channel configuration to the monitor. The 3500 Rack Configuration Software stores custom
configuration data in a Custom Products Modification File. Custom Products Modification files fol-
low the naming convention: <modification #.mod>. You must place these files in the
19
Acceleration Measurement
\3500\Rackcfg\Mods\ directory. When you select a CP Mod file, the software displays a window
that describes the function of the modification. CP Mod files are available through Bently Nevada,
Inc.'s Custom Products Division. Contact your local sales representative for details.
20
2. Acceleration 2 Configuration
External Barriers.
l You can install only 18 high-frequency accelerometer transducers in a full rack of standard
transducers. This is because the rack can power only 18 high-frequency Accelerometer
transducers.
l When you modify a full-scale value, readjust the setpoints that are associated with the
static value.
21
Acceleration Measurement
22
3. Acceleration Verification
3. Acceleration Verification
The following sections will describe how to test alarms, verify channels, verify filter corner frequen-
cies, and test OK limits for Acceleration and Acceleration 2 channels. You verify the output values
and alarm setpoints by varying the input signal level and verifying that the Verification screen
reports the correct results on the test computer. You can configure Acceleration channels for the
channel values and alarms shown in the table.
Table 3-1: Acceleration Channel Values and Alarms
Channel Values Over Alarms Under Alarms
Direct X
1X Amplitude X X
2x Amplitude X X
Frequency: 100 Hz
23
Acceleration Measurement
1. Keyphasor Signal
2. Keyphasor I/O Module
3. 40 k resistor
4. 100 µF capacitor
5. Keyphasor multiplier/divider
6. Simulated input signal
7. Typical I/O module
8. Function Generator
9. Multimeter
10. Power supply
24
3. Acceleration Verification
3.2.1 Direct
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, “Test
Equipment and Software Setup."
Note
You will not require items 1 through 5 in the Figure "Test Equipment Setup" to test Direct Alarms.
3. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
4. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
5. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the
bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
6. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
7. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint
25
Acceleration Measurement
level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
8. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
9. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
10. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
11. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
12. Repeat steps 1 through 11 for all configured channels.
Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.
1. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the
26
3. Acceleration Verification
bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint
level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator phase to be below the Under Alarm setpoint lev-
els.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.
3.2.3 1X Phase
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
Note
If you cannot change the phase output, change the phase alarm setpoints to activate the over and under
phase alarms. You must download the setpoints to the monitor for them to take effect.
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the phase reading within the setpoint levels on the bar graph display of the
27
Acceleration Measurement
Verification screen.
Note
The Amplitude must be a minimum of 42.7 mV to produce a valid Phase reading.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the phase reading to just exceed the Over Alert/Alarm 1 setpoint level and wait for 2
or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from green to yellow and that the Current Value Field indicates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the phase reading to just exceed the Over Danger/Alarm 2 setpoint level and wait for
2 or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from yellow to red and that the Current Value Field indicates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the phase reading below the Over Alarm setpoint levels. If the non-latching option is
configured, verify that the color of the bar graph indicator changes to green and that the
Current Value Box contains no indication of alarms. Press the Reset switch to reset latching
alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator phase to be below the Under Alarm setpoint lev-
els.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.
Note
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.
28
3. Acceleration Verification
1. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
2. Connect the test equipment and run the software as described in the section, “Test
Equipment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the
bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint
level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator amplitude to be below the Under Alarm setpoint
levels.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
29
Acceleration Measurement
3.2.5 2X Phase
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
Note
If you cannot change the phase output, change the phase alarm setpoints to activate the over and under
phase alarms. You must download the setpoints to the monitor for them to take effect.
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Adjust the phase reading within the setpoint levels on the bar graph display of the Ver-
ification screen.
Note
The Amplitude must be a minimum of 42.7 mV to produce a valid Phase reading.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the phase reading to just exceed the Over Alert/Alarm 1 setpoint level and wait for 2
or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from green to yellow and that the Current Value Field indicates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the phase reading to just exceed the Over Danger/Alarm 2 setpoint level and wait for
2 or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from yellow to red and that the Current Value Field indicates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the phase reading below the Over Alarm setpoint levels. If the non-latching option is
configured, verify that the color of the bar graph indicator changes to green and that the
Current Value Box contains no indication of alarms. Press the Reset switch to reset latching
alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2
30
3. Acceleration Verification
setpoints by adjusting the function generator phase to be below the Under Alarm setpoint
levels.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.
Note
These parameters have an accuracy specification of ±1% of full scale for amplitude and 3º for phase.
3.3.1 Direct
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Use the equation and examples shown below to calculate the full-scale voltage. Adjust the
amplitude of the function generator to the calculated voltage.
Advisory
Use the Transducer Scale Factor displayed in the Scale Factor Box on the Verification Screen.
Full Scale Voltage = Direct Meter Top Scale— Transducer Scale Factor
Example 1
31
Acceleration Measurement
Example 2
4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
5. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section "If a Channel Fails a Verification Test" in your hardware manual.
6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.
Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Use the procedure in "Calculating the Input Voltage for Full Scale" to calculate the full-scale
voltage. Adjust the function generator (sine wave) amplitude to the calculated value.
4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
32
3. Acceleration Verification
is 001.
5. Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
6. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section"If a Channel Fails a Verification Test" in your hardware manual.
7. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
8. Repeat steps 1 through 7 for all configured channels.
3.3.3 1X Phase
If your test equipment cannot change the phase output to a known value, use the procedure in
"If Your Test Equipment Cannot Change the 1X Phase Output". If your test equipment can change
the phase output to a known value, use the procedure in "If Your Test Equipment Can Change the
1X Phase Output".
3.3.3.1 If Your Test Equipment Cannot Change the 1X Phase Output
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Attach one channel of the 2-channel oscilloscope to the vibration signal buffered output
and attach the other channel to the associated Keyphasor signal buffered output to
observe both signals simultaneously.
5. Measure the phase. Measure 1X Phase from the leading edge of the Keyphasor pulse to the
first positive peak of the vibration signal. Refer to the figure, which illustrates a phase of 45°.
Verify that the 1X Phase bar graph display and Current Value Box readings are approx-
imately what you measured. If integration is enabled, then add 90 degrees to the measured
value to obtain the correct reading from the monitor.
33
Acceleration Measurement
1. 1X vibration signal
2. Keyphasor signal
3. Time
4. 0°
5. One Cycle
6. 360°
7. Phase lag = 45°
If your test equipment can change the phase output to a known value, use the following pro-
cedure.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the phase reading for mid-scale. Verify that the bar graph display and Current Value
Box readings are within 1.5% of mid-scale.
5. If the readings do not meet specifications, verify that the input signal is correct. If the
34
3. Acceleration Verification
monitor still does not meet specifications or fails any other part of this test, you must
replace the monitor. See the section "If a Channel Fails a Verification Test†in your hard-
ware manual.
6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.
Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, “Test Equip-
ment and Software Setup."
3. Use the formulas in “Calculating the Input Voltage for Full Scale” to calculate the full-scale
voltage value. Adjust the function generator (sine wave) amplitude to the calculated value.
4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
5. Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
6. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section “If a Channel Fails a Verification Test” in your hardware manual.
7. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
8. Repeat steps 1 through 7 for all configured channels.
3.3.5 2X Phase
If your test equipment cannot change the 2X phase output to a known value, use the procedure
in "If Your Test Equipment Cannot Change the 2X Phase Output." If your test equipment can
change the phase output to a known value, use the procedure in "If Your Test Equipment Can
Change the 2X Phase Output."
35
Acceleration Measurement
1. 0°
2. First Cycle
3. One shaft revolution
4. Second cycle
5. 2X Vibration Signa
6. Phase lag = 90°
7. Keyphasor signal
8. 360°
9. Time
36
3. Acceleration Verification
Unconfigured Configured
Configured Unconfigured
Any other configuration:
Configured Configured
37
Acceleration Measurement
Advisory
Use the Transducer Scale Factor displayed in the Scale Factor Box on the Verification Screen.
Use the following conversion formulas to convert Metric units to English Units:
l SF(V/g) = SF in V/(m/s2) * 9.8135 (m/s2/g)
l FS (mm/s) = (FS in in/s) / 2.54 mm/in
Example:
Calculate the input voltage for a channel with the following configuration:
38
3. Acceleration Verification
Verification Frequency =
= 283 Hz
Input Voltage (Vrms) = (1.0 in/s * 0.1 V/g * 283 Hz * 0.3535) / 30.72
= 0.326 Vrms
Input Voltage (Vpk-pk) = (1.0 in/s * 0.1 V/g * 283 Hz) / 30.72
= 0.921Vpk-pk
The transducer Scale Factor is always specified as volts per g pk or volts per m/ss pk.
Example 1:
Example 2:
39
Acceleration Measurement
= 0.4076 Vpp
Vrms input = (0.01019 V/(m/s2 ) * 20 ) × 0.707
= 0.1440 V rms
Note
If the Danger Bypass is active, then the BYPASS LED will be on. All other channels in the rack must be OK or
bypassed for the OK relay to energize.
6. Verify that the OK relay on the System Monitor indicates OK (is energized). (See the appro-
priate System Monitor manual for more information.)
7. Increase the power supply voltage (more negative) until the OK LED just goes off (upper
limit). Verify that the Channel OK State line on the Verification screen reads Not OK and that
the OK Relay indicates Not OK. Verify that Verification screen displays an Upper OK Limit
voltage that is equal to or more positive than the input voltage.
8. Adjust the power supply voltage to -7.00 Vdc.
9. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay ener-
gizes. Verify that the Channel OK State line in the Channel Status section reads OK.
10. Gradually decrease the power supply voltage (less negative) until the OK LED just goes off
(lower limit). Verify that the Channel OK State line in the Channel Status section reads Not OK
and that the OK Relay indicates Not OK. Verify that the Verification screen displays a Lower
OK Limit voltage that is equal to or more negative than the input voltage.
11. Adjust the power supply voltage to -7.00 Vdc.
12. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
40
3. Acceleration Verification
energizes. Verify that the Channel OK State line in the Channel Status section reads OK.
13. If you cannot verify any configured OK limit, you must replace the monitor. Refer to “If a
Channel Fails a Verification Test” in your monitor hardware manual.
14. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
15. Repeat steps 1 through 14 for all configured channels.
16. Return the bypass switches for all configured channels back to their original settings.
Note for table: Values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules
41
Acceleration Measurement
42
4. Acceleration Configuration
4. Acceleration Configuration
This section is included as a reference for the obsolete Acceleration sensors.
4.1.1 Direct
Direct data represents the overall peak-to-peak vibration. This static value includes all frequen-
cies within the selected Direct Frequency Response.
4.1.1.1 Full-Scale Range
This section details the available full-scale ranges for the different acceleration types.
43
Acceleration Measurement
Table 4-1: 23733-03 Standard Acceleration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk
0-5 g pk
0-10 g pk
0-2 g rms
0-20 g pk
0-5 g rms 0-1 in/s pk
0-25 g pk
0-10 g rms 0-2 in/s pk 0-1 in/s rms
0-40 g pk
0-20 g rms 0-4 in/s pk 0-2 in/s rms
0-45 g pk
0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-20 m/s2 pk
0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk Custom
0-100 m/s2 rms 0-100 mm/s pk
0-100 m/s2 pk Custom
0-200 m/s2 rms
0-200 m/s2 pk
Custom
0-250 m/s2 pk
0-400 m/s2 pk
Custom
0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 rms Custom
0-100 m/s2 pk 0-100 mm/s pk
Custom Custom
0-200 m/s2 pk
Custom
44
4. Acceleration Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0- 30 g rms
Custom
45
Acceleration Measurement
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-250 m/s2 pk
Custom
0-25 g rms
0-40 g rms
Custom
0-5 g pk
0-10 g pk
0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 pk 0-100 m/s2 rms 0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk Custom Custom
0-200 m/s2 pk
0-400 m/s2 pk
0-450 m/s2pk
Custom
46
4. Acceleration Configuration
Note
Whenever you modify a full-scale range, you should readjust the setpoints that are associated with this static
value.
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed channel
to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a Bypassed chan-
nel.
47
Acceleration Measurement
l Closing the Trip Multiply contact on the System Monitor or Power Input Module (3500
ENCORE Systems)
l Issuing the Trip Multiply command over an industrial protocol (example: Modbus)
l Issuing the Trip Multiply command in the 3500 Rack Configuration Software
4.1.3 Type
The following transducer types are available for the Acceleration Channel with a non-barrier I/O
module.
l 23733-03 Standard Acceleration
l 24145-02 High Frequency Acceleration
l 330400 Standard Integral Acceleration
l 330425 Standard Integral Acceleration
l 49578-01 Standard Acceleration
l 155023-01 High Frequency Acceleration
l 3300450 HT Integral Acceleration
l Non-standard
The following transducer types are available for the Acceleration Channel with a barrier I/O mod-
ule.
l 23733-03 Standard Acceleration
l 330400 Standard Integral Acceleration
l 330425 Standard Integral Acceleration
48
4. Acceleration Configuration
l If you select a Non-standard transducer, the software sets the setpoint OK limits to±1 volt
from the Upper and Lower OK Limits that are selected.
49
Acceleration Measurement
Note: The values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules.
Note
In the 3500 ENCORE systems, the jumper is located on the monitor.
50
4. Acceleration Configuration
4.1.10 Delay
Delay is the time for which a static value must remain at or above an over alarm level, or below an
under alarm level, before the monitor declares an alarm as active.
4.1.10.1 Alert Delay
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all available
static values. Alert is the first level alarm that occurs when the transducer signal level exceeds the
selected Alert/Alarm 1 setpoint. You can set this setpoint on the Setpoint screen.
4.1.10.2 Danger Delay
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds. Danger is
the second level alarm that occurs when the transducer signal level exceeds the selected
Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
4.1.10.3 100 ms Option
The 100 ms (typical) option applies only to the Danger time delay and has the following effects:
If the 100 ms option is OFF:
l You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
l You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
l The software sets the Danger time delay to 100 ms.
l You can set the Danger time delay for only the primary static value.
51
Acceleration Measurement
4.1.11.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value drops
below the configured setpoint level.
4.1.11.3 Timed OK Channel Defeat
Timed OK Channel Defeat is an option that prevents a channel from returning to an OK status
until that channel's transducer has remained in an OK state for the specified period of time. If you
enable the option, the software sets the time to 30 seconds. This option prevents false trips that
intermittent transducers can cause.
4.1.11.4 Monitor Danger Relay Voting
This option allows you to add logic processing to channel alarming.
l OR - if either channel of a channel pair is in danger alarm, the danger alarm relay is acti-
vated.
l AND - if both channels of a channel pair are in danger alarm, the danger alarm relay is acti-
vated.
Relay Voting is available when the Dual Relay option is selected.
52
4. Acceleration Configuration
4.1.12 Barriers
Barriers are devices that restrict the amount of energy that can flow into a hazardous area. Select
the MTL 796(-) Zener External option or Galvanic Isolators if you will connect external safety bar-
riers between the monitor and the transducer. If your application uses an internal barrier I/O mod-
ule, select the internal option.
4.1.13 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK the status
will stay Not OK until you use one of the following methods to issue a reset:
l Pressing the reset switch on the front of the System Module
l Closing the contact on the Power Input Module (PIM)
l Issuing the reset command over Modbus
l Issuing the reset command through the 3500 Display Interface Module
l Issuing the reset command in the 3500 Rack Configuration Software
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track the
defined OK status of the transducer.
4.1.14 CP Mod
Selecting the CP Mod button in the Channel Options Dialog Box allows you to download a Cus-
tom channel configuration to the monitor. The 3500 Rack Configuration Software stores custom
configuration data in a Custom Products Modification File. Custom Products Modification files fol-
low the naming convention: <modification #.mod>. You must place these files in the
\3500\Rackcfg\Mods\ directory. When you select a CP Mod file, the software displays a window
that describes the function of the modification. CP Mod files are available through Bently Nevada,
Inc.'s Custom Products Division. Contact your local sales representative for details.
Note
You can place the setpoint Over and Under limits only within the OK limits of the specified transducer.
53
Acceleration Measurement
54
4. Acceleration Configuration
Consider a channel configuration with a 0 - 10 mils full-scale range and an alarm setpoint at 6
mils. Full scale is 10 mils - 0 mils = 10 mils, so the hysteresis = 10 mils/64 = 0.16 mils. The channel
input, therefore, must fall below 6 mils - 0.16 mils = 5.84 mils before the channel is out of alarm.
55
Acceleration Measurement
56