Distribution Oil Transformer
Distribution Oil Transformer
TRANSFORMERS
OIL IMMERSED up to 6.3 MVA
www.alfanar.com
Contents
1- General Information 4
2- Applications 10
3- Product Portfolio 11
4- Product Breakdown 12
5- Transformer Classifications 13
A - Standard Losses Transformers 14
B - High Efficiency Transformers 18
C - Utility Transformers (SEC) 19
1 - Pad Mounted Transformers 19
2 - Pole Mounted Transformers 21
3 - Unit Substations 23
D- Special Transformers 25
1 - PV Transformers 25
2- LV/LV Transformers 26
3 - MV/MV Transformers 27
4 - Dual Voltage Transformers 28
• On Low Voltage 29
• On Medium Voltage 29
5 - Oil Transfomrers with On-Load Tap Change (OLTC) 30
6 - Transformers with Hybrid Insulation Winding 31
7 - Non-Mineral Oil Transformers (KNAN) 32
6 - Accessories 33
• Standard Accessories 34
1. Bushing 34
2. Cable Box 38
3. Oil Level Indicator 38
4. Thermometer 38
5. Pressure Relief Valve 38
6. Earthing Terminal on Tank 39
7. Drain Valve 39
8. Tap Changer 39
9. Lifting Lugs 39
• Optional Accessories 40
1. DMCR 40
2. Oil Conservator 40
3. Buchholz Relay 40
4. Air Breather 40
5. Roller 40
6. Winding Temperature Indicator 40
7 - Package and Unit Substations 41
• Design and Structure 41
− Ring Main Unit 42
− Transformer 44
− Low Voltage Panel 45
• Technical Features 46
8 - Service 47
9 - Testing 48
10 - Inquiry Form 49
1 - General Information
A - Standards
The IEC and BS Standards for transformers and their parts are the most widely applied
standards in most countries where local electric authorities have either adopted one of
these standards or created one that suits the needs, laws and regulations of their country.
The following list of main Standards refers to the most common electrical applications.
The Standards may have been amended, but the relevant amendments are not mentioned
here.
IEC 60076-3 Insulation levels, dielectric tests and external clearances in air
IEC 60296 Unused mineral insulating oils for transformers and switchgear
4
1 - General Information
C - Technical Aspects
Power Rating and Voltage Levels
A power rating is the rated voltage (multiplied by the phase-factor for three-phase transformers) and the rated line
current at center tap when several taps are provided.
P = V *I*1.73
“V” is the rated line to line voltage
“I” is the rated line current of the transformer
“1.73” is the numerical value for the square root of 3.
Transformers are usually energized from a network which has a defined voltage level which is the primary (feed)
voltage level.Transformers should transform the primary voltage to a new voltage, the secondary voltage level,
that is required by the consumer.
Transformers can be designed to operate with two primary voltages (one at a time), therefore, if the network
voltage must be changed in the future, the same unit will be used.
Transformers can be designed to generate two secondary voltages simultaneously, thus, outputting two levels for
two applications.
The primary and secondary voltages define a Basic Insulation Level (BIL) of 75, 95, 110,
125, 170 and 200kV. The transformer is designed accordingly for electrical withstand of over-voltages.
1 - General Information
Altitude
The transformers are suitable for operation at altitudes of up to 1000m above sea level. Site altitudes above 1000m
require the use of special designs and should be mentioned in the order.
Vector Group
The vector group is the International Electrotechnical Commission (IEC) method of categorizing the high voltage
(HV) windings and low voltage (LV) winding configurations of three-phase transformers. The vector group
designation indicates the windings configurations and the difference in phase angle between them.
The vector group determines the phase displacement between the primary and the secondary winding, and each unit
in the vector group refers to 30 degrees displacement. A vector group Dyn11 is delta on primary, star on secondary,
with neutral brought out and 330-degree phase displacement.
6
1 - General Information
Tank Types
The transformer tank is usually a non-rigid structure with corrugated panels, designed to withstand mechanical
stresses, absorb oil expansion, and meet the thermal evacuation constraints.
For power rating above 3150kVA, the tank is usually designed with rigid structure, cooling radiators and
conservator.
Magnetic Circuits
The structure of magnetic circuit are:
• Three legs construction
• Step lap stacking
Made from a cold rolled, grain oriented silicon steel strips (CRGO), each strip (0.23, 0.27 or 0.30mm thick) is
insulated on both sides by Carlite.
Permissible Tolerances
Manufacturing tolerances are the deviations between the measured values and the guaranteed values.
Unless otherwise specified in the order, the tolerances are limited to the values specified in IEC 60076-1.
1 - General Information
Frequency
Frequency is the number of occurrences of a repeating event per unit of time. It is also referred to as temporal
frequency, which emphasizes the contrast to spatial frequency and angular frequency. The period is the duration of
time of one cycle in a repeating event, so the period is the reciprocal of the frequency.
The frequency at which the transformer is designed to operate is 50Hz or 60Hz and is
set in accordance with the network frequency.
8
Winding Coils
An electromagnetic coil is an electrical conductor such as a wire in the shape of a coil, spiral or helix used in
applications where electric currents interact with magnetic fields. Either an electric current is passed through the
wire of the coil to generate a magnetic field, or conversely an external time-varying magnetic field through the
interior of the coil generates an EMF (voltage) in the conductor.
Both the primary and secondary windings are made of copper or aluminum. The primary voltage is directly wound
on the secondary voltage winding, with insulating barriers and cooling channels between the two windings.
Secondary voltage coils are rectangular wires or foil conductors. Primary voltage coils are round enamel wires, or
rectangular paper insulated wires for high power ratings, or paper insulated round wires.
Adequate channels for oil circulation are integrated in the windings to provide efficient cooling and to limit the hot
spot temperature.
2
2 - Applications
The distribution transformer provides the final voltage transformation in the electric power distribution system,
stepping down the networks medium voltage to low voltage, the level used by the consumer, and is considered one
of the most important links in the distribution network.
Utility
Generation, transmission, distribution substations,
water and waste water treatment plants.
10
3 - Product Portfolio
1 7
2 9
3 10
11
12
6 13
12
5 - Transformer Classifications
A distribution transformer or service transformer is a transformer that provides the final voltage transformation in
the electric power distribution system, stepping down the voltage used in the distribution lines to the level used by
the customer.
Whether the transformers are used for infrastructure systems, industry or households, alfanar provides the right
transformer for every need – from compact distribution transformers to limited power transformers with ratings up
to 6300 A.
Transformers can be classified based on many factors like installation or losses which is the most important factor
in the transformer.
In any electrical machine, ‘loss’ can be defined as the difference between input power and output power.
A - Standard Losses Transformers
As per the International Standarads and local Authorities requirments , with a Full cabability to match IEC, SEC and
BS 50708-2-1 Tier 1 , Tier 2 and Tier 3.
Under those values a standard losses transformer is made to fulfil the customer requirements with a competitive cost
and high quality.
14
Technical Data
Standard IEC60076
Winding CU or ALU
alfanar High Efficiency Transformers offer the best ratio between initial cost and operating cost for sensitive
applications.
Lowering the energy consumption results in reduced operating costs and less harmful emissions for the customer’s
operations.
Technical Data
Three Phase, Oil Immersed Distribution Transformers
Transformer Type
with lossess as per ECO design
Standard IEC60076,Losses refer to commission regulation (EU) No 548, Tier 2 ( 1 July 2021)
Winding CU or ALU
18
C - Utility Transformers “SEC”
With a proper design selection, they can be located near or inside buildings for greater flexibility and savings, and
are designed to withstand environmental hazards.
The transformers are designed to meet or exceed applicable local and international standards such as IEC and BS
standards.
All transformers are manufactured and are produced expressly to meet a customer’s exacting specifications.
Technical Data
Three Phase, Oil Immersed Distribution Transformers
Transformer Type
Pad Mounted
Winding CU or ALU
20
C - Utility Transformers “SEC”
These transformers typically service urban and rural residential and commercial loads. Other uses include light
industrial and commercial lighting applications.
Technical Data
Three Phase, Oil Immersed Distribution Transformers
Transformer Type
Pole Mounted
Winding CU or ALU
22
C - Utility Transformers “SEC”
3 - Unit Substations
The unit substation transformer is designed for commercial and industrial applications to convert distribution
voltages to utilization voltages. They are constructed to interconnect easily with both primary and secondary
switchgear.
Unit substations follow the system concept of locating transformers as close as practical to areas of load
concentration at utilization voltages to minimize the lengths of secondary distribution cables and buses.
Unit Substations are a compact solution for multiple functions, and can be used in either indoor or outdoor
applications.
General
56-SDMS-07, 56-SDMS-09 USS With aluminum transformer & aluminum busbars LVDP
Related Specification
56-SDMS-01, 56-SDMS-03 USS With copper transformer & copper busbars LVDP
Ambient Temperature Up to 55 C
Outdoor color RAL 7035 or RAL 7033
Location of Operation Outdoor
Degree of Protection Up to IP 54
Electrical Characteristics
Nominal Unit S/S Rating kVA 300, 500, 1000, 1500, 2000 kVA
MV Rating kV 13.8 kV, 33 kV, 34.5-33kV (dual)
LV Rating V 400V, 230V, 400-230V (dual)
Rated Frequency Hz 60
Transformer
24
D - Special Transformers
1. PV Transformers
PV transformers are the ideal solution for photo voltaic systems. The Technology used along with the appropriate
sizing of the core, the framework, and the high quality materials used result in the most suitable product in terms of
quality, reliability, efficiency and cost effectiveness.
Technical Data
Transformer Type Three Phase, Photo Voltic Oil Immersed Distribution Transformers
Standard IEC60076
Winding CU or ALU
Common Data Three Phase, Oil Immersed Distribution Transformers (Indoor or Outdoor Installation)
Standard - IEC60076
Rated Frequency Hz 60 or 50
Top Oil °C 50
Max. Temperature Rise*
Average Winding °C 55
26
D - Special Transformers
3 - MV/MV Transformers
MV/MV transformers are manufactured according to customer request in order to meet the technical features of the
plant where they will be installed. alfanar provides technical engineering support from the preliminary studies of
the transformer to assist the customer in the specification selection.
Common Data Three Phase, Oil Immersed Distribution Transformers (Indoor or Outdoor Installation)
Standard - IEC60076
Rated Frequency Hz 60 or 50
Top Oil °C 50
Max. Temperature Rise*
Average Winding °C 55
LI 75 / AC 28 / Um 12
LI 95 / AC 38 / Um 17.5
Primary Insulation Level
LI 125 / AC 50 / Um 24
LI 170 / AC 70 / Um 36
A dual voltage transformer can be defined as a transformer capable of providing two types of voltages, i.e. if the two
separate windings are connected in series, they will provide the sum of voltages supplied to the two coils and if the
two windings are connected in parallel, then the net voltage will be decreased. These voltages can be switched
within the transformer according to the type of output required by using a dual voltage switch.
Using a transformer which has reconnectable windings greatly reduces costs and saves time as many power
applications require a number of voltage levels for different machines, in this case using different types of
transformers is not a viable solution.
28
� On Low Voltage
Common Data Three phase, Oil Immersed Distribution Transformers (Indoor or Outdoor Installation)
Standard - IEC60076
Rated Frequency Hz 60 or 50
Top Oil °C 50
Max. Temperature Rise
Average Winding °C 55
LI 75 / AC 28 / Um 12
LI 95 / AC 38 / Um 17.5
Primary Insulation Level
LI 125 / AC 50 / Um 24
LI 170 / AC 70 / Um 36
� On Medium Voltage
Common Data Three phase, Oil Immersed Distribution Transformers (Indoor or Outdoor Installation)
Standard - IEC60076
Rated Frequency Hz 60 or 50
Top Oil °C 50
Max. Temperature Rise*
Average Winding °C 55
Rated Primary Voltage As per customer's request kV 22/11 or 13.8-11 or 11-6.6 , etc
LI 75 / AC 28 / Um 12
LI 95 / AC 38 / Um 17.5
Primary Insulation Level
LI 125 / AC 50 / Um 24
LI 170 / AC 70 / Um 36
Onload Tap Changer: On-load tap changer (OLTC), also known as On-circuit tap changer (OCTC), is a tap changer
in applications where a supply interruption during a tap change is unacceptable, the transformer is often fitted with
a more expensive and complex on load tap changing mechanism.
Technical Data
Three Phase, Oil Immersed Distribution Transformers with
Transformer Type
On-Load Tap Change (OLTC)
Standard IEC60076
Winding CU or ALU
30
D - Special Transformers
6- Non-Mineral Oil Transformers (KNAN)
The designation of cooling types of oil distribution transformers depends on the fire point of the oil being used in
the transformer. Mineral oils are symbolized with “O” with minimum flash point 135°C as per IEC 60296- Ed. 4,
2012.
Non-mineral oils such as silicone oil, Synthetic Ester (which is also known in the market by the brand “Midel”) and
Natural Ester (vegetable oils) are designated with “K” since their fire point is above 300°C.
Each letter in KNAN transformer cooling stands for:
K - indicates a beyond 300-degree Celsius fire point
N - denotes Natural
A - is equal to Air
N - Natural
• 100% fire safety record
• High fire point >300˚C
• Classified as K-class
• Renowned resistance to ignition
• Midel doesn’t contribute to the fire
• Self-extinguishing (Fire extinguished in 7.5 Seconds)
• No risk of pool fires
alfanar High Temperature Transformers
The high temperature oil transformer is characterized by its high dielectric strength, high flash point, wide service
temperature range, low vapor pressure, good heat capacity values, low pour point, low viscosity change at extremely
high and low temperatures, and inertness to virtually all substrates.
Features
• High dielectric strength fluid
• High fire point > 300°minimal flammability and
high temperature stability
• Low viscosity change, low volatility
• High thermal oxidation resistance
• Chemically inert
• Low toxicity
• Compatible with most existing transformer
insulation systems
• Longer service life than conventional
transformer oils
D - Special Transformers
7- Transformer with hybrid insulation winding
Three hybrid winding types share the use of conventional barrier insulation and the use of high-temperature
insulation on the windings.
32
6 - Accessories
Standard Accessories
1. Bushing
Transformer bushings connect the network cables to the primary and secondary windings through a metallic cover
while electrically isolating them.
The bushing’s rating is chosen depending on the voltage, current and applications.
Standard Accessories
a. LV Bushing
Max Max
Description
Voltage (kV) Current (A)
DT 1/250 1 250
DT 1/630 1 630
DT 1/1000 1 1000
DT 1 / 2000 1 2000
DT 1/3150 1 3150
DT 3/250 3 250
M12 M20
101
48
44
44 29
101
Ø24
DT1-KV/1000A
DT1-KV/630A
Max Max Max Max Max Max
Voltage Current Voltage Current Voltage Current
DT 1/250 (kV) (A) DT 1/630 (kV) (A) DT 1/1000 (kV) (A)
M12
100 40
50 Ø17
144
72 54
40 20
17
48 24
Ø14
144
340
372
DT1-KV/3150A
DT1-KV/2000A
Max Max Max Max Max Max
Voltage Current Voltage Current Voltage Current
DT 1 / 2000 (kV) (A) DT 1/3150 (kV) (A) DT 3/250 (kV) (A)
34
Standard Accessories
a. LV Bushing
Max Max
Description
Voltage (kV) Current (A)
DT 3/630 3 630
DT 3/4500 3 4500
DT 3/6300 3 6300
50 50
M20 25 25
35 17
35 17
202
202
DT3-KV/630A Bar3-KV/1600A
Voltage Current Voltage Current Voltage Current
DT 3/630 (kV) (A) Bar 3.6/850 (kV) (A) Bar 3.6/1600 (kV) (A)
63
17 25
35
65
35
292
Bar3-KV/2500A
Voltage Current Voltage Current Voltage Current
Bar 3.6/2500 (kV) (A) DT 3/4500 (kV) (A) DT 3/6300 (kV) (A)
63 63
18 18
25 25
35
35
Ø11 Ø11
216
MonoBlock1.1-KV/1700A
Voltage Current Voltage Current
Monoblock Monoblock
(kV) (A) (kV) (A)
1.1/800 1.1/1700
1 800 1 1700
70
18 63
18 25
25
35
35
Ø11 Ø11
216
216
MonoBlock1.1-KV/4000A
MonoBlock1.1-KV/2500A
Voltage Current Voltage Current
Monoblock Monoblock
(kV) (A) (kV) (A)
1.1/2500 1.1/4000
1 2500 1 4000
36
Standard Accessories
b. HV Bushing
T 20NF/250AMP-(CD440) Description
Max
Voltage (kV)
Max
Current (A)
Creepage
(mm)
Plugin Bushing *
T 20NF/250AMP-(CD440) Description
Max Max Creepage
T 30NF/250AMP-(CD600)
Voltage (kV) Current (A) (mm)
T 30NF/250AMP-(CD1650)
Plugin Bushing *
2. Cable Box
Cable boxes are enclosures for the transformer terminals. They provide
protection from hazardous access to terminals, and protect the terminals
from water, dust and mechanical impacts up to different degrees.
Protection degrees are described in IEC 60529. The cable box can be
either top or side accessible depending on customer requirements.
4. Thermometer
The dial type thermometer indicates the maximum highest oil temperature
reached during a certain period.
Two contacts are optional to provide an electrical signal, the first is for an
alarm and the second for tripping.
38
6. Earthing Terminal on Tank
Two earthing points are integrated in each tank, stainless stud, stainless flag with 12mm hole and stainless threaded
M10 terminal are the available earthing point types.
7. Drain Valve
The drain valve is used to drain or sample the transformer oil
from the transformer tank. These valves are fitted to the
transformer tank by welding the pipe of the valve to the tank.
These valves are 100% tested to ensure no leakages.
8. Tap Changer
The network voltage is usually not stable and varies between
different locations. To keep the secondary voltage at a nominal
value, a linear tap changer is used.
9. Lifting Lugs
Lifting lugs are used for untanking and lifting. 2 lugs are
supplied for units weighing up to 3.5 tons, 4 lugs for heavier
units.
Optional Accessories
1. DMCR Relay
A DMCR relay is a multifunctional device. It indicates the temperature and oil level
and is equipped with electrical contacts for:
• Gas formation
• Pressure excess
• 2 Temperature levels: alarm and trip
2. Oil Conservator
A cylindrical tank mounted on the supporting structure on the roof of the transformer
(main tank). The main function of the oil conservator is to provide adequate space for
expansion of oil inside the transformer for a breathing type tank transformer.
3. Buchholz Relay
The Buchholz Relay is used in conjunction with the conservator. Oil leakages, gas
formations, and quick oil flow to the conservator are internal faults detected by the
Buchholz Relay. Dry contacts are
provided to signal these alarms.
4. Air Breather
The air breather is installed on the oil conservator. During normal operation the oil
temperature changes resulting in an oil volume change, generating a bi-directional air
flow from and to the conservator. The air breather contains silica gel which absorbs the
air moisture. On delivery, the silica gel is pink, and becomes colorless when
moisturized. Silica gel can be recycled by heating to 120 degrees until the color turns
back to pink.
5. Roller
Bi-directional rollers are used for ground mounted units: diameter 125mm for ratings
up to 630 kVA, diameter 150/200 mm for higher ratings.
40
7 - Package and Unit Substations
Design and Structure
alfanar Package and Unit Substations are completely self-contained solutions for power distribution that include
outdoor duty enclosure, medium voltage switchgear, distribution transformer, low voltage panel, and accessories
such as power factor improvement equipment, control and protection equipment, all providing a cost effective and
efficient total installation. It can be manufactured as a lighting substation (LSS), or Step Down/Step up substations,
MV/MV, MV/LV, LV/:V
The solution packages are built in accordance to IEC Standards and Saudi Electricity Company (SEC)
specifications, where the distinguished design provides the customer with a high level of flexibility to cover a wide
range of applications.
The construction of the unit substation is almost the same as the package substation but without the MV side.
MV Side (Ring Main Unit)
Each package substation contains the MV part which is in most cases the Ring Main Unit, known as the (RMU).
alfanar has designed its own RMU under the name of SFA-RM.
SFA-RMs are designed for the supply of sustainable energy and protecting electrical equipment in secondary
distribution networks up to 36kV.
SFA-RM units are the best solution for indoor/outdoor distribution substations.With their compact design they suit
various network applications such as transformer substations, wind power plants, industrial zones.
Rated Frequency 50 / 60 Hz
21 KA / 1 Sec
Rated Short Time Withstand Current
21 KA / 3 Sec
Rated Filling SF6 Gas Level for Insulation 1.2 bar (absolute)
Electrical Endurance
E3 / E0
Switch-Disconnector/Earthing Switch
Mechanical Endurance M1
Ring Switch
Feeder (S)
Nominal Current Up to 630 A
Short Circuit Making Current 21 kA (also valid for earthing switch) 54.6kA Peak
Electrical Endurance E3
Mechanical Endurance M1
TEE-OFF
Feeder (B)
Nominal Current Up to 630 A
• Oil immersed conservator type or hermetically sealed or dry type transformers can be installed
• Transformer bushings can be located on top or side of transformer as per customer needs
• Wide range of transformer capacities up to 3150 kVA
• Typical kVA’s: 75, 100, 150, 160, 200, 250, 300, 315, 400, 500, 630, 750, 800, 1000, 1200, 1250, 1500,
1600, 2000,2500, 3000, 3150
• alfanar package and unit substations are designed for simple and easy transformer installation onsite or
integrated into the PSS in the factory
44
Low Voltage Panel
LV Panel is manufactured for safe distribution and efficient control of electricity in residential, commercial and
industrial premises.
• Incoming feeder options can be directly connected with circuit breakers and busbar links
• The LV busbar rating depends on the transformer rating
• Various number and ratings of outgoing feeders depend on transformer size and customer requirements
• Equipment for metering, protection, BMS, SCADA and control is available
• Incoming breaker up to 5000 A (Drawout/Fixed, Manual/Motorized)
• Current transformers
• Outgoing circuit breakers
• Sleeves busbar
• Special requirements-Auto transfer system (ATS), Power factor correction (PFC)
PSS Technical Features
General
MV and LV Up to IP 54
Degree of Protection
Transformer IP 23
Electrical Characteristics
Transformer
46
8 - Service
To complement its position as a market leader of transformer manufacturing and supply, alfanar provides testing
and commissioning services.
Our highly qualified and competent commissioning engineers undertake the complete electrical testing and
commissioning of transformers and ancillary equipment.
• Live testing is performed on the circuits if the result of the dead test has been recorded as unsatisfactory,
and once the installation has been put back together following the dead testing.
Therefore, alfanar has equipped its testing lab with the most modern testing equipment and instrumentation
devices to ensure conformity to the highest level of quality and safety, where every transformer produced by
alfanar is tested according to IEC Standards.
Routine Tests
1- Measurement of winding resistance
2- Measurement of voltage ratio and phase displacement
3- Measurement of short circuit impedance and load losses
4- Measurement of no-load losses and current
5- Dielectric routine tests
(separate source AC voltage withstand test and short duration induced over-voltage withstand test)
6- Measurement of insulation resistance
Type Tests
1- Temperature rise test according to IEC 60076-2
2- Lighting impulse test according to IEC 60076-3
Special Tests
1- Short circuit withstand test (as per IEC 60076-5)
2- Measurement of zero-sequence impedance(s) on three-phase transformers
3- Determination of sound levels (as per IEC 60076-10)
4- Measurement of the harmonics of the no-load current
48
10 - Inquiry Form
Ref No:
Customer Name :
Project :
CRM sub-opportunity :
7- Max. altitude from sea level of operating location of transformer < = 1000 >1000
Parameter of Transformer
1 Quantity Unit
7 Rated frequency 60 HZ 50 Hz
Use Standard Accessories ( Oil level indicator - Oil thermometer - Pressure relief valve.) Yes No
Roller Yes
50
Notes
For catalogue soft copy scan QR code MKT_129576_Dry Manual_Jan 2023
www.alfanar.com