23 82 19 - Fan Coil Units
23 82 19 - Fan Coil Units
23 82 19 - Fan Coil Units
Part 1 General
Part 2 Products
2.1 MANUFACTURERS
A. Dunham - Bush
B. Sinko
C. Trane
D. Carrier
E. Or Approved Equal
2.2 QUALIFICATIONS
A. Qualifications of Manufacturer: Furnish fan coil units which are the product of a manufacturer who
has proven experience in manufacturing these units for a period of at least five (5) years.
B. Reference Codes and Standard: ARI 411 or approved equivalent.
C. Factory tests for all water coil at the pressure as specified in the 'Water Coils' section of this
Specification.
D. Nameplate: Securely attach name plate on each fan coil unit showing manufacturer's name, serial
and model number, tag number and country of manufacturer.
2.13 FILTERS
A. 25mm thick disposable type filter shall be used.
2.14 THERMOSTAT
A. Unless otherwise specified, each fan coil unit shall have its own electronic type room thermostat
with 3 speed and on/off fan switch.
B. Thermostat shall be suitable for both wall and ceiling mounted installation.
C. Sample of each type of the thermostat/fan switch shall be submitted for approval.
D. Control and power wiring between the thermostat and the fan coil unit shall be provided. Unless
otherwise approved by the Project Manager or run above the false ceiling, all wiring between
thermostat and fan coil unit shall be concealed in the wall, floor or column.
E. Each room thermostat shall also have temperature indicator in deg. C and temperature setting
facilities.
F. Exact location of the thermostat shall be agreed by the Project Manager, allowance for length
wiring connector.
G. The controls for the fan coil units shall be capable of interfacing with the BMS or other control
system for remote operation of the units.
Part 3 Execution
A. Store all fan coil units in a place free from moisture and cement dust, salty atmosphere etc. to
avoid corrosion/ damages of the surface coating of the equipment and clogging up the internal
voids of the insulation.
B. Handle the fan coil unit with special care to avoid scratching and damage of the surface coating
of the equipment.
C. Fit equipment and appurtenance to the space provided and make readily serviceable.
D. Provide hot-dip galvanized hangers, supports and vibration isolators (as specified) for the proper
installation of equipment.
E. Provide proper electrical connections to power points which are (provided by) the Electrical Sub-
Contractor.
F. Make proper pipework connections.
G. Do not support piping and ductwork connection from fan coil units casing.
H. Provide filters as specified in the “Filter” section of this Specification.
I. Location and mounting height of room thermostat shall be agreed with the Project Manager.
J. Provide control, power, and monitoring interfacing to electrical and building management systems,
where specified.
K. Provide isolation valves, flow control valve, drain taps and manual purge valve as specified in
piping connections.
L. Unless otherwise indicated in the Specification or Drawings, construct all casings with constant
cross section.
M. Joints/connections between dissimilar metals shall be isolated by dielectric insulation.
END OF SECTION