TD 8622

This document provides technical specifications for a 1250 KVA transformer ordered by Bioron Medics. Key details include: a step down transformer with an insulation class of A and ONAN cooling, operating at 11000V/415V and 50Hz, with efficiencies of 98.49% at full load and 98.99% at half load. Standard fittings include bushings, a nameplate, tap changer switch, oil level indicator, conservator tank, and explosion vent.

Uploaded by

Abdur Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views1 page

TD 8622

This document provides technical specifications for a 1250 KVA transformer ordered by Bioron Medics. Key details include: a step down transformer with an insulation class of A and ONAN cooling, operating at 11000V/415V and 50Hz, with efficiencies of 98.49% at full load and 98.99% at half load. Standard fittings include bushings, a nameplate, tap changer switch, oil level indicator, conservator tank, and explosion vent.

Uploaded by

Abdur Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

HAMMAD ENGINEERING CO.

(PVT) LIMITED
TECHNICAL DATA FOR TRANSFORMER
Annexure-A
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Dated : February 3, 2023
Customer: Bioron Medics REF H/TR/E-8622

Rating 1250 KVA


Type Indoor/ Outdoor
Utilization Step Down `
Insulation Class A
Type of Cooling ONAN
Phases 3
Frequency 50 Hz
HV Voltage 11000 V
LV Voltage 415 V
HV Current 66 A
LV Current 1739 A
HV Tappings Normal, ±2.5, -5, -7.5 % Volts
Connections HV Delta, LV Star
Vector Group Dyn11
No Load Losses 2100 Watts *
Load Losses 17000 Watts *
Impedance @ 75 °C 5.00 % *
Temperature Rise , Oil / winding 50/55°C above 50°C ambient
Efficiency at Full Load & U.P.F 98.49 %
Efficiency at 1/2 Load & U.P.F 98.99 %
RegulaAon at Full Load & U.P.F 1.48 %
Type of Tank Tubular / Conservator Type
Terminals, H.V / L.V 3/4 Nos.
Service Altitude above Sea Level 1000 Mtr. ( Max)
Transformer Oil IEC 60296
* (Subject to tolerance according to Specification IEC 60076)
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
STANDARD FITTINGS AND ACCESSORIES
1 H.T Bushings on Top Cover 8 Bi Directional Wheels
2 L.T Bushings on Top Cover 9 Earthing Terminals
3 Name & Rating Plate 10 Dial Type Thermometer
4 OffCircuit Tap Changer Switch 11 Silica Gel Breather
5 Oil Level indicator 12 Oil Filling Plug
6 Oil Conservator Tank 13 Oil Drain & Sampling Valve
7 Explosion Vent 14 Lifting Lugs