The document discusses Alfa variable air volume (VAV) control units from Astic Insulation Materials Industries. It describes Alfa bypass and pressure independent VAV units. Bypass units are duct mounted and pressure dependent, suitable for both cooling and heating systems. They control air quantity to zones based on load requirements. Pressure independent units control air volume flow rate into occupied zones in response to thermostat or building management system signals. The document provides specifications, features, dimensions, sound power data and notes for several Alfa VAV models.

Uploaded by

Marwan Nizar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views8 pages

Alfa Vav

The document discusses Alfa variable air volume (VAV) control units from Astic Insulation Materials Industries. It describes Alfa bypass and pressure independent VAV units. Bypass units are duct mounted and pressure dependent, suitable for both cooling and heating systems. They control air quantity to zones based on load requirements. Pressure independent units control air volume flow rate into occupied zones in response to thermostat or building management system signals. The document provides specifications, features, dimensions, sound power data and notes for several Alfa VAV models.

Uploaded by

Marwan Nizar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

IMI

ASTIC INSULATION MATERIALS INDUSTRIES


Defining Air Solutions.. . . . . . .

ALFA VAV UNITS


BYPASS AND PRESSURE INDEPENDENT TYPE
Defining Air Solutions.. . . . . . .
ALFA VARIABLE AIR VOLUME CONTROL UNITS BYPASS TYPE

"ALFA variable Air Volume (VAV) Control Units are duct mounted pressure dependent bypass type unit, ideal
for low and medium pressure application. These units are suitable for both cooling and heating systems. The
temperature can be preset on the electronic analogue/digital thermostat, which senses the room
temperature and controls the VAV unit. The required quantity of air to each zone is pumped in to the area
based on load requirement and the balance air by passed through the bypass section of the VAV unit above
false ceiling or to return air ducts.

Features of ALFA Bypass VAV Control Unit


► Easy to install
► Powder Coated ALFA VAVs can easily be located to suit interior requirements
► Our Design ensures low pressure drops on air side
► Special acoustic treatment helps to achieve low noise control level
► ALFA VAVs operates with digital thermostat to ensures precise temperature control
► ALFA VAVs available with ON/OFF controls – optional
► ALFA VAVs suitable for both heating and cooling control system
► ALFA VAV with sound attenuators - Optional
► ALFA VAVs have bypass balancing dampers & properly designed integral outlets which can be suitable
for Pre-insulated, GI, SS & Aluminium air conditioning duct system

ALFA VAV Series


► Bypass type
► Low NC levels
► Low air side pressure drops
► Galvanized steel construction
► Stainless steel construction - optional
► Aluminium construction - optional

Technical Features 2 Way VAV with


Modulating Actuator
Stainless Steel Construction

► 20BWG galvanized steel sturdy design & Damper blade with 18 BWG with rubber gasket to eliminate the
noise, ALFA VAVs are with round/rectangular inlet as per standards, Outlets are rectangular with Slip &
Drive connection
► Powder coating suits interior requirements& prevent corrosion
► ALFA VAV casing with acoustically & thermally lined internal insulation/ linear of 25 mm thick &32 Kg/m3
density, loose edges are sealed and covered with Z strip stiffeners to prevent air erosion
► ALFA VAVs are sealed and gasket mechanically for air tight construction
► Size ranging from 100 CFM to 3000 CFM.
Defining Air Solutions.. . . . . . .
Dimensional Data ALFA VAV-01 to 05

Discharge Bypass

Modulating Actuator

Air flow

INLET DISCHARGE LENGTH BYPASS OPENING


MODEL NO. CFM
A B C D E

ALFA VAV-1 80 TO 200 Ǿ 125 250 X 200 400 180 105

ALFA VAV-2 160 TO 400 Ǿ 200 300 X 250 400 230 150

ALFA VAV-3 240 TO 600 Ǿ 250 350 X 300 550 280 250

ALFA VAV-4 320 TO 800 Ǿ 300 400 X 350 550 330 250

ALFA VAV-5 480 TO 1200 Ǿ 350 450 X 400 600 380 260

Dimensional Data ALFA VAV-06 to 08

Bypass Air flow

Discharge

Modulating Actuator

INLET DISCHARGE LENGTH BYPASS OPENING


MODEL NO. CFM
A B C D E

ALFA VAV-6 840 TO 1500 Ǿ 400 500 X 250 610 435 180

ALFA VAV-7 960 TO 2400 400 X 500 600 X 250 610 535 180

ALFA VAV-8 1280 TO 3000 400 X 600 800 X 250 610 740 175
Defining Air Solutions.. . . . . . .

Selection Data
SOUND POWER DB SOUND POWER DB

OCTAVE BAND MAX. OCTAVE BAND MAX.


MODEL NO. CFM ∆Ps MODEL NO. CFM ∆Ps
(2). (3). (4). (5). (6). (7). DISC. RADIATED (2). (3). (4). (5). (6). (7). DISC. RADIATED

125 250 500 1000 2000 4000 NC NC 125 250 500 1000 2000 4000 NC NC

75 0.07 40 31 24 17 15 15 - 10 480 0.03 42 30 21 21 20 21 - -

120 0.14 47 41 34 28 24 23 12 12 720 0.06 47 39 31 29 26 24 - 12


BVAV-01 BVAV-05
160 0.24 51 49 42 36 30 26 14 14 960 0.11 50 46 39 34 30 26 12 16

200 0.35 55 54 48 42 35 28 19 20 1200 0.17 53 51 44 38 33 28 13 21

160 0.05 44 30 22 19 17 20 - - 840 0.03 42 30 22 19 19 18 - -

240 0.12 49 41 33 29 25 25 12 13 960 0.06 48 40 33 28 25 22 - 13


BVAV-02 BVAV-06
320 0.21 52 48 41 36 31 28 13 19 1280 0.12 52 47 40 35 30 25 11 16

400 0.33 54 53 47 42 36 31 15 25 1500 0.18 55 53 46 40 34 28 13 23

240 0.04 42 31 22 20 18 21 - - 960 0.04 41 32 27 18 15 16 - 11

360 0.09 56 39 32 28 25 24 - 11 1440 0.10 49 42 38 31 27 26 - 15


BVAV-03 BVAV-07
480 0.16 50 45 40 34 30 27 12 14 1920 0.18 54 50 46 39 35 33 12 23

600 0.25 52 49 46 39 34 29 13 22 2400 0.29 58 56 52 46 41 38 14 30

320 0.03 41 28 19 18 18 21 - - 1280 0.04 44 37 33 27 23 22 - 11

480 0.07 46 38 30 26 24 23 - 12 1920 0.09 51 47 42 36 32 29 11 15


BVAV-04 BVAV-08
640 0.12 49 45 37 31 28 25 11 15 2560 0.15 57 54 48 43 39 34 12 23

800 0.2 52 50 43 35 31 27 13 22 3000 0.23 61 59 53 48 44 37 14 31

Notes
► ∆Ps static pressure difference from inlet to discharge.
► Dash (----) indicates sound power dB or NC level less than 10.
► ∆Ps is the minimum pressure drop required to deliver CFM shown with the primary damper in wide open
position (Bypass Closed).

Discharge NC Levels are Based on


► 1.5 mtr rectangular 300x300 duct lined with 25mm thick fibreglass insulation.
► Rectangular tee attenuation entering branch duct.
► 1.8mtr lined flex duct (200mm diameter).
► Maximum of 300 CFM per outlet .
► Space effect factor (141 m³) at 1.5 mtr from outlet.
► End reflection.
► Environmental adjustment factor.
Defining Air Solutions.. . . . . . .
PRESSURE INDEPENDENT TYPE VAV

"Alfa Pressure independent VAV units are an innovative solution manufactured with the greatest precision and
latest manufacturing techniques at Astic Industries. Alfa pressure independent terminal units are designed to
control air volume flow rate for supply air on variable volume system. These units are designed to supply the air
flow rate of conditioned air into an occupied zone in response to control signal from a thermostat or building
management system. The components of the unit include an acoustically lined sheet metal box round inlet
damper, sensor and rectangular outlet. Alfa PI VAV are connected with Nepcross cross flow differential sensor
( Naptronic Make Canada) for measuring the air volume, which is located in the upstream section of the VAV
chamber .The sensing points collectively average the primary air velocity pressure across the entire inlet area.
These terminal units also incorporate control components, (VAV actuator, transformer), which are factory
fitted and inhouse calibrated to ensure meet all design criteria . This enable the terminal to monitor desired air
flow rate as indicated by the thermostat or input signal of 0-10V and compensate instantly for any changes in
supply air pressure that might tend to alter the supply air volume - resulted as pressure independent variable
air volume system.

Features And Benefits


► Galvanized steel casing,mechanically sealed for low leakage construction.
► Circular damper blades for better flow management
► Full range of opinion and accessories available (heating coils, attenuators…etc)
► Available with imported Nertronic,Canada make of Nepcross Cross flow sensor,controller,Actuator and
Thermostat CO2 sensor
► Nepcross Cross flow sensors amplify sufficiently for differential pressure signals and minimize the white noise
associated with the signal amplification.
► Dampers rotate in a low friction and long life Brass bearings.
► Control componets encased in control panels
► Acoustic lining with glass fibre wood suitable for air velocity up to 20 m/s
► Flexible silicone gasket on damper blades for low leakage
► Shaft indicator for damper position

Construction Details of Pressure Independent VAV


► Air terminal casing ,inlets are manufactured from 22 G galvanized steel conforming to ASTM A 653,LFQ and
G 90 coating
► Damper shall have internal acoustic lining of 25 mm thick and 48 Kg/m3 density
► Damper blades shall be manufactured from 0.9mm galvanized sheets with flexible gasket to ensure low
leakage.
► Damper bearing –brass bush 12mm
► Aluminuim flow grid – Nepcross sensor ( Neptronic Make Canada)
► Supplied with imported Neptonic, Canada make controller ,Actuator and Thermostat
► Grooved inlet connection tube for added rigidity and secure flex duct connections
► Rectangular discharge with slip and drive cleat duct connection
Defining Air Solutions.. . . . . . .
Single Duct Air Terminal Unit, Cooling Only
Top View
Inlet Size Width Height Length
Model Number
Air
in mm mm mm
ALFA PI - VAV - 6 6 305 203 420
Flow
ALFA PI - VAV - 8 8 305 254 420
ALFA PI - VAV - 10 10 356 318 420
ALFA PI - VAV - 12 12 406 381 480
ALFA PI - VAV - 14 14 508 445 500
ALFA PI - VAV - 16 16 608 451 550
Control Panel (std)With Cover
Side View

Air
Height
Flow

Single Duct Air Terminal Unit With Electric Heat


Top View

Width X
Air Height

Flow

Electric Heater
Control Panel (Std)

Inlet Size Width Height Length


Model Number
in mm mm mm
ALFA PI - VAV - EH - 6 6 305 203 890
ALFA PI - VAV - EH - 8 8 305 254 890
ALFA PI - VAV - EH - 10 10 356 318 890
ALFA PI - VAV - EH- 12 12 406 381 890
ALFA PI - VAV - EH - 14 14 508 445 890
ALFA PI - VAV -EH - 16 16 608 451 890

Single Duct Air Terminal Unit With Integral Attuenuator


Top View

Air
Inlet Width X Height
Flow Size

Control Panel(Std)With Cover

Inlet Size Width Height Length


Model Number
in mm mm mm
ALFA PI - VAV - SA - 6 6 305 203 915
ALFA PI - VAV - SA - 8 8 305 254 915
ALFA PI - VAV - SA - 10 10 356 318 915
ALFA PI - VAV - SA - 12 12 406 381 915
ALFA PI - VAV - SA - 14 14 508 445 915
ALFA PI - VAV - SA - 16 16 608 451 915
Defining Air Solutions.. . . . . . .
Radiated And Discharge Sound Power, ∆Ps=1.5in.wg

MODEL NO. Min Ps CFM Sound (db) 125 Hz 250 Hz 500 Hz 1K Hz 2K Hz 4K Hz


RADIATED 60 53 49 44 41 36
ALFA PI-VAV-6 0.08 400
DISCHARGE 69 64 60 53 49 49
RADIATED 64 57 52 44 39 34
ALFA PI-VAV-8 0.01 700
DISCHARGE 77 71 62 58 55 53
RADIATED 60 58 52 44 38 32
ALFA PI-VAV-10 0.02 1100
DISCHARGE 75 70 65 60 56 53
RADIATED 63 56 54 45 41 40
ALFA PI-VAV-12 0.01 1600
DISCHARGE 70 67 62 60 59 57
RADIATED 64 57 55 45 40 34
ALFA PI-VAV-14 0.01 2100
DISCHARGE 68 62 61 63 63 60
RADIATED 66 62 56 50 47 44
ALFA PI-VAV-16 0.03 2800
DISCHARGE 76 69 66 64 64 60

“Nepcross” Cross Flow Sensor


Nepcross has been developed in order to give Independent Box Manufactures
the ability to participate in the lucrative VAV pressure independent market.
Now,the independent box manufactures have the choice to use the Nepcross
with different VAV controllers or use the Nepcross with Neptronic Pressure
Independent controllers.
The Neptronic Pressure Independent Controllers (and corresponding
thermostats) are available in free standing mode EVC or BAC net configuration
mode EVCB.

Nepcross Design Achieves Two Major Objectives


1. Amplify sufficiently for the differential pressure signal.
2. Minimize the white noise associated with the signal
amplification.
This has been accomplished by Nepcross’s unique circular
static pressure amplification probe and the geometry of the
total pressure radial probes.
The static pressure amplification circular probe collects the
pressure signal from strategically located pressure ports along
its outer diameter
The average static pressure signal (ASSP)is sent to the Low port
of the electronic transducer. The ASAP is responsible for the
amplification of the resulting Velocity Pressure Signal.
The Neptronic VAV controllers have tailored curves also in the
lower velocities which are more representative of the actual
velocities rather than based on one point calibration and
theoretical assumptions. That feature makes the total
Neptronic assembly a perfect solution for modern VAV
application

VAV Single Duct Controller & Actuator


www.neptronic.com
The VAV package consists of 2 parts, namely the thermostat and the EVC
which is a combination of an actuator and a controller which mounts
directly to the damper jackshaft on the side of the VAV box.
The EVC is available in two versions:a BTL listed BAC net application specific
version (EVCB) or a stand-alone version (EVC).
Defining Air Solutions.. . . . . . .

Inner Diameter (Inch) 6” 8” 10” 12” 14” 16”

Area 0.196 ft2 0.349 ft2 0.545 ft2 0.785 ft2 1.069 ft2 1.396 ft2

Velocity Constant 2812 FPM 2740 FPM 2841FPM 2822 FPM 2666 FPM 2837 FPM

Velocity Pressure Constant 0.49 0.47 0.50 0.49 0.45 0.50

K Factor 552 CFM 956 CFM 1550 CFM 2216 CFM 2850 CFM 3961 CFM

Amplification Factor F 2.60 2.30 2.30 2.15 2.15 2.10

Total Pressure Ports(ASHARE Standard 62) 12 12 16 16 20 20

Velocity Range 300 TO 3000 FPM(1.5 TO 1.52 m/s)

Temparature Range -400 C to 800C (-400 F tO 1760 F)

Materials Nepcross: Aluminium & PC/ABS


Collar 22 gauge galvanozed steel

Installation

Factory
Dubai Investment Park - ll, Dubai 32218, U A E | Ph : +971 4 88 00 729, Fax : +971 4 88 00 726
Head Office
106, The Arcade Building, Al Garhoud, Dubai 32218, UAE | Ph : +971 4 282 8005, Fax : +971 4 282 8006
www.astic-dubai.com [email protected]