RIGID CELLULOSE MEDIA

LEAVING AIR ENTERING AIR

45o
UP

TYPE 45/15 EVAPORATIVE COOLING PADS

Copyright 2002 Metal Form Mfg Form No. Media/02

5960 West Washington Street Phoenix, AZ 85043 tel: 602-233-1211 fax: 602-233-2033 Email: [email protected] www.nrgsvr.com
GENERAL FEATURES

• Consistent cooling performance, year after year. • Self-Supporting – The inherent structural
rigidity of each pad reduces the need for wire
• Fast wet-out for maximum cooling at start-up. grids, framing or holding strips.
· Low pressure drop to maximize air-flow. · Custom Sizes – Various heights and depths can
· More Cooling than fiber pads. be cut for specific applications.

· Longer Life – Up to five times as long as standard · Higher Air Velocity – Rigid Cellulose Media’s
Aspen pads. unique design handles more than three times the
air velocity of standard Aspen pads.
APPLICATIONS
Rigid Cellulose Media’s simplicity of installation is a direct result of its exclusive design and unique
manufacturing process. Rigid Media is typically use for:

• Comfort Cooling for plants, commercial buildings • Humidification for wintertime heating.
and institutions.
· Water Cooling for indirect evaporative coolers.
· Pre-Cooling for air-cooled refrigeration systems.
· Space Cooling for greenhouses.
· Air Washers for industrial air conditioning
systems. · Cooling for manufacturing processes.

TYPE 45/15 SPECIFICATIONS

WEIGHT WATER TEMP


DRY WET MAX
1.98 LBS/FT3 4.16 LBS/FT3 200oF

FACE VELOCITY AIR TEMP


MAX MIN 150 oF CONTINUOUS
750 FPM 200 FPM 300 oF INTERMITTENT

SQUARE FEET of SURFACE STANDARD SIZES


123 FT2/FT3 3” REINFORCED PAD FOR PRE-COOLERS
CUT DEPTHS: 4”, 6”, 8”, 10”, 12” to 24”
CUT WIDTHS: 2” to 12”
CUT HEIGHTS: 12” to 72”

2
Media Saturation Effectiveness

Saturation Effectiveness ( Efficiency - % )

Velocity Pad Thickness


FPM 4” 6” 8” 12” 24”
200 72 85 91 98 99
300 68 82 90 97 99
400 62 77 85 94 99
500 59 74 83 93 99
600 56 70 80 91 99

Media Static Pressure Loss, (in.wc.)


Static Pressure Loss (in. wc .)
Static Pressure Loss (in. w.c.)

Velocity Pad Thickness


FPM 4” 6” 8” 12” 24”
200 0.014 0.021 0.030 0.041 0.082

300 0.031 0.046 0.063 0.093 0.180

400 0.055 0.083 0.110 0.165 0.330

500 0.086 0.129 0.165 0.260 0.510

600 0.124 0.185 0.228 0.370 0.740

3
IMPORTANT !
In order to get the best performance from your cooling pads, they must be installed properly.

RED DYE

45.0°

ENTERINGAIR LEAVINGAIR

15°

Pads must always be installed with the steeper flute angle sloping down toward the air
entering side. The reasoning is simple. The steeper angle puts more water on the hot,
dry, dirty side of the pad where it is needed most. It also counteracts the tendency of
the air to push the water toward the pad. The leaving air side of replacement pads
are marked across the top -back edge with red dye.

To extend the useful life of your cooling pads, rotate the pads 180º degrees once each
cooling season so that the top-back is now front-bottom. Red dye marked pads would
now be at the front-bottom.
15°

ENTERINGAIR LEAVINGAIR

45.0°

REDDYE

If the media becomes clogged with contaminants and/or mineral deposits which cannot
be removed by cleaning, or the media loses its structural integrity such that it restricts
airflow, pad replacement is recommended.