Sinorix™

ACTF230-PNEUMS
IG-01 IG-55, IG-100, IG-541, CO2

Pneumatic actuator for F230 cylinder valve


● Compatibility with F230 valves
● Mounting on the actuation port PM
● Product includes pneumatic actuator and rotating tee fitting
● Multi-purpose: compatible with the entire pressure range used in the pilot line of
the Sinorix™ automatic CO2 or inert gas extinguishing systems with F230 cylinder
valves

Product code: S54476-B520-A1

A6V11162625_en--_b Smart Infrastructure


2023-05-25 Building Products
Use
This product must only be used with SinorixTM fixed automatic extinguishing systems.

Functions
An actuator is a valve opening device used to release the gas contained in the cylinder.
The pneumatic actuator is fitted to the cylinder valve PM actuation port. It is activated by the
pressure from the pilot line.

Type summary

Item Description Item Description

1 Rotating tee fitting with two L6 (m) 3 M18x1 connection to F230 PM port
connections (M12x1.5, EO 24°)

2 F1120046 pneumatic actuator 4 L6 (m) connection (M12x1.5, EO 24°)

Equipment combinations
Compatible valves

Reference Description Product code

F230-IG200 Cylinder valve F2302000 S54476-B500-A2

F230-IG300 Cylinder valve F2303000 S54476-B500-A3

F230-CO2-190 Cylinder valve F2301001 S54476-B500-A11

F230-CO2-250 Cylinder valve F2301000 S54476-B500-A1

Other associated products

Reference Description Product code

BLEED-360 PN360 L6 bleed valve S54476-B530-A2

2
Siemens Schweiz AG A6V11162625_en--_b
Building Products 2023-05-25
Notes
Safety
This product may only be installed by Siemens-authorized specialized installers, with
experience in the design, installation and maintenance of automatic extinguishing systems.
During installation, it must be ensured that:
● this product is installed in compliance with the accident prevention regulations and
national regulations in force,
● this product is used as intended,
● any danger is avoided,
● Siemens requirements are met (assembly instructions, technical instructions,
commissioning, and operating instructions),
● the operators have received and understood the information related to this product.
At commissioning, ensure compliance with the legislation in force, technical regulations and
safety instructions.
Failure to comply with Siemens' instructions may result in serious bodily injury or significant
property damage, for which Siemens cannot be held liable.
Siemens reserves the right to make technical modifications and/or improvements at any
time.
Mounting
● Remove the cap from the PM actuation port.
● Screw the actuator onto the PM valve actuation port by hand.
● Tighten using a 19 mm wrench:
Torque: 8 Nm
● Screw the actuator's tee fitting onto the actuator body by hand.
● Screw the pilot hoses and/or the bleed valve at the end of the pilot line onto the L6
outlets of the tee fitting by hand.
● Adjust the position of the hoses to guide the actuator's tee fitting.
● Tighten the tee fitting using a 14 mm wrench:
Torque: 5 Nm
● Tighten the pilot hoses and/or the bleed valve using a 14 mm wrench:
Torque: 5 Nm

Close the pilot line with a bleed valve.

Refer to the installation instructions for details.

3
Siemens Schweiz AG A6V11162625_en--_b
Building Products 2023-05-25
Maintenance

Storage
● Store in its original packaging, protected from shocks.
● Store in a clean and dry location, protected from bad weather.

Inspection

The product must be inspected as often as required by applicable local regulations. For
more information, refer to the maintenance documentation.

● Check that the product is in good condition.


● Check that each fitting has been properly tightened using the appropriate wrench. Re-
tighten if necessary.

Refer to the mounting and maintenance instructions to obtain the detailed procedure.

After an actuation
● Unscrew the actuator from the cylinder valve.
● Replace the cylinder.
● Move PM actuation port cap from full to empty cylinder.
● Fit actuator to the PM actuation port.

Only use actuators in good condition.

4
Siemens Schweiz AG A6V11162625_en--_b
Building Products 2023-05-25
Technical data

Technical data

Actuation pressure
nominal PN8 (bar)
minimum 8 bar(1)
maximum 360 bar

Gaseous agent IG-01, IG-55, IG-100, IG-541, CO2

Thread
Actuator M18x1 F230 cylinder valve (PM actuation port)
Tee fitting L6(M12x1.5)

Materials
Actuator body Brass, stainless steel
Tee fitting Galvanized steel
Seal NBR

Operating temperature -20 °C to +50 °C, non-condensing

Transport and storage temperature -40 °C to +70 °C, non-condensing

Weight (including tee fitting) 0.40 kg

(1)
includes the required safety factor

OEM type

F1120046

Certifications and compliances

VdS G320005

LPCB 126z/23

RoHS Compliant

305/2011/EU (CPR) EN 12094-4 / EN 12094-6 0786-CPR-30230

The declared performance and conformity can be seen in the Declaration of Performance (DoP) and/or the EU
Declaration of Conformity (DoC), which are obtainable via the Customer Support Center: Tel. +49 89 9221-8000
or https://siemens.com/bt/download.

5
Siemens Schweiz AG A6V11162625_en--_b
Building Products 2023-05-25
Dimensions

Dimensions in mm

Issued by
© Siemens 2023
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

Document ID A6V11162625_en--_b
Edition 2023-05-25

You might also like