5100332-00 - Salwico Cruise - User Guide - M - EN - 2018 - AA
5100332-00 - Salwico Cruise - User Guide - M - EN - 2018 - AA
5100332-00 - Salwico Cruise - User Guide - M - EN - 2018 - AA
1 Introduction....................................................................................... 1
1.1 About this Manual ............................................................................ 1
1.2 Approvals........................................................................................... 2
1.3 Symbols used in the manual ............................................................. 2
3 Control Panels................................................................................... 5
3.1 Control Panel M 4.3.......................................................................... 5
3.1.1 General............................................................................................ 5
3.1.2 Description of Keys and Indicators................................................. 5
3.1.3 Guide to the Menu System.............................................................. 9
4 Operations ......................................................................................... 21
4.1 Access Levels ..................................................................................... 21
4.2 Login.................................................................................................. 22
4.3 Pre-Alarm .......................................................................................... 22
4.4 Fire Alarm ......................................................................................... 22
4.4.1 Information Displayed when “Fire” is Flashing ............................. 22
4.4.2 Mute a Fire Alarm........................................................................... 23
4.4.3 Reset a Fire Alarm .......................................................................... 24
4.4.4 Several Alarms................................................................................ 24
4.4.5 Type of Fire Alarms from Conventional Zones .............................. 24
4.7 Reconnecting..................................................................................... 31
4.7.1 Reconnecting Disabled Items ......................................................... 31
4.7.2 Reconnecting Periodic Disablements ............................................. 31
4.7.3 Reconnecting Disabled Alarm Delays ............................................ 32
4.7.4 Remove All Disablements .............................................................. 32
5 Testing................................................................................................ 35
5.1 About Testing..................................................................................... 35
5.2 Test Mode Overview .......................................................................... 35
5.3 Testing a Fire-detecting Zone........................................................... 36
5.4 Recommended Test Equipment......................................................... 37
5.5 Reset Test Mode................................................................................. 37
5.6 Test the Control Panel Display ......................................................... 37
Index ................................................................................................. 62
User Guide 1 Introduction
1 Introduction
NOTE!
This user guide has been revised based on system version 1.10.10 but is valid for
Control panel software versions beginning with version 1.0.0.
The chapter Fire Detection System gives general information about the system.
The chapter Control Panels describes the function of the Control panel and the
Repeater in the Fire detection system.
The chapter Operations describes how to operate the Fire detection system.
The chapter Testing provides brief instructions on how to connect and test the
system (detailed information is found in the Service & Maintenance manual).
The Fault Code List in the Appendix lists the different fault codes.
1.2 Approvals
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint!
Hint symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
The Fire detection system is built on a scalable platform. A Single Central System
contains up to 126 Modules and a Multi Central System up to 30 Centrals.
3 Control Panels
As shown in the figure above, the control panel is divided into three sections:
A = System Indicators
B = Operational Controls
C = Numerical Keypad
1. Power
Steady green light Power supply to the control panel is OK.
2. System fault
Flashing yellow light Main process fault. A serious system fault in the
system.
3. Test
Steady yellow light At least one zone is manually set in test mode.
4. Warning
Steady yellow light At least one warning indication exists.
5. Zone
Steady yellow light At least one zone or a loop unit is disabled.
Flashing yellow light At least one zone or a loop unit is in fault condition.
(Priority over disablement indication.)
6. Alarm device
Steady yellow light At least one alarm device output is disabled.
Flashing yellow light At least one alarm device output is in fault condition.
9. USB
USB connection for USB memory stick to load or save data.
1. Main indicators
Fire alarm
The Fire alarm key indicates existance of a fire alarm and gives direct access to
the Fire alarm list. Indications:
Flashing red light One or more un-muted fire alarm(s) in the system.
Steady red light All fire alarms are muted.
Pre-Alarm
The Pre-Alarm key indicates existance of a pre-alarm and gives direct access to
the Pre-Alarm list. Indications:
Flashing orange light One or more un-muted pre-alarm(s) in the system.
Steady orange light All pre-alarms are muted.
Fault
The Fault key indicates existance of a fault and gives direct access to the Fault
alarm list. Indications:
Flashing yellow light One or more un-muted fault(s) in the system.
Steady yellow light All faults are muted.
Disablements
The Disablements key indicates existance of a disablement and activates the
Disablements menu. Indications:
Steady yellow light At least one disabled function in the system.
Shortcuts
The Shortcut key activates the customer specific shortcut list. Indications:
Steady orange light The alternatives in the shortcut list and the
corresponding indicators (Shortcut 1, Shortcut 2 and
Shortcut 3) are set in the configuration program.
2. Status
This key gives direct access to the System status summary list with Alarms
(Fire and Pre-Alarms), Maintenance (Faults and Warnings) and Disablements
(Active and Periodic).
Shortcuts are:
1. Upload the system log to USB Memory stick.
2. Go to the maintenance menu.
3. Menu
This key gives direct access to the main menu and all system functions.
4. Navigation and Command Keys
The arrow keys are used to navigate menus, select different menu alternatives,
and show details for list items.
Go to the previous item
in the list or menu.
ESC
The Escape key is used to go to the default menu.
OK
This key is used to select a menu alternative or to accept a function. The OK key is
also in some cases used to show details for a selected list entry.
5. Display
The control panel has a backlited 4.3" graphical, 480×272 pixels, 16-bit colour
display.
6. Alarm keys
Multiple alarms
Press this key to scroll through the different alarms. The list always returns to the first
fire alarm after 30 seconds of inactivity.
Reset
This green key is used to request for a reset of a selected alarm, fault or disablement.
Mute
This red key is used to acknowledge the alarm and mute the local buzzer.
1. Numerical keypad
Keys 0 - 9
The numerical keypad is used to enter numerical values. Keys 1–9 are also used as
shortcuts when navigating in the menus.
Erase
This key is used to erase characters from the text display.
Enter
This key is used to select a menu alternative or to accept a function. The Enter key is
also used to show details for a selected list entry.
Day mode
Increase the brightness/contrast level for the indicators and display on the panel.
Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.
In the lower part of the display the different options available for each individual
menu are shown.
The numerical keypad is used to enter information, e.g. zone and detector number.
1 Fault Alarms
2 Fire Alarms
3 Disablements
1 Fault List
4 Login
2 Warning List
5 Settings
3 Reset All Faults
6 Service Menu
7 History
8 Condition List
1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Fire List
4 Login 2 Pre-Alarm List
5 Settings 3 Resound (restart bells)
6 Service Menu 4 Reset All Fire Alarms
7 History
8 Condition List
3 Disablements menu
1 Fault Alarms
1 New disablement (access lvl 2B)
2 Fire Alarms
2 List disablements
3 Disablements
3 List periodic disablements
4 Login
4 List old disablements
5 Settings
5 Remove all disablements
6 Service Menu
6 Alarm Delay
7 History
7 List Alarm Delay
8 Condition List
Alternatives Description
3 External Control Deactivate 1 External Controls or 2 Alarm Transfer . See
list External Control Disablements, page 13 for more
information.
4 Alarm Device (Bells etc.) Disables the outputs for alarm devices, such as audible (e.g.
bells) and optical alarm devices.
5 Test Mode Set a zone into test mode.
2. Alarm Transfer
Disables the supervised alarm transfer output, which is normally used in
on-shore installations to alert the fire brigade in case of a fire alarm. Select
System or Central to disable.
See also section About Disablements, page 27 for more information about the
Disablements.
4 Login Menu
1 Fault Alarms
2 Fire Alarms
3 Disablements User 1
4 Login User 2
5 Settings User 3
6 Service Menu User 4
7 History
8 Condition List
See Login, page 22 for more information about the Login menu alternatives.
5 Settings Menu
1 Fault Alarms
1 Set Dimmer
2 Fire Alarms
2 Set Time
3 Disablements
3 Set Date
4 Login
4 Test Display
5 Settings
5 Alarm Delay Times
6 Service Menu
6 Keyboard Beep
7 History
7 Cause Effect in Test Mode
8 Condition List
6 Service Menu
Access level 2B is needed for basic functions and access level 4 is needed to
perform advanced service options.
Hint!
The Service menu is described in more detail in the separate Service and
Maintenance manual.
Configuration sub-menu
1 System Details
2 Centrals 1 Reload configuration/reboot this module
3 Modules 2 Load configuration from USB memory
4 Zones 3 Save configuration to USB memory
5 Loops 4 Save changes to configuration
6 Configuration 5 Remove configuration
7 Firmware 6 Synchronise system configuration
8 System Log 7 Reboot system (this module excluded)
9 I/O lists
Hint!
The Configuration menu is described in more detail in the Installation &
Commissioning manual and the Service & Maintenance manual.
7 History Menu
1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Fire History List
4 Login 2 Fault History List
5 Settings 3 Disable History List
6 Service Menu 4 Common History List
7 History
8 Condition List
1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Satisfactory
4 Login 2 Poor
5 Settings Detectors not listed in these two
6 Service Menu choices are in Good condition.
7 History
8 Condition List
The Condition list menu provides the means to perform a status check of the
detectors in the system. Detectors that are no longer in good condition but still fully
functional will be present in either of these lists, and detectors in good condition
will not be present at all.
NOTE!
In systems with CCP version 1.9.10 or older, dirty detectors are instead removed
from the poor condition list and are only present in the warning or fault list with
the description "130 DIRTY SENSOR".
• Fire alarms
• Fault alarms
• Disablements
Repeater panel
•
Power
Green steady light indicates that the power supply to the repeater panel is OK.
•
Local Mute
Silence the local buzzer alarm.
•
Fire - Fault - Dis.
Press the key to select the lists: Fire Alarm, Fault Alarm and Disablements.
•
Navigation key – previous
•
Navigation key – next
Scroll to next item in the selected list.
•
Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.
•
Day mode
Increase the brightness/contrast level for the indicators and display on the panel.
• Lamp test
When you press the keys for Day and Night mode at the same time, all the repeater
panel indicators as well as the display are lit and the buzzer is sounding – if not, they
are not working correctly.
4 Operations
Some functions in the menus will require a higher access level than the default
level due to safety restrictions.
Access level 2 is the default level. After the access level has been changed to a
higher level, it automatically returns to access level 2 when the control panel has
not been used for 30 minutes. For special applications access level 1 can be
applied. This will allow the user to only mute the local buzzer and scroll though the
fire and fault lists.
2B Operator access level Personnel trained and authorised to Same permissions as level 2, plus
Enter access code for level 2B operate the system in case of fire or this additional permission:
via menu/login. maintenance. • Make disablements
3 Power User access level Personnel trained and authorised to Same permissions as level 2B, plus
Enter access code for level 3 via make changes to the configured these additional permissions:
menu/login. system. • Possibility to make changes to
the configured system
4 Service access level Only authorised service personnel All functions available, including
Enter access code for level 4 via trained by an authorised service advanced service options.
menu/login. organisation.
A Control Panel M 4.3 could be programmed to view events in the system with
restricted rights to operate functions. For example a fire alarm is shown, but mute
and reset are not allowed.
4.2 Login
WARNING!
To secure the functionality of the fire detection system only authorised users
should be given access to disablement or test mode privileges in the system.
4.3 Pre-Alarm
The pre-alarm function gives an early alarm to fire conditions (e.g., a smouldering
fire). The indication “Pre-Alarm” begins flashing on the control panel.
Fire alarms have priority over pre-alarms, pre-alarms have priority over faults.
The pre-alarm is also added to the Pre-Alarm List found under: Menu » 2 Fire
Alarms » 2 Pre-Alarm List.
An active pre-alarm can be muted, this silences the internal buzzer and causes the
pre-alarm indicator to stop flashing. The indicator remains lit until the pre-alarm is
reset. A pre-alarm will remain in the Pre-Alarm List until it has been muted and
reset.
The pre-alarm usually does not activate any alarm devices or external outputs.
The following sections describes the information displayed during a fire alarm,
how to mute and reset an alarm, and the different types of alarms.
• Number of alarm(s)
• First, last and current list entry
• Zone in alarm
• Type of unit in alarm
• Address number of unit in alarm (only for addressable loop)
• Supplementary text (defined in system configuration)
• Time of alarm
• Date of alarm
• Supplementary text about location of the detector (defined in system
configuration)
WARNING!
If an internal hardware or software fault has occurred it has to be restored as
prompt as possible in order to secure the functionality of the complete fire
detection system.
• the repair of the faulty system within the mean repair time (MRT). During this
time the continuing safety shall be ensured by additional measures and
constraints. The safety integrity provided by these measures and constraints
shall be at least equal to the safety integrity provided by the FDS in the absence
of any faults.
The following sections describe the information that is displayed when a fault
occurs, and how to mute and reset a fault.
The control panel displays a fault with information about where in the system the
fault occurred and a short description of that fault.
Hint!
See the Fault Code list for further information about cause and remedy.
The fault message is also added to the fault list found under: 1 Fault Alarms » 1
Fault List.
4.5.7 Warnings
NOTE!
The user shall monitor and act on warning messages according to the presented
information about the state of the system. (Warnings are not as serious as faults and
only of informative nature.)
• Perform suitable maintenance if needed.
The warnings priority level is lower than the ordinary fault alarm level.
The warning is also added to the Warning list found under: Menu » 1 Fault Alarms
» 2 Warnings.
A warning will remain in the Warnings list until the fault condition is under the
level for warnings.
4.6 Disablements
4.6.1 About Disablements
WARNING!
To secure the functionality of the fire detection system only authorised persons
should be given access to disablement privileges in the system.
The available disablements (permanent, timer, clock and periodic) are described in
the next chapter.
NOTE!
The yellow Disablements indicator is lit on the control panel when at least one
disablement is activated in the system and remains lit until all disablements are
reconnected.
DANGER!
When a fire detector or zone is disabled, the fire detection system will not be able
to detect any occurring fire in that area. It is therefore important that disablements
are minimized in terms of quantity of disabled units and duration of time.
Hint!
If dual detectors heat/smoke are installed, it is possible to disable only the smoke
detection part of the detector and keep the heat detecting part active or vice versa.
Permanent disablement
The device is permanently disabled until it is manually enabled.
NOTE!
It is possible to limit the disablement time by defining a maximum disablement
time in the configuration program.
Timer disablement
Disablement is instantaneous and lasts for the time period entered (hh:mm).
Maximum disablement time is 23 hours 59 minutes. Maximum disablement time
can be limited depending on rules and regulations.
Clock disablement
Enter a reconnection time. Disablement is instantaneous and the reconnection will
take place next time the entered time occurs. The maximum disablement time is 23
hours 59 minutes.
Periodic disablement
A disablement for a certain time period during certain days of the week. Example:
Disable zone 1 each Tuesday and Friday between 7.00 - 17.00.
The new disablement is also added in the disablements list under: Menu » 3
Disablements » 2 Disablement list
NOTE!
Disabling of individual detectors is only possible on addressable loops.
Hint!
It is also possible to disable detectors from the Fire List.
NOTE!
Only permanent disablements can be reactivated.
The alarm delay may be disabled which means that there will be no delay between
the fire alarm and the activation of the alarm device outputs.
NOTE!
Delay time is only possible to set if no time is set in the configuration program.
Examples of external control groups are fans or outputs controlling fire doors.
4.7 Reconnecting
4.7.1 Reconnecting Disabled Items
All disablements in the system are presented in the disablement list. Any
reconnection is made from this list.
The Service menu is used for configuring the system in the commissioning phase,
as well as for troubleshooting and making updates when the system is in operation.
The menu has functions for loading and saving information from/to an approved
USB memory stick (available from an authorised dealer).
The Service menu displays a list of the 9 service menu alternatives, as shown
below.
1 System Details
2 Centrals
3 Modules
4 Zones
5 Loops
6 Configuration
7 Firmware
8 System Log
9 I/O lists
Please refer to the Service and Maintenance manual for detailed information about
the Service menu.
The system log files can be downloaded using an approved USB memory stick
(available from an authorised dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
1 Connect the USB memory stick to the USB port on the Control M 4.3
panel.
2 Choose Menu » 6 Service Menu » 8 System Log » 1 Save syslog.
3 Press OK to save the systems log files to the USB memory stick.
4 The system will now download the system log files. Wait until this process
is complete!
5 Disconnect the USB memory stick and copy the system log files to a PC.
File name example: sysLog_no_YYYY-MM-DD-xxxxxx
5 Testing
CAUTION!
Check for contaminated detectors. Use the Control panel menu system to display a
list showing in which condition the detectors are.
For additional information about testing, please refer to the Service and
Maintenance Manual.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
NOTE!
A warning will be displayed on the menu screen as long as the system is not
running Cause/Effect, which is the two first minutes after the system has been
powered up
• External alarm devices and controls are by default not activated in case of a fire.
Hint!
This functionality can be turned off if controls are to be tested while the
tested zone is in test mode.
(Menu » 3 Disablements » 1 New Disablement » 3 External Controls)
• The alarm level is lowered to give a quick response to detector test equipment.
• LED indicators on loop units are blinking.
• Each tested loop unit will indicate activation with a steady LED indicator.
• Key events (as well as information of system components and system software)
will be stored in the system log which can be saved on a USB memory stick. If
a printer is connected to the system, alarms will automatically be printed as a
result of the tested units.
• The units in alarm are automatically reset when the heat or smoke concentration
is under the alarm level, or when the test key is removed from the manual call
point.
NOTE!
Fire alarm from zones not in test mode will be handled normally by the fire
detection system.
The zone in test mode will automatically return to normal operation after two
hours.
CAUTION!
During system start-up the smoke detectors perform a 15 minutes calibration
according to the level of particles in the air. No tests should be done during this
period.
1 Put the zone into test mode under: Menu » Access level 2B is required.
3 Disablements » 1 New disablement » 5
Test Mode .
2 Select a zone and confirm by pressing the The Disablements, Test, and
key. Zone/Unit indicators light to
confirm that they are in test
mode.
Each detector, manual call point and input in this fire zone can be tested during the
next two hours. Refer to Test Mode Overview, page 35 for further information
about a zone in test mode.
All alarms are listed under: Menu » 7 History » 1 Fire History List .
To return the tested zone to its normal condition, refer to Reset Test Mode, page
37.
CAUTION!
If the system previously had been put into regular fire detection service, a zone in
test mode should be manually monitored, e.g. by a fire watch in order to maintain a
tolerable risk level.
NOTE!
Use appropriate test equipment.
See section Recommended Test Equipment, page 37.
For detailed information, please refer to the data sheets for the products.
1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 List disablements.
2 Choose the zone in the disablement list and then press .
• The display
• All indications on the control panel
NOTE!
The user has to verify that the display and all indications are working properly.
This function will not generate a fault alarm in case something is faulty.
1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
2 Verify that the display momentarily shows a test image.
3 Verify that all system indicators and operational keys momentarily lights
up.
WARNING!
In case of remedy “replace the unit” or “replace the module” – this has to be
carried out as soon as possible in order to secure the functionality of the fire
detection system.
Listed in the table below are all fault codes generated by system modules1 and loop units2 ,
their causes, and how an operator with knowledge of the system can classify and solve the
problem.
A fault generated by a system module is often identified as:
“CENTRAL nn Unit type nn Fault description , FAULT nnn”
A loop unit fault is often identified as:
“ZONE nn Unit type nn Fault description , FAULT nnn”
Hint!
Instructions for troubleshooting and replacement can be found in the Installation
manual or the Service & Maintenance manual.
Unit or
Fault Code Cause Remedy Failure classification
Module
One module has
been replaced by
Switch to the correct module. • Minor fault if
another type of
module. redundant system
and only one
One module address
module in the
has been changed to
redundant function.
the same address as
another module on Check address of the modules. • Major fault if
System the same backbone redundant system
modules (a secondary fault and one or more
appears). modules in the
redundant function.
Defect module. Replace the module.
Cable break, short • Major fault if one or
circuit or wrong more modules in a
Locate the cable break, short non-redundant
electrical connection
circuit or check the electrical system.
of the internal
connections.
communication bus
NO ANSWER (BBI to BBE).
Explanation: Lost
The loop unit has
communication.
electrically been
128 The system has Connect the loop unit.
disconnected from
recognized a
the loop.
unit/module but
lost contact. The loop unit has Check that the correct loop unit
been replaced by is installed.
another type of loop
unit, or the loop unit Check that the ID switch for an • Minor fault if only
ID has been I/O ICxx unit is set correct. one detector within
changed. an area covered by
other detectors.
One loop unit 1. Check address of the units.
Loop units
address has been set • Major fault if two or
2. Rescan or restart the loop.
to the same address more detectors
as another loop unit within the same
on the same loop (a area.
secondary fault
appears).
Defect unit. Replace the unit.
Cable break or short
circuit in a loop (a Locate the cable break or short
secondary fault circuit.
appears).
Unit or
Fault Code Cause Remedy Failure classification
Module
The detector has a
faulty sensor Replace the unit.
element.
The smoke detector Protect the detector from the
is exposed to strong airflow or consider repositioning
airflow. the detector.
• Check the device on the
129 SENSOR FAULT Loop units Input on a sub-loop sub-loop. Major fault
has a removed or
faulty device, an • Check the end of line
open circuit, or a component.
cable break. • Locate the cable break.
Loop I/O Check that the cable between Major or Minor fault
IN1 CABLE There is a cable
133 units with input and end of line resistor is depending on project
BREAK break on input 1.
inputs complete. specific function.
Loop I/O Check that the cable between Major or Minor fault
IN2 CABLE There is a cable
134 units with input and end of line resistor is depending on project
BREAK break on input 2.
inputs complete. specific function.
Unit or
Fault Code Cause Remedy Failure classification
Module
Charger M 1. Measure the voltage from the
power source.
• If voltage OK, change
External 24V power
loop unit.
Loop units source missing or
135 EXT 24V FAIL with the local power • If voltage NOT OK, Major fault.
external supply unit is change the DC/DC.
power defective.
2. If problem not solved contact
an authorized service office.
There is a fault in
the feedback
Check the cable for the feedback
between the loop
from the connected device to the
Loop I/O unit and the Major or Minor fault
FEEDBACK loop unit, for instance the
136 units with externally connected depending on project
FAULT door/damper.
inputs device (for example, specific function.
a door or a damper).
External load is Check the cable and the external
missing. load.
Loop I/O A supervised unit
Major or Minor fault
POSITION units with (for example, a door
137 Check for abnormal conditions. depending on project
FAULT specific or damper) is in the
specific function.
IDs wrong position.
• Major fault if no
short circuit
isolators on the
A short circuit in the
CM 4.3 loop.
detector loop cable
CM 2.2 Locate the short circuit.
or conventional • Major fault if loop
I/O M 70
LOOP SHORT zone. with short circuit
138 but not for
CIRCUIT
non-affected areas.
Loop unit
with short A short circuit in the
Locate the short circuit. Major fault.
circuit detector loop cable.
isolator
• Major fault if no
short circuit
isolators on the
Short circuit on the loop.
LOOP A SHORT
139 Loop M X A-side of a detector Locate the short circuit.
CIRCUIT • Major fault if loop
loop.
with short circuit
but not for
non-affected areas.
Unit or
Fault Code Cause Remedy Failure classification
Module
• Major fault if no
short circuit
isolators on the
Short circuit on the loop.
LOOP B SHORT
140 Loop M X B-side of a detector Locate the short circuit.
CIRCUIT • Major fault if loop
loop.
with short circuit
but not for
non-affected areas.
• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK positive conductor
141 Loop M X Locate the cable break.
POSITIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.
• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK negative conductor
142 Loop M X Locate the cable break.
NEGATIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.
Unit or
Fault Code Cause Remedy Failure classification
Module
UNKNOWN The Loop M X
TYPE OF LOOP cannot identify the
Replace the unit.
UNIT FOUND type of the affected
Explanation: The loop unit.
145 type of loop unit Loop units Major fault.
found is not Wrong type of 1. Install the correct type.
corresponding to detector has been
the configuration 2. Rescan or restart the loop.
installed.
file.
A timer loop unit Major or Minor fault
Loop based
146 TIMER STUCK has been active for Check the status of the loop unit. depending on project
timers
more than 12 hours. specific function.
CM 4.3 Short circuit has
CM 2.2 1. Locate the short circuit.
been detected on an
I/O M 70 output to the 2. Reset the fault.
SHORT I/O M 700 affected module.
149 Major fault.
CIRCUIT Short circuit has
been detected on Locate the short circuit on the
Loop units
external cabling to external cabling to the loop unit.
the loop unit.
Loop I/O 1. Open the valve.
External equipment Major or Minor fault
units with
150 VALVE CLOSED indicates that the 2. Contact an authorized service depending on project
specific
valve is closed. office. specific function.
IDs
1. Check the address of the
system module.
The affected system
System module is not in the 2. Check the system
modules system configuration file.
configuration file. 3. Contact an authorized service
office.
PRESENT NOT
152 Minor fault.
CONFIGURED 1. Check the address of the loop
unit.
The affected loop
unit is not in the 2. Check the system
Loop units configuration file.
system
configuration file. 3. Contact an authorized service
office.
There is an earth
Charger M
fault on the positive Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
155 Minor fault.
POSITIVE has detected an earth Locate the earth fault on the
Loop units fault on the positive external power supply to the
conductor from the loop unit.
power supply.
Unit or
Fault Code Cause Remedy Failure classification
Module
There is an earth
Charger M
fault on the negative Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
156 Minor fault.
NEGATIVE has detected an earth Locate the earth fault on the
Loop units fault on the negative external power supply to the
conductor from the loop unit.
power supply.
ChangeOv A fuse has been
Replace the fuse.
er M Ext blown.
157 FUSE FAULT Minor fault.
A fuse in a power Contact an authorized service
Loop unit
loop unit has blown. office.
A battery fuse has
been blown, or a
Charger M Replace fuse or restore the cable.
cable to the battery
BATTERY is broken. Major or Minor fault
158 CABLE/FUSE 1. Check the connection to the depending on project
FAULT There is a problem specific function.
battery.
with the battery
Loop units
connected to the 2. Consider replacing the
power loop unit. battery.
CM 4.3
CM 2.2
RM 4.3 A cable break or
Charger M short circuit has Restore the cable.
CABLE I/O M 70 been detected.
159 BREAK/SHORT I/O M 700 Major fault.
CIRCUIT Loop M X
• Check the end of line
Loop I/O Input on a loop unit
component.
units with has an cable break
inputs or short circuit. • Locate the cable break.
Charger M
ChangeOv Emergency power Major or Minor fault
EMERGENCY Check the emergency power
162 depending on project
POWER FAULT er M Ext has been lost. supply.
specific function.
Loop units
Unit or
Fault Code Cause Remedy Failure classification
Module
The battery charger
BATTERY (Charger M) is The battery charger (Charger M)
164 Charger M Minor fault.
CHARGER unable to charge the is unable to charge the battery.
battery.
EXTERNAL
CM 4.3
FAULT
CM 2.2
Can be generated Major or minor fault.
RM 4.3 External equipment
165 by customized Check the external equipment. See project specific
Charger M is indicating a fault.
defined fault. See system description.
I/O M 70
Custom text for the
I/O M 700
particular fault.
CHECKSUM
EEP
The booting
Only applicable
sequence was not
167 for a redundant Loop M X Rescan or restart the loop. Minor fault.
completed in a
controlled loop
correct way.
with two Loop M X
modules
If restarts happen repeatedly
System The module has
168 RESTARTED without known reason, contact Minor fault.
modules restarted.
an authorized service office.
The module has
1. Restart the module.
been in the
TOO LONG System
169 validating or 2. Contact an authorized service Minor fault.
BOOT TIME modules
configuring states office.
for too long.
CM 4.3 There is too high
EXTERNAL Check the load and reduce if
170 CM 2.2 external load on a Major fault.
LOAD possible.
I/O M 70 conventional zone.
EXTERNAL CM 4.3 Unexpected voltage
171 POWER CM 2.2 detected in a Located and remove the source. Major fault.
SOURCE I/O M 70 conventional zone.
1. Measure the voltage from the
power source.
• If voltage OK, change
Low voltage on the module.
primary 28VDC
LOW POWER • If voltage NOT OK,
172 Charger M power supply to the Major fault.
SUPPLY PSU 1 change or adjust the
internal system
DC/DC.
modules.
2. Contact an authorized service
office.
Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source. • Minor fault if power
• If voltage OK, change sources are
Low voltage on the module. redundant and not
secondary 28VDC from the same
LOW POWER • If voltage NOT OK,
173 Charger M power supply to the source.
SUPPLY PSU 2 change or adjust the
internal system
DC/DC. • Major fault if power
modules.
from the same
2. Contact an authorized service power source.
office.
The configuration
file is corrupt. 1. Download the configuration
file again.
An error has
occurred during 2. Contact an authorized service
downloading of the office.
CM 4.3
SYSTEM configuration file.
CM 2.2
176 CONFIGURATI Open configuration file in the Major fault.
CM X
ON FAULT The configuration correct version of CCPConf and
RM 4.3
file is saved in an resave the configuration file.
incompatible Which version of CCPConf used
version of the depends on the version of the
CCPConf. firmwares installed in the CCP
modules.
Loop I/O
External equipment Major or Minor fault
LOW units with Check the pressure on the
177 indicates low depending on project
PRESSURE specific supervised unit.
pressure. specific function.
IDs
Charger M
The main power
180 MAINS POWER ChangeOv Check the main power supply. Major fault.
supply is lost.
er M Ext
Unit or
Fault Code Cause Remedy Failure classification
Module
The connection
between the main
processor and the
CM 4.3
processor handling
the keyboard input
has been lost.
The module is
leaking power. The
INTERNAL Charger M supply and Contact an authorized service
181 Major fault.
FAULT consumption differ office.
greatly.
The Loop M X has
failed to schedule a
loop unit it
Loop M X considers to be in
working condition
for more than 30
minutes.
• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
183 CH 1
modules on channel 1 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.
• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
184 CH 2
modules on channel 2 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.
Unit or
Fault Code Cause Remedy Failure classification
Module
CM 4.3
CAUSE/EFFECT Fault detected in the Contact an authorized service
210 CM 2.2 Major fault.
ERROR configuration file. office.
CM X
The system fails to
SYNCHRONISA System Contact an authorized service
212 synchronize with the Major fault.
TION SIGNAL modules office.
affected module.
The configuration
file in the system is Synchronise the configuration
not the same in all file between all panel.
CM 4.3 modules.
CM 2.2 Central X Module Y
CM X settings in
CONFIG NOT RM 4.3 configuration file Check configuration and
213 SYNCHRONIZE Major fault.
compared to DIP-settings.
D
DIP-settings are not
OK.
The DIP-settings of
the Charger M are Check configuration and
Charger M
incorrect compared DIP-settings.
to configuration file.
The Charger M is
delivering a higher
current than the
maximum allowed
current limit to the
CURRENT affected Bus/Output. 1. Check the number of
modules configured.
214 LIMIT Charger M The Charger M is Major fault.
EXCEEDED consuming a higher 2. Check the external load.
current than the
maximum allowed
current limit from
the affected
PSU/Battery.
The battery
connected to the
CHARGING
affected Charger M Charge the battery with an
215 CURRENT Charger M Major fault.
is charged with a external charger.
EXCEEDED
higher current than
allowed.
The firmware in a 1. Try to reset the fault.
Charger M
module does not 2. If not possible to reset try to
ChangeOv
comply with the update firmware again.
er M Ext
INCOMPATIBL modules hardware (Might demand for system
216 I/O M 70 Major fault.
E FIRMWARE version. reboot.)
I/O M 700
The fault might
Mux M 16 3. Contact an authorized service
occur during
Relay M 8 office.
firmware update.
Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source.
• If voltage OK, change
The voltage module.
delivered from PSU
HIGH • If voltage NOT OK,
217 Charger M 1 to the affected Major fault.
VOLTAGE PSU 1 change or adjust the
Charger M module
DC/DC.
is too high.
2. Contact an authorized service
office.
Unit or
Fault Code Cause Remedy Failure classification
Module
A PSU is connected 1. Check the electrical
to the PSU 2 input connections according to the
on the affected drawings.
PSU2 PRESENT Charger M module,
2. Check the configuration file.
222 NOT Charger M but the Charger M Minor fault.
CONFIGURED module is not 3. Contact an authorized service
configured to have a office.
PSU connected to
PSU 2 input.
The voltage level
internally in the
Charger M is at least
1 volt below the
voltage delivered
from the PSUs.
INTERNAL Contact an authorized service
223 Charger M Without battery Major fault.
VOLTAGE LOW office.
charge, the system
shuts down at 18.5
VDC. With battery
charge, the system
shuts down at 21
VDC.
The voltage level
internally in the
Charger M is at least
1 volt above the
voltage delivered
INTERNAL from the PSU:s.
Contact an authorized service
224 VOLTAGE Charger M Without battery Major fault.
office.
HIGH charge, the system
starts up at 20.0
VDC. With battery
charge, the system
starts up at 25.5
VDC.
CM 4.3
CM 2.2
When the affected
CM X
module measures 1. Check backbone signals for
Charger M
the X-Fire signal in cable breaks.
ChangeOv
225 XFIRE SIGNAL the backbone, the Major fault.
er M Ext 2. Contact an authorized service
voltage level of the
I/O M 70 office.
signal is below 4
I/O M 700
volts.
Loop M X
Relay M 8
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
primary system bus connections according to the
CM 4.3 redundant.
PRIMARY within 30 seconds drawings.
226 CM 2.2
SYSTEM BUS by the master • Major fault if
CM X 2. Contact an authorized service
(module with communication is
office.
address 1) in the not redundant.
affected central.
Unit or
Fault Code Cause Remedy Failure classification
Module
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
secondary system connections according to the
CM 4.3 redundant.
SECONDARY bus within 30 drawings.
227 CM 2.2
SYSTEM BUS seconds by the slave • Major fault if
CM X 2. Contact an authorized service
(module with communication is
office.
address 2) in the not redundant.
affected central.
1. Check the electrical
The affected module connections according to the
has not responded drawings.
CM 4.3
NO ANSWER within 30 seconds
228 CM 2.2 2. Replace the module. Major fault.
SYSTEM BUS on
CM X
primary/secondary 3. Contact an authorized service
system bus. office.
Unit or
Fault Code Cause Remedy Failure classification
Module
The bootloader in 1. Try to reset the fault.
the affected module 2. If not possible to reset try to
Charger M cannot start the update firmware again.
ChangeOv application due to a (Might demand for system
er M Ext corrupted firmware. reboot.)
INVALID I/O M 70 This fault might
232 occur during a 3. Contact an authorized service Major fault.
APPLICATION I/O M 700
firmware upgrade. office.
Loop M X
Mux M 16
The module has a The fault is resettable once the
Relay M 8
higher protocol module is downgraded.
version than the
central master.
A relay is broken or
in a state that
damages the relay.
233 RELAY Relay M 8 Replace the module. Major fault.
(The voltage over
the relay coil is too
high.)
The affected module 1. Check for cable breaks on
NO ANSWER is not answering on the extension bus. Major or Minor fault
RM 4.3
234 EXTENSION the extension bus depending on project
MN400 2. Contact an authorized service
BUS where it is specific function.
office.
connected.
1. Check the address of the
The type of module module according to
WRONG TYPE
System found is different electrical drawings.
236 OF MODULE Major fault.
modules from the type
FOUND 2. Contact an authorized service
configured.
office.
Unit or
Fault Code Cause Remedy Failure classification
Module
The voltage level of
the GA signal in the
backbone is below 4
CM 4.3 volts.
CM 2.2 (Fault generated by 1. Check that Charger M puts
CM X modules which have out a monitoring voltage on
RM 4.3 GA-morse the backbone
239 GA FAULT Major fault.
Charger M configured for any
2. Contact an authorized service
I/O M 70 of its outputs)
office.
I/O M 700 NOTE: Critical
Relay M 8 error which can
cause the GA
functionality from
working.
A write operation
Major or Minor fault
DEVICE WRITE into the loop unit’s
241 Loop units Replace the loop unit. depending on project
FAULT internal EEPROM
specific function.
memory failed.
CM 4.3 The system has not
Contact an authorized service
242 SERVICE TIME CM 2.2 been serviced for a Major fault.
office.
CM X period of time.
System
modules Internal system Contact an authorized service
255 ILLEGAL Major fault.
error. office.
Loop units
Active high By active high it means that the output is normally not energized in normal condition
and when system is not energized. By active high on input it means that the input is
normally not energized. This is the NO contact on a relay.
Active low By active low it means that the output is normally energized in normal condition and
system running. By active low on input it means that the input is normally energized.
This is the NC contact on a relay.
Alarm condition The state of the system when a fire or gas has been detected.
Alarm delay When activated the activation of alarm devices will be delayed for a preset time
(normally 2 minutes).
Alarm device Device that is activated in case of fire, for example audible and optical alarms like
bells, sirens and flashlights.
Alarm Transfer Output A supervised output for signalling that a fire has occurred. The Alarm Transfer Output
is usually used in onshore systems for alerting the fire brigade.
APF Application Program File.
Application program file A file holding the application parameters for the FDS.
ASP detector Aspiration detector.
Backbone Bus External The main bus outside a central cabinet used for communication between modules and
(BBE) stretched central parts. It consists of two redundant RS485 channels, two 24 VDC
power lines and the Basic Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone Bus Internal (BBI) The main bus inside a central cabinet used for communication between modules. It
consists of two redundant RS-485 channels, two 24 VDC power lines and the Basic
Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone segment A Backbone bus may be split in several segments. Power feeding can be separate for
each segment by using one Charger M per segment. Communication can be isolated
between segments by using Isolator modules.
Basic Backup Signal (BBU) A signal in the Backbone bus that is used for transmitting the central's alarm status.
The signal is only used when a module in managed mode loses communication with its
controller module.
BER Bit Error Rate
BusCon M 20 A Bus Connector with 20 connectors in the flat-cable. This unit is used to connect the
Control M 4.3 to the backbone bus and also has the common fire and fault outputs.
Cause/Effect The Cause/Effect program defines how the inputs and outputs of the system should act.
CCP Consilium Common Platform. General modules which create a system for Consilium
products.
CCP platform An umbrella name for all the modules and devices that can be connected together, e.g.
“the Control M 4.3 module is a member of the CCP platform”.
Central A Central is a complete system that can operate autonomously; monitor its detectors
and inputs, activate its outputs and display its faults and alarms. If connected to other
centrals, it exchanges information with the other centrals via the System bus, thus
allowing all centrals to act as one system.
Each central can only have one Backbone bus.
Central cabinet Enclosure to contain a complete or part of a central.
Charger M The Charger Module. Can connect two PSU’s and a battery and feeds the power
channels on the backbone bus.
Compact central Central cabinet including basic functionality of Fire Detection System such as: Control
panel, Power supply, Battery backup, basic I/Os and at least one analogue addressable
loop. The cabinet supplies limited expansion possibilities.
Configuration File A file holding the configurable parameters for the FDS.
Control module The Control M 4.3, the Control M 2.2 and the Control M X can all act as Controller
modules, i.e. be in controller mode.
Control panel The Control M 4.3 and Control M 2.2 can act as a Control panel, i.e. they have an HMI
and the rights to manipulate and supervise the system.
Controller mode Control modules can run in Controller mode, i.e. being Master or Hot Standby Master
within a central. Control modules can also be in managed mode, that is being a module
that is managed by the master. All other modules are always running in managed
mode.
Controller module A Control module that is in Controller mode (master or hot standby) in a central or
system.
Control M 2.2 A Control Panel with a 2.2” graphical colour display used to manage and supervise a
system.
Control M 4.3 Control Module with a 4.3” display, a keyboard and all the mandatory indications
required to comply with EN 54.
Control M X Control Module, a control module without a display, keyboard or mandatory
indications.
CR It is a heat detector class. The C means fixed alarm temperature at 84ºC. The R means
it also gives alarm for RoR.
CS Heat detector classification in EN 54-7; ‘C’ class indicates a static response
temperature of 84°C and ‘S’ that the detector will not respond below 80°C.
DCS Distributed Central System (see also Stretched central).
Detector A device capable of detecting smoke, heat, flames or gas.
DIP switch Dual in-line package switch. Used to set address etc. on loop units and modules.
Disablement Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
will be inhibited.
EMC Electromagnetic Compatibility.
EMI Electromagnetic Interference.
EN 54 The European product standard for fire detection and fire alarm systems.
ESD System Emergency Shut Down System, embedded system taking care of safety procedures in
case of emergency, for example shut down of fire doors, ventilation etc.
Ex Ex can mean different things depending on when it is mentioned. Examples: ‘Ex
proof’ means ‘Explosion Proof’, ‘Ex area’ means ‘Hazardous Area’ which is an area
where the atmosphere might be explosive. ‘Ex certified’ means both ATEX and IECEx
certification.
Ex-classification The protection type used in a hazardous area; e.g. Ex d.
Extension bus An additional (RS485) bus used inside a central for intra-central communication. The
Extension bus is typically used for connecting Repeater modules (that does not require
redundant communication and power) and should not be confused with the Backbone
bus.
External communication Communication to external entities is called external communication, using for
example MODBUS, NMEA or TCMS protocols.
External control Outputs used to control external equipment, for example fire doors.
Fault condition The state of the system when a fault is detected.
I/O 700 An Input/Output type providing a different function depending on the configuration of
the system. The programmable functions are:
• General Input
• Fault Input
• Output (24 VDC/700 mA)
I/O Module A module with inputs and/or outputs. I/O modules always run in Managed mode, that
is they must be managed by a Controller module.
I/O pin or I/O signal An I/O pin or an I/O signal is a logical signal, compare to terminal.
IDA The IDA communication protocol.
Inter-central communication Communication between centrals is called inter-central communication.
Interface channel A communication channel used to interface the systems with external devices.
Interface channels can be configured to communicate on different protocols.
Internal power supply Output power from PSU.
Intra-central communication Communication within a central is called intra-central communication. This
communication is between modules.
IP Ingress Protection - rating used to specify the environmental protection (enclosure) of
electrical equipment.
IS Intrinsically Safe.
Isolator M Isolator Module; used to distribute a part of a FDS.
ISS Integrated Safety System.
Loop The same as a loop-line.
Loop cable A cable which the FDS uses to power and communicate with the loop units. The loop
begins and ends in the loop module in the FDS.
Loop module The piece of hardware within the FDS which powers and communicates with the loop
units connected to its loop-line.
Loop unit Fire detectors, gas detectors, manual call points and other devices that can be
connected to the Loop.
Loop-line A common name for the cable, loop devices and other equipment connected to a loop
module.
Loop-line IS A part of the loop-line protected by a galvanic isolator.
LRU A Line-Replaceable Unit (LRU) is a modular component that is designed to be
replaced quickly at an operating location.
Managed mode The opposite of Controller mode. All modules that are managed by a Controller
module are in Managed mode.
MCP Manual Call Point.
MCS Multi Central System. A system consisting of more than one central.
MFZ Main Fire Zone.
Mode of operation Modules in the system can take on different roles. Connected to the Backbone bus they
can be in:
• Central Controller Mode (Master or Hot Standby)
• Central Managed Mode
Modules connected to the System bus can be in:
• System Controller Mode (Master or Hot Standby)
• System Managed Mode
Module A module that is a part of the platform, where it can be used to build centrals. Modules
within the platform generally supply a Backbone bus interface. Controller modules
also have a System bus Interface.
Module address Module addresses are set via DIP switches on the modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
N/A Not Applicable.
OEM Original Equipment Manufacturer.
PA Public Addressing.
Power output Output providing power supply, normally used to power external devices.
Pre-Alarm condition A condition preceding the Alarm condition to give early warning for potentially
dangerous situations like a smouldering fire.
Programmable output Output which signal behaviour is configurable via the Configuration program.
PSU Power Supply Unit.
Rate of Rise Rate of Rise functionality by using C/E commands for setting of a different alarm
threshold and temperature rise threshold for heat detectors.
Redundancy Refers to the quality or state of being redundant, that is exceeding what is necessary or
normal. In the system the term is used to describe backup functionality like in Hot
Standby Controller modules.
Redundant loop Redundant loop means loop module redundancy on one single loop-line between two
loop modules.
Relay Electrically operated switch output, normally providing C/NO/NC contacts for
connection of signal receiver.
Repeater panel The main attribute for Repeater panels is that they can show information but not affect
the central (or system) they belong to. The Repeater M 4.3 is a Repeater panel.
RS-485 Serial communication interface used for external communication and BackBone bus.
Is a standard defining the electrical characteristics of drivers and receivers for use in
balanced digital multipoint systems.
Safe State Modules enter 'safe state' when they detect system faults. Modules in Safe State put
their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
Salwico Language A text based interpreting language for making logical cause effect expressions
developed by Consilium.
SCI Short Circuit Isolator.
SCM Software Configuration Management.
SCS Single Central System.
SMig system Salwico Safety Management interactive graphics, a PC-based software package
providing graphical presentation and control of the system.
Spur Branch from a loop-line without return.
Stretched central (DCS) A central that is physically distributed to two or more physical locations. One location
may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
Sub-loop It is possible to connect sub-loop units to some loop units using a sub-loop cable. The
cable is however not a loop. One end is connected to the loop unit and the other end is
connected to the sub-loop unit.
Sub-loop unit A device which cannot be connected directly to the loop. A sub-loop unit can be a
switch or a relay contact will be used to send a fire or fault alarm to the FDS.
Synchronization signal A signal in the Backbone bus that is used for transmitting synchronization signal used
by system modules to synchronize there behaviour.
System A system consists of a number of loop units and one or more centrals.
System bus The communication bus used for connecting multi-central systems. The System bus is
used for inter-central communication but can also be used for external communication.
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System bus.
TBD To Be Done, To Be Decided/Determined.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Test condition Detectors put in the Test condition (or test mode) are inhibited from generating the
Alarm condition but the alarms are displayed on the Control panels to prove that the
tested detectors are operational.
USB Universal Serial Bus, a communications bus that may be used to connect flash
memories, keyboards, mice or other devices.
Warning Condition The state of the system when a warning is detected. Warnings are not as serious as
faults and only of informative nature, for example in case of a lightly contaminated
detector.
Zone A group of detectors located in a geographical area.
Index
A Fire alarm key, Control Panel M 4.3...................... 7
About testing.......................................................... 35 Fire alarm menu, Control Panel M 4.3 .................. 9
Access level ........................................................... 21 Fire alarm, reset ..................................................... 24
Alarm delay............................................................ 30 Fire alarm, Reset several alarms ............................ 24
Alarm delay off indicator, Control Panel M 4.3 .... 6 Fire alarm, From conventional zones..................... 24
Alarm device indicator, Control Panel M 4.3 ........ 6 Fire detection system ............................................. 21
Arrow keys, Control Panel M 4.3 .......................... 8 Fire detection system, System description............. 3
Arrow keys, Repeater M 4.3 .................................. 18 Fire history list ....................................................... 36
Fire alarm, Information displayed in the Control
Panel....................................................................... 23
C Fire alarm, Mute..................................................... 23
Clock disablement.................................................. 28 Fire-Fault-Dis. key, Repeater M 4.3 ...................... 18
Condition list menu, Control Panel M 4.3 ............. 9
Control Panel M 4.3, Description of numerical
keypad .................................................................... 9
G
Control panel display, Testing................................ 37 General alarm system............................................. 21
Control Panel M 4.3, Description of operational
controls................................................................... 7 H
Control Panel M 4.3, Description of system History menu, Control Panel M 4.3 ....................... 9
indicators................................................................ 6
Custom indicators, Control Panel M 4.3................ 6
Custom specific restrictions................................... 21
L
Lamp test keys, Repeater M 4.3............................. 19
Local Mute key, Repeater M 4.3............................ 18
D Login menu, Control Panel M 4.3 ......................... 9
Day mode key, Control Panel M 4.3...................... 9
Day mode key, Repeater M 4.3.............................. 19
Disablement list ..................................................... 37
M
Disablement list ..................................................... 28 Menu ...................................................................... 9
Disablement, Acknowledgement ........................... 28 Menu key, Control Panel M 4.3 ............................. 8
Disablements menu, Control Panel M 4.3 ............. 9 Multiple alarms key, Control Panel M 4.3............. 8
Disablements key, Control Panel M 4.3................. 7 Mute key, Fault alarm ............................................ 25
Disabling a conventional zone ............................... 29 Mute key, Fire alarm .............................................. 23
Disabling addressable detectors............................. 29 Mute key, Control Panel M 4.3.............................. 8
Disabling alarm devices......................................... 30
Disabling alarm transfer output ............................. 31 N
Disabling an addressable zone ............................... 29 Night mode key, Control Panel M 4.3 ................... 9
Disabling external outputs ..................................... 31 Night mode key, Repeater M 4.3 ........................... 19
Disabling manual call points.................................. 29
Download system log file ...................................... 33
O
OK key, Control Panel M 4.3................................. 8
E
Enter key, Control Panel M 4.3.............................. 9
Erase key, Control Panel M 4.3 ............................. 9
P
Escape key, Control Panel M 4.3 ........................... 8 Periodic disablement.............................................. 28
Permanent disablement .......................................... 28
Power indicator, Control Panel M 4.3.................... 6
F Power indicator, Repeater M 4.3 ........................... 18
Fault alarm menu, Control Panel M 4.3................. 9 Pre-Alarm key, Control Panel M 4.3 ..................... 7
Fault alarm, Information displayed in the Control Pre-Alarm list......................................................... 22
Panel....................................................................... 25
Fault alarm, Mute................................................... 25
Fault alarm, Reset from the Fault list..................... 26
R
Fault report............................................................. 33 Reconnecting disabled alarm delays...................... 32
Fault alarm, Reset .................................................. 26 Reconnecting disabled items.................................. 31
Fault alarm, Reset all faults ................................... 26 Reconnecting periodic disablements...................... 31
Fault key, Control Panel M 4.3 .............................. 7 Remove all disablements ....................................... 32
www.consilium.se