Hvac Boq1
Hvac Boq1
Hvac Boq1
24"x10" - -
16"x10" - -
E.G
20"x12" - -
20"x14" - -
40x28 - 2
FRESH AIR 40"x24" - 4
LOUVER with
back drift damper 48"x20" - 4
60x20 - -
40x24 - 15
40x28 - 4
20x12 - 2
FRESH AIR LOUVER 30x8 - -
WITH SAND TRAP
40x16 - -
30x14 -
60x20 - 1
60x36 - -
20X10 - 2
24X12 - -
DOOR LOVER
24X18 - -
24X20 - 1
46X16 3 -
E.A.L 32"X10" - -
24X16 - 4
Pressure reilf damper
with pressur control 24X24 - 7
system
LOCATION
UPPER TOTAL
1ST 2ND 3RD 4TH ROOF
ROOF
- 6 11 4 - - 22
1 28 21 - - - 72
4 13 12 1 2 - 41
7 47 21 6 - - 113
103 94 59 16 46 - 409
64 45 77 65 33 - 310
13 16 12 - 18 - 62
- - - - - - 3
3 - 1 - 2 - 6
3 34 16 6 - - 88
45 84 48 7 13 - 258
56 24 38 35 - - 168
9 15 9 14 30 - 87
1 1 1 - - - 3
- - - 3 - - 3
24 49 52 11 - - 136
3 41 27 1 - - 72
8 14 12 - - - 34
- 5 2 - - - 7
23 10 2 - - - 35
- 5 6 4 - - 15
19 - - 1 - - 20
- 4 3 - - - 7
- - - - - - 1
- - - 3 - - 3
- - - 32 - - 32
- - 2 - - - 2
- - - 3 - - 3
- - - 3 - - 3
- - - 3 - - 3
- - - - - - 2
- - - - - - 4
- - - - - - 4
- - - - 4 - 4
- - - - - - 15
- - - - - - 4
- - - - - - 2
1 - - - - - 1
2 - - - - - 2
1 - - - - - 1
- - - - - - 1
2 - - - - - 2
- - - 3 2 - 7
2 - - - - - 2
2 - - - - - 2
- - 2 2 - - 5
- - - - - - 3
8 - - - - - 8
- - - - - - 4
- - - - - - 7
LOCATION
TYPE VALVE SIZE UPPER
GROUND 1ST 2ND 3RD 4TH ROOF
ROOF
BALL VALVE Ø 1"
Ø 3/4 " 2 - - - - - -
Ø1" - - - - 2 - -
Ø 1 1/4 " - - - 2 - 2 -
Ø 1 1/2 " 2 - - 4 4 - -
Ø2" 2 - 4 - 2 4 -
GATE VALVE
Ø 2 1/2 " 2 - 2 2 - 2 -
Ø3" - 2 4 2 - - -
Ø4" - 2 2 - - - -
Ø6" - 2 - - - - -
Ø 10 " - 2 - - - - -
Ø 3/4 " 1 - - - - - -
Ø1" - - - - 1 - -
Ø 1 1/4 " - - - 1 - 1 -
Ø 1 1/2 " 1 - - 2 2 - -
Ø2" 1 - 2 - 1 2 -
BALANCE VALVE
Ø 2 1/2 " 1 - 1 1 - 1 -
Ø3" - 1 2 1 - - -
Ø4" - 1 1 - - - -
Ø6" - 1 - - - - -
Ø 10 " - 1 - - - - -
TOTAL
2
2
4
10
12
8
8
4
2
2
1
1
2
5
6
4
4
2
1
1
ITEMS
Basement
CHILLED WATER NETWORK
CHILLER- 650 T.R
0
(Baltimor, evapco or approved equal) fitlration system (sand filter withfttration pump
300gpm
Local Handrails , Ladder & Safety Cage and Internal Lower Walkway
0
CHILLED WATER PRIMARY PUMPS -1560GPM
0
CHILLED WATER SECONDARY PUMPS 1560GPM
0
C.T-01 rate flow rate 1950 gpm
0
C.T.P-1,2,3,4 constant speed (1450 RPM) pumps -1950 GPM
0
Expansion tank with pressurizing unit
0
Chilled Water Network
- Dosing system shall be automatic type c/w dozing pumps and controls for automatic operation
0
Condenser Water Network
- Dosing system shall be automatic type c/w dozing pumps and controls for automatic operation
0
- Operation hours :18 [hr/day]
System Cleaning and Flushing include supply of chemicals and provision of Systems Cleaning and Flushing include
supply of chemicals and provision of cleaning equipment, System Cleaning and Flushing based on building chilled water
network and capacity of chiller. 0
COOLING CAPACITY 3X 650 T.R
0
AIR SEPERATOR(FLUSHING TYPE)
Supplying, installing, and commisioning of an air seperator and a make up water assembly c/w alla connections, isolation
valves, check valves, flow meters, presure regulating valves, relief valves, pressure gagues, strainers, piping, mounting
frame. ets, as herein specified and according
to P.T.S & P.D. 0
- dia 14"
0
AIR HANDLING UNIT
Supplying, Installing, and testing commissioning of double skin (5cm- insulation internal and external sheet 1.0 mm) Air
Handling Units 450- 550 f.p.m coile velocity according to the schedules and specifications including
accessories,components,supply fan, electric heater, cooling coil, HEPA FILTER, bag filter, prefilter,supply plenum box,
mixing box, dampers, and (copper tube aluminum fin with zinc coated), DIDW high efficiency air foil , forward or backward
curved fan, [C/W window + lamp+ eliminator
+acces door hanging ,.. etc] and all necessary accessories as per standard specification. (not include the VFD) earthing, and steel
base and frame, hookup,shut-off valves, balancing valve, PICV control valve, drainage valves, vent valves, strainer, neoprene
connectors, thermometers, pressure gauges, piping required to be connected with the system include fittings, flanges, bolts, nuts,
gaskets, supports and paint, Rubber pads, sealers for leakage, thermal insulation complete with cladding, tags, labels, flow
indicators and color code finishing, duct connection and flexible duct at supply and fresh air intake. See arrangement drawing,
and detail drawings. (air handling units classified hygienic). See arrangement drawing, and detail drawings.Note:- Final static
pressure to be submitted by contractor for approval without
variation order or extra cost.
SUPPLY AIR VALVE Box
A.V-SA-02 0
A.V-SA-03 0
A.V-SA-04 0
RETURN/EXHAUST AIR VALVE Box 0
A.V.R-EXH-00 0
A.V.R-EXH-01 0
A.V.R-EXH-02 0
A.V.R-EXH-03 0
A.V.R-EXH-04 0
FRESH AIR VALVE Box 0
A.V.R-FA-01 0
A.V.R-FA-02 0
A.V.R-FA-04 0
WALL MOUNTED TYPE WITH GRAVITY SHUTTER ائطيةEمراوح ح 0
W.M-17 1700 CFM WITH 0.10 in.wg
0
W.M-20 2000 CFM WITH 0.10 in.wg
0
- W.M-01 100 CFM WITH 0.10 in.wg
1
- W.M-02 200 CFM WITH 0.10 in.wg
0
W.M-05 500 CFM WITH 0.15 in.wg
0
W.M-12 1200 CFM WITH 0.25 in.wg
0
W.M-035 3500 CFM WITH 0.35 in.wg
0
W.M-05 5000 CFM WITH 0.35 in.wg
0
CENTRIFUGAL INLINE EXHAUST FAN
- FCU - P -03, 800 CFM with 2.0 T.R and 0.20 inwg 0
- FCU - P - 04, 1000 CFM with 2.50 T.R and 0.25 inwg 0
- FCU - P - 05, 1200 CFM with 3.0 T.R and 0.25 inwg 0
FAN COIL UNITS WITHOUT ELEC HEATER :
0
SP.U-12, 12,000 BTU/HR
3 0 0 0 0 0 0 3
3 0 0 0 0 0 0 3
4 0 0 0 0 0 0 4
4 0 0 0 0 0 0 4
0 3 0 0 0 0 0 3
0 4 0 0 0 0 0 4
0 1 0 0 0 0 0 1
1 0 0 0 0 0 0 1
0 1 0 0 0 0 0
0 1 0 0 0 0 0 1
0 0 0 0 0 0
0 1 0 0 0 0 0 1
0 0 0 0 0 0
0 1 0 0 0 0 0 1
0
0 0 0 0 0 1 0 1
0 0 0 0 0 2 0 2
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 1 0 0 0 0 0 1
0 0 0 0 0 0 1 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 1 0 0 0 0 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 1 0 0 0 0 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0
0
0
0
0 0 0 0 0 4 2 6
0
0 0 0 0 0 3 3 6
0 0 0 0 0 0 1 1
0
3 0 0 0 0 0 0 3
2 0 0 0 0 0 0 2
4 0 0 0 0 0 0 4
2 0 0 0 0 0 0 2
0
1 0 5 7 5 0 0 18
0 0 1 9 0 0 0 10
0 1 0 0 0 0 0 1
1 0 0 0 0 0 0 1
0 0 3 0 0 0 0 3
1 0 4 6 5 0 0 16
0 0 3 0 0 0 0 3
0 0 1 0 0 0 0 1
0 0 0 3 0 0 0 3
0 0 0 3 0 0 0 3
0 0 0 2 0 0 0 2
0
0 1 0 0 0 0 0 1
0 5 0 0 0 0 0 5
2 1 1 1 1 0 0 6
10 0 0 0 0 0 0 10
0 0 0 0 0 4 0 4
0 2 0 0 0 0 0 2
2 0 0 0 0 0 0 2
3 0 0 0 0 0 0 3
0 0
2 0 0 0 0 0 0 2
0 1 0 0 0 0 0 1
0 0 0 0 0 8 0 8
0 0 25 14 0 0 0 39
0 1 0 1 0 0 0 2
0 0 0 0 0 0 1 1
1 0 0 0 0 0 0 1
4 0 0 0 0 0 0 4
0 1 0 0 0 0 0 1
0 0 0 0 0 0 0 1
0
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
1 0 0 0 0 0 0 1
0 0
0 0 0 0 0 2 0 2
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 2 0 2
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 1
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
0 0 0 0 0 1 0 1
0 0
0 0 0 0 1 1 0 2
0 0
0 0 0 32 17 0 0 49
0 0 0 2 1 0 0 3
0 0 0 2 3 0 0 5
0 0
24 3 24 15 9 0 0 75
5 1 19 8 4 2 0 39
4 7 21 1 2 0 0 35
7 6 7 7 13 0 0 40
6 0 4 0 0 0 0 10
8 0 0 0 0 0 0 8
1 0 0 0 0 0 0 1
1 2 2 2 2 4 0 13
0 3 0 0 0 0 0 3
2 0 0 0 0 0 0 2
0 0 0 0 0 1 0 1
0 0 0 0 0 0 1 1
3 0 0 0 0 1 0 4
3 0 0 0 0 4 0 7
10 0 0 0 0 6 0 16
0 0 0 0 3 0 0 3
0 0 0 0 1 0 0 1
0 0 0 1 0 0 0 1
1 0 0 0 0 0 0 1
0 1 0 0 0 0 0 1
Length (m)
Pipe Diameter (in)
Ground 1st 2nd 3rd 4th Roof
Ø 3/4" 215.30 16.74 279.40 214.26 96.26 37.30
Ø 1" 168.00 178.00 275.25 320.00 217.30 370.30
Ø1.25" 128.84 68.99 128.21 145.96 92.71 150.50
Ø 1.5" 104.08 34.35 68.59 56.94 52.85 83.05
Ø2" 77.70 26.35 208.61 38.82 30.56 56.47
Ø 2.5" 52.57 54.29 76.80 3.90 103.80 30.40
Ø 3" 48.92 64.34 4.58 - - 88.27
Ø 4" - 137.19 15.66 - - 22.80
Ø 5" - - - - - 5.21
Ø 6" - 275.04 - - - 176.55
Ø 8" - 7.02 - - - 4.00
Ø 10" 100.80 68.46 - - - 25.90
Ø 12" - - - - - 20.60
Ø 14" 177.11 - - - - -
Ø 16" 59.75 58.65 - - - -
ength (m)
Upper upper Total Length(M)
Upper roof RISER
roof
- - 20.00 879.26
8.57 - 24.00 1,561.42
75.69 - 24.00 814.90
7.17 - 24.00 431.03
56.14 - 24.00 518.65
- - 20.00 341.76
59.16 71.50 26.00 362.77
98.70 3.23 26.00 303.58
- - 20.00 25.21
63.52 - 24.00 539.11
114.75 - 24.00 149.77
- - 20.00 215.16
- - 20.00 40.60
- - 4.00 181.11
- - 8.00 126.40
Duct type Weight (Ton) notes
Galvanized steel 192.3
Black steel 1.2 for exhaust fan in kitchen
Stainless steel 0.3 for exhaust fan in kitchen
General notes:
01 Supply installation and commissioning of a complete system of Air
condition system, ductwork, all piping, fittings and controls as herein
specified and shown on plans. Price for system shall include all required
equipment accessories, pipe sleeves & Escutcheons, Equipment
identification, tools & spare parts, protective painting of all systems ...etc.
15623 01
WATER- COOLED CENTRIFUGAL CHILLERS:
02.2 (Baltimor, evapco or approved equal) fitlration system (sand filter withfttration pump 300gpm
Local Handrails , Ladder & Safety Cage and Internal Lower Walkway No. 3 3
supply and install steel structure base and frame for three cooling towers
02.3 L.S 1 1
02.4 above (desigen to be supplied by contractor and to be approved by consultant) L.S 1 1
15540 03 CHILLED WATER PUMP
Supply,Installation, connection, testing, balancing and commissioning of chilled water pumps (VERTICAL
INLINE TYPE), according to the schedules and specifications including all accessories, components, coupling
guard, include to supply steel base and frame, shut-off valves Balancing valve, Suction Diffuser , check valve,
drainage valve, vent valve, strainer, neoprene connectors, earthing ,piping required to be connected with the
system including fittings, flange, bolts, nuts, gaskets, supports, painting, thermometers temperature, pressure
gauge, thermal insulation for pump complete with aluminum cladding, tags, labels flow indicators and color
codes.capacity must be matching and compatible with above chiller, Isolation and supporting against seismic
and all other accessories as shown per drawings and specifications and the assets of the industry to be
certified brands Bell and Gossett - Crane- Armstroing - or approved
equal - item including. 1- With skide base and viberation isolators & 2-
04 CONDENSER WATER PUMP
Supply,Installation, connection, testing, balancing and commissioning of condenser water pumps(vertical
inline TYPE), according to the schedules and specifications including all accessories, components, coupling
guard, include to supply steel base and frame, shut-off valves Balancing valve, check
04.1 C.T.P-1,2,3,4 constant speed (1450 RPM) pumps -1950 GPM at static head of 100FT.(one is stand by) No. 4 4
15526 05 EXPANSION TANKS (WITH PRESSURIZING UNIT) لتمددBBزاناBخ
Supply and Install of closed type expansion tank with pressurization unit and according to the schedule and
specifications including all accessories, pumps ,components, steel base, frame, water shut-off valves, vent
valves, drain valves, level indicator, cortroler valves, thermometers temperature and pressure solenoid valve,
piping required to be connected with the system include, fittings, flanges, bolts, nuts, gaskets, supports and
painting, rubber pads for sound, thermal insulation of the tank complete with cladding, tags, labels flow
indicators and color finishing, startup and commissioning of the unit. Isolation and supporting against seismic
of
above mentioned Expansion Tanks
05.1 1- Closed type dynamic expansion with two pump and control system
2- standard accessories
3- Steel base and frame
4- Level indicator
5- gauges
6- Piping
06.1 Chilled Water Network
06.1.1 - Dosing system shall be automatic type c/w dozing pumps and controls for automatic operation
Sys. 1 1
06.2 Condenser Water Network
- Dosing system shall be automatic type c/w dozing pumps and controls for automatic operation
Supplying, Installing, and testing commissioning of double skin (5cm- insulation internal and external sheet
1.0 mm) Air Handling Units 450- 550 f.p.m coile velocity according to the schedules and specifications
including accessories,components,supply fan, electric heater, cooling coil, HEPA FILTER, bag filter,
prefilter,supply plenum box, mixing box, dampers, and (copper tube aluminum fin with zinc coated), DIDW high
efficiency air foil , forward or backward curved fan, [C/W window + lamp+ eliminator
+acces door hanging ,.. etc] and all necessary accessories as per standard specification. (not include the VFD)
earthing, and steel base and frame, hookup,shut-off valves, balancing valve, PICV control valve, drainage valves,
vent valves, strainer, neoprene connectors, thermometers, pressure gauges, piping required to be connected with the
system include fittings, flanges, bolts, nuts, gaskets, supports and paint, Rubber pads, sealers for leakage, thermal
insulation complete with cladding, tags, labels, flow indicators and color code finishing, duct connection and flexible
duct at supply and fresh air intake. See arrangement drawing, and detail drawings. (air handling units classified
hygienic). See arrangement drawing, and detail drawings.Note:- Final static pressure to be submitted by contractor
for approval without
variation order or extra cost.
08.1 Arrangement (A) OPERATING ROOM
08.1.1 F.AHU-CESAREAN DELIVERY-01, 2900 CFM 25 TR WITH 2.0 in.wg No. 0 1
08.1.2 F.AHU-OP-01, 1600 CFM 13 TR WITH 3.00 in.wg No. 2 2
08.1.3 F.AHU-OP-02, 2200 CFM 17 TR WITH 3.00 in.wg No. 1 1
08.1.4 F.AHU-OP-03, 3000 CFM 25 TR WITH 3.00 in.wg No. 2 1
00.1.7 Arrangement (B) Total fresh air
08.4.3 F.AHU-OD-01, 15350 CFM 110 TR WITH 2.0 in.wg No. 1 0
08.4.4 F.AHU-03, 4800 CFM 35 TR WITH 2.0 in.wg No. 0 1
08.4.5 - F.AHU-R-03, 4950 CFM 35 TR WITH 2.0 in.wg No. 1 0
08.4.6 - F.AHU-R-06, 12800 CFM 90 TR WITH 2.0 in.wg No. 1 0
08.4.7 F.AHU-06, 12950 CFM 92 TR WITH 2.0 in.wg No. 0 1
08.4.8 F.AHU-LAB-01, 5400 CFM 38 TR WITH 2.0 in.wg No. 1 1
08.3 ARRANGEMENT ( C) ISOLATION ROOM WITH HEPA
08.3.1 F.AHU-ISO-01, 3650 CFM 25 TR WITH 3.0 in.wg No. 1 1
08.3.2 F.AHU-ISO-02, 7700 CFM 55 TR WITH 3.0 in.wg No. 1 1
08.3.3 F.AHU-END-01, 8450 CFM 56 TR WITH 3.0 in.wg No. 0 1
08.4 ARRANGEMENT ( D) FRESH AIR FOR FCU
08.4.1 F.AHU-01, 3225 CFM 16 TR WITH 2.0 in.wg No. 0 1
08.4.2 - F.AHU-01, 2350 CFM 12 TR WITH 2.0 in.wg NO. 1 0
08.4.3 F.AHU-R-01, 5425 CFM 25TR WITH 2.0 in.wg No. 0 1
08.4.4 F.AHU-02, 3700 CFM 18 TR WITH 2.0 in.wg No. 1 1
08.4.5 F.AHU-04, 3550 CFM 17 TR WITH 2.0 in.wg No. 0 1
08.4.6 F.AHU-05, 10955 CFM 52 TR WITH 2.0 in.wg No. 0 1
08.4.7 FAHU-OP.DEP-01, 15400 CFM 110 TR WITH 2.0 in.wg No. 0 1
08.5 ARRANGEMENT ( F ) (CIRCULATING)
08.5.1 -AHU-01, 6800 CFM 22 TR WITH 1.50 in.wg No. 1 0
08.5.2 AHU-02, 7850 CFM 25 TR WITH 1.50 in.wg No. 1 0
08.5.3 -AHU-03, 13700 CFM 43 TR WITH 2.0 in.wg No. 1 0
08.5.4 -AHU-04, 15200 CFM 47 TR WITH 2,00 in.wg No. 1 0
08.5.2 AHU-02, 8050 CFM 24 TR WITH 1.50 in.wg No. 0 1
08.5.3 AHU-03, 17750 CFM 55 TR WITH 2.0 in.wg No. 0 1
08.5.4 AHU-04, 14500 CFM 45 TR WITH 2,00 in.wg No. 0 1
08.5.4 AHU-05, 15450 CFM 70 TR WITH 2,00 in.wg No. 0 1
08.5.4 AHU-06, 4500 CFM 70 TR WITH 2,00 in.wg No. 0 1
08.5.5 AHU-KIT-01, 5550 CFM 20 TR WITH 1,50 in.wg No. 1 1
08.5.5 AHU-KIT-02, 15200 CFM 50 TR WITH 1,50 in.wg No. 0 1
08.5.5 AHU-KIT-03, 12900 CFM 41 TR WITH 1,50 in.wg No. 0 1
08.5.6 -AHU-LUND-01, 7250 CFM 25 TR WITH 2,00 in.wg No. 1 1
08.5.7 AHU-COR-01, 14850 CFM 40 TR WITH 2,00 in.wg No. 1 1
08.5.8 -AHU-COR-02, 14,000 CFM 43 TR WITH 2,00 in.wg No. 1 0
08.5.8 AHU-COR-02,13650 CFM 43 TR WITH 2,00 in.wg No. 0 1
Supplying, installing & commissioning of DECORATING HIGH WALL, c/w, cooling coil ARI, AL fins coil,
expansion device,thermostate, charging valves, multispeed fan motor and controls, remote control switch, overloads,
controls, wirring contactors, refrigerant charge, supports, and all necessary accessories as per specifications and
drawings, with the following
specifications.
Supply, install, connection, testing and commission of VRV Heat Pump Outdoor unit complete with all standard,
double skin accessories as shown on drawings, schedules and specifications such as (DX- coil with copper tube
pipes, copper fins, axial fan vertical direction ulta low noise fan, scroll hermatic compressor type, one circuit, type
with R-410A, Safety Devices & all accessories and all necessary accessories as per specifications and
drawings with the following specifications.
12 DX SPLIT UNITS
Supplying, installing & commissioning of split air conditioning unit, c/w, hermatic compressor, condenser coil,
condenser fan and motor, expansion device, charging valves and controls, evaporator unit, remote control
switch, overloads, controls, wirring contactors, refrigerant charge, refrigerant pipes supports,refrigerant pipes
and all necessary accessories as per specifications and drawings, with the following specifications:-
12.1 High wall (Decorative Split Type)
12.1.1 SP.U-12, 12,000 BTU/HR No. 3 4
12.1.2 SP.U-24, 24,000 BTU/HR No. 7 7
12.1.3 SP.U-30, 30,000 BTU/HR
No. 18 16
Ceiling fan
Supplying and Install, co-ordinate with supplier,connection, testing,
balancing, startup and commissioning of Ceiling fan, air crrtain c/w electrical power and control cables
connection
, and all necessary accessories as per the specifications, drawings, and as herein specified:
Ceiling fan
12.1.00 3 blade diameter 56" No. 18 0
12.1.00 FANS
13.1.1 Supplying, installing & commissioning of Exhaust fans;wall mounted type, epoxy coated impeller and
housingc/w electric motors class F IP55
, casing, gravity shutter, and bird screen at discharge sid
e, hangers, supports, canvass duct connections, electrical power and control cables connection, and all
necessary accessories as per the specifications
, drawings, and as herein specified: Note:- Final static pressure to be submitted by contractor for approval
without variation order or extra
13.1.00 WALL MOUNTED TYPE WITH GRAVITY SHUTTER ائطيةOمراوح ح
14.1.1 - W.M-01 100 CFM WITH 0.10 in.wg No. 6 6
14.1.2 - W.M-02 200 CFM WITH 0.10 in.wg No. 11 10
14.1.3 - W.M-03 300 CFM WITH 0.15 in.wg No. 1 0
14.1.4 - W.M-04 500 CFM WITH 0.15 in.wg No. 1 4
14.1.5 - W.M-05 1000 CFM WITH 0.25 in.wg No. 2 0
14.1.6 - W.M-06 2000 CFM WITH 0.25 in.wg No. 2 2
14.1.7 - W.M-07 3000 CFM WITH 0.35 in.wg No. 2 0
14.1.8 - W.M-08 4000 CFM WITH 0.35 in.wg No. 2 0
14.1.9 - W.M-09 5000 CFM WITH 0.35 in.wg No. 5 3
14.1.10 W.M-17 1700 CFM WITH 0.10 in.wg No. 0 1
14.1.11 W.M-20 2000 CFM WITH 0.10 in.wg No. 0 5
14.1.4 W.M-12 1200 CFM WITH 0.25 in.wg No. 0 2
14.1.7 W.M-035 3500 CFM WITH 0.35 in.wg No. 0 2
14.1.9 Note:- FOR ALL ELECTRICAL ROOM to be interlock with fire alame and figthing system
13.2.00 CENTRIFUGAL INLINE EXHAUST FAN
14.2.1 EXH.F-01, 100 CFM, 0.15 IN.WG No. 3 2
14.2.2 EXH.F-02, 200 CFM, 0.20 IN.WG No. 2 1
14.2.3 EXH.F-03, 300 CFM, 0.20 IN.WG No. 8 8
14.2.4 - EXH.F-P-01, 100 CFM, 0.20 IN.WG No. 51 39
14.2.5 - EXH.F-P-02, 150 CFM, 0.20 IN.WG No. 4 2
14.2.3 EXH.F-08, 800 CFM, 0.75 IN.WG No. 0 1
14.2.6 EXH.F-12, 1200 CFM, 0.75 IN.WG No. 0 1
14.2.6 EXH.F-30, 3000 CFM, 0.75 IN.WG No. 5 4
14.2.7 EXH.F-40, 4000 CFM, 0.75 IN.WG No. 1 1
14.2.8 EXH.F-75, 7500 CFM with 1.00 IN.WG No. 1 1
14.2.9 - EXH.F-84, 8400 CFM with 1.00 IN.WG No. 1 0
14.2.10 EXH.F-15, 150 CFM, 0.20 IN.WG No. 0 1
14.3.00 FAN SECTION
14.3.1 EXH.F-GR-01, 1300 CFM, 1.00 IN.W No. 1 1
14.3.2 EXH.F-GR-02, 1500 CFM, 1.00 IN.W No. 1 1
14.3.3 EXH.F-GR-03, 2350 CFM, 1.00 IN.W No. 1 1
14.3.4 EXH.F-GR-04, 3450 CFM, 1.25 IN.W No. 1 1
14.3.5 EXH.F-GR-05, 3700 CFM, 1.25 IN.W No. 1 1
14.3.6 - EXH.F-06, 6600 CFM, 1.25 IN.W No. 1 0
14.3.7 EXH.F-GR-06, 8800 CFM, 1.25 IN.W No. 0 1
14.3.8 EXH.F-GR-07, 7900 CFM, 1.25 IN.W No. 1 1
14.3.9 EXH.F-STR-01, 10200 CFM, 1.25 IN.W No. 0 1
14.3.10 EXH.F-WSH , 12800 CFM, 1.5 IN.W No. 0 1
14.4.00 Centrifugal Belt Drive Type
14.4.1 - EXH.F-OP-01, 1650 CFM with 1.25 inwg No. 1 1
14.4.2 EXH.F-OP-02, 1600 CFM with 1.25 inwg No. 2 2
14.4.3 - EXH.F-OP-03, 2250 CFM with 1.25 inwg No. 1 1
14.4.4 - EXH.F-OP.DEP-03 8700 CFM with 2.00 inwg No. 1 1
14.4.5 - EXH.F-CE-01, 1300 CFM with 1.00 inwg No. 1 1
14.4.6 EXH.F-CE.COR-01, 1500 CFM with 1.00 inwg No. 1 1
14.4.7 - EXH.F-ISO-01, 3950 CFM with 2.50 inwg WITH HEPA FILTER No. 1 0
14.4.7 EXH.F-ISO-01, 4050 CFM with 2.50 inwg WITH HEPA FILTER No. 0 1
14.4.8 - EXH.F-ISO-02, 8750 CFM with 2.50 inwg WITH HEPA FILTER No. 1 1
14.4.9 - EXH.F-01, 600 CFM with 0.50 inwg No. 1 0
14.4.10 - EXH.F-02, 1250 CFM with 1.00 inwg No. 2 2
14.4.11 - EXH.F-03, 1500 CFM with 1.00 inwg No. 1 0
14.4.9 EXH.F-01, 600 CFM, 0.75 IN.WG No. 0 1
14.4.11 EXH.F-03, 1550 CFM, 1 IN.WG No. 0 1
14.4.12 EXH.F-04, 3350 CFM, 1.25 IN.WG No. 1 1
14.4.13 - EXH.F-05, 3700 CFM with 1.50 inwg No. 1 0
14.4.14 - EXH.F-06, 4450 CFM with 1.50 inwg No. 1 0
14.4.15 - EXH.F-07, 5350 CFM with 1.50 inwg No. 1 0
14.4.16 - EXH.F-08, 7000 CFM with 1.50 inwg No. 1 0
14.4.13 EXH.F-05, 4300 CFM, 1.5 IN.WG No. 0 1
14.4.14 EXH.F-06, 4800 CFM, 1.5 IN.WG No. 0 1
14.4.15 EXH.F-07, 5750 CFM, 1.5 IN.WG No. 0 1
14.4.16 EXH.F-08, 9800 CFM, 1.5 IN.WG No. 0 1
14.4.17 EXH.F-ENDO-63, 6800 CFM with 2.00 inwg No. 0 1
13.1.00 KITCHEN EXHAUST FAN
Supplying, installing & commissioning of Exhaust fans for kitchen exhaust 950 RPM, belt driven,tube
centrifugal ,black steel ,epoxy coated impeller and housing,suitabl
e for air stream up to 130C c/w electric motors class f IP55, casing, gravity shutter, and bird screen at
discharge side, hangers, supports, canvass duct connections, electrical power
and control cables connection, and all necessary accessories as per the specifications, drawings, and as herein
specified:
Note:- "notes:final
Final capacity
static pressure according
to be to by
submitted kit.contractor
furniture"
for approval without variation order or extra cost.
14.6.1 - EXH.F-KT-01, 9000 CFM with 2.25 inwg 1 1
FRESH AIR FAN
FAF-KT-01,8000CFM with 1.5 in w.g 1 1
FA.F-01,12500CFM WITH 2.5 IN W.G 0 1
14.8 Pressurization ROOF TOP FAN (FAN SECTION WITH PREFILTER)
Inter lock with pressure relif motorized volume damper
Supplying of Pressurization Fan c/w electric motors class f IP55, casing, steel
base, spring vibration isouator, canvass duct connections, electrical power and
control cables connection, and all necessary accessories as per the specifications, drawings, and as herein specified:
Note:- Final static pressure to be submitted by contractor for approval without
extra cost. No. 6 0
- PR.F-UR-01 16000 CFM with 2.00 inwg
14.8.1
Supplying of Pressurization Fan c/w electric motors class f IP55, casing, steel
base, spring vibration isouator, canvass duct connections, electrical power and
control cables connection, and all necessary accessories as per the specifications, drawings, and as herein specified:
Note:- Final static pressure to be submitted by contractor for approval without No. 0 6
extra cost.
- PR.F-UR-01 12000 CFM with 2.00 inwg
14.8.1
14.9 Smoke Fan
14.9.1 Supplying, installing & commissioning of smoke extraction fans; centrifugal type,epoxy coated impeller and
housing, smoke rated 300C for 2hr c/w electric motors class F IP55, long casing, gravity shutter, and bird
screen at discharge side, hangers, supports, canvass duct connections, electrical power and control cables
connection, and all necessary accessories as per the specifications, drawings, and as herein specified:
Note:- Final static pressure to be submitted by contractor for approval
Supply, installation, connecting, testing, commissioning and balancing of air curtain with all accessories,
components, devices as per schedules
and specifications
15.1 - AC-01 , (100 cm, 1600 cfm) No. 3 3
15.2 - AC-02 , (110 cm, 2200 cfm) No. 2 2
15.3 - AC-03, (120 cm, 2800 cfm) No. 4 4
15.4 - AC-04, (900 cm, 1200 cfm) No. 2 2
SUPPLY AIR VALVE Volume Box (Hyginic)
16 Supply and install of standard fan SUPPLY AIR VALVE volume concealed complete with digital thermostate
and all accessories standard, accessories as shown on drawings,( ONE OR 60 SECOND ACTION) schedules and
specifications and motorized volume control damper) factory assmebly complete with,temperature
controller, electrical heater, flexible connection, sealers for sound and leakage and isolation screens Item
including testing, balancing, startup and - commissioning of the units.and fitted to ductwork and including
electrical heater & power and control cables connection to AHU built into structure including insulation
to match surrounding ductwork as described in the specification and
16.1 SUPPLY AIR VALVE Box
16.1.1 A.V-SA-01 From ( 150 To 500 ) CFM 1 KW No. 3 0
16.1.2 A.V-SA-02 From ( 500 To 1000 ) CFM 3 KW No. 22 18
16.1.3 A.V-SA-03 From ( 1000 To 1500 ) CFM 3 KW No. 9 10
16.1.4 A.V-SA-04 From ( 1500 To 2000 ) CFM 6 KW No. 4 1
16.1.5 A.V-SA-06 From ( 2500 To 3000 ) CFM 9 KW No. 2 0
16.2 RETURN/EXHAUST AIR VALVE Box
16.2.1 A.V.R-EXH-00 No. 0 1
16.2.1 A.V.R-EXH-01 From ( 150 To 500 ) CFM No. 1 3
16.2.2 A.V.R-EXH-02 From ( 500 To 1000 ) CFM No. 22 16
16.2.3 A.V.R-EXH-03 From ( 1000 To 1500 ) CFM No. 8 3
16.2.4 A.V.R-EXH-04 No. 0 1
16.2.4 A.VR-EXH-07 From ( 3000 To 3500 ) CFM No. 1 0
16.3 FRESH AIR VALVE Box
16.3.1 A.V.R-FA-01 No. 0 3
16.3.2 A.V.R-FA-02 No. 0 3
16.3.3 A.V.R-FA-04 No. 0 2
17 DUCTED ELECTRIC STEAM HUMIDIFIER - WITH CONTROL PANLE
Supply, installation, connecting, testing, commissioning and balancing of steam humidifier with all accessories,
components, devices as per schedules and specifications includeing electrical power and control cables connection to
AHU, and all necessary accessories as per the specifications, drawings, and as
herein specified:
Supply and install, connecting, testing and commissioning of fan coil units (FCUs) according to the schedules
and specifications including accessories, component, complete with coils, fan, filter, water shut-off valves,
double regulating valves, drainage valve, vent valves, PICV control valves, strainer, neoprene connector and
dielectric connection,digital thermostate, copper or black seamless piping required to be connected with the
system include copper piping, fittings, bolts, nuts, gaskets, supports, paint, thermometers temperature,
pressure gauges, rubber pads sealer for leakage, thermostate, thermal insulation of the pipes complete with
tags, cladding, labels flow indicator and color code
finishing. with electric heater See connection drawing, detail and schedule drawings
18.1 FAN COIL UNITS WITH ELEC HEATER :
43101.0 - FCU - P -03, 800 CFM with 2.0 T.R and 0.20 inwg No. 49 49
43102.0 - FCU - P - 04, 1000 CFM with 2.50 T.R and 0.25 inwg No. 3 3
43103.0 - FCU - P - 05, 1200 CFM with 3.0 T.R and 0.25 inwg No. 4 5
18 FAN COIL UNITS WITHOUT ELEC HEATER :
43132 - FCU - 01, 400 CFM with 1.0T.R and 0.15 inwg No. 75 75
43133.0 - FCU - 02, 600 CFM with 1.5T.R and 0.15 inwg No. 39 39
43134 - FCU - 03, 800 CFM with 2T.R and 0.20 inwg No. 47 35
43135 - FCU - 04, 1000 CFM with 2.5T.R and 0.20 inwg No. 57 40
43136.0 - FCU - 05, 1200 CFM with 3T.R and 0.25 inwg No. 24 10
43137 - FCU - 09, 2000 CFM with 5T.R and 0.25 inwg No. 8 8
PIPE AND FITTINGS
19
Supply and install of black seamless steel pipes according to specifications and as shown on drawings
complete with pipes, fittings, specialties, tags, connections, flanges, bolts, nuts, gaskets, sealers, coupling and
expansion joint, supports, hangers including rods, anchors, beams, rollers, saddle and surface cleaning,
treatment, painting of flow indicators with color code finishing, cutting, normalizing bending as well as rubber
pads for sound isolation, testing, balancing and start-up to the
20 DRAIN PIPES AND FITTINGS
Supply, installation, connection, testing of drain piping network for HVAC system from galvanized steel for outdoor
drainage
piping and PVC for indoor drainage piping, complete with fittings
, and all other accessories as per drawings and specification.
Supply, installation connecting, testing and commissioning of galvanized or black steel or aluminum, or
stainless steel materials fabricated, according to the specifications and drawings including all accessories,
complete with-but not limited to: delivers, stored in good conditions, flexible connection, splitter linear
diffuser boxes, inspection doors, support, hangers, rods, anchors nuts, bolts, riveting and sealers, sleeves, tags,
charts labels, color code finishing, flow indicator, earthing, see detail
drawings.
Supply, installation, connection, testing and commissioning of fire dampers complete with all accessoreis as
shown on drawings and
24.1 1 square inch IN2 170,000 170,000
25 Volume damper
Supply, install, conntection, testing and commissioning of additional separation manual volume dampers and
blind capping flange, complete with all accessories as shown on drawing and specifications to manage
operation of stages.
29.2 Supply and install 12 mm thickness blanket arm flix duct insulation for acoustic absorption inside first section
of ducts connects to fan coil units and air handling units, non combustible, faced with smoth tissue with
minimum thekness 3mm, including all required adhesive, sealing, metal strips and any other accessories M2 12,000 12,000
needed for proper installation and
29.3 Supply, installation, connection, testing and commission of 0.3mm aluminum cladding for exposed duct and
pipes at the roof, and all accessories as shown on drawings and specifications.
M2 2,500 2,500
29.4 Supply, Installation, Connection, Testing and Commission of Black Steel Duct thermal insulation from rockwall
5 cm complete with all accessories as shown on drawings and specifications. M2 500 500
29.5 Supplying, fabricated ,installed ,connection and testing of armed flexible duct thermal insulation complete
with cladding, vapor barrier and all accessories as shown on drawings and specifications.
29.5.1 - dia 8" M 300 300
29.5.2 - dia 10"
M 250 250
15932
30 AIR DISTRIBUTION
Supply, install, connection, balancing and commissioning of grilles, slots, diffusers complete with-but not
limited to straightners, dampers, plenums, clamps, hangers support and paint and all other accessories as
per specifications and as shown on drawings.
30.2 Supply Ceiling Diffusers with face size 24"x24"
30.2.1 - 6"x6" No. 25 22
30.2.2 - 8"x8" No. 110 72
30.2.3 - 10"x10" No. 75 41
30.2.4 - 12"x12" No. 125 113
30.2.5 - 14"x14" No. 380 409
30.2.6 - 16"x16" No. 300 310
30.2.7 - 18"x18" No. 90 62
30.2.8 - In square (fixed price with any quantity) in2 1 1
30.3 Return Ceiling Diffusers
30.3.1 - 8"x8" No. 10 3
30.3.2 - 10"x10" No. 5 6
30.3.3 - 12"x12" No. 110 88
30.3.4 - 14"x14" No. 210 258
30.3.5 - 16"x16" No. 200 168
30.3.6 - 18"x18" No. 200 87
30.3.7 - 20"x20" No. 20 3
30.3.8 - 24"x24" No. 25 3
30.3.9 - In square (fixed price with any quantity) in2 1 1
30.4 Supply Register
30.4.1 16"x6" No. 10 1
30.4.2 16"x4" No. 4 3
30.4.3 - In square (fixed price with any quantity) in2 1 1
30.5 Exhaust Ceiling Diffusers
30.5.1 - 6"x6" No. 250 136
30.5.2 - 8"x8" No. 110 72
30.5.3 - 10"x10" No. 50 34
30.5.4 - 12"x12" No. 30 7
30.5.5 - 14"x14" No. 55 35
30.5.6 - 16"x16" No. 45 15
30.5.7 - 18"x18" No. 20 20
30.5.7 24"x24" No. 0 7
30.5.8 - In square (fixed price with any quantity) in2 1 1
30.6 Exhaust Grille
31.1 Total HVAC system testing, adjusting, and balancing, for both air and water by a third part specialized in such
works;having experienced personnel;well equipped with the approperiate devices, including all required
instrumentations, leakage tests, devices, reports, as per the standard specifications confirming the
requirements of ASHRAE. L.S 1 1
32 Painting to pipework
32.1 Painting to exposed piping as specification L.S 1 1
HVAC. WORKS
LE
TOTAL