100% found this document useful (1 vote)
168 views64 pages

Acceleration Measurements: Operation and Maintenance Manual

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 64

Operation and Maintenance Manual

Bently Nevada* Asset Condition Monitoring

Acceleration Measurements

Part Number 287552-01


Rev. A (09/12)
Acceleration Measurement

©2011 - 2012   Bently Nevada, Inc.


All rights reserved.

The information contained in this document is subject to change without notice.

* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Com-
pany.
Bently Nevada, Keyphasor, Velomitor

The following are trademarks of the legal entities cited:

Printed in USA. Uncontrolled when transmitted electronically

Contact Information

The following contact information is provided for those times when you cannot contact your
local representative:

1631 Bently Parkway South


Mailing Address Minden, Nevada USA  89423
USA
1.775.782.3611
Telephone
1.800.227.5514
Fax 1.775.215.2873
Internet www.ge-mcs.com/bently

ii
Additional Information
NOTE
This manual does not contain all the information required to operate and maintain the monitoring system. The
following is a complete list of the 3500 ENCORE manuals. Refer to these manuals for other required information.

3300 System Upgrade Manual (part number 287550-01)


3500/15E Power Supply Manual (part number 287549-01)
3500/23E System Monitor Manual (part number 287545-01
3500/42E Vibration Monitor Manual (part number 287546-01)
3500/45E Position Monitor Manual (part number 288619-01)
3500/50E Tachometer Monitor Manual (part number 287548-01)
3500/61E & 67E Temperature Monitor Manual (part number 287547-01)
3500 Acceleration Measurement Manual (part number 287552-01)
3500 Case Expansion Measurement Manual (part number 288621-01)
3500 Complementary Input Differential Expansion Measurement Manual (part number 288623-01)
3500 Eccentricity Measurement Manual (part number 287555-01)
3500 Radial Vibration Manual (part number 287558-01)
3500 Ramp Differential Expression Measurement Manual (part number 288620-01)
3500 Shaft Absolute Measurement Manual (part number 287554-01)

3500 Thrust & Diff Expansion Measurement Manual (part number 287553-01)
3500 Valve Position Measurement Manual (part number 288622-01)
3500 Velocity Measurement Manual (part number 287551-01)

Product Disposal Statement


Customers and third parties, who are not member states of the European Union, who are in con-
trol of the product at the end of its life or at the end of its use, are solely responsible for the proper
disposal of the product. No person, firm, corporation, association or agency that is in control of
product shall dispose of it in a manner that is in violation of any applicable federal, state, local or
international law. Bently Nevada, Inc. is not responsible for the disposal of the product at the end
of its life or at the end of its use.

iii
Acceleration Measurement

iv
Contents
1. General Information 1
1.1 ENCORE Acceleration 2 Screen Displays 2
1.1.1 Display Components 4
2. Acceleration 2 Configuration 5
2.1 Transducer Filtering and Configuration 5
2.1.1 Transducer Selection 5
2.1.1.1 Type 5
2.1.1.2 Customize Button 6
2.1.1.3 I/O Module Attached - Jumper Position 8
2.1.1.4 Take Input From Channel 1 (3) Transducer 8
2.1.2 Barriers 8
2.1.3 Corner Frequencies 8
2.1.4 High-Pass Filter 9
2.1.5 Low-Pass Filter 9
2.2 Variables and Alarms Configuration 9
2.2.1 Enable 10
2.2.1.1 Enable Check Boxes 10
2.2.1.2 Direct 10
2.2.1.3 Bias Voltage 10
2.2.1.4 1X Ampl 10
2.2.1.5 1X Phase Lag 10
2.2.1.6 2X Ampl 10
2.2.1.7 2X Phase Lag 10
2.2.1.8 Full-Scale Range 10
2.2.1.9 Clamp Value 14
2.2.1.10 RMS 14
2.2.1.11 Integrate 14
2.2.2 Delay 14
2.2.2.1 Alert Delay 14
2.2.2.2 Danger Delay 14
2.2.2.3 100 ms Option 14
2.2.3 Alarm Mode 15
2.2.3.1 Latching 15

v
Acceleration Measurement

2.2.3.2 Non-latching 15
2.2.3.3 Timed OK Channel Defeat 15
2.2.3.4 Monitor Danger Relay Voting 16
2.2.4 OK Mode 16
2.2.5 Trip Multiply 16
2.2.6 Recorder Output 17
2.2.6.1 Two mA Clamp 17
2.3 Alarm Setpoints 17
2.3.1 Alarm Setpoint Dialog 18
2.3.2 Available Setpoints 18
2.3.3 Alarm Hysteresis 19
2.4 General Parameters and Buttons 19
2.4.1 Set Defaults Button 19
2.4.2 CP Mod 19
2.4.3 Print Form Button 20
2.4.4 Point Names Button 20
2.5 Configuration Considerations 20
3. Acceleration Verification 23
3.1 Test Equipment and Software Setup 23
3.1.1 Test Equipment Setup 23
3.1.2 Verification Screen Setup 24
3.2 Test Alarms 25
3.2.1 Direct 25
3.2.2 1X Amplitude (1X Amp) 26
3.2.3 1X Phase 27
3.2.4 2X Amplitude (2X Amp) 28
3.2.5 2X Phase 30
3.3 Verify Channel Values 31
3.3.1 Direct 31
3.3.2 1X Amplitude (1X Ampl) 32
3.3.3 1X Phase 33
3.3.3.1 If Your Test Equipment Cannot Change the 1X Phase Output 33
3.3.3.2 If Your Test Equipment Can Change the 1X Phase Output 34
3.3.4 2X Amplitude (2X Ampl) 35
3.3.5 2X Phase 35
3.3.5.1 If Your Test Equipment Cannot Change the 2X Phase Output 36

vi
3.3.5.2 If Your Test Equipment Can Change the 2X Phase Output 37
3.3.6 Calculating Verification Frequency 37
3.3.7 Calculating the Input Voltage for Full Scale 38
3.3.7.1 Full Scale Formulas With Integration 38
3.3.7.2 Full Scale Equations Without Integration 39
3.4 Test OK Limits 40
3.4.1 Acceleration OK Limits 41
4. Acceleration Configuration 43
4.1 Configuration Options 43
4.1.1 Direct 43
4.1.1.1 Full-Scale Range 43
4.1.1.2 Clamp Value 47
4.1.1.3 Recorder Output 47
Two mA Clamp 47
4.1.2 Trip Multiply 47
4.1.3 Type 48
4.1.4 Customize Button 48
4.1.5 I/O Module Attached - Jumper Position 50
4.1.6 Take Input From Channel 1 (3) Transducer 50
4.1.7 Corner Frequencies 50
4.1.8 High-Pass Filter 51
4.1.9 Low-Pass Filter 51
4.1.10 Delay 51
4.1.10.1 Alert Delay 51
4.1.10.2 Danger Delay 51
4.1.10.3 100 ms Option 51
4.1.11 Alarm Mode 52
4.1.11.1 Latching 52
4.1.11.2 Non-latching 52
4.1.11.3 Timed OK Channel Defeat 52
4.1.11.4 Monitor Danger Relay Voting 52
4.1.12 Barriers 53
4.1.13 OK Mode 53
4.1.14 CP Mod 53
4.2 Alarm Setpoints 53
4.2.1 Alarm Setpoint Dialog 54

vii
Acceleration Measurement

4.2.2 Available Setpoints 54


4.2.3 Alarm Hysteresis 54
4.3 Configuration Considerations 55

viii
1.  General Information

1. General Information
Acceleration measurements are generally made with an Accelerometer. You typically use these
measurements to evaluate the high frequency vibration of a machine casing or bearing housing
that is due to blade passage, gear mesh, cavitation, rolling element bearing defects, and other
conditions. For harmonic motion, acceleration is often expressed as g or a. Typical units for accel-
eration are feet per second per second peak (ft/s2 pk), meters per second per second peak (m/s2
pk), or more commonly g pk (acceleration of gravity = 386.1 in/s2 pk = 32.17 ft/s2 pk = 9.81 m/s2 pk).

Note
Acceleration, as well as velocity, are zero-to-peak (pk) measurements.

You program Acceleration channels in pairs. These channels, depending on configuration, typ-
ically condition the input signals into various parameters called "œstatic values" . You can con-
figure Alert setpoints for each active static value and Danger setpoints for any 2 of the active
static values.

Advisory
If you plan to use housing measurements for overall machine protection, you should consider the usefulness of
the measurement for each application. Most common machine malfunctions (imbalance, misalignment, etc.) orig-
inate at the rotor and increase (or at least change) rotor vibration. For any housing measurement alone to be
effective for overall machine protection, the system must faithfully transmit a significant amount of rotor vibra-
tion to the bearing housing or machine casing, or more specifically, to the mounting location of the transducer.

In addition, you should exercise care in the physical installation of the transducer. Improper installation can
decrease the transducer amplitude and frequency response and/or generate signals which do not represent
actual machine vibration.

Upon request, Bently Nevada, Inc can provide engineering services to determine whether housing meas-
urements are appropriate for the machine in question and/or to provide installation assistance.

There are 2 different channel types, Acceleration and Acceleration 2, which support the meas-
urement of acceleration. The Acceleration channel type supports only the Direct measurement
and works with the 3500/42 and 3500/42M. The Acceleration 2 channel type, which is an
enhanced version of the Acceleration channel type, supports Direct, 1X Amplitude 1X Phase, 2X
Amplitude, and 2X Phase. The Acceleration 2 channel type is available on 3500/42E monitors and
on 3500/42M monitors with revision 2.1 or higher firmware. The Acceleration 2 channel type
requires version 3.2 of the 3500 System Configuration software.

 Advisory
When upgrading from an Acceleration to an Acceleration 2 channel type you must take care with any DCS or PLC
programming that uses data from the Communications Gateway. The order and the number of values differ for
the Acceleration and Acceleration 2 static data and alarm status data. This may require you to change your DCS
or PLC programming. If this is undesirable you should use the Acceleration channel type.

1
Acceleration Measurement

Alert
A sudden mechanical impact can over-range velocity, acceleration, or Velomitor* sensors. If you enable Timed
OK Channel Defeat on the monitor and the over-range signal exceeds the OK limits, the monitor may not annun-
ciate an alarm. This may result in a missed alarm and temporary loss of machine protection. You can disable
Timed OK Channel Defeat on velocity and acceleration channel types.

Alert
Mechanical impacts will occur on reciprocating compressors. Disable Timed OK Channel Defeat when using veloc-
ity, acceleration, or Velomitor sensors to monitor crankcase or crosshead vibration.

Advisory
We do not recommend 3500/42M or 3500/42E monitors for acceleration measurements on reciprocating com-
pressors. Consider using the Bently Nevada* 3500/70M monitor for acceleration measurements on reciprocating
compressors.

1.1 ENCORE Acceleration 2 Screen Displays


Acceleration 2 channels have 7 screens. Screens 1 through 6 are displayed in the Figure. Screen 7
contains the channels' point names.

2
1.  General Information

1. Channels 1 & 2 Direct Value


2. Channels 1 & 2 Bias Voltage
3. Channels 1 & 2 1X Amplitude Measurements
4. Channels 1 & 2 1X Phase Measurements
5. Channels 1 & 2 2X Amplitude Measurements
6. Channels 1 & 2 2X Phase Measurements

Figure 1 - 1: Acceleration 2 Vibration I/O Screens

3
Acceleration Measurement

1.1.1 Display Components

1. Display Title
2. Upper Full Scale Range (FSR)
3. Upper Danger Setpoint (Red Solid Line)
4. Upper Alert Setpoint (Amber Solid Line)
5. Channel Bar
6. Lower Alert Setpoint (Amber Dashed Line)
7. Lower Danger Setpoint (Red Dashed Line)
8. Lower Full Scale Range
9. Channel Measured Value
10. Channel Units
11. Phase Danger Area (Red)
12. Phase Alert Area (Amber)
13. Channel Indicator
14. Zero Point (Black Solid Line)
15. Page Number Sequence

Figure 1 - 2: Components Description

4
2.  Acceleration 2 Configuration

2. Acceleration 2 Configuration
This section discusses the configuration considerations and the 3500 Rack Configuration Soft-
ware screens that are associated with the Acceleration 2 Channel Type.

2.1 Transducer Filtering and Configuration


This section describes the options that the Acceleration Channel configuration screen provides.

Figure 2 - 1: Transducer Setup + Filtering Tab

2.1.1 Transducer Selection


2.1.1.1 Type
The following transducer types are available for the Acceleration Channel with a non-barrier I/O
module.
l 23733-03 Standard Acceleration
l 24145-02 High Frequency Acceleration
l 330400 Standard Integral Acceleration

5
Acceleration Measurement

l 330425 Standard Integral Acceleration


l 49578-01 Standard Acceleration
l 155023-01 High Frequency Acceleration
l 3300450 HT Integral Acceleration
l Non-standard
The following transducer types are available for the Acceleration Channel with a barrier I/O mod-
ule.
l 23733-03 Standard Acceleration
l 330400 Standard Integral Acceleration
l 330425 Standard Integral Acceleration
l 49578-01 Standard Acceleration
l 3300450 HT Integral Acceleration
l Non-standard
2.1.1.2 Customize Button
You use this button to adjust the Scale Factor for transducers. Refer to the "Adjusting the Scale
Factor and Zero Position" section of your hardware manual. Also, note that:
l If you select Non-standard as the transducer type, you can also adjust the OK Limits.
l The Non-standard transducer's scale factor must be between 5 and 115 mV/g.
l The Upper and Lower OK Limits must differ by at least 2 volts.

l If you select a Non-standard transducer, the software sets the setpoint OK limits to±1 volt
from the Upper and Lower OK Limits that are selected.

6
2.  Acceleration 2 Configuration

Figure 2 - 2: Customize Dialog


Table 2-1: Scale Factor by Transducer Type (+/-15% scale factor adjustment allowed)
Without With Bently Nevada Standard I/O Discrete TMR I/O Bussed TMR I/O
Transducer Barriers Internal Barriers Barriers with Barriers with Barriers
Type
(mV/g) (mV/g)) (mV/g) (mV/g) (mV/g)
23733-03 100 96 95.6 100 99.4
24145-02 100 Not supported Not supported Not supported Not supported
330400 100 96 95.6 95.6 95.6
330425 25 24 23.9 23.9 23.9
49578-01 25 24 23.9 25 23.9
155023-01 25 Not supported Not supported Not supported Not supported
3300450
100 96 95.6 100 ?
HT

Table 2-2: OK Limits by Transducer Type


Upper OK Limits (V) Lower OK Limits (V) Center Bias Voltage (V)
Transducer
Type Without Bar- With Bar- Without Bar- With Bar- Without Bar- With Bar-
riers riers riers riers riers riers
23733-03 -15.05 -13.85 -2.75 -3.10 -8.90 -8.475

7
Acceleration Measurement

Upper OK Limits (V) Lower OK Limits (V) Center Bias Voltage (V)
Transducer
Type Without Bar- With Bar- Without Bar- With Bar- Without Bar- With Bar-
riers riers riers riers riers riers
(-15.05) (-2.75) (-8.90)
Not Sup- Not Sup- Not Sup-
24145-02 -15.05 -2.75 -8.90
ported ported ported
-13.85 -3.10 -8.475
330400 -15.05 -2.75 -8.90
(-15.05) (-2.75) (-8.90)
-10.86 -5.34 -8.10
330425 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
-10.86 -5.34 -8.10
49578-01 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
Not Sup- Not Sup- Not Sup-
155023-01 -11.37 -5.63 -8.50
ported ported ported
3300450 HT -22.00 ? -1.00 ? -12.5 ?

Note: The values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules.
2.1.1.3 I/O Module Attached - Jumper Position
This option returns the position of the transducer jumper on the I/O Module in 3500 systems.

Note
In the 3500 ENCORE systems, the jumper is located on the monitor.

2.1.1.4 Take Input From Channel 1 (3) Transducer


This causes the even numbered channel to make its transducer input identical to the odd num-
bered channel that makes up the channel pair. This will also set items that a change in transducer
would affect, such as Barriers.

2.1.2 Barriers
Barriers are devices that restrict the amount of energy that can flow into a hazardous area. Select
the MTL 796(-) Zener External option or Galvanic Isolators if you will connect external safety bar-
riers between the monitor and the transducer. If your application uses an internal barrier I/O mod-
ule, select the internal option.

2.1.3 Corner Frequencies


If you do not select a filter, then the software will configure the corner frequencies as follows:
l If you disable integration, software will configure the monitor with a 3 Hz High-pass Filter
(HPF) and a 30 kHz Low-pass Filter (LPF).

8
2.  Acceleration 2 Configuration

l If you enable integration, software will configure the monitor with a 10 Hz HPF and a 20 kHz
LPF.

2.1.4 High-Pass Filter


The High-pass Filter is a 4-pole filter that you must set at least 2 octaves away from the Low-pass
Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
HPF <= (LPF / 4)

2.1.5 Low-Pass Filter


The Low-pass Filter is a 4-pole filter that you must be set at least 2 octaves away from the High-
pass Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
LPF >= (HPF x 4)
When you select band-pass filtering, you must set the high-pass and low-pass filters at least 2
octaves apart.

2.2 Variables and Alarms Configuration

Figure 2 - 3: Variables+Alarms Tab

9
Acceleration Measurement

2.2.1 Enable
The following items are found within the Enable group on the dialog.
2.2.1.1 Enable Check Boxes
Click the checkbox next to the static value to specify that the channel will provide that value.
2.2.1.2 Direct
Direct data represents the overall peak-to-peak vibration. This static value includes all frequen-
cies within the selected Direct Frequency Response.
2.2.1.3 Bias Voltage
Bias voltage is the dc voltage that the system uses as a bias for the transducer. You can use this
value as a diagnostic tool for evaluating system integrity.
This measurement contains no information about the condition of the machinery being mon-
itored. It has been provided only for monitoring system diagnostics.

2.2.1.4 1X Ampl
In a complex vibration signal, 1X Ampl is the notation for the amplitude component that occurs at
the rotative speed frequency.
2.2.1.5 1X Phase Lag
In a complex vibration signal, 1X Phase Lag is the notation for the phase lag component that
occurs at the rotative speed frequency.
2.2.1.6 2X Ampl
In a complex vibration signal, 2X Ampl is the notation for the amplitude component having a
frequency equal to twice the shaft rotative speed.

2.2.1.7 2X Phase Lag


In a complex vibration signal, 2X Phase Lag is the notation for the phase lag component having a
frequency equal to twice the shaft rotative speed. 2X phase lag is the angular measurement from
the leading or trailing edge of the Keyphasor* pulse to the following positive peak of the 2X vibra-
tion signal.
2.2.1.8 Full-Scale Range
This section details the available full-scale ranges for the different acceleration types.
Table 2-3: 23733-03 Standard Acceleration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk 0-2 g rms 0-1 in/s pk 0-1 in/s rms

0-5 g pk 0-5 g rms 0-2 in/s pk 0-2 in/s rms

10
2.  Acceleration 2 Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-10 g pk

0-20 g pk

0-25 g pk
0-10 g rms
0-40 g pk
0-20 g rms 0-4 in/s pk
0-45 g pk
0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-20 m/s2 pk
0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk Custom
0-100 m/s2 rms 0-100 mm/s pk
0-100 m/s2 pk Custom
0-200 m/s2 rms
0-200 m/s2 pk
Custom
0-250 m/s2 pk

0-400 m/s2 pk
Custom

Table 2-4: 24145-02 High Frequency Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk

0-5 g pk 0-2 g rms 0-1 in/s pk

0-10 g pk 0-5 g rms 0-2 in/s pk 0-1 in/s rms

0-20 g pk 0-10 g rms 0-4 in/s pk 0-2 in/s rms

0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms

0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 rms Custom
0-100 m/s2 pk 0-100 mm/s pk
Custom Custom
0-200 m/s2 pk
Custom

Table 2-5: 33040 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk 0-0.5 g rms

0-5 g pk 0-1g rms 0-1 in/s pk


0-10 g pk 0- 2 g rms 0-2 in/s pk 0-1 in/s rms
0-20 g pk 0-5 g rms 0-4 in/s pk 0-2 in/s rms
0-45 g pk 0-10 g rms 0-25 mm/s pk 0-25 mm/s rms
0-20 m/s2 pk 0-20 g rms 0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk 0- 30 g rms Custom
0-100 mm/s pk
0-100 m/s2 pk 0-10 m/s2 rms Custom

0-200 m/s2 pk 0 -20 m/s2 rms

11
Acceleration Measurement
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-50 m/s2 rms

0-100 m/s2 rms


0-400 m/s2pk
0-200 m/s2 rms
Custom
0-300 m/s2 rms

Custom

Table 2-6: 49578-01 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS

0-20 g pk 0-20 g rms

0-25 g pk 0-25 g rms

0-40 g pk 0-40 g rms

0-50 g pk 0-50 g rms


0-2 in/s pk 0-2 in/s rms
0-20 m/s2 pk 0-20 m/s2 rms
0-4 in/s pk 0-4 in/s rms
0-50 m/s2 pk 0-50 m/s2 rms
0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 pk 0-100 m/s2 rms
0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk 0-200 m/s2 rms
Custom Custom
0-250 m/s2 pk 0-250 m/s2 rms

0-400 m/s2 pk 0-400 m/s2 rms

0-500 m/s2 pk 0-500 m/s2 rms


Custom Custom

Table 2-7: 330425 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-20 g pk 0-20 g rms

0-25 g pk 0-25 g rms

0-40 g pk 0-40 g rms


0-2 in/s pk 0-2 in/s rms
0-50 g pk 0-50 g rms
0-4 in/s pk 0-4 in/s rms
0-75 g pk 0-20 m/s2 rms
0-6 in/s pk 0-6 in/s rms
0-20 m/s2 pk 0-50 m/s2 rms
0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk 0-100 m/s2 rms
0-100 mm/s pk 0-100 mm/s rms
0-100 m/s2 pk 0-200 m/s2 rms
0-150 mm/s pk 0-150 mm/s rms
0-200 m/s2 pk 0-250 m/s2 rms
Custom Custom
0-250 m/s2 pk 0-400 m/s2 rms

0-400 m/s2 pk 0-500 m/s2rms

0-500 m/s2 pk Custom

12
2.  Acceleration 2 Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-700 m/s2

Custom

Table 2-8: 155023-01 High Frequency Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-20 g rms

0-25 g rms

0-40 g rms

0-50 g rms 0-4 in/s rms


N/A 0-200 m/s2 rms N/A 0-100 mm/s rms
0-250 m/s2 rms Custom

0-400 m/s2 rms

0-500 m/s2 rms

Custom

Table 2-9: 33040 High Temperature


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk

0-5 g pk

0-10 g pk

0-20 g pk 0-2 g rms

0-25 g pk 0-5 g rms 0-1 in/s pk 0-1 in/s rms

0-40 g pk 0-10 g rms 0-2 in/s pk 0-2 in/s rms

0-45 g pk 0-20 g rms 0-4 in/s pk 0-4 in/s rms

0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms

0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms

0-100 m/s2 pk 0-100 m/s2 rms 0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk Custom Custom
0-200 m/s2 pk

0-250 m/s2 pk Custom

0-400 m/s2 pk

0-450 m/s2pk
Custom

Note
Whenever you modify a full-scale range, you should readjust the setpoints that are associated with this static
value.

13
Acceleration Measurement

2.2.1.9 Clamp Value


The value sent to the recorders and Modbus when the monitor receives invalid input. Invalid input
can be caused by:
l Channel Not OK status
l Monitor Not Ok status
The clamp value is not shown on the monitor display or in the 3500 Rack Configuration software.
l 3500 Systems:
The monitor clamps only the Recorder Outputs and the values provided through the Com-
munication Gateway and Display Interface Module when the static value is invalid.
l 3500 ENCORE Systems:
The monitor clamps only the Recorder Outputs and the values provided over Modbus
when the static value is invalid.
2.2.1.10 RMS
When you select RMS, the monitor will measure all of the direct, 1X amplitude, and 2X amplitude
values for the channel as RMS.
2.2.1.11 Integrate
Integration applies to all values, except bias voltage and phase,which the monitor returns. When
you select integration, the available Full-scale ranges will change to reflect this. This will also limit
the frequency support to 20kHz.

2.2.2 Delay
Delay is the time for which a static value must remain at or above an over alarm level, or below an
under alarm level, before the monitor declares an alarm as active.
2.2.2.1 Alert Delay
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all available
static values. Alert is the first level alarm that occurs when the transducer signal level exceeds the
selected Alert/Alarm 1 setpoint. You can set this setpoint on the Setpoint screen.
2.2.2.2 Danger Delay
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds. Danger is
the second level alarm that occurs when the transducer signal level exceeds the selected
Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
2.2.2.3 100 ms Option
The 100 ms (typical) option applies only to the Danger time delay and has the following effects:

14
2.  Acceleration 2 Configuration

If the 100 ms option is OFF:


l You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
l You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
l The software sets the Danger time delay to 100 ms.
l You can set the Danger time delay for only the primary static value.

2.2.3 Alarm Mode


The options for Alarm Mode are Latching and Non-latching. You can set the Alarm Mode option
for both the Alert and Danger alarms.
2.2.3.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops below the
configured setpoint level. The channel will remain in alarm until you use one of the following meth-
ods to reset it:
l Pressing the RESET button on the System Monitor
l Closing the contact on the Power Input Module (PIM)
l Clicking the Reset button in the Operator Display software1
l Issuing a reset command over Modbus
l Issuing the rest command through the Communication Gateway or Display Interface Mod-
ule1
l Issuing a reset command in the 3500 Rack Configuration Software
1 3500 Systems Only

2.2.3.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value drops
below the configured setpoint level.
2.2.3.3 Timed OK Channel Defeat
Timed OK Channel Defeat is an option that prevents a channel from returning to an OK status
until that channel's transducer has remained in an OK state for the specified period of time. If you
enable the option, the software sets the time to 30 seconds. This option prevents false trips that
intermittent transducers can cause.

Alert
A sudden mechanical impact can over-range velocity, acceleration, or Velomitor* sensors. If you enable Timed OK

15
Acceleration Measurement

Alert
Channel Defeat on the monitor and the over-range signal exceeds the OK limits, the monitor may not annunciate
an alarm. This may result in a missed alarm and temporary loss of machine protection. You can disable Timed OK
Channel Defeat on velocity and acceleration channel types.

2.2.3.4 Monitor Danger Relay Voting


This option allows you to add logic processing to channel alarming.
l OR - if either channel of a channel pair is in danger alarm, the danger alarm relay is acti-
vated.
l AND - if both channels of a channel pair are in danger alarm, the danger alarm relay is acti-
vated.
Relay Voting is available when the Dual Relay option is selected.

2.2.4 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK the status
will stay Not OK until you use one of the following methods to issue a reset:
l Pressing the reset switch on the front of the System Module
l Closing the contact on the Power Input Module (PIM)
l Issuing the reset command over Modbus
l Issuing the reset command through the 3500 Display Interface Module
l Issuing the reset command in the 3500 Rack Configuration Software
Non-latching

If you configure a channel for Non-latching OK, the OK status of that channel will track the
defined OK status of the transducer.

2.2.5 Trip Multiply


The Trip Multiply value temporarily increases the alarm (Alert and Danger) setpoint values. Manual
(operator) action normally applies this value during startup to allow a machine to pass through
high vibration speed ranges without triggering monitor alarm indications. High vibration speed
ranges may include system resonances and other normal transient vibrations. The multiplier is
configurable from 1X to 3X in 0.25X increments. The Trip Multiply state of the rack can be toggled
by the following methods:
l Closing the Trip Multiply contact on the System Monitor or Power Input Module (3500
ENCORE Systems)

16
2.  Acceleration 2 Configuration

l Issuing the Trip Multiply command over an industrial protocol (example: Modbus)
l Issuing the Trip Multiply command in the 3500 Rack Configuration Software

2.2.6 Recorder Output


Use the list to select the static value of the channel that the monitor sends to the 4 to 20 mA
recorder. The current at the recorder output is proportional to the measured value over the chan-
nel full-scale range. An increase in the static value increases the current at the recorder output.
If you select Phase Lag then the 2 available options are "with Hysteresis" and "without Hysteresis"
.
The Hysteresis option helps prevent the Recorder Output from jumping from Full to Bottom Scale
when the phase measurement is near 0 or 359 degrees. When you check the Hysteresis option,
the recorder signal operates as follows:
l The monitor scales the recorder output so that 4 mA corresponds to 0 degrees and 20 mA
corresponds to 380 degrees (360 plus 20 degrees).
l An increasing phase measurement does not transition until the measurement has gone 20
degrees past 360 degrees. At this point, the recorder signal switches from 20 mA to a signal
that corresponds to 20 degrees, or 4.842 mA.
l A decreasing phase measurement transitions at 0 degrees (4 mA). At this point, the recorder
signal switches from 4 mA to a signal that corresponds to 360 degrees, or 19.158 mA.
2.2.6.1 Two mA Clamp
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed channel
to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a Bypassed chan-
nel.

2.3 Alarm Setpoints


This section specifies the available setpoints for each type of channel. A setpoint is the level
within the full-scale range that determines when an alarm occurs. You can set Alert/Alarm 1 set-
points for every static value on each channel. The channel will drive an Alert/Alarm 1 indication if
1 or more of the channel static values exceed their setpoints. You can set up to 4 Danger/Alarm 2
setpoints (2 over setpoints and 2 under setpoints) for up to 2 of the static values. You may select
any 2 of the available static values for the channel.

Note
You can place the setpoint Over and Under limits only within the OK limits of the specified transducer.

17
Acceleration Measurement

2.3.1 Alarm Setpoint Dialog


Use the Setpoint Configuration Screen in the 3500 Rack Configuration Software, shown in Figure
"Acceleration 2 Septoint Configuration", to adjust Alert/Alarm 1 and Danger/Alarm 2 setpoints for
a channel.

Figure 2 - 4: Acceleration 2 Setpoint Configuration

2.3.2 Available Setpoints


The table below lists the Alert/Alarm 1 and Danger/Alarm 2 setpoints that are available for the
Acceleration 2 channel type. Modbus uses the setpoint number. Bias Voltage is not available as
an alarming parameter.
Table 2-10: Acceleration 2 Available Setpoints
Setpoint Number Acceleration 2
1 Over Direct
2 Over 1X Ampl
3 Under 1X Ampl
4 Over 1X Phase Lag
5 Under 1X Phase Lag
6 Over 2X Ampl
7 Under 2X Ampl

18
2.  Acceleration 2 Configuration

Setpoint Number Acceleration 2


8 Over 2X Phase Lag
9 Under 2X Phase Lag
10 Danger (configurable)
11 Danger (configurable)
12 Danger (configurable)
13 Danger (configurable)

Advisory
The older Acceleration channel type had only 2 setpoints. Setpoint Number 2 was the Danger setpoint. The equiv-
alent Acceleration 2 setpoint is now Setpoint Number 10.

2.3.3 Alarm Hysteresis


The alarming hysteresis for all channel configurations is 1/64th of full scale. When a channel
exceeds an alarm setpoint, it must fall back below the setpoint less the amount of hysteresis
before it can go out of alarm.
Example:
Consider a channel configuration with a 0 - 10 mils full-scale range and an alarm setpoint at 6
mils. Full scale is 10 mils - 0 mils = 10 mils, so the hysteresis = 10 mils/64 = 0.16 mils. The channel
input, therefore, must fall below 6 mils - 0.16 mils = 5.84 mils before the channel is out of alarm.

2.4 General Parameters and Buttons


Note
Please refer to the 3500 Rack Configuration Software Online Help for more information on these items.

2.4.1 Set Defaults Button


Returns all settings on the current configuration screen and on the screens at levels below the
current screen to the default settings.

Note
Clicking on Set Defaults returns the settings on all screens at levels below the current screen to their default set-
tings even if the changes at lower levels were confirmed by clicking on the OK button at the lower level screen.

2.4.2 CP Mod
Selecting the CP Mod button in the Channel Options Dialog Box allows you to download a Cus-
tom channel configuration to the monitor. The 3500 Rack Configuration Software stores custom
configuration data in a Custom Products Modification File. Custom Products Modification files fol-
low the naming convention: <modification #.mod>. You must place these files in the

19
Acceleration Measurement

\3500\Rackcfg\Mods\ directory. When you select a CP Mod file, the software displays a window
that describes the function of the modification. CP Mod files are available through Bently Nevada,
Inc.'s Custom Products Division. Contact your local sales representative for details.

2.4.3 Print Form Button


Click this button to send a copy of the current configuration screen to the printer.

2.4.4 Point Names Button


Click this button to assign a custom name to a channel of data. Custom names allow an operator
easily to identify which machine point is being examined. Default names are displayed as
RxxSxxCxx to denote the rack, slot, and channel source of the data.

2.5 Configuration Considerations


Consider the following items before configuring an Acceleration 2 Channel:
l When you select "No Keyphasor" , you cannot select the 1X Amplitude (Ampl) and Phase
Lag or 2X Amplitude (Ampl) and Phase Lag.
l If you select a Keyphasor channel, a Keyphasor must be configured and enabled in the sys-
tem.
l You can enable the 1X and 2X Phase values and alarms only if you configure the selected
Keyphasor channel for an events per revolution value equal to 1.
l The full-scale options that each static value allows depend on the transducer type.
l You must configure monitors in channel pairs (for example, you may configure Channels 1
and 2 as Acceleration and Channels 3 and 4 as Radial Vibration).
l When you select integration, the software will change the available Full-scale ranges to
reflect this. This will also limit the frequency support to 20 kHz.
l When you select integration, the software will set the high-pass filter to 10 Hz, if it is not
already set to a higher frequency, and the vector parameters will be inactive below 10 Hz.
l When you select band-pass filtering, you must set the high-pass and low-pass filters at
least 2 octaves apart.
l When you select RMS, all of the static values for the channel will be in RMS units.
l When you select the Acceleration Dual Path channel type, the monitor uses transducer 1
for channels 1 and 2 and transducer 3 for channels 3 and 4.
l When you use Dual Path you must configure both channels for the same transducer type.
l High frequency accelerometer transducers do not support Internal Barrier I/O Modules and

20
2.  Acceleration 2 Configuration

External Barriers.
l You can install only 18 high-frequency accelerometer transducers in a full rack of standard
transducers. This is because the rack can power only 18 high-frequency Accelerometer
transducers.
l When you modify a full-scale value, readjust the setpoints that are associated with the
static value.

21
Acceleration Measurement

22
3.  Acceleration Verification

3. Acceleration Verification
The following sections will describe how to test alarms, verify channels, verify filter corner frequen-
cies, and test OK limits for Acceleration and Acceleration 2 channels. You verify the output values
and alarm setpoints by varying the input signal level and verifying that the Verification screen
reports the correct results on the test computer. You can configure Acceleration channels for the
channel values and alarms shown in the table.
Table 3-1: Acceleration Channel Values and Alarms
Channel Values Over Alarms Under Alarms
Direct X
1X Amplitude X X
2x Amplitude X X

3.1 Test Equipment and Software Setup


You can use the following test equipment and software setup as the initial set up that all the ver-
ification procedures require.

3.1.1 Test Equipment Setup


Connect the power supply, function generator, Keyphasor multiplier/divider, and multimeter to
COM and SIG of channel 1 with polarity as shown in Figure "Test Equipment Setup" to simulate the
transducer signal. The test equipment outputs should be floating relative to earth ground.
Set the test equipment as shown in Table "Test Equipment Settings".
Table 3-2: Test Equipment Settings
Power Supply Function Generator Keyphasor Multiplier/Divider
-7.00 Vdc Waveform: Sine wave Multiply Switch: 001

DC Volts: 0 Vdc Divide Switch: 001

Frequency: 100 Hz

Amplitude level: Minimum (above zero)

23
Acceleration Measurement

1. Keyphasor Signal
2. Keyphasor I/O Module
3. 40 k resistor
4. 100 µF capacitor
5. Keyphasor multiplier/divider
6. Simulated input signal
7. Typical I/O module
8. Function Generator
9. Multimeter
10. Power supply

Figure 3 - 1: Test Equipment Setup

3.1.2 Verification Screen Setup


1. Run the 3500 Rack Configuration Software on the test computer.
2. Choose Verification from the Utilities menu.

24
3.  Acceleration Verification

3. Choose the proper Slot number and Channel number.


4. Click the Verify button.

3.2 Test Alarms


The general test procedure for alarm setpoints is to use a function generator to simulate the vibra-
tion and Keyphasor signal.
You test the alarm levels by varying the output from the test equipment and verifying that the Ver-
ification screen reports the correct results on the test computer. You need test only those alarm
parameters that are configured and being used. The general test procedure to verify current
alarm operation will include simulating a transducer input signal and varying this signal:
l to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints
l to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints
l to produce a non-alarm condition
When varying the signal from an alarm condition to a non-alarm condition, you must consider
alarm hysteresis. Adjust the signal well below the alarm setpoint to clear the alarm.

3.2.1 Direct
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, “Test
Equipment and Software Setup."

Note
You will not require items 1 through 5 in the Figure "Test Equipment Setup" to test Direct Alarms.

3. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
4. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
5. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the
bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
6. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
7. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint

25
Acceleration Measurement

level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
8. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
9. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
10. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
11. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
12. Repeat steps 1 through 11 for all configured channels.

3.2.2 1X Amplitude (1X Amp)

Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.

1. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.

2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the

26
3.  Acceleration Verification

bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint
level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator phase to be below the Under Alarm setpoint lev-
els.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.

3.2.3 1X Phase
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
Note
If you cannot change the phase output, change the phase alarm setpoints to activate the over and under
phase alarms. You must download the setpoints to the monitor for them to take effect.

3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the phase reading within the setpoint levels on the bar graph display of the

27
Acceleration Measurement

Verification screen.

Note
The Amplitude must be a minimum of 42.7 mV to produce a valid Phase reading.

5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the phase reading to just exceed the Over Alert/Alarm 1 setpoint level and wait for 2
or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from green to yellow and that the Current Value Field indicates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the phase reading to just exceed the Over Danger/Alarm 2 setpoint level and wait for
2 or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from yellow to red and that the Current Value Field indicates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the phase reading below the Over Alarm setpoint levels. If the non-latching option is
configured, verify that the color of the bar graph indicator changes to green and that the
Current Value Box contains no indication of alarms. Press the Reset switch to reset latching
alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator phase to be below the Under Alarm setpoint lev-
els.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.

3.2.4 2X Amplitude (2X Amp)

Note
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.

28
3.  Acceleration Verification

1. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
2. Connect the test equipment and run the software as described in the section, “Test
Equipment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Adjust the function generator amplitude within the setpoint levels on the bar graph display
of the Verification screen.
5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the function generator amplitude to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of the
bar graph indicator changes from green to yellow and that the Current Value Field indi-
cates an alarm.
7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the function generator amplitude to just exceed the Over Danger/Alarm 2 setpoint
level and wait for 2 to 3 seconds after the alarm time delay expires. Verify that the color of
the bar graph indicator changes from yellow to red and that the Current Value Field indi-
cates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the function generator amplitude below the Over Alarm setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator changes to
green and that the Current Value Box contains no indication of alarms. Press the Reset
switch to reset latching alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2 set-
points by adjusting the function generator amplitude to be below the Under Alarm setpoint
levels.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK

29
Acceleration Measurement

relay energizes. Press the RESET switch to reset the OK LED.


14. Repeat steps 1 through 13 for all configured channels.

3.2.5 2X Phase
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."

Note
If you cannot change the phase output, change the phase alarm setpoints to activate the over and under
phase alarms. You must download the setpoints to the monitor for them to take effect.

3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Adjust the phase reading within the setpoint levels on the bar graph display of the Ver-
ification screen.

Note
The Amplitude must be a minimum of 42.7 mV to produce a valid Phase reading.

5. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.
6. Adjust the phase reading to just exceed the Over Alert/Alarm 1 setpoint level and wait for 2
or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from green to yellow and that the Current Value Field indicates an alarm.

7. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.
8. Adjust the phase reading to just exceed the Over Danger/Alarm 2 setpoint level and wait for
2 or 3 seconds after the alarm time delay expires. Verify that the color of the bar graph indi-
cator changes from yellow to red and that the Current Value Field indicates an alarm.
9. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.
10. Adjust the phase reading below the Over Alarm setpoint levels. If the non-latching option is
configured, verify that the color of the bar graph indicator changes to green and that the
Current Value Box contains no indication of alarms. Press the Reset switch to reset latching
alarms.
11. Repeat steps 3 through 10 to test the Under Alert/Alarm 1 and Under Danger/Alarm 2

30
3.  Acceleration Verification

setpoints by adjusting the function generator phase to be below the Under Alarm setpoint
levels.
12. If you cannot verify any configured alarm, check the configured setpoints again. If the mon-
itor still does not alarm properly or fails any other part of this test, you must replace the mon-
itor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.
13. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
14. Repeat steps 1 through 13 for all configured channels.

3.3 Verify Channel Values


The general test procedure for channel values is to use a function generator to simulate the vibra-
tion and Keyphasor input signal. You verify the output values by varying the input vibration sig-
nal level (both peak-to-peak amplitude and dc voltage bias) and verifying that the Verification
screen reports the correct results on the test computer.

Note
These parameters have an accuracy specification of ±1% of full scale for amplitude and 3º for phase.

3.3.1 Direct
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."

3. Use the equation and examples shown below to calculate the full-scale voltage. Adjust the
amplitude of the function generator to the calculated voltage.

Advisory
Use the Transducer Scale Factor displayed in the Scale Factor Box on the Verification Screen.

Full Scale Voltage = Direct Meter Top Scale— Transducer Scale Factor
Example 1

Direct Meter Top Scale = 10 mil


Transducer Scale Factor = 200 mV/mil = 0.200 V/mil
Full Scale = (10 mils— 0.200 V/mil)
= 2.000 Vpk-pk

31
Acceleration Measurement

Vrms = (0.707/2)— (Vpk-pk), for a sine wave input


= (0.707/2)— (2.000 Vpk-pk)
= 0.707 Vrms

Example 2

Direct Meter Top Scale = 200 µm


Transducer Scale Factor = 7.874 V/mm
= 0.007874 V/µm
Full Scale = (200 µm— 0.007874 V/µm)
= 1.5748 Vpk-pk

Vrms = (0.707/2)— (Vpk-pk), for a sine wave input


= (0.707/2)— (1.574 Vpk-pk)
= 0.5566 Vrms

4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
5. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section "If a Channel Fails a Verification Test" in your hardware manual.
6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.

3.3.2 1X Amplitude (1X Ampl)

Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.

1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Use the procedure in "Calculating the Input Voltage for Full Scale" to calculate the full-scale
voltage. Adjust the function generator (sine wave) amplitude to the calculated value.
4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting

32
3.  Acceleration Verification

is 001.
5. Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
6. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section"If a Channel Fails a Verification Test" in your hardware manual.
7. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
8. Repeat steps 1 through 7 for all configured channels.

3.3.3 1X Phase
If your test equipment cannot change the phase output to a known value, use the procedure in
"If Your Test Equipment Cannot Change the 1X Phase Output". If your test equipment can change
the phase output to a known value, use the procedure in "If Your Test Equipment Can Change the
1X Phase Output".
3.3.3.1 If Your Test Equipment Cannot Change the 1X Phase Output
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Attach one channel of the 2-channel oscilloscope to the vibration signal buffered output
and attach the other channel to the associated Keyphasor signal buffered output to
observe both signals simultaneously.
5. Measure the phase. Measure 1X Phase from the leading edge of the Keyphasor pulse to the
first positive peak of the vibration signal. Refer to the figure, which illustrates a phase of 45°.
Verify that the 1X Phase bar graph display and Current Value Box readings are approx-
imately what you measured. If integration is enabled, then add 90 degrees to the measured
value to obtain the correct reading from the monitor.

33
Acceleration Measurement

1. 1X vibration signal
2. Keyphasor signal
3. Time
4. 0°
5. One Cycle
6. 360°
7. Phase lag = 45°

Figure 3 - 2: 1X Phase Measurement Example for 45° Phase Lag


6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.
3.3.3.2 If Your Test Equipment Can Change the 1X Phase Output

If your test equipment can change the phase output to a known value, use the following pro-
cedure.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 001.
4. Adjust the phase reading for mid-scale. Verify that the bar graph display and Current Value
Box readings are within 1.5% of mid-scale.
5. If the readings do not meet specifications, verify that the input signal is correct. If the

34
3.  Acceleration Verification

monitor still does not meet specifications or fails any other part of this test, you must
replace the monitor. See the section "If a Channel Fails a Verification Test†in your hard-
ware manual.
6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.

3.3.4 2X Amplitude (2X Ampl)

Advisory
The Keyphasor signal must be triggering and have a valid rpm value for you to check this parameter.

1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, “Test Equip-
ment and Software Setup."
3. Use the formulas in “Calculating the Input Voltage for Full Scale” to calculate the full-scale
voltage value. Adjust the function generator (sine wave) amplitude to the calculated value.
4. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
5. Verify that the bar graph display and Current Value Box readings are within ±1% of full
scale.
6. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section “If a Channel Fails a Verification Test” in your hardware manual.

7. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
8. Repeat steps 1 through 7 for all configured channels.

3.3.5 2X Phase
If your test equipment cannot change the 2X phase output to a known value, use the procedure
in "If Your Test Equipment Cannot Change the 2X Phase Output." If your test equipment can
change the phase output to a known value, use the procedure in "If Your Test Equipment Can
Change the 2X Phase Output."

35
Acceleration Measurement

3.3.5.1 If Your Test Equipment Cannot Change the 2X Phase Output


1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Attach one channel of the 2-channel oscilloscope to the vibration signal buffered output
and attach the other channel to the associated Keyphasor signal buffered output to
observe both signals simultaneously.
5. Measure the phase. Measure 2X Phase from the leading edge of the Keyphasor pulse to the
first positive peak of the vibration signal. Refer to the Figure below which illustrates a phase
of 90°. Verify that the 2X Phase bar graph display and Current Value Box read approx-
imately what you measured. Note that 2X indicates 2 cycles of vibration signal per shaft rev-
olution.

1. 0°
2. First Cycle
3. One shaft revolution
4. Second cycle
5. 2X Vibration Signa
6. Phase lag = 90°
7. Keyphasor signal
8. 360°
9. Time

Figure 3 - 3: 2X Phase Measurement Example for 90º Phase Lag


6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK

36
3.  Acceleration Verification

relay energizes. Press the RESET switch to reset the OK LED.


7. Repeat steps 1 through 6 for all configured channels.
3.3.5.2 If Your Test Equipment Can Change the 2X Phase Output
If your test equipment can change the phase output to a known value, use the following pro-
cedure.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, "Test Equip-
ment and Software Setup."
3. Set the Keyphasor multiplier/divider so that the multiply setting is 001 and the divide setting
is 002.
4. Adjust the phase reading for mid-scale. Verify that the bar graph display and Current Value
Box readings are within ±1.5% of mid-scale.
5. If the readings do not meet specifications, verify that the input signal is correct. If the mon-
itor still does not meet specifications or fails any other part of this test, you must replace the
monitor. See the section "If a Channel Fails a Verification Test" in your hardware manual.
6. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
7. Repeat steps 1 through 6 for all configured channels.

3.3.6 Calculating Verification Frequency


Table "Verification Frequencies" summarizes how to determine the verification frequency based
on the configured low-pass filter and high-pass filter corner frequencies.
Table 3-3: Verification Frequencies
Low-Pass Filter Corner High Pass Filter Corner
Verification Frequency (Hz)
Frequency (LPF) Frequency (HPF)
Unconfigured Unconfigured 100

Unconfigured Configured

If units are RMS:

Configured Unconfigured
Any other configuration:

Configured Configured

37
Acceleration Measurement

3.3.7 Calculating the Input Voltage for Full Scale


To verify channel values and corner frequencies you must use the following formulas to cal-
culate the input voltage for Full-scale.

Advisory
Use the Transducer Scale Factor displayed in the Scale Factor Box on the Verification Screen.

3.3.7.1 Full Scale Formulas With Integration


l To input rms volts for peak full scale units:
Input Voltage (Vrms) = (FS * SF * VF * 0.3535)/30.72
l To input peak-to-peak volts for peak full scale units:
l Input Voltage (Vrms) = (FS * SF * VF)/30.72
l To input rms volts for rms full scale units:
Input Voltage (Vpk-pk) = (FS * SF * VF * 0.5)/30.72
l To input peak-to-peak volts for RMS full scale units:
Input Voltage (Vpk-pk) = (FS * SF * VF * 1.414)/30.72
l where
FS = the full scale value in g or m/s2
SF = the Velocity scale factor in V/g or V/(m/s2)
VF = the calculated value from "Calculating Verification Frequency."

Use the following conversion formulas to convert Metric units to English Units:
l SF(V/g) = SF in V/(m/s2) * 9.8135 (m/s2/g)
l FS (mm/s) = (FS in in/s) / 2.54 mm/in
Example:
Calculate the input voltage for a channel with the following configuration:

Transducer Scale Factor = 10.19 mV/ms2


Full Scale = 25 mm/s2 pk
HPF = 10 Hz
LPF = 8000 Hz

38
3.  Acceleration Verification

1. Convert Metric units to English units.

Scale Factor = 10.19mV/(m/s2) x 9.8135 (m/s2)/g


= 100 mV/g
Full-scale = (25 mm/s2) / 2.54 mm/in
= 1.0 in/s

2. Calculate the input voltage.

Verification Frequency =
= 283 Hz

Input Voltage (Vrms) = (1.0 in/s * 0.1 V/g * 283 Hz * 0.3535) / 30.72
= 0.326 Vrms
Input Voltage (Vpk-pk) = (1.0 in/s * 0.1 V/g * 283 Hz) / 30.72
= 0.921Vpk-pk

3.3.7.2 Full Scale Equations Without Integration


Table 3-4: Full Scale Formulas - No Integration
Units To Input RMS Volts To Input Peak to Peak Volts
g pk (TSF x Full-scale) x 0.707 (TSF x Full-scale) x 2
g rms (TSF x Full-scale) (TSF x Full-scale) x 2 .82
m/s2 pk (TSF x Full-scale) X 7.07 (TSF x Full-scale) x 2
m/s2 rms (TSF x Full-scale) (TSF x Full-scale) x 2.82

TSF = Transducer Scale Factor


The formulas require that the TSF is in volts and the TSF and Full-Scale values are both of the
same unit system (metric or English).

The transducer Scale Factor is always specified as volts per g pk or volts per m/ss pk.
Example 1:

Transducer Scale Factor = 100 mV g


Full Scale = 2 g pk
Peak-to-Peak input = (0.100 V g * 2) * 2
= 0.4V pp
Vrms input = (0.100 V * 2) * 0.707
= 0.1414 Vrms

Example 2:

Transducer Scale Factor = 10.19 mV/(m/s2)


Full Scale = 20 m/s2 pk
Peak to Peak input = (0.01019 V/(m/s2 ) * 20) * 2

39
Acceleration Measurement
= 0.4076 Vpp
Vrms input = (0.01019 V/(m/s2 ) * 20 ) × 0.707
= 0.1440 V rms

3.4 Test OK Limits


The general approach for testing OK limits is for you to input a dc voltage and adjust the voltage
above the Upper OK Limit and below the Lower OK Limit. This will produce a channel Not OK con-
dition and cause the OK Relay to change state (de-energize). The test computer displays the
Upper OK Limit and Lower OK Limits on the Verification screen.
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the I/O mod-
ule.
2. Connect the test equipment and run the software as described in the section, “Test Equip-
ment and Software Setup."
3. Bypass all other configured channels.
4. Adjust the power supply voltage to -7.00 Vdc.
5. Press the RESET switch. Verify that the monitor OK LED is on and that the Channel OK State
line in the Channel Status section of the Verification screen reads OK.

Note
If the Danger Bypass is active, then the BYPASS LED will be on. All other channels in the rack must be OK or
bypassed for the OK relay to energize.

6. Verify that the OK relay on the System Monitor indicates OK (is energized). (See the appro-
priate System Monitor manual for more information.)
7. Increase the power supply voltage (more negative) until the OK LED just goes off (upper
limit). Verify that the Channel OK State line on the Verification screen reads Not OK and that
the OK Relay indicates Not OK. Verify that Verification screen displays an Upper OK Limit
voltage that is equal to or more positive than the input voltage.
8. Adjust the power supply voltage to -7.00 Vdc.
9. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay ener-
gizes. Verify that the Channel OK State line in the Channel Status section reads OK.
10. Gradually decrease the power supply voltage (less negative) until the OK LED just goes off
(lower limit). Verify that the Channel OK State line in the Channel Status section reads Not OK
and that the OK Relay indicates Not OK. Verify that the Verification screen displays a Lower
OK Limit voltage that is equal to or more negative than the input voltage.
11. Adjust the power supply voltage to -7.00 Vdc.
12. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay

40
3.  Acceleration Verification

energizes. Verify that the Channel OK State line in the Channel Status section reads OK.
13. If you cannot verify any configured OK limit, you must replace the monitor. Refer to “If a
Channel Fails a Verification Test” in your monitor hardware manual.
14. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and SIG
channel terminals on the I/O module. Verify that the OK LED comes on and that the OK
relay energizes. Press the RESET switch to reset the OK LED.
15. Repeat steps 1 through 14 for all configured channels.
16. Return the bypass switches for all configured channels back to their original settings.

3.4.1 Acceleration OK Limits


Table 3-5: Acceleration Default OK Limits (Assume ±50 mV accuracy for check tolerance)
Transducer Type Lower OK Limit (V) Upper OK Limit (V)
23733-03 without barriers -2.7 to -2.8 -15.0 to "“15.1
-3.05 to -3.15 -13.8 to -13.9
23733-03 with barriers
(-2.7 to -2.8) (-15.0 to -15.1)
49578-01 without barriers -5.58 to -5.68 -11.32 to -11.42
-5.29 to -5.39 -10.81 to -10.91
49578-01 with barriers
(-5.58 to - 5.68) (-11.32 to -11.42)
24145-02 without barriers -2.7 to -2.8 -15.0 to -15.1
155023-01 without barriers -5.58 to -5.68 -11.32 to "“11.42
-3.05 to -3.15 -13.8 to -13.9
330400 with barriers
(-2.7 to -2.8) (-15.0 to -15.10)
330400 without barriers -2.7 to -2.8 -15.0 to -15.1
-5.29 to -5.39 -10.81 to -10.91
330425 with barriers
(-5.58 to -5.68) (-11.32 to -11.42)
330425 without barriers -5.58 to - 5.68 -11.32 to - 11.42
330540HT without barriers
330540HT with barriers

Note for table: Values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules

41
Acceleration Measurement

42
4.  Acceleration Configuration

4. Acceleration Configuration
This section is included as a reference for the obsolete Acceleration sensors.

4.1 Configuration Options


This section describes the options available on the Acceleration Channel configuration screen
shown figure below.

Figure 4 - 1: Acceleration Channel Configuration

4.1.1 Direct
Direct data represents the overall peak-to-peak vibration. This static value includes all frequen-
cies within the selected Direct Frequency Response.
4.1.1.1 Full-Scale Range
This section details the available full-scale ranges for the different acceleration types.

43
Acceleration Measurement
Table 4-1: 23733-03 Standard Acceleration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk

0-5 g pk

0-10 g pk
0-2 g rms
0-20 g pk
0-5 g rms 0-1 in/s pk
0-25 g pk
0-10 g rms 0-2 in/s pk 0-1 in/s rms
0-40 g pk
0-20 g rms 0-4 in/s pk 0-2 in/s rms
0-45 g pk
0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms
0-20 m/s2 pk
0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-50 m/s2 pk Custom
0-100 m/s2 rms 0-100 mm/s pk
0-100 m/s2 pk Custom
0-200 m/s2 rms
0-200 m/s2 pk
Custom
0-250 m/s2 pk

0-400 m/s2 pk
Custom

Table 4-2: 24145-02 High Frequency Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk

0-5 g pk 0-2 g rms 0-1 in/s pk

0-10 g pk 0-5 g rms 0-2 in/s pk 0-1 in/s rms

0-20 g pk 0-10 g rms 0-4 in/s pk 0-2 in/s rms

0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms

0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 rms Custom
0-100 m/s2 pk 0-100 mm/s pk
Custom Custom
0-200 m/s2 pk
Custom

Table 4-3: 33040 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk 0-0.5 g rms 0-1 in/s pk
0-1 in/s rms
0-5 g pk 0-1g rms 0-2 in/s pk
0-2 in/s rms
0-10 g pk 0- 2 g rms 0-4 in/s pk
0-25 mm/s rms
0-20 g pk 0-5 g rms 0-25 mm/s pk
0-50 mm/s rms
0-45 g pk 0-10 g rms 0-50 mm/s pk
Custom
0-20 m/s2 pk 0-20 g rms 0-100 mm/s pk

44
4.  Acceleration Configuration
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0- 30 g rms

0-10 m/s2 rms


0-50 m/s2 pk
0 -20 m/s2 rms
0-100 m/s2 pk
0-50 m/s2 rms
0-200 m/s2 pk Custom
0-100 m/s2 rms
0-400 m/s2pk
0-200 m/s2 rms
Custom
0-300 m/s2 rms

Custom

Table 4-4: 49578-01 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS

0-20 g pk 0-20 g rms

0-25 g pk 0-25 g rms

0-40 g pk 0-40 g rms

0-50 g pk 0-50 g rms


0-2 in/s pk 0-2 in/s rms
0-20 m/s2 pk 0-20 m/s2 rms
0-4 in/s pk 0-4 in/s rms
0-50 m/s2 pk 0-50 m/s2 rms
0-50 mm/s pk 0-50 mm/s rms
0-100 m/s2 pk 0-100 m/s2 rms
0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk 0-200 m/s2 rms
Custom Custom
0-250 m/s2 pk 0-250 m/s2 rms

0-400 m/s2 pk 0-400 m/s2 rms

0-500 m/s2 pk 0-500 m/s2 rms


Custom Custom

Table 4-5: 330425 Standard Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-20 g pk 0-20 g rms

0-25 g pk 0-25 g rms 0-2 in/s pk 0-2 in/s rms


0-40 g pk 0-40 g rms 0-4 in/s pk 0-4 in/s rms
0-50 g pk 0-50 g rms 0-6 in/s pk 0-6 in/s rms
0-75 g pk 0-20 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms
0-20 m/s2 pk 0-50 m/s2 rms 0-100 mm/s pk 0-100 mm/s rms
0-50 m/s2 pk 0-100 m/s2 rms 0-150 mm/s pk 0-150 mm/s rms
0-100 m/s2 pk 0-200 m/s2 rms Custom Custom

0-200 m/s2 pk 0-250 m/s2 rms

45
Acceleration Measurement
Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-250 m/s2 pk

0-400 m/s2 pk 0-400 m/s2 rms

0-500 m/s2 pk 0-500 m/s2rms

0-700 m/s2 Custom

Custom

Table 4-6: 155023-01 High Frequency Acceleration


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-20 g rms

0-25 g rms

0-40 g rms

0-50 g rms 0-4 in/s rms


N/A 0-200 m/s2 rms N/A 0-100 mm/s rms
0-250 m/s2 rms Custom

0-400 m/s2 rms

0-500 m/s2 rms

Custom

Table 4-7: 33040 High Temperature


Non-Integrated Peak Non-Integrated RMS Integrated Peak Integrated RMS
0-2 g pk

0-5 g pk

0-10 g pk

0-20 g pk 0-2 g rms

0-25 g pk 0-5 g rms 0-1 in/s pk 0-1 in/s rms

0-40 g pk 0-10 g rms 0-2 in/s pk 0-2 in/s rms

0-45 g pk 0-20 g rms 0-4 in/s pk 0-4 in/s rms

0-20 m/s2 pk 0-20 m/s2 rms 0-25 mm/s pk 0-25 mm/s rms

0-50 m/s2 pk 0-50 m/s2 rms 0-50 mm/s pk 0-50 mm/s rms

0-100 m/s2 pk 0-100 m/s2 rms 0-100 mm/s pk 0-100 mm/s rms
0-200 m/s2 pk Custom Custom
0-200 m/s2 pk

0-250 m/s2 pk Custom

0-400 m/s2 pk

0-450 m/s2pk
Custom

46
4.  Acceleration Configuration

Note
Whenever you modify a full-scale range, you should readjust the setpoints that are associated with this static
value.

4.1.1.2 Clamp Value


The value sent to the recorders and Modbus when the monitor receives invalid input. Invalid input
can be caused by:
l Channel Not OK status
l Monitor Not Ok status
The clamp value is not shown on the monitor display or in the 3500 Rack Configuration software.
l 3500 Systems:
The monitor clamps only the Recorder Outputs and the values provided through the Com-
munication Gateway and Display Interface Module when the static value is invalid.
l 3500 ENCORE Systems:
The monitor clamps only the Recorder Outputs and the values provided over Modbus
when the static value is invalid.
4.1.1.3 Recorder Output
The recorder output is the static value of a channel that the monitor sends to the 4 to 20 mA
recorder. The recorder output is proportional to the measured value over the channel full-scale
range. An increase of the static value increases the current at the recorder output.
Two mA Clamp

Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed channel
to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a Bypassed chan-
nel.

4.1.2 Trip Multiply


The Trip Multiply value temporarily increases the alarm (Alert and Danger) setpoint values. Manual
(operator) action normally applies this value during startup to allow a machine to pass through
high vibration speed ranges without triggering monitor alarm indications. High vibration speed
ranges may include system resonances and other normal transient vibrations. The multiplier is
configurable from 1X to 3X in 0.25X increments. The Trip Multiply state of the rack can be toggled
by the following methods:

47
Acceleration Measurement

l Closing the Trip Multiply contact on the System Monitor or Power Input Module (3500
ENCORE Systems)
l Issuing the Trip Multiply command over an industrial protocol (example: Modbus)
l Issuing the Trip Multiply command in the 3500 Rack Configuration Software

4.1.3 Type
The following transducer types are available for the Acceleration Channel with a non-barrier I/O
module.
l 23733-03 Standard Acceleration
l 24145-02 High Frequency Acceleration
l 330400 Standard Integral Acceleration
l 330425 Standard Integral Acceleration
l 49578-01 Standard Acceleration
l 155023-01 High Frequency Acceleration
l 3300450 HT Integral Acceleration
l Non-standard
The following transducer types are available for the Acceleration Channel with a barrier I/O mod-
ule.
l 23733-03 Standard Acceleration
l 330400 Standard Integral Acceleration
l 330425 Standard Integral Acceleration

l 49578-01 Standard Acceleration


l 3300450 HT Integral Acceleration
l Non-standard

4.1.4 Customize Button


You use this button to adjust the Scale Factor for transducers. Refer to the "Adjusting the Scale
Factor and Zero Position" section of your hardware manual. Also, note that:
l If you select Non-standard as the transducer type, you can also adjust the OK Limits.
l The Non-standard transducer's scale factor must be between 5 and 115 mV/g.
l The Upper and Lower OK Limits must differ by at least 2 volts.

48
4.  Acceleration Configuration

l If you select a Non-standard transducer, the software sets the setpoint OK limits to±1 volt
from the Upper and Lower OK Limits that are selected.

Figure 4 - 2: Customize Dialog


Table 4-8: Scale Factor by Transducer Type (+/-15% scale factor adjustment allowed)
Without With Bently Nevada Standard I/O Discrete TMR I/O Bussed TMR I/O
Transducer Barriers Internal Barriers Barriers with Barriers with Barriers
Type
(mV/g) (mV/g)) (mV/g) (mV/g) (mV/g)
23733-03 100 96 95.6 100 99.4
24145-02 100 Not supported Not supported Not supported Not supported
330400 100 96 95.6 95.6 95.6
330425 25 24 23.9 23.9 23.9
49578-01 25 24 23.9 25 23.9
155023-01 25 Not supported Not supported Not supported Not supported
3300450
100 96 95.6 100 ?
HT

49
Acceleration Measurement

Table 4-9: OK Limits by Transducer Type


Upper OK Limits (V) Lower OK Limits (V) Center Bias Voltage (V)
Transducer
Type Without Bar- With Bar- Without Bar- With Bar- Without Bar- With Bar-
riers riers riers riers riers riers
-13.85 -3.10 -8.475
23733-03 -15.05 -2.75 -8.90
(-15.05) (-2.75) (-8.90)
Not Sup- Not Sup- Not Sup-
24145-02 -15.05 -2.75 -8.90
ported ported ported
-13.85 -3.10 -8.475
330400 -15.05 -2.75 -8.90
(-15.05) (-2.75) (-8.90)
-10.86 -5.34 -8.10
330425 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
-10.86 -5.34 -8.10
49578-01 -11.37 -5.63 -8.50
(-11.37) (-5.63) (-8.50)
Not Sup- Not Sup- Not Sup-
155023-01 -11.37 -5.63 -8.50
ported ported ported
3300450 HT -22.00 ? -1.00 ? -12.5 ?

Note: The values in parentheses are for Bently Nevada, Inc. Internal Barrier I/O Modules.

4.1.5 I/O Module Attached - Jumper Position


This option returns the position of the transducer jumper on the I/O Module in 3500 systems.

Note
In the 3500 ENCORE systems, the jumper is located on the monitor.

4.1.6 Take Input From Channel 1 (3) Transducer


This causes the even numbered channel to make its transducer input identical to the odd num-
bered channel that makes up the channel pair. This will also set items that a change in transducer
would affect, such as Barriers.

4.1.7 Corner Frequencies


If you do not select a filter, then the software will configure the corner frequencies as follows:
l If you disable integration, software will configure the monitor with a 3 Hz High-pass Filter
(HPF) and a 30 kHz Low-pass Filter (LPF).
l If you enable integration, software will configure the monitor with a 10 Hz HPF and a 20 kHz
LPF.

50
4.  Acceleration Configuration

4.1.8 High-Pass Filter


The High-pass Filter is a 4-pole filter that you must set at least 2 octaves away from the Low-pass
Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
HPF <= (LPF / 4)

4.1.9 Low-Pass Filter


The Low-pass Filter is a 4-pole filter that you must be set at least 2 octaves away from the High-
pass Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
LPF >= (HPF x 4)
When you select band-pass filtering, you must set the high-pass and low-pass filters at least 2
octaves apart.

4.1.10 Delay
Delay is the time for which a static value must remain at or above an over alarm level, or below an
under alarm level, before the monitor declares an alarm as active.
4.1.10.1 Alert Delay
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all available
static values. Alert is the first level alarm that occurs when the transducer signal level exceeds the
selected Alert/Alarm 1 setpoint. You can set this setpoint on the Setpoint screen.
4.1.10.2 Danger Delay
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds. Danger is
the second level alarm that occurs when the transducer signal level exceeds the selected
Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
4.1.10.3 100 ms Option
The 100 ms (typical) option applies only to the Danger time delay and has the following effects:
If the 100 ms option is OFF:
l You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
l You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
l The software sets the Danger time delay to 100 ms.
l You can set the Danger time delay for only the primary static value.

51
Acceleration Measurement

4.1.11 Alarm Mode


The options for Alarm Mode are Latching and Non-latching. You can set the Alarm Mode option
for both the Alert and Danger alarms.
4.1.11.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops below the
configured setpoint level. The channel will remain in alarm until you use one of the following meth-
ods to reset it:
l Pressing the RESET button on the System Monitor
l Closing the contact on the Power Input Module (PIM)
l Clicking the Reset button in the Operator Display software1
l Issuing a reset command over Modbus
l Issuing the rest command through the Communication Gateway or Display Interface Mod-
ule1
l Issuing a reset command in the 3500 Rack Configuration Software
1 3500 Systems Only

4.1.11.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value drops
below the configured setpoint level.
4.1.11.3 Timed OK Channel Defeat
Timed OK Channel Defeat is an option that prevents a channel from returning to an OK status
until that channel's transducer has remained in an OK state for the specified period of time. If you
enable the option, the software sets the time to 30 seconds. This option prevents false trips that
intermittent transducers can cause.
4.1.11.4 Monitor Danger Relay Voting
This option allows you to add logic processing to channel alarming.
l OR - if either channel of a channel pair is in danger alarm, the danger alarm relay is acti-
vated.
l AND - if both channels of a channel pair are in danger alarm, the danger alarm relay is acti-
vated.
Relay Voting is available when the Dual Relay option is selected.

52
4.  Acceleration Configuration

4.1.12 Barriers
Barriers are devices that restrict the amount of energy that can flow into a hazardous area. Select
the MTL 796(-) Zener External option or Galvanic Isolators if you will connect external safety bar-
riers between the monitor and the transducer. If your application uses an internal barrier I/O mod-
ule, select the internal option.

4.1.13 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK the status
will stay Not OK until you use one of the following methods to issue a reset:
l Pressing the reset switch on the front of the System Module
l Closing the contact on the Power Input Module (PIM)
l Issuing the reset command over Modbus
l Issuing the reset command through the 3500 Display Interface Module
l Issuing the reset command in the 3500 Rack Configuration Software
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track the
defined OK status of the transducer.

4.1.14 CP Mod
Selecting the CP Mod button in the Channel Options Dialog Box allows you to download a Cus-
tom channel configuration to the monitor. The 3500 Rack Configuration Software stores custom
configuration data in a Custom Products Modification File. Custom Products Modification files fol-
low the naming convention: <modification #.mod>. You must place these files in the
\3500\Rackcfg\Mods\ directory. When you select a CP Mod file, the software displays a window
that describes the function of the modification. CP Mod files are available through Bently Nevada,
Inc.'s Custom Products Division. Contact your local sales representative for details.

4.2 Alarm Setpoints


This section specifies the available setpoints for each type of channel. A setpoint is the level
within the full-scale range that determines when an alarm occurs. You can set Alert/Alarm 1 set-
points for every static value on each channel. The channel will drive an Alert/Alarm 1 indication if
1 or more of the channel static values exceed their setpoints. You can set up to 4 Danger/Alarm 2
setpoints (2 over setpoints and 2 under setpoints) for up to 2 of the static values. You may select
any 2 of the available static values for the channel.

Note
You can place the setpoint Over and Under limits only within the OK limits of the specified transducer.

53
Acceleration Measurement

4.2.1 Alarm Setpoint Dialog


Use the Setpoint Configuration Screen in the 3500 Rack Configuration Software, shown in Figure
"Acceleration Septoint Configuration", to adjust Alert/Alarm 1 and Danger/Alarm 2 setpoints for a
channel.

Figure 4 - 3: Acceleration Setpoint Configuration

4.2.2 Available Setpoints


The table below lists the Alert/Alarm 1 and Danger/Alarm setpoints that are available for the Accel-
eration channel type. Modbus uses the setpoint number. Bias Voltage is not available as an alarm-
ing parameter.
Table 4-10: Acceleration Available Setpoints
Setpoint Number Acceleration
1 Over Direct
2 Danger (Over Direct)

4.2.3 Alarm Hysteresis


The alarming hysteresis for all channel configurations is 1/64th of full scale. When a channel
exceeds an alarm setpoint, it must fall back below the setpoint less the amount of hysteresis
before it can go out of alarm.
Example:

54
4.  Acceleration Configuration

Consider a channel configuration with a 0 - 10 mils full-scale range and an alarm setpoint at 6
mils. Full scale is 10 mils - 0 mils = 10 mils, so the hysteresis = 10 mils/64 = 0.16 mils. The channel
input, therefore, must fall below 6 mils - 0.16 mils = 5.84 mils before the channel is out of alarm.

4.3 Configuration Considerations


Consider the following items before configuring an Acceleration Channel:
l The software automatically selects the "No Keyphasor" option for this channel type. This
channel type requires no Keyphasor signals.
l The Acceleration Direct full-scale range depends on the transducer type.
l You must configure monitors in channel pairs (for example, you may configure Channels 1
and 2 as Acceleration and Channels 3 and 4 as Radial Vibration).
l When you modify a full-scale value, readjust the setpoints that are associated with the
static value.
l If you select a Non-standard transducer, then the software sets the setpoint OK limits to
±1 volt from the Upper and Lower OK Limits that are selected.
l When you select integration, the software will change the available Full-scale range to
reflect this.
l When you select band-pass filtering, you must set the high-pass and low-pass filters at
least 2 octaves apart.
l When you activate 2 channels of acceleration the maximum channel frequency that the
monitor supports is as shown in the Table "Acceleration Channel Type Frequency Ranges" .
l When you activate a single channel of acceleration, the maximum channel frequency that
the monitor supports is as shown in the Table "Acceleration Channel Type Frequency
Ranges" .
l The Latching OK Mode and the Timed OK Channel Defeat options are not compatible.
l High frequency accelerometer transducers do not support Internal Barrier I/O Modules and
External Barriers.
l You can install only 18 high-frequency accelerometer transducers in a full rack of standard
transducers. This is because the rack can power only 18 high-frequency Accelerometer
transducers.

55
Acceleration Measurement

56

You might also like