5100332-00 - Salwico Cruise - User Guide - M - EN - 2018 - AA

Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

Salwico Cruise

Fire Detection System


User Guide
Consilium Marine & Safety AB
Fire & Gas Marine Division
Phone: +46 31 710 77 00
Fax: +46 31 710 78 00
E-mail: Service: [email protected]
Spares: [email protected]
 
Consilium Marine & Safety AB
Navigation Division
Phone: +46 8 563 05 100
Fax: +46 8 563 05 199
E-mail: Service, APT: [email protected]
Spares: [email protected]
 
The contents of this document are subject to revision without notice
due to continued progress in methodology, design and manufacturing.
Consilium assumes no legal responsibility for any error or damage
resulting from the usage of this document.
 
March 2018
Document no. 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA
Part no. 5100332-00

© Copyright 2018, Consilium Marine & Safety AB


Table of contents

1 Introduction....................................................................................... 1
1.1 About this Manual ............................................................................ 1
1.2 Approvals........................................................................................... 2
1.3 Symbols used in the manual ............................................................. 2

2 Fire Detection System ....................................................................... 3


2.1 System Description............................................................................ 3
2.2 System Block Diagram...................................................................... 3

3 Control Panels................................................................................... 5
3.1 Control Panel M 4.3.......................................................................... 5
3.1.1 General............................................................................................ 5
3.1.2 Description of Keys and Indicators................................................. 5
3.1.3 Guide to the Menu System.............................................................. 9

3.2 Repeater M 4.3 .................................................................................. 18


3.2.1 General............................................................................................ 18
3.2.2 Description of Keys and Indicators................................................. 18

4 Operations ......................................................................................... 21
4.1 Access Levels ..................................................................................... 21
4.2 Login.................................................................................................. 22
4.3 Pre-Alarm .......................................................................................... 22
4.4 Fire Alarm ......................................................................................... 22
4.4.1 Information Displayed when “Fire” is Flashing ............................. 22
4.4.2 Mute a Fire Alarm........................................................................... 23
4.4.3 Reset a Fire Alarm .......................................................................... 24
4.4.4 Several Alarms................................................................................ 24
4.4.5 Type of Fire Alarms from Conventional Zones .............................. 24

4.5 Fault Alarm ....................................................................................... 24


4.5.1 Information Displayed when “Fault” is Flashing ........................... 24
4.5.2 Mute a Fault .................................................................................... 25
4.5.3 Reset a Fault.................................................................................... 26
4.5.4 Reset a Fault from the Fault List..................................................... 26
4.5.5 Reset All Faults............................................................................... 26
4.5.6 Fault Messages................................................................................ 26
4.5.7 Warnings ......................................................................................... 27

4.6 Disablements ..................................................................................... 27


4.6.1 About Disablements........................................................................ 27
4.6.2 Available Types of Disablements ................................................... 28
4.6.3 Acknowledgement of a New Disablement ..................................... 28
4.6.4 Disabling Zones .............................................................................. 29
4.6.5 Disabling Addressable Detectors & Manual Call Points................ 29
4.6.6 Disabling Alarm Devices................................................................ 29
4.6.7 Old Disablements............................................................................ 30
Table of contents

4.6.8 Disabling Alarm Delay ................................................................... 30


4.6.9 Disabling External Control Groups ................................................ 31
4.6.10 Disabling an Alarm Transfer Output .............................................. 31

4.7 Reconnecting..................................................................................... 31
4.7.1 Reconnecting Disabled Items ......................................................... 31
4.7.2 Reconnecting Periodic Disablements ............................................. 31
4.7.3 Reconnecting Disabled Alarm Delays ............................................ 32
4.7.4 Remove All Disablements .............................................................. 32

4.8 Service Menu..................................................................................... 32


4.8.1 About the Service Menu ................................................................. 32
4.8.2 Save the System Log to a USB Memory Stick ............................... 33
4.8.3 How to report a fault ....................................................................... 33

5 Testing................................................................................................ 35
5.1 About Testing..................................................................................... 35
5.2 Test Mode Overview .......................................................................... 35
5.3 Testing a Fire-detecting Zone........................................................... 36
5.4 Recommended Test Equipment......................................................... 37
5.5 Reset Test Mode................................................................................. 37
5.6 Test the Control Panel Display ......................................................... 37

6 Appendix - Fault Code List............................................................... 39


6.1 Fault Code List.................................................................................. 39

7 Appendix - Definitions and Abbreviations....................................... 55


7.1 Definitions and Abbreviations .......................................................... 56

8 Quick Guide for Control Panel M 4.3.............................................. 61

Index ................................................................................................. 62
User Guide 1 Introduction

1 Introduction

1.1 About this Manual


This User Guide is intended for personnel using the Fire detection system and
provides basic understanding how to operate the system.

NOTE!
This user guide has been revised based on system version 1.10.10 but is valid for
Control panel software versions beginning with version 1.0.0.

The chapter Fire Detection System gives general information about the system.

The chapter Control Panels describes the function of the Control panel and the
Repeater in the Fire detection system.

The chapter Operations describes how to operate the Fire detection system.

The chapter Testing provides brief instructions on how to connect and test the
system (detailed information is found in the Service & Maintenance manual).

The Fault Code List in the Appendix lists the different fault codes.

Figure 1. Salwico Cruise Fire Detection System, an example.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 1


1 Introduction User Guide

1.2 Approvals

1.3 Symbols used in the manual


DANGER!
Risk of serious or fatal injury to the user, and/or severe damage to the product, if
the instructions are not followed.

WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.

CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.

NOTE!
Note symbols alert you to important facts and conditions.

Hint!
Hint symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.

2 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 2 Fire Detection System

2 Fire Detection System

2.1 System Description


This Fire detection system is a state-of-the-art, analogue-addressable, fire-detection
system designed to meet marine, industrial and transport requirements. Special care
is given to ergonomics and user-friendliness with its logical and intuitive operator
panel.

2.2 System Block Diagram


The following figure shows a typical system and its connected components, see
Definitions and Abbreviations, page 56 in the Appendix for explanation of terms
and abbreviations.

The Fire detection system is built on a scalable platform. A Single Central System
contains up to 126 Modules and a Multi Central System up to 30 Centrals.

Figure 2. Single Central System (SCS)

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 3


2 Fire Detection System User Guide

Figure 3. Multi Central System (MCS)

4 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

3 Control Panels

3.1 Control Panel M 4.3


3.1.1 General
This menu-operated system monitors and controls all system functionality. The
control panel's clear graphical display makes it easy to use.

3.1.2 Description of Keys and Indicators

Figure 4. Keys and indicators for the control panel

As shown in the figure above, the control panel is divided into three sections:

A = System Indicators
B = Operational Controls
C = Numerical Keypad

Part A: System Indicators

Figure 5. The system indicators section of the control panel

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 5


3 Control Panels User Guide

The System Indicators section is comprised of the following indicators:

1. Power
Steady green light Power supply to the control panel is OK.

2. System fault
Flashing yellow light Main process fault. A serious system fault in the
system.

3. Test
Steady yellow light At least one zone is manually set in test mode.

4. Warning
Steady yellow light At least one warning indication exists.

5. Zone
Steady yellow light At least one zone or a loop unit is disabled.
Flashing yellow light At least one zone or a loop unit is in fault condition.
(Priority over disablement indication.)

6. Alarm device
Steady yellow light At least one alarm device output is disabled.
Flashing yellow light At least one alarm device output is in fault condition.

7. Alarm delay off


Steady yellow light The alarm delay function is disabled.

8. Custom indication 1-3


Colour and pattern of Custom LED indication is defined in the system configuration.

9. USB
USB connection for USB memory stick to load or save data.

6 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

Part B: Operational Controls

Figure 6. The operational section of the control panel

1. Main indicators
Fire alarm
The Fire alarm key indicates existance of a fire alarm and gives direct access to
the Fire alarm list. Indications:
Flashing red light One or more un-muted fire alarm(s) in the system.
Steady red light All fire alarms are muted.

Pre-Alarm
The Pre-Alarm key indicates existance of a pre-alarm and gives direct access to
the Pre-Alarm list. Indications:
Flashing orange light One or more un-muted pre-alarm(s) in the system.
Steady orange light All pre-alarms are muted.

Fault
The Fault key indicates existance of a fault and gives direct access to the Fault
alarm list. Indications:
Flashing yellow light One or more un-muted fault(s) in the system.
Steady yellow light All faults are muted.

Disablements
The Disablements key indicates existance of a disablement and activates the
Disablements menu. Indications:
Steady yellow light At least one disabled function in the system.

Shortcuts
The Shortcut key activates the customer specific shortcut list. Indications:
Steady orange light The alternatives in the shortcut list and the
corresponding indicators (Shortcut 1, Shortcut 2 and
Shortcut 3) are set in the configuration program.

2. Status

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 7


3 Control Panels User Guide

This key gives direct access to the System status summary list with Alarms
(Fire and Pre-Alarms), Maintenance (Faults and Warnings) and Disablements
(Active and Periodic).
Shortcuts are:
1. Upload the system log to USB Memory stick.
2. Go to the maintenance menu.

3. Menu
This key gives direct access to the main menu and all system functions.
4. Navigation and Command Keys
The arrow keys are used to navigate menus, select different menu alternatives,
and show details for list items.
Go to the previous item
in the list or menu.

Selects the chosen


Go to previous menu.
menu alternative.

Go to the next item


in the list or menu.

ESC
The Escape key is used to go to the default menu.

OK
This key is used to select a menu alternative or to accept a function. The OK key is
also in some cases used to show details for a selected list entry.

5. Display
The control panel has a backlited 4.3" graphical, 480×272 pixels, 16-bit colour
display.
6. Alarm keys
Multiple alarms
Press this key to scroll through the different alarms. The list always returns to the first
fire alarm after 30 seconds of inactivity.

Reset
This green key is used to request for a reset of a selected alarm, fault or disablement.

Mute
This red key is used to acknowledge the alarm and mute the local buzzer.

8 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

Part C: Numerical Keypad

Figure 7. The keypad on the control panel.

1. Numerical keypad
Keys 0 - 9
The numerical keypad is used to enter numerical values. Keys 1–9 are also used as
shortcuts when navigating in the menus.

Erase
This key is used to erase characters from the text display.

Enter
This key is used to select a menu alternative or to accept a function. The Enter key is
also used to show details for a selected list entry.

Day mode
Increase the brightness/contrast level for the indicators and display on the panel.

Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.

3.1.3 Guide to the Menu System


The fire detection system is menu-operated. All system functions are available
from the different menus. The fire detection system is normally displaying a
greeting screen. From the greeting screen press Menu to enter the menu system.

Default screen Menu


1 Fault Alarms
Installation name
2 Fire Alarms
Project number
3 Disablements
4 Login
5 Settings
6 Service Menu
7 History
8 Condition List

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 9


3 Control Panels User Guide

How to navigate the menu system


• Navigate in the menu alternatives with the and arrow keys. It is also
possible to choose a menu alternative by entering the menu number.
• Select a menu alternative with the arrow key or the key.
• Use the arrow key to go back to the previous menu.

In the lower part of the display the different options available for each individual
menu are shown.

The numerical keypad is used to enter information, e.g. zone and detector number.

The key erases the last character.

Table 1. Top menu alternatives


Alternatives Description
1 Fault alarms The menu from which fault and warning messages are listed
and handled.
2 Fire alarms Fire alarms and pre-alarms are displayed and managed from
this menu. Muted alarm devices may be reactivated here.
3 Disablements Disabled parts of the fire detection system are added,
removed, or listed from this menu. (For instructions, see
About Disablements, page 27.)
4 Login Log in from this menu by entering a personal access code.
For further details see section Login, page 22.
5 Settings Use this menu to adjust system parameters, such as the
dimmer level, date, time and alarm delay time.
It is also possible to make a lamp test for the control panel
under “Test display”.
6 Service menu Use this menu to list and view information about the system
and its components. It is also possible to make disablements
of the listed units. The Service menu is described in more
detail in the separate Service and Maintenance manual.
Access level 2B is needed for basic functions and access
level 4 is needed to perform advanced service options.
7 History Use this menu to view previous events in the fire detection
system.
8 Condition list Use this menu to create lists of detectors that are no longer in
good condition but still fully functional. The purpose of the
satisfactory and poor condition lists is to give an early
indication of which detectors need to be replaced in the
future.

10 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

1 Fault Alarms Menu

1 Fault Alarms
2 Fire Alarms
3 Disablements
1 Fault List
4 Login
2 Warning List
5 Settings
3 Reset All Faults
6 Service Menu
7 History
8 Condition List

Table 2. Fault alarm menu alternatives


Alternatives Description
1 Fault List Shows all present fault alarms.
2 Warning List Shows all present warning messages.
3 Reset All Faults The system will attempt to reset all present fault alarms in
the Fault List.

2 Fire Alarms Menu

1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Fire List
4 Login 2 Pre-Alarm List
5 Settings 3 Resound (restart bells)
6 Service Menu 4 Reset All Fire Alarms
7 History
8 Condition List

Table 3. Fire alarm menu alternatives


Alternatives Description
1 Fire List Shows all present Fire Alarms.
2 Pre-Alarm List Shows all present Pre-Alarms.
3 Resound (restart bells) If the alarm devices have been silenced by pressing Mute
key , this function will restart them (if the fire alarm has
not been reset).
4 Reset All Fire Alarms The system will attempt to reset all fire alarms in the Fire
List.

3 Disablements menu

1 Fault Alarms
1 New disablement (access lvl 2B)
2 Fire Alarms
2 List disablements
3 Disablements
3 List periodic disablements
4 Login
4 List old disablements
5 Settings
5 Remove all disablements
6 Service Menu
6 Alarm Delay
7 History
7 List Alarm Delay
8 Condition List

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 11


3 Control Panels User Guide

Table 4. Disablemens menu alternatives


Alternatives Description
1 New disablements Adds new disablements.
This requires access level 2B.
2 List disablements Shows all active disablements in the system. A periodic
disablement that is not active will not be shown in this list,
but in the list periodic disablements (mentioned below). The
reconnection of a disabled unit is made from this list. See
section Reconnecting Disabled Items, page 31 for more
details.
3 List periodic Shows all periodic disablements in the system. The removal
disablements of periodic disablements is made from this list.
4 List old disablements This list displays the 150 previously removed disablements
and allows these older disablements to be reactivated.
Hint!
This function is very useful if the same disablement
is frequently needed during irregular time periods.
Just mark the appropriate old disablement in the list
and press 0 to reactivate it.
This requires access level 2B.
5 Remove all disablements Removes all active disablements shown in the Disablement
list.
DANGER!
Periodic disablements are not permanently removed.
Only the periodic disablement's active period is
removed. Use alternative "3 List periodic
disablements" to remove periodic disablements.
6 Alarm Delay Disables the alarm delay function.
Alarm delay is a programmable time delay between when a
fire is detected and until the alarm device outputs are
activated.
See Disabling Alarm Delay, page 30 for more information.
7 List Alarm Delay Shows all active alarm delays in the system. The
reconnection of a disabled alarm delay is made from this list.
See section Reconnecting Disabled Alarm Delays, page
32 for more details.

New disablement sub-menu

1 New disablement (access 2B) 1 Zones


2 List disablements 2 Detectors & Manual Call Points
3 List periodic disablements 3 External Controls
4 List old disablements 4 Alarm Device (bells etc.)
5 Remove all disablements 5 Test Mode

Table 5. New disablement menu alternatives


Alternatives Description
1 Zones Disable entire zones for a specified time period or
permanently.
2 Detectors & Manual Disable individual detectors or manual call points for a
Call Points specified time period or permanently.

12 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

Alternatives Description
3 External Control Deactivate 1 External Controls or 2 Alarm Transfer . See
list External Control Disablements, page 13 for more
information.
4 Alarm Device (Bells etc.) Disables the outputs for alarm devices, such as audible (e.g.
bells) and optical alarm devices.
5 Test Mode Set a zone into test mode.

External Control Disablements


1. External Controls
Disables outputs (all or individual groups) to external controls. This means that
an alarm condition will not cause activation of the selected group.
• All groups
Disable all external controls (doors, fire, fault, ventilation and indication).
• Doors
Disable external door controls in the system.
• Fire
Disable external fire controls in the system.
• Fault
Disable external fault controls in the system.
• Ventilation
Disable external ventilation controls in the system.
• Indication
Disable external indication controls in the system.

2. Alarm Transfer
Disables the supervised alarm transfer output, which is normally used in
on-shore installations to alert the fire brigade in case of a fire alarm. Select
System or Central to disable.

See also section About Disablements, page 27 for more information about the
Disablements.

4 Login Menu

1 Fault Alarms
2 Fire Alarms
3 Disablements User 1
4 Login User 2
5 Settings User 3
6 Service Menu User 4
7 History
8 Condition List

See Login, page 22 for more information about the Login menu alternatives.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 13


3 Control Panels User Guide

5 Settings Menu

1 Fault Alarms
1 Set Dimmer
2 Fire Alarms
2 Set Time
3 Disablements
3 Set Date
4 Login
4 Test Display
5 Settings
5 Alarm Delay Times
6 Service Menu
6 Keyboard Beep
7 History
7 Cause Effect in Test Mode
8 Condition List

Table 6. Settings menu alternatives


Alternatives Description
1 Set Dimmer Use this menu to adjust the contrast level (1–9) for the
display and indications on the control panel.
2 Set Time Use this menu to set the system time.
It is possible to synchronize the system clock with the ship's
central time.
3 Set Date Use this menu to set the system date.
NOTE!
Dates before year 2000 are not accepted by the fire
detection system.
4 Test Display Use this menu to activate a lamp test in order to visually
verify the function of the display and all indications on the
control panel.
5 Alarm Delay Times Use this menu to adjust the programmable alarm delay times
(access level 3) if no time is set in the configuration program.
Time 1 is adjustable between 1 or 2 minutes. Time 2 (reset)
is only used for on-shore installations.
See section Disabling Alarm Delay, page 30 for more
information.
6 Keyboard Beep Use this menu to turn the keyboard beep ON or OFF.
7 Cause Effect in Test Use this menu to turn the Cause Effect programming ON or
Mode OFF during test mode. If set to ON, the outputs are activated
(access level 2) as normal during test mode.

6 Service Menu

1 Fault Alarms 1 System Details


2 Fire Alarms 2 Centrals
3 Disablements 3 Modules
4 Login 4 Zones
5 Settings 5 Loops
6 Service Menu 6 Configuration
7 History 7 Firmware
8 Condition List 8 System Log
9 I/O lists

Access level 2B is needed for basic functions and access level 4 is needed to
perform advanced service options.

14 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

Hint!
The Service menu is described in more detail in the separate Service and
Maintenance manual.

Table 7. Service menu alternatives


Alternatives Description
1 System Details This menu lists the installed system's information, such as
name and reference number (if defined). It also lists when
the system was last configured and by which program.
2 Centrals Use this menu to list information about the installed centrals
and the modules in each central.
3 Modules Use this menu to list information about the installed system
modules. It is possible to display all details about the
modules, such as installed detector loops, installed program
versions, input/output status. It is also possible to print
information.
4 Zones This menu shows a list of all zones configured in the system.
It is possible to list all loop units in a zone if the zone
consists of addressable loop units, disable zones or loop
units, and set a single fire detector in alarm condition.
Installation Mode can be activated for loops and zones
containing addressable loop units. Loop units affected by
Installation Mode will stop reporting faults of type ‘present
not configured’, ‘configured not present’ and ‘no answer’.
5 Loops This menu shows a list of all physical loops installed in an
analogue addressable system. A loop can consist of
conventional or addressable fire detectors and other loop
units. It is possible to add and to disable entire loops. Use
Scan Loop to force a scan of the loop for new loop units.
Installation Mode can be activated. Loop units affected by
Installation Mode will stop reporting faults of type ‘present
not configured’, ‘configured not present’ and ‘no answer’.
6 Configuration This menu is used to configure the system as further
explained in Configuration sub-menu, page 16.
7 Firmware Use this menu to download firmware to modules, load or
backup service pack, and to start or stop an automatic
update.
8 System log The System log menu contains sub-menus to save a syslog
or to reset service interval.
Once the System Log is copied to a USB memory stick, it
can be sent to an authorised service organisation for further
technical assistance. See section About the Service Menu,
page 32 for further information and instructions.
9 I/O lists I/O lists with sub-menus Input list and Output list. Use these
menus to inspect or disable active inputs and outputs in the
system and on loops.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 15


3 Control Panels User Guide

Configuration sub-menu

1 System Details
2 Centrals 1 Reload configuration/reboot this module
3 Modules 2 Load configuration from USB memory
4 Zones 3 Save configuration to USB memory
5 Loops 4 Save changes to configuration
6 Configuration 5 Remove configuration
7 Firmware 6 Synchronise system configuration
8 System Log 7 Reboot system (this module excluded)
9 I/O lists

Hint!
The Configuration menu is described in more detail in the Installation &
Commissioning manual and the Service & Maintenance manual.

Table 8. Configuration sub-menu alternatives


Alternatives Description
1 Reload Reload the configuration when a new updated configuration
configuration/reboot this file has been downloaded to the system. The operation will
module reboot this control module only.
2 Load configuration from Download a new configuration file from a suitable USB
USB Memory memory stick.
3 Save configuration to Copy the existing configuration file to a suitable USB
USB Memory memory stick.
4 Save changes to CAUTION!
configuration It is highly recommended to backup the
configuration file before continuing.
Use this command to save all changes made from the control
panel to the system configuration.
NOTE!
The changes are not permanently saved in the
configuration file until this command is performed.
5 Remove configuration Select and remove files from a list of configuration files in
the system.
6 Synchronise system CAUTION!
configuration It is highly recommended to backup the
configuration file before continuing.
Use this command to synchronise the configuration files in
the system.
7 Reboot system (this The operation will reboot the system with this control
module excluded) module excluded.
There will be a 15 seconds delay before the system restarts.
8 Synchronise the Use this menu to change the active configuration of the CS
CS-modules modules.
NOTE!
This menu alternative is intended for SIL classified
systems only.

16 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

7 History Menu

1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Fire History List
4 Login 2 Fault History List
5 Settings 3 Disable History List
6 Service Menu 4 Common History List
7 History
8 Condition List

Table 9. History menu alternatives


Alternatives Description
1 Fire History List Shows a chronological list of the last 1000 fire alarms.
2 Fault History List Shows a chronological list of the last 1000 fault alarms.
3 Disable History List Shows a chronological list of the last 1000 disablements.
4 Common History List Shows a common chronological list of the last 1000
pre-alarms, fire alarms, fault alarms, disablements, warnings,
and I/Os.

8 Condition List Menu

1 Fault Alarms
2 Fire Alarms
3 Disablements 1 Satisfactory
4 Login 2 Poor
5 Settings Detectors not listed in these two
6 Service Menu choices are in Good condition.
7 History
8 Condition List

The Condition list menu provides the means to perform a status check of the
detectors in the system. Detectors that are no longer in good condition but still fully
functional will be present in either of these lists, and detectors in good condition
will not be present at all.

Table 10. Condition list menu alternatives


Alternatives Description
1 Satisfactory This list shows detectors that still are in satisfactory condition (50-80%
(Lightly dirty) and fully functional. However, the environment has started to
contaminated degenerate the detectors and they are no longer in good condition. Please
detectors) consider to replace the detectors during the next planned maintenance
work.
2 Poor This list shows detectors that have gone beyond satisfactory condition
(Heavily and entered poor condition (81-100% dirty), but are still fully functional.
contaminated When the detector has gone beyond poor condition it is also shown in
detectors) the fault or warning list (depending on the configuration), with the
description "130 DIRTY SENSOR". (See also Note below).
When a detector has reached poor condition it shall be replaced. It will
be removed from the condition list after replacement.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 17


3 Control Panels User Guide

NOTE!
In systems with CCP version 1.9.10 or older, dirty detectors are instead removed
from the poor condition list and are only present in the warning or fault list with
the description "130 DIRTY SENSOR".

3.2 Repeater M 4.3


3.2.1 General
The repeater panel is used to monitor functions in the fire detection system. It is
possible to view and list:

• Fire alarms
• Fault alarms
• Disablements

3.2.2 Description of Keys and Indicators

Figure 8. Keys and indicators for the repeater panel.

Repeater panel

Power
Green steady light indicates that the power supply to the repeater panel is OK.


Local Mute
Silence the local buzzer alarm.


Fire - Fault - Dis.
Press the key to select the lists: Fire Alarm, Fault Alarm and Disablements.


Navigation key – previous

18 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 3 Control Panels

Scroll to previous item in the selected list.


Navigation key – next
Scroll to next item in the selected list.


Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.


Day mode
Increase the brightness/contrast level for the indicators and display on the panel.

• Lamp test
When you press the keys for Day and Night mode at the same time, all the repeater
panel indicators as well as the display are lit and the buzzer is sounding – if not, they
are not working correctly.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 19


3 Control Panels User Guide

20 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

4 Operations

4.1 Access Levels


CAUTION!
To prevent un-authorised operation of the system access levels protect the different
functions of the fire detection system.

Some functions in the menus will require a higher access level than the default
level due to safety restrictions.

Access level 2 is the default level. After the access level has been changed to a
higher level, it automatically returns to access level 2 when the control panel has
not been used for 30 minutes. For special applications access level 1 can be
applied. This will allow the user to only mute the local buzzer and scroll though the
fire and fault lists.

Description of Access levels


There are different access levels as shown in the following table:

Table 11. Access levels


Access Procedure to enter level User Permissions
level
2 Operator access level Personnel trained and authorised to For viewing of fire or fault alarms:
None operate the system in case of fire or • Fire alarms have priority over
maintenance. fault alarms.
• Possibility to mute local buzzer.
• Access to the menu system
• List status
• Reset and muting of alarms

2B Operator access level Personnel trained and authorised to Same permissions as level 2, plus
Enter access code for level 2B operate the system in case of fire or this additional permission:
via menu/login. maintenance. • Make disablements

3 Power User access level Personnel trained and authorised to Same permissions as level 2B, plus
Enter access code for level 3 via make changes to the configured these additional permissions:
menu/login. system. • Possibility to make changes to
the configured system

4 Service access level Only authorised service personnel All functions available, including
Enter access code for level 4 via trained by an authorised service advanced service options.
menu/login. organisation.

Custom Specific Restrictions


NOTE!
Permissions on the different access levels can in some cases vary depending on
programmed custom specific restrictions.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 21


4 Operations User Guide

A Control Panel M 4.3 could be programmed to view events in the system with
restricted rights to operate functions. For example a fire alarm is shown, but mute
and reset are not allowed.

4.2 Login
WARNING!
To secure the functionality of the fire detection system only authorised users
should be given access to disablement or test mode privileges in the system.

Each user shall be assigned to a specific access level.

To log in to the system:

1 Go to Menu » 4 Login and select user.


2 Enter the four-digit access code for the The system will acknowledge
user. if the correct code is entered.

4.3 Pre-Alarm
The pre-alarm function gives an early alarm to fire conditions (e.g., a smouldering
fire). The indication “Pre-Alarm” begins flashing on the control panel.

Fire alarms have priority over pre-alarms, pre-alarms have priority over faults.

The pre-alarm is also added to the Pre-Alarm List found under: Menu » 2 Fire
Alarms » 2 Pre-Alarm List.

An active pre-alarm can be muted, this silences the internal buzzer and causes the
pre-alarm indicator to stop flashing. The indicator remains lit until the pre-alarm is
reset. A pre-alarm will remain in the Pre-Alarm List until it has been muted and
reset.

The pre-alarm usually does not activate any alarm devices or external outputs.

4.4 Fire Alarm


4.4.1 Information Displayed when “Fire” is Flashing
DANGER!
In case of a fire alarm use the information viewed on the display to verify the alarm
and take the appropriate actions based on local safety procedures.

The following sections describes the information displayed during a fire alarm,
how to mute and reset an alarm, and the different types of alarms.

22 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

Figure 9. A fire alarm is detected in the system.

The following information is displayed in the Control Panel:

• Number of alarm(s)
• First, last and current list entry
• Zone in alarm
• Type of unit in alarm
• Address number of unit in alarm (only for addressable loop)
• Supplementary text (defined in system configuration)

Press for more details:

• Time of alarm
• Date of alarm
• Supplementary text about location of the detector (defined in system
configuration)

4.4.2 Mute a Fire Alarm


The Mute key has different functions depending on the current access level.

1 Press Silences the internal buzzer


and all external alarm
devices*, and mutes the fire
alarm indication. The fire
indicator stops flashing, but
remains lit until the Fire
Alarm is reset.
2 Press for more details.

* Programmable function of external devices, set in the Configuration program


(programmed by system Cause/Effect).

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 23


4 Operations User Guide

4.4.3 Reset a Fire Alarm


1 Press to reset the current Fire Alarm. NOTE!
Alarms cannot be
reset as long as the
device remains in
alarm condition.
When reset is not possible a
dialog box appears to explain
why.

4.4.4 Several Alarms


If there is more than one fire alarm in the system, the indication is activated.
The first and last fire alarms are always displayed in the control panel.

1 Scroll through the different fire alarms with


the key or the / arrow keys.
2 Mute and reset as above. For detailed instructions, see
Mute a Fire Alarm, page 23
and Reset a Fire Alarm, page
24.

4.4.5 Type of Fire Alarms from Conventional Zones


The fire detection system will display whether it was a single detector or a manual
call point/multiple detectors that generated the fire alarm. If two or more detectors
are activated in the same zone, the fire alarm will be presented as a manual call
point/multiple detectors.

4.5 Fault Alarm


4.5.1 Information Displayed when “Fault” is Flashing
WARNING!
In case of a fault alarm use the information viewed on the display to verify and
reset the fault.
Use the list of fault codes in the manual for more information about cause and
remedy.
If the problem remains take the appropriate actions to restore the functionality of
the fire detection system.

WARNING!
If an internal hardware or software fault has occurred it has to be restored as
prompt as possible in order to secure the functionality of the complete fire
detection system.

The detection of a dangerous fault shall result in either:

• a specified action to achieve or maintain a safe state; or

24 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

• the repair of the faulty system within the mean repair time (MRT). During this
time the continuing safety shall be ensured by additional measures and
constraints. The safety integrity provided by these measures and constraints
shall be at least equal to the safety integrity provided by the FDS in the absence
of any faults.

The following sections describe the information that is displayed when a fault
occurs, and how to mute and reset a fault.

Figure 10. A fault is detected in the system.

The following information is displayed in the Control Panel:

• Number of detected fault(s)


• Type of fault
• Identification of the faulty loop unit or module
• Supplementary text for the faulty loop unit or module (defined in system
configuration)

Press for more details:

• Time when the fault occurred


• Date when the fault occurred
• Supplementary text about the location of the fault (defined in system
configuration)

4.5.2 Mute a Fault


1 Press to silence internal buzzer and mute all faults in the list.
2 Press for more details.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 25


4 Operations User Guide

4.5.3 Reset a Fault


1 Press to reset the current fault alarm. NOTE!
If the cause of the
fault alarm remains,
the alarm cannot be
reset. Check the fault
code in the Fault Code
List to solve the
problem.

4.5.4 Reset a Fault from the Fault List


All faults in the system are shown in the fault list.

1 Go to the fault list under: Menu » 1Fault


Alarms » 1 Fault List
2 Choose the fault in the fault list and then NOTE!
press to reset the fault alarm. If the cause of the
fault alarm remains,
the alarm cannot be
reset. Check the
problem, solve it, and
reset the fault.

4.5.5 Reset All Faults


1 Go to: Menu » 1 Fault Alarms » 3 Reset All
Faults
2 Press The system will make an
attempt to reset all faults.

4.5.6 Fault Messages


WARNING!
In case of a fault alarm use the information viewed on the display to verify and
reset the fault.
If the problem remains take the appropriate actions to restore the functionality of
the fire detection system.

The control panel displays a fault with information about where in the system the
fault occurred and a short description of that fault.

Hint!
See the Fault Code list for further information about cause and remedy.

The fault message is also added to the fault list found under: 1 Fault Alarms » 1
Fault List.

26 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

4.5.7 Warnings
NOTE!
The user shall monitor and act on warning messages according to the presented
information about the state of the system. (Warnings are not as serious as faults and
only of informative nature.)
• Perform suitable maintenance if needed.

The warnings priority level is lower than the ordinary fault alarm level.

The warning is also added to the Warning list found under: Menu » 1 Fault Alarms
» 2 Warnings.

A warning will remain in the Warnings list until the fault condition is under the
level for warnings.

4.6 Disablements
4.6.1 About Disablements
WARNING!
To secure the functionality of the fire detection system only authorised persons
should be given access to disablement privileges in the system.

It is possible to disable different devices attached to the system, such as detectors,


manual call points, alarm devices, external control devices, and loops.

The available disablements (permanent, timer, clock and periodic) are described in
the next chapter.

All disablements are presented in a disablement list.

NOTE!
The yellow Disablements indicator is lit on the control panel when at least one
disablement is activated in the system and remains lit until all disablements are
reconnected.

To perform a disablement you must enter access level 2B or higher.

DANGER!
When a fire detector or zone is disabled, the fire detection system will not be able
to detect any occurring fire in that area. It is therefore important that disablements
are minimized in terms of quantity of disabled units and duration of time.

Hint!
If dual detectors heat/smoke are installed, it is possible to disable only the smoke
detection part of the detector and keep the heat detecting part active or vice versa.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 27


4 Operations User Guide

4.6.2 Available Types of Disablements


1 Permanent disablement
2 Timer disablement
3 Clock disablement
4 Periodic disablement

There are four different types of disablements available.

Permanent disablement
The device is permanently disabled until it is manually enabled.

NOTE!
It is possible to limit the disablement time by defining a maximum disablement
time in the configuration program.

Timer disablement
Disablement is instantaneous and lasts for the time period entered (hh:mm).
Maximum disablement time is 23 hours 59 minutes. Maximum disablement time
can be limited depending on rules and regulations.

Clock disablement
Enter a reconnection time. Disablement is instantaneous and the reconnection will
take place next time the entered time occurs. The maximum disablement time is 23
hours 59 minutes.

Take the time entered under consideration on vehicles/trains/ships going through


different time zones. If the system time is not synchronized with the
vehicle/train/ship's central time, adjust the time manually or connect the system to
a central clock via the serial interface.

Periodic disablement
A disablement for a certain time period during certain days of the week. Example:
Disable zone 1 each Tuesday and Friday between 7.00 - 17.00.

Take the time entered under consideration on vehicles/trains/ships going through


different time zones. If the system time is not synchronized with the
vehicle/train/ship's central time, adjust the time manually or connect the system to
a central clock via the serial interface.

4.6.3 Acknowledgement of a New Disablement


Once a new disablement is correctly entered, an acknowledgement is presented on
the control panel. The Disablements key indicates with steady yellow light, use it
to activate the Disablements list.

The new disablement is also added in the disablements list under: Menu » 3
Disablements » 2 Disablement list

28 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

4.6.4 Disabling Zones


(Access level 2B or higher)

Disabling a Conventional Zone

1 Select Menu » 3 Disablements » 1 New disablement » 1 Zones


2 Choose Zone (Zone number)
3 Choose disablement type (Permanent, Timer, Clock or Periodic)
4 Enter time (if Timer, Clock or Periodic was chosen in the previous step)

Disabling an Addressable Zone

1 Select Menu » 3 Disablements » 1 New disablement » 1 Zones


2 Choose Zone (Zone number)
3 Choose detector type (Smoke detectors, All detectors, Heat detectors,
Flame detectors, or Manual Call Points)
4 Choose disablement type (Permanent, Timer, Clock or Periodic)
5 Enter time (if Timer, Clock or Periodic was chosen in the previous step)

4.6.5 Disabling Addressable Detectors & Manual Call


Points
(Access level 2B or higher)

NOTE!
Disabling of individual detectors is only possible on addressable loops.

1 Select Menu » 3 Disablements » 1 New Disablement » 2 Detectors &


Manual Call Points
2 Choose zone (Zone number)
3 Choose unit type (Smoke detectors, All detectors, Heat detectors, Flame
detectors, or Manual Call Points)
4 Choose unit address or interval (address number(s))
5 Choose disablement type (Permanent, Timer, Clock, or Periodic)
6 Enter time (if Timer, Clock, or Periodic was chosen in the previous step)

Hint!
It is also possible to disable detectors from the Fire List.

4.6.6 Disabling Alarm Devices


(Access level 2B or higher)

Examples of alarm devices are bells, buzzers and flash lights.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 29


4 Operations User Guide

Disablements of alarm devices:

1 Select Menu » 3 Disablements » 1 New Disablement » 4 Alarm Device


(Bells etc.)

4.6.7 Old Disablements


Use this menu to reactivate previously performed disablements.

NOTE!
Only permanent disablements can be reactivated.

1 Select Menu » 3 Disablements » 4 List old disablements


2 Mark the appropriate old disablement in the list and and press “0” to
reactivate the disablement.

4.6.8 Disabling Alarm Delay


An alarm delay function will delay the activation of alarm devices in case of a fire
alarm. The delay time is programmable.

The alarm delay may be disabled which means that there will be no delay between
the fire alarm and the activation of the alarm device outputs.

1 Select Menu » 3 Disablements » 6 Alarm


Delay
2 Select central.
3 Select type of delay (Permanent, Timer, See Available Types of
Clock or Periodic) Disablements , page 28 for
explanation.

Set delay time (Access level 3 or higher):

NOTE!
Delay time is only possible to set if no time is set in the configuration program.

1 Select Menu » 5 Settings » 5 Alarm Delay


Times » 1 Alarm Delay Time 1 (mute)

Alarm Delay Time 2 (reset) is only used for special applications.

30 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

4.6.9 Disabling External Control Groups


(Access level 2B or higher)

Examples of external control groups are fans or outputs controlling fire doors.

1 Select Menu » 3 Disablements » 1 New


Disablement » 3 External Controls » 1
External Controls
2 Select an output category to be disabled. All groups = all categories of
doors, ventilation, etc.
3 Select System or Central. Press OK. It is possible to disable all the
external controls in the entire
system or in individual
centrals.
4 Press

4.6.10 Disabling an Alarm Transfer Output


(Access level 2B or higher)

Disablements of the alarm transfer output, used in industrial installations to alert


the fire brigade in case of a fire alarm:

1 Select Menu » 3 Disablements » 1 New Disablement » 3 External Controls


» 2 Alarm Transfer

4.7 Reconnecting
4.7.1 Reconnecting Disabled Items
All disablements in the system are presented in the disablement list. Any
reconnection is made from this list.

1 Select Menu » 3 Disablements » 2 List disablements


2 Choose the disablement you want to cancel.
3 Press

4.7.2 Reconnecting Periodic Disablements


Periodic disablements in the system are presented in the periodic disablement list.

Reconnecting is made from this list:

1 Select Menu » 3 Disablements » 3 List periodic disablements


2 Choose the periodic disblement you want to cancel.
3 Press

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 31


4 Operations User Guide

4.7.3 Reconnecting Disabled Alarm Delays


All disabled alarm delays in the system are presented in the alarm delays list. Any
reconnection is made from this list.

1 Select Menu » 3 Disablements » 7 List Alarm Delays


2 Choose the disablement you want to cancel.
3 Press

4.7.4 Remove All Disablements


This menu removes all active disablements presented in the Disablement list.

1 Select Menu » 3 Disablements » 5 Remove


all disablements
2 Confirm with OK to remove (reset) all NOTE!
active disablements in the system. Periodic disablements
are not permanently
removed. Only the
periodic disablement's
active period is
removed.

4.8 Service Menu


4.8.1 About the Service Menu
(Access level 2 for basic functions, but access level 4 is needed to perform
advanced service options.)

The Service menu is used for configuring the system in the commissioning phase,
as well as for troubleshooting and making updates when the system is in operation.
The menu has functions for loading and saving information from/to an approved
USB memory stick (available from an authorised dealer).

The Service menu displays a list of the 9 service menu alternatives, as shown
below.

1 System Details
2 Centrals
3 Modules
4 Zones
5 Loops
6 Configuration
7 Firmware
8 System Log
9 I/O lists

32 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 4 Operations

Please refer to the Service and Maintenance manual for detailed information about
the Service menu.

4.8.2 Save the System Log to a USB Memory Stick


If you want to check the information saved in the system log you can download it
from the central unit. The system log files contain information generated for
evaluating the system, such as lists of system components, system software and key
events. 

Table 12. The following lists are included in the log


Centrals list Key events
Disablement list Modules list
Fault list Periodic disablement list
Fire alarm list Pre alarm list
History list Warning list

The system log files can be downloaded using an approved USB memory stick
(available from an authorised dealer).

CAUTION!
Do not remove the USB memory stick until the download is finished.

1 Connect the USB memory stick to the USB port on the Control M 4.3
panel.
2 Choose Menu » 6 Service Menu » 8 System Log » 1 Save syslog.
3 Press OK to save the systems log files to the USB memory stick.
4 The system will now download the system log files. Wait until this process
is complete!
5 Disconnect the USB memory stick and copy the system log files to a PC.
File name example: sysLog_no_YYYY-MM-DD-xxxxxx

4.8.3 How to report a fault


In case it is not possible to troubleshoot and solve a specific problem, please follow
these guidelines when contacting an authorized service office.

• Describe the fault symptom, be specific


• Describe how the fault situation can be generated
• Attach a system log file (instructions for download from the Fire detection
system can be found in section Save the System Log to a USB Memory Stick,
page 33)
• Attach the configuration file (instructions for download from the Fire detection
system can be found in the Service & Maintenance manual or in the
Configuration manual)
• Attach the backbone log if applicable
• Add your contact information

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 33


4 Operations User Guide

34 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 5 Testing

5 Testing

5.1 About Testing


CAUTION!
Perform visual inspection of all fire detectors as often as needed to find detectors
which have deliberately been covered (vandalised). Because a covered detector
will not be able to detect a fire and the fire detection system can't detect if a
detector has been covered.

CAUTION!
Check for contaminated detectors. Use the Control panel menu system to display a
list showing in which condition the detectors are.

For additional information about testing, please refer to the Service and
Maintenance Manual.

NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).

NOTE!
A warning will be displayed on the menu screen as long as the system is not
running Cause/Effect, which is the two first minutes after the system has been
powered up

5.2 Test Mode Overview


The system has a special test mode function which makes the testing easier. 

When a zone is in test mode:

• External alarm devices and controls are by default not activated in case of a fire.
Hint!
This functionality can be turned off if controls are to be tested while the
tested zone is in test mode.
(Menu » 3 Disablements » 1 New Disablement » 3 External Controls)

• The alarm level is lowered to give a quick response to detector test equipment.
• LED indicators on loop units are blinking.
• Each tested loop unit will indicate activation with a steady LED indicator.
• Key events (as well as information of system components and system software)
will be stored in the system log which can be saved on a USB memory stick. If
a printer is connected to the system, alarms will automatically be printed as a
result of the tested units.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 35


5 Testing User Guide

• The units in alarm are automatically reset when the heat or smoke concentration
is under the alarm level, or when the test key is removed from the manual call
point.

NOTE!
Fire alarm from zones not in test mode will be handled normally by the fire
detection system.
The zone in test mode will automatically return to normal operation after two
hours.

5.3 Testing a Fire-detecting Zone


The functions of the FDS shall be tested at the interval stated in each application
specific documentation.

CAUTION!
During system start-up the smoke detectors perform a 15 minutes calibration
according to the level of particles in the air. No tests should be done during this
period.

1 Put the zone into test mode under: Menu » Access level 2B is required.
3 Disablements » 1 New disablement » 5
Test Mode .
2 Select a zone and confirm by pressing the The Disablements, Test, and
key. Zone/Unit indicators light to
confirm that they are in test
mode.

Each detector, manual call point and input in this fire zone can be tested during the
next two hours. Refer to Test Mode Overview, page 35 for further information
about a zone in test mode.

All alarms are listed under: Menu » 7 History » 1 Fire History List .

To return the tested zone to its normal condition, refer to Reset Test Mode, page
37.

CAUTION!
If the system previously had been put into regular fire detection service, a zone in
test mode should be manually monitored, e.g. by a fire watch in order to maintain a
tolerable risk level.

NOTE!
Use appropriate test equipment.
See section Recommended Test Equipment, page 37.

36 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 5 Testing

5.4 Recommended Test Equipment


Table 13. List of recommended test equipment for Fire detection systems
Product  Description
Testifire Multi-stimulus detector tester for smoke and
heat detectors
Salwico Solo 330 Smoke detector tester
Smoke Sabre Aerosol smoke detector tester
Salwico SOLO 461 Heat detector tester
Salwico IR Test lamp IR flame detector tester
Salwico UV Test lamp UV flame detector test lamp
W8066 UV test lamp
Test key for manual call point A test key is supplied with each call point

For detailed information, please refer to the data sheets for the products.

5.5 Reset Test Mode


NOTE!
After testing is completed, return the tested zone to its normal condition.
Before exiting test mode, make sure there are no detectors or manual call points in
alarm condition.
The tested zone will automatically return to normal operation after two hours if no
manual reset have been performed.

To reset test mode:

1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 List disablements.
2 Choose the zone in the disablement list and then press .

5.6 Test the Control Panel Display


With the function Test display it is possible to verify the functionality of:

• The display 
• All indications on the control panel

NOTE!
The user has to verify that the display and all indications are working properly.
This function will not generate a fault alarm in case something is faulty.

1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
2 Verify that the display momentarily shows a test image.
3 Verify that all system indicators and operational keys momentarily lights
up.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 37


5 Testing User Guide

38 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

6 Appendix - Fault Code List

6.1 Fault Code List

WARNING!
In case of remedy “replace the unit” or “replace the module” – this has to be
carried out as soon as possible in order to secure the functionality of the fire
detection system.

Listed in the table below are all fault codes generated by system modules1 and loop units2 ,
their causes, and how an operator with knowledge of the system can classify and solve the
problem.
A fault generated by a system module is often identified as:
“CENTRAL nn Unit type nn Fault description , FAULT nnn”
A loop unit fault is often identified as:
“ZONE nn Unit type nn Fault description , FAULT nnn”

Hint!
Instructions for troubleshooting and replacement can be found in the Installation
manual or the Service & Maintenance manual.

1) Central components and control/repeater panels.


2) Units connected to the loop line, e.g. detectors and manual call points.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 39


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
One module has
been replaced by
Switch to the correct module. • Minor fault if
another type of
module. redundant system
and only one
One module address
module in the
has been changed to
redundant function.
the same address as
another module on Check address of the modules. • Major fault if
System the same backbone redundant system
modules (a secondary fault and one or more
appears). modules in the
redundant function.
Defect module. Replace the module.
Cable break, short • Major fault if one or
circuit or wrong more modules in a
Locate the cable break, short non-redundant
electrical connection
circuit or check the electrical system.
of the internal
connections.
communication bus
NO ANSWER (BBI to BBE).
Explanation: Lost
The loop unit has
communication.
electrically been
128 The system has Connect the loop unit.
disconnected from
recognized a
the loop.
unit/module but
lost contact. The loop unit has Check that the correct loop unit
been replaced by is installed.
another type of loop
unit, or the loop unit Check that the ID switch for an • Minor fault if only
ID has been I/O ICxx unit is set correct. one detector within
changed. an area covered by
other detectors.
One loop unit 1. Check address of the units.
Loop units
address has been set • Major fault if two or
2. Rescan or restart the loop.
to the same address more detectors
as another loop unit within the same
on the same loop (a area.
secondary fault
appears).
Defect unit. Replace the unit.
Cable break or short
circuit in a loop (a Locate the cable break or short
secondary fault circuit.
appears).

40 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
The detector has a
faulty sensor Replace the unit.
element.
The smoke detector Protect the detector from the
is exposed to strong airflow or consider repositioning
airflow. the detector.
• Check the device on the
129 SENSOR FAULT Loop units Input on a sub-loop sub-loop. Major fault
has a removed or
faulty device, an • Check the end of line
open circuit, or a component.
cable break. • Locate the cable break.

There are two loop 1. Check address of the units.


units with the same
2. Rescan or restart the loop.
address on the loop.
Minor fault (or Service
fault).
The fault code is
presented before the
The detector has a
Smoke contamination level
130 DIRTY SENSOR dirty (contaminated) Replace the detector.
detectors becomes critical for the
sensor element.
risk of spurious alarm
or no alarm. The
remedy shall still be
performed.
Fewer loop units Check the loop configuration
found than and electrical connections.
configured. Loop
units not correctly 1. Check address of the units. Major fault.
TOO FEW
Detector association
131 LOOP UNITS Loop M X installed or 2. Rescan or restart the loop.
addressed. missing for internal
FOUND
control.
Missing answer Check the address (possible
from one or more double address).
units. Otherwise replace the unit.
More loop units
Check the loop configuration
found than Major fault.
TOO MANY and electrical connections.
configured. Detector association
132 LOOP UNITS Loop M X
1. Check address of the units. missing for internal
FOUND Loop units not control.
correctly installed. 2. Rescan or restart the loop.

Loop I/O Check that the cable between Major or Minor fault
IN1 CABLE There is a cable
133 units with input and end of line resistor is depending on project
BREAK break on input 1.
inputs complete. specific function.
Loop I/O Check that the cable between Major or Minor fault
IN2 CABLE There is a cable
134 units with input and end of line resistor is depending on project
BREAK break on input 2.
inputs complete. specific function.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 41


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
Charger M 1. Measure the voltage from the
power source.
• If voltage OK, change
External 24V power
loop unit.
Loop units source missing or
135 EXT 24V FAIL with the local power • If voltage NOT OK, Major fault.
external supply unit is change the DC/DC.
power defective.
2. If problem not solved contact
an authorized service office.

There is a fault in
the feedback
Check the cable for the feedback
between the loop
from the connected device to the
Loop I/O unit and the Major or Minor fault
FEEDBACK loop unit, for instance the
136 units with externally connected depending on project
FAULT door/damper.
inputs device (for example, specific function.
a door or a damper).
External load is Check the cable and the external
missing. load.
Loop I/O A supervised unit
Major or Minor fault
POSITION units with (for example, a door
137 Check for abnormal conditions. depending on project
FAULT specific or damper) is in the
specific function.
IDs wrong position.
• Major fault if no
short circuit
isolators on the
A short circuit in the
CM 4.3 loop.
detector loop cable
CM 2.2 Locate the short circuit.
or conventional • Major fault if loop
I/O M 70
LOOP SHORT zone. with short circuit
138 but not for
CIRCUIT
non-affected areas.

Loop unit
with short A short circuit in the
Locate the short circuit. Major fault.
circuit detector loop cable.
isolator
• Major fault if no
short circuit
isolators on the
Short circuit on the loop.
LOOP A SHORT
139 Loop M X A-side of a detector Locate the short circuit.
CIRCUIT • Major fault if loop
loop.
with short circuit
but not for
non-affected areas.

42 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
• Major fault if no
short circuit
isolators on the
Short circuit on the loop.
LOOP B SHORT
140 Loop M X B-side of a detector Locate the short circuit.
CIRCUIT • Major fault if loop
loop.
with short circuit
but not for
non-affected areas.

• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK positive conductor
141 Loop M X Locate the cable break.
POSITIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.

• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK negative conductor
142 Loop M X Locate the cable break.
NEGATIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.

1. Check the connection


between the module and the
CM 4.3 A serial protocol has other end connected via the
CM 2.2 communication serial protocol.
CM X problems.
2. Contact an authorized service • Minor fault if in no
COMMUNICATI office. combination with
ON ERROR other faults
Explanation: The Faulty loop unit. Replace the loop unit.
143 • Major fault if in
communication 1. Locate interference source.
Interference on loop combination with
with a loop unit is
cable or loop unit 2. If not possible to solve the other faults i.e.
deficient.
from external problem, contact an Fault 128.
Loop units
source. authorized service office.

There are two loop 1. Check address of the units.


units with the same
2. Rescan or restart the loop.
address on the loop.
The type of loop
1. Change configuration.
unit found in the
loop is different 2. Contact an authorized service
LOOP UNIT from the original office.
144 TYPE Loop units type configured. Major fault.
CHANGED A loop unit has been
1. Check address of the units.
incorrectly
addressed during a 2. Rescan or restart the loop.
replacement.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 43


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
UNKNOWN The Loop M X
TYPE OF LOOP cannot identify the
Replace the unit.
UNIT FOUND type of the affected
Explanation: The loop unit.
145 type of loop unit Loop units Major fault.
found is not Wrong type of 1. Install the correct type.
corresponding to detector has been
the configuration 2. Rescan or restart the loop.
installed.
file.
A timer loop unit Major or Minor fault
Loop based
146 TIMER STUCK has been active for Check the status of the loop unit. depending on project
timers
more than 12 hours. specific function.
CM 4.3 Short circuit has
CM 2.2 1. Locate the short circuit.
been detected on an
I/O M 70 output to the 2. Reset the fault.
SHORT I/O M 700 affected module.
149 Major fault.
CIRCUIT Short circuit has
been detected on Locate the short circuit on the
Loop units
external cabling to external cabling to the loop unit.
the loop unit.
Loop I/O 1. Open the valve.
External equipment Major or Minor fault
units with
150 VALVE CLOSED indicates that the 2. Contact an authorized service depending on project
specific
valve is closed. office. specific function.
IDs
1. Check the address of the
system module.
The affected system
System module is not in the 2. Check the system
modules system configuration file.
configuration file. 3. Contact an authorized service
office.
PRESENT NOT
152 Minor fault.
CONFIGURED 1. Check the address of the loop
unit.
The affected loop
unit is not in the 2. Check the system
Loop units configuration file.
system
configuration file. 3. Contact an authorized service
office.

There is an earth
Charger M
fault on the positive Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
155 Minor fault.
POSITIVE has detected an earth Locate the earth fault on the
Loop units fault on the positive external power supply to the
conductor from the loop unit.
power supply.

44 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
There is an earth
Charger M
fault on the negative Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
156 Minor fault.
NEGATIVE has detected an earth Locate the earth fault on the
Loop units fault on the negative external power supply to the
conductor from the loop unit.
power supply.
ChangeOv A fuse has been
Replace the fuse.
er M Ext blown.
157 FUSE FAULT Minor fault.
A fuse in a power Contact an authorized service
Loop unit
loop unit has blown. office.
A battery fuse has
been blown, or a
Charger M Replace fuse or restore the cable.
cable to the battery
BATTERY is broken. Major or Minor fault
158 CABLE/FUSE 1. Check the connection to the depending on project
FAULT There is a problem specific function.
battery.
with the battery
Loop units
connected to the 2. Consider replacing the
power loop unit. battery.

CM 4.3
CM 2.2
RM 4.3 A cable break or
Charger M short circuit has Restore the cable.
CABLE I/O M 70 been detected.
159 BREAK/SHORT I/O M 700 Major fault.
CIRCUIT Loop M X
• Check the end of line
Loop I/O Input on a loop unit
component.
units with has an cable break
inputs or short circuit. • Locate the cable break.

Too high current on


I/O M 700 Check external load.
the output.
Too high current on Contact an authorized service
CABLE Loop M X
160 the loop line. office. Major fault.
OVERLOAD
The loop unit is
Loop units reporting too high Check external load.
current.
1. Check the connection
There is a problem between the loop unit and the
Major or Minor fault
with the power power supply.
161 POWER FAULT Loop units depending on project
supply to the power
2. Contact an authorized service specific function.
loop unit.
office

Charger M
ChangeOv Emergency power Major or Minor fault
EMERGENCY Check the emergency power
162 depending on project
POWER FAULT er M Ext has been lost. supply.
specific function.
Loop units

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 45


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
The battery charger
BATTERY (Charger M) is The battery charger (Charger M)
164 Charger M Minor fault.
CHARGER unable to charge the is unable to charge the battery.
battery.
EXTERNAL
CM 4.3
FAULT
CM 2.2
Can be generated Major or minor fault.
RM 4.3 External equipment
165 by customized Check the external equipment. See project specific
Charger M is indicating a fault.
defined fault. See system description.
I/O M 70
Custom text for the
I/O M 700
particular fault.
CHECKSUM
EEP
The booting
Only applicable
sequence was not
167 for a redundant Loop M X Rescan or restart the loop. Minor fault.
completed in a
controlled loop
correct way.
with two Loop M X
modules
If restarts happen repeatedly
System The module has
168 RESTARTED without known reason, contact Minor fault.
modules restarted.
an authorized service office.
The module has
1. Restart the module.
been in the
TOO LONG System
169 validating or 2. Contact an authorized service Minor fault.
BOOT TIME modules
configuring states office.
for too long.
CM 4.3 There is too high
EXTERNAL Check the load and reduce if
170 CM 2.2 external load on a Major fault.
LOAD possible.
I/O M 70 conventional zone.
EXTERNAL CM 4.3 Unexpected voltage
171 POWER CM 2.2 detected in a Located and remove the source. Major fault.
SOURCE I/O M 70 conventional zone.
1. Measure the voltage from the
power source.
• If voltage OK, change
Low voltage on the module.
primary 28VDC
LOW POWER • If voltage NOT OK,
172 Charger M power supply to the Major fault.
SUPPLY PSU 1 change or adjust the
internal system
DC/DC.
modules.
2. Contact an authorized service
office.

46 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source. • Minor fault if power
• If voltage OK, change sources are
Low voltage on the module. redundant and not
secondary 28VDC from the same
LOW POWER • If voltage NOT OK,
173 Charger M power supply to the source.
SUPPLY PSU 2 change or adjust the
internal system
DC/DC. • Major fault if power
modules.
from the same
2. Contact an authorized service power source.
office.

1. Measure the voltage from the


power source.
• If voltage OK, change
module.
The incoming 24
LOW POWER
VDC supply to the • If voltage NOT OK,
175 SUPPLY Loop M X Major fault.
internal circuit change or adjust the
OPERATING
boards is too low. DC/DC.

2. Contact an authorized service


office.

The configuration
file is corrupt. 1. Download the configuration
file again.
An error has
occurred during 2. Contact an authorized service
downloading of the office.
CM 4.3
SYSTEM configuration file.
CM 2.2
176 CONFIGURATI Open configuration file in the Major fault.
CM X
ON FAULT The configuration correct version of CCPConf and
RM 4.3
file is saved in an resave the configuration file.
incompatible Which version of CCPConf used
version of the depends on the version of the
CCPConf. firmwares installed in the CCP
modules.
Loop I/O
External equipment Major or Minor fault
LOW units with Check the pressure on the
177 indicates low depending on project
PRESSURE specific supervised unit.
pressure. specific function.
IDs
Charger M
The main power
180 MAINS POWER ChangeOv Check the main power supply. Major fault.
supply is lost.
er M Ext

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 47


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
The connection
between the main
processor and the
CM 4.3
processor handling
the keyboard input
has been lost.
The module is
leaking power. The
INTERNAL Charger M supply and Contact an authorized service
181 Major fault.
FAULT consumption differ office.
greatly.
The Loop M X has
failed to schedule a
loop unit it
Loop M X considers to be in
working condition
for more than 30
minutes.
• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
183 CH 1
modules on channel 1 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.

• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
184 CH 2
modules on channel 2 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.

The module hasn’t


CM 4.3 received any
NO POLL CM 2.2 communication Check system status for the
185 Major fault.
FROM MASTER CM X from the backbone configured master.
RM 4.3 master in the last 30
seconds.
A short circuit or
Major or Minor fault
cable break has been Check the line or device
188 CABLE FAULT Loop units depending on project
detected on an I/O connected to the I/O port.
specific function.
port on a loop unit.
The protocol version
The fault is resettable once all
of a module (slave
incompatible modules have
INCOMPATIBL System and/or controller) is
196 reported a compatible version. Major fault.
E MODULES modules not compatible with
Alternatively they must be
the central master
removed or disabled.
version.
The type of loop
WRONG TYPE 1. Change the loop unit.
unit found is
209 OF LOOP UNIT Loop units Minor fault.
different from the 2. Rescan or restart the loop.
FOUND
type configured.

48 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
CM 4.3
CAUSE/EFFECT Fault detected in the Contact an authorized service
210 CM 2.2 Major fault.
ERROR configuration file. office.
CM X
The system fails to
SYNCHRONISA System Contact an authorized service
212 synchronize with the Major fault.
TION SIGNAL modules office.
affected module.
The configuration
file in the system is Synchronise the configuration
not the same in all file between all panel.
CM 4.3 modules.
CM 2.2 Central X Module Y
CM X settings in
CONFIG NOT RM 4.3 configuration file Check configuration and
213 SYNCHRONIZE Major fault.
compared to DIP-settings.
D
DIP-settings are not
OK.
The DIP-settings of
the Charger M are Check configuration and
Charger M
incorrect compared DIP-settings.
to configuration file.
The Charger M is
delivering a higher
current than the
maximum allowed
current limit to the
CURRENT affected Bus/Output. 1. Check the number of
modules configured.
214 LIMIT Charger M The Charger M is Major fault.
EXCEEDED consuming a higher 2. Check the external load.
current than the
maximum allowed
current limit from
the affected
PSU/Battery.
The battery
connected to the
CHARGING
affected Charger M Charge the battery with an
215 CURRENT Charger M Major fault.
is charged with a external charger.
EXCEEDED
higher current than
allowed.
The firmware in a 1. Try to reset the fault.
Charger M
module does not 2. If not possible to reset try to
ChangeOv
comply with the update firmware again.
er M Ext
INCOMPATIBL modules hardware (Might demand for system
216 I/O M 70 Major fault.
E FIRMWARE version. reboot.)
I/O M 700
The fault might
Mux M 16 3. Contact an authorized service
occur during
Relay M 8 office.
firmware update.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 49


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source.
• If voltage OK, change
The voltage module.
delivered from PSU
HIGH • If voltage NOT OK,
217 Charger M 1 to the affected Major fault.
VOLTAGE PSU 1 change or adjust the
Charger M module
DC/DC.
is too high.
2. Contact an authorized service
office.

1. Measure the voltage from the


power source. • Minor fault if power
• If voltage OK, change sources are
The voltage module. redundant and not
delivered from PSU from the same
HIGH • If voltage NOT OK,
218 Charger M 2 to the affected source.
VOLTAGE PSU 2 change or adjust the
Charger M module
DC/DC. • Major fault if power
is too high.
from the same
2. Contact an authorized service power source.
office.

1. Check the fuse.


• If fuse OK, change
module.
The fuse protecting • If fuse NOT OK, change
FUSE FAULT
219 Charger M the PSU 1 voltage the fuse (or change the Major fault.
PSU 1
input is broken. module if LRU).

2. Contact an authorized service


office.

1. Check the fuse.


• Minor fault if power
• If fuse OK, change
sources are
module.
redundant and not
The fuse protecting • If fuse NOT OK, change from the same
FUSE FAULT
220 Charger M the PSU 2 voltage the fuse (or change the source.
PSU 2
input is broken. module if LRU).
• Major fault if power
from the same
2. Contact an authorized service
power source.
office.

A PSU is connected 1. Check the electrical


to the PSU 1 input connections according to the
on the affected drawings.
PSU1 PRESENT Charger M module,
2. Check the configuration file.
221 NOT Charger M but the Charger M Minor fault.
CONFIGURED module is not 3. Contact an authorized service
configured to have a office.
PSU connected to
PSU 1 input.

50 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
A PSU is connected 1. Check the electrical
to the PSU 2 input connections according to the
on the affected drawings.
PSU2 PRESENT Charger M module,
2. Check the configuration file.
222 NOT Charger M but the Charger M Minor fault.
CONFIGURED module is not 3. Contact an authorized service
configured to have a office.
PSU connected to
PSU 2 input.
The voltage level
internally in the
Charger M is at least
1 volt below the
voltage delivered
from the PSUs.
INTERNAL Contact an authorized service
223 Charger M Without battery Major fault.
VOLTAGE LOW office.
charge, the system
shuts down at 18.5
VDC. With battery
charge, the system
shuts down at 21
VDC.
The voltage level
internally in the
Charger M is at least
1 volt above the
voltage delivered
INTERNAL from the PSU:s.
Contact an authorized service
224 VOLTAGE Charger M Without battery Major fault.
office.
HIGH charge, the system
starts up at 20.0
VDC. With battery
charge, the system
starts up at 25.5
VDC.
CM 4.3
CM 2.2
When the affected
CM X
module measures 1. Check backbone signals for
Charger M
the X-Fire signal in cable breaks.
ChangeOv
225 XFIRE SIGNAL the backbone, the Major fault.
er M Ext 2. Contact an authorized service
voltage level of the
I/O M 70 office.
signal is below 4
I/O M 700
volts.
Loop M X
Relay M 8
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
primary system bus connections according to the
CM 4.3 redundant.
PRIMARY within 30 seconds drawings.
226 CM 2.2
SYSTEM BUS by the master • Major fault if
CM X 2. Contact an authorized service
(module with communication is
office.
address 1) in the not redundant.
affected central.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 51


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
secondary system connections according to the
CM 4.3 redundant.
SECONDARY bus within 30 drawings.
227 CM 2.2
SYSTEM BUS seconds by the slave • Major fault if
CM X 2. Contact an authorized service
(module with communication is
office.
address 2) in the not redundant.
affected central.
1. Check the electrical
The affected module connections according to the
has not responded drawings.
CM 4.3
NO ANSWER within 30 seconds
228 CM 2.2 2. Replace the module. Major fault.
SYSTEM BUS on
CM X
primary/secondary 3. Contact an authorized service
system bus. office.

1. Check cabinet and battery


temperature.
The battery or
229 OVERHEATED Charger M Charger M is too 2. Check the battery condition. Major fault.
hot. 3. Contact an authorized service
office.

CM 4.3 1. Measure the voltage from the


CM 2.2 power source.
CM X • If voltage OK, change
RM 4.3 module.
Too low voltage
LOW VOLTAGE ChangeOv
detected on the • If voltage NOT OK,
230 CH 1 er M Ext Major fault.
backbone bus power change or adjust the
BACKBONE I/O M 70
supply, channel 1. DC/DC.
I/O M 700
Loop M X
2. Contact an authorized service
Mux M 16
office.
Relay M 8
CM 4.3 1. Measure the voltage from the
CM 2.2 power source.
CM X • If voltage OK, change
RM 4.3 module.
Too low voltage
LOW VOLTAGE ChangeOv
detected on the • If voltage NOT OK,
231 CH 2 er M Ext Major fault.
backbone bus power change or adjust the
BACKBONE I/O M 70
supply, channel 2. DC/DC.
I/O M 700
Loop M X
2. Contact an authorized service
Mux M 16
office.
Relay M 8

52 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 6 Appendix - Fault Code List

Unit or
Fault Code Cause Remedy Failure classification
Module
The bootloader in 1. Try to reset the fault.
the affected module 2. If not possible to reset try to
Charger M cannot start the update firmware again.
ChangeOv application due to a (Might demand for system
er M Ext corrupted firmware. reboot.)
INVALID I/O M 70 This fault might
232 occur during a 3. Contact an authorized service Major fault.
APPLICATION I/O M 700
firmware upgrade. office.
Loop M X
Mux M 16
The module has a The fault is resettable once the
Relay M 8
higher protocol module is downgraded.
version than the
central master.
A relay is broken or
in a state that
damages the relay.
233 RELAY Relay M 8 Replace the module. Major fault.
(The voltage over
the relay coil is too
high.)
The affected module 1. Check for cable breaks on
NO ANSWER is not answering on the extension bus. Major or Minor fault
RM 4.3
234 EXTENSION the extension bus depending on project
MN400 2. Contact an authorized service
BUS where it is specific function.
office.
connected.
1. Check the address of the
The type of module module according to
WRONG TYPE
System found is different electrical drawings.
236 OF MODULE Major fault.
modules from the type
FOUND 2. Contact an authorized service
configured.
office.

Check the power supply to the


aspiration detector. (Green
control LED inside aspiration
box shall be lit when power
No external power OK.)
to the aspiration • If voltage OK and Fan not
(ASP) unit. running, see "Fan broken"
below.
• If voltage NOT OK, change
Aspirating or adjust the DC/DC.
238 FLOW FAULT smoke Major fault.
detector The fan in an
aspiration detector Check in the aspiration box if a
does not work red LED is lit at the same time
correctly. as the green.
(Fault generated by • If yes, change the aspiration
the Loop M X). box.
NOTE: Critical
• If no, change the smoke
error which can
detector inside the aspiration
cause the detector to
box.
not detect a fire
alarm.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 53


6 Appendix - Fault Code List User Guide

Unit or
Fault Code Cause Remedy Failure classification
Module
The voltage level of
the GA signal in the
backbone is below 4
CM 4.3 volts.
CM 2.2 (Fault generated by 1. Check that Charger M puts
CM X modules which have out a monitoring voltage on
RM 4.3 GA-morse the backbone
239 GA FAULT Major fault.
Charger M configured for any
2. Contact an authorized service
I/O M 70 of its outputs)
office.
I/O M 700 NOTE: Critical
Relay M 8 error which can
cause the GA
functionality from
working.
A write operation
Major or Minor fault
DEVICE WRITE into the loop unit’s
241 Loop units Replace the loop unit. depending on project
FAULT internal EEPROM
specific function.
memory failed.
CM 4.3 The system has not
Contact an authorized service
242 SERVICE TIME CM 2.2 been serviced for a Major fault.
office.
CM X period of time.
System
modules Internal system Contact an authorized service
255 ILLEGAL Major fault.
error. office.
Loop units

54 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 7 Appendix - Definitions and Abbreviations

7 Appendix - Definitions and Abbreviations

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 55


7 Appendix - Definitions and Abbreviations User Guide

7.1 Definitions and Abbreviations


Definitions and abbreviations for the fire detection system. 

Active high By active high it means that the output is normally not energized in normal condition
and when system is not energized. By active high on input it means that the input is
normally not energized. This is the NO contact on a relay.
Active low By active low it means that the output is normally energized in normal condition and
system running. By active low on input it means that the input is normally energized.
This is the NC contact on a relay.
Alarm condition The state of the system when a fire or gas has been detected.
Alarm delay When activated the activation of alarm devices will be delayed for a preset time
(normally 2 minutes).
Alarm device Device that is activated in case of fire, for example audible and optical alarms like
bells, sirens and flashlights.
Alarm Transfer Output A supervised output for signalling that a fire has occurred. The Alarm Transfer Output
is usually used in onshore systems for alerting the fire brigade.
APF Application Program File.
Application program file A file holding the application parameters for the FDS.
ASP detector Aspiration detector.
Backbone Bus External The main bus outside a central cabinet used for communication between modules and
(BBE) stretched central parts. It consists of two redundant RS485 channels, two 24 VDC
power lines and the Basic Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone Bus Internal (BBI) The main bus inside a central cabinet used for communication between modules. It
consists of two redundant RS-485 channels, two 24 VDC power lines and the Basic
Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone segment A Backbone bus may be split in several segments. Power feeding can be separate for
each segment by using one Charger M per segment. Communication can be isolated
between segments by using Isolator modules.
Basic Backup Signal (BBU) A signal in the Backbone bus that is used for transmitting the central's alarm status.
The signal is only used when a module in managed mode loses communication with its
controller module.
BER Bit Error Rate
BusCon M 20 A Bus Connector with 20 connectors in the flat-cable. This unit is used to connect the
Control M 4.3 to the backbone bus and also has the common fire and fault outputs.
Cause/Effect The Cause/Effect program defines how the inputs and outputs of the system should act.
CCP Consilium Common Platform. General modules which create a system for Consilium
products.
CCP platform An umbrella name for all the modules and devices that can be connected together, e.g.
“the Control M 4.3 module is a member of the CCP platform”.
Central A Central is a complete system that can operate autonomously; monitor its detectors
and inputs, activate its outputs and display its faults and alarms. If connected to other
centrals, it exchanges information with the other centrals via the System bus, thus
allowing all centrals to act as one system.
Each central can only have one Backbone bus.
Central cabinet Enclosure to contain a complete or part of a central.
Charger M The Charger Module. Can connect two PSU’s and a battery and feeds the power
channels on the backbone bus.

56 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 7 Appendix - Definitions and Abbreviations

Compact central Central cabinet including basic functionality of Fire Detection System such as: Control
panel, Power supply, Battery backup, basic I/Os and at least one analogue addressable
loop. The cabinet supplies limited expansion possibilities.
Configuration File A file holding the configurable parameters for the FDS.
Control module The Control M 4.3, the Control M 2.2 and the Control M X can all act as Controller
modules, i.e. be in controller mode.
Control panel The Control M 4.3 and Control M 2.2 can act as a Control panel, i.e. they have an HMI
and the rights to manipulate and supervise the system.
Controller mode Control modules can run in Controller mode, i.e. being Master or Hot Standby Master
within a central. Control modules can also be in managed mode, that is being a module
that is managed by the master. All other modules are always running in managed
mode.
Controller module A Control module that is in Controller mode (master or hot standby) in a central or
system.
Control M 2.2 A Control Panel with a 2.2” graphical colour display used to manage and supervise a
system.
Control M 4.3 Control Module with a 4.3” display, a keyboard and all the mandatory indications
required to comply with EN 54.
Control M X Control Module, a control module without a display, keyboard or mandatory
indications.
CR It is a heat detector class. The C means fixed alarm temperature at 84ºC. The R means
it also gives alarm for RoR.
CS Heat detector classification in EN 54-7; ‘C’ class indicates a static response
temperature of 84°C and ‘S’ that the detector will not respond below 80°C.
DCS Distributed Central System (see also Stretched central).
Detector A device capable of detecting smoke, heat, flames or gas.
DIP switch Dual in-line package switch. Used to set address etc. on loop units and modules.
Disablement Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
will be inhibited.
EMC Electromagnetic Compatibility.
EMI Electromagnetic Interference.
EN 54 The European product standard for fire detection and fire alarm systems.
ESD System Emergency Shut Down System, embedded system taking care of safety procedures in
case of emergency, for example shut down of fire doors, ventilation etc.
Ex Ex can mean different things depending on when it is mentioned. Examples: ‘Ex
proof’ means ‘Explosion Proof’, ‘Ex area’ means ‘Hazardous Area’ which is an area
where the atmosphere might be explosive. ‘Ex certified’ means both ATEX and IECEx
certification.
Ex-classification The protection type used in a hazardous area; e.g. Ex d.
Extension bus An additional (RS485) bus used inside a central for intra-central communication. The
Extension bus is typically used for connecting Repeater modules (that does not require
redundant communication and power) and should not be confused with the Backbone
bus.
External communication Communication to external entities is called external communication, using for
example MODBUS, NMEA or TCMS protocols.
External control Outputs used to control external equipment, for example fire doors.
Fault condition The state of the system when a fault is detected.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 57


7 Appendix - Definitions and Abbreviations User Guide

FDS Fire Detection System.


Firmware Embedded software.
FSK Frequency Shift Keying.
GA-auto Automatically generated signal according to a pre-defined pattern (e.g. 7 short 1 long
signal) for alarm devices or the PA system.
GA-Morse Signal pattern generated manually via the GA button.
GA General Alarm, common activation of alarm devices and activation of the PA system.
GDS Gas Detection System.
GRP Glass-Reinforced Plastic.
Heavy duty manual call point A heavy duty manual call point is made of GRP, metal or similar material and it has a
high level of corrosion resistance.
Hot Standby mode Controller modules in Hot Standby mode can take over the responsibilities of the
Controller module managing a central.
I/O Input/output.
I/O 70 An Input/Output type providing a different function depending on the configuration of
the system. The programmable functions are:
• General Input
• Fault Input
• Conventional Fire Alarm Zone
• Output (24 VDC/70 mA)

I/O 700 An Input/Output type providing a different function depending on the configuration of
the system. The programmable functions are:
• General Input
• Fault Input
• Output (24 VDC/700 mA)

I/O Module A module with inputs and/or outputs. I/O modules always run in Managed mode, that
is they must be managed by a Controller module.
I/O pin or I/O signal An I/O pin or an I/O signal is a logical signal, compare to terminal.
IDA The IDA communication protocol.
Inter-central communication Communication between centrals is called inter-central communication.
Interface channel A communication channel used to interface the systems with external devices.
Interface channels can be configured to communicate on different protocols.
Internal power supply Output power from PSU.
Intra-central communication Communication within a central is called intra-central communication. This
communication is between modules.
IP Ingress Protection - rating used to specify the environmental protection (enclosure) of
electrical equipment.
IS Intrinsically Safe.
Isolator M Isolator Module; used to distribute a part of a FDS.
ISS Integrated Safety System.
Loop The same as a loop-line.
Loop cable A cable which the FDS uses to power and communicate with the loop units. The loop
begins and ends in the loop module in the FDS.

58 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 7 Appendix - Definitions and Abbreviations

Loop module The piece of hardware within the FDS which powers and communicates with the loop
units connected to its loop-line.
Loop unit Fire detectors, gas detectors, manual call points and other devices that can be
connected to the Loop.
Loop-line A common name for the cable, loop devices and other equipment connected to a loop
module.
Loop-line IS A part of the loop-line protected by a galvanic isolator.
LRU A Line-Replaceable Unit (LRU) is a modular component that is designed to be
replaced quickly at an operating location.
Managed mode The opposite of Controller mode. All modules that are managed by a Controller
module are in Managed mode.
MCP Manual Call Point.
MCS Multi Central System. A system consisting of more than one central.
MFZ Main Fire Zone.
Mode of operation Modules in the system can take on different roles. Connected to the Backbone bus they
can be in:
• Central Controller Mode (Master or Hot Standby)
• Central Managed Mode
Modules connected to the System bus can be in:
• System Controller Mode (Master or Hot Standby)
• System Managed Mode

Module A module that is a part of the platform, where it can be used to build centrals. Modules
within the platform generally supply a Backbone bus interface. Controller modules
also have a System bus Interface.
Module address Module addresses are set via DIP switches on the modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
N/A Not Applicable.
OEM Original Equipment Manufacturer.
PA Public Addressing.
Power output Output providing power supply, normally used to power external devices.
Pre-Alarm condition A condition preceding the Alarm condition to give early warning for potentially
dangerous situations like a smouldering fire.
Programmable output Output which signal behaviour is configurable via the Configuration program.
PSU Power Supply Unit.
Rate of Rise Rate of Rise functionality by using C/E commands for setting of a different alarm
threshold and temperature rise threshold for heat detectors.
Redundancy Refers to the quality or state of being redundant, that is exceeding what is necessary or
normal. In the system the term is used to describe backup functionality like in Hot
Standby Controller modules.
Redundant loop Redundant loop means loop module redundancy on one single loop-line between two
loop modules.
Relay Electrically operated switch output, normally providing C/NO/NC contacts for
connection of signal receiver.
Repeater panel The main attribute for Repeater panels is that they can show information but not affect
the central (or system) they belong to. The Repeater M 4.3 is a Repeater panel.

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 59


7 Appendix - Definitions and Abbreviations User Guide

RS-485 Serial communication interface used for external communication and BackBone bus.
Is a standard defining the electrical characteristics of drivers and receivers for use in
balanced digital multipoint systems.
Safe State Modules enter 'safe state' when they detect system faults. Modules in Safe State put
their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
Salwico Language A text based interpreting language for making logical cause effect expressions
developed by Consilium.
SCI Short Circuit Isolator.
SCM Software Configuration Management.
SCS Single Central System.
SMig system Salwico Safety Management interactive graphics, a PC-based software package
providing graphical presentation and control of the system.
Spur Branch from a loop-line without return.
Stretched central (DCS) A central that is physically distributed to two or more physical locations. One location
may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
Sub-loop It is possible to connect sub-loop units to some loop units using a sub-loop cable. The
cable is however not a loop. One end is connected to the loop unit and the other end is
connected to the sub-loop unit.
Sub-loop unit A device which cannot be connected directly to the loop. A sub-loop unit can be a
switch or a relay contact will be used to send a fire or fault alarm to the FDS.
Synchronization signal A signal in the Backbone bus that is used for transmitting synchronization signal used
by system modules to synchronize there behaviour.
System A system consists of a number of loop units and one or more centrals.
System bus The communication bus used for connecting multi-central systems. The System bus is
used for inter-central communication but can also be used for external communication.
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System bus.
TBD To Be Done, To Be Decided/Determined.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Test condition Detectors put in the Test condition (or test mode) are inhibited from generating the
Alarm condition but the alarms are displayed on the Control panels to prove that the
tested detectors are operational.
USB Universal Serial Bus, a communications bus that may be used to connect flash
memories, keyboards, mice or other devices.
Warning Condition The state of the system when a warning is detected. Warnings are not as serious as
faults and only of informative nature, for example in case of a lightly contaminated
detector.
Zone A group of detectors located in a geographical area.

60 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


User Guide 8 Quick Guide for Control Panel M 4.3

8 Quick Guide for Control Panel M 4.3

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 61


Index

Index
A Fire alarm key, Control Panel M 4.3...................... 7
About testing.......................................................... 35 Fire alarm menu, Control Panel M 4.3 .................. 9
Access level ........................................................... 21 Fire alarm, reset ..................................................... 24
Alarm delay............................................................ 30 Fire alarm, Reset several alarms ............................ 24
Alarm delay off indicator, Control Panel M 4.3 .... 6 Fire alarm, From conventional zones..................... 24
Alarm device indicator, Control Panel M 4.3 ........ 6 Fire detection system ............................................. 21
Arrow keys, Control Panel M 4.3 .......................... 8 Fire detection system, System description............. 3
Arrow keys, Repeater M 4.3 .................................. 18 Fire history list ....................................................... 36
Fire alarm, Information displayed in the Control
 
Panel....................................................................... 23
C Fire alarm, Mute..................................................... 23
Clock disablement.................................................. 28 Fire-Fault-Dis. key, Repeater M 4.3 ...................... 18
Condition list menu, Control Panel M 4.3 ............. 9  
Control Panel M 4.3, Description of numerical
keypad .................................................................... 9
G
Control panel display, Testing................................ 37 General alarm system............................................. 21
Control Panel M 4.3, Description of operational  
controls................................................................... 7 H
Control Panel M 4.3, Description of system History menu, Control Panel M 4.3 ....................... 9
indicators................................................................ 6  
Custom indicators, Control Panel M 4.3................ 6
Custom specific restrictions................................... 21
L
Lamp test keys, Repeater M 4.3............................. 19
 
Local Mute key, Repeater M 4.3............................ 18
D Login menu, Control Panel M 4.3 ......................... 9
Day mode key, Control Panel M 4.3...................... 9  
Day mode key, Repeater M 4.3.............................. 19
Disablement list ..................................................... 37
M
Disablement list ..................................................... 28 Menu ...................................................................... 9
Disablement, Acknowledgement ........................... 28 Menu key, Control Panel M 4.3 ............................. 8
Disablements menu, Control Panel M 4.3 ............. 9 Multiple alarms key, Control Panel M 4.3............. 8
Disablements key, Control Panel M 4.3................. 7 Mute key, Fault alarm ............................................ 25
Disabling a conventional zone ............................... 29 Mute key, Fire alarm .............................................. 23
Disabling addressable detectors............................. 29 Mute key, Control Panel M 4.3.............................. 8
Disabling alarm devices......................................... 30  
Disabling alarm transfer output ............................. 31 N
Disabling an addressable zone ............................... 29 Night mode key, Control Panel M 4.3 ................... 9
Disabling external outputs ..................................... 31 Night mode key, Repeater M 4.3 ........................... 19
Disabling manual call points.................................. 29  
Download system log file ...................................... 33
 
O
OK key, Control Panel M 4.3................................. 8
E  
Enter key, Control Panel M 4.3.............................. 9
Erase key, Control Panel M 4.3 ............................. 9
P
Escape key, Control Panel M 4.3 ........................... 8 Periodic disablement.............................................. 28
Permanent disablement .......................................... 28
 
Power indicator, Control Panel M 4.3.................... 6
F Power indicator, Repeater M 4.3 ........................... 18
Fault alarm menu, Control Panel M 4.3................. 9 Pre-Alarm key, Control Panel M 4.3 ..................... 7
Fault alarm, Information displayed in the Control Pre-Alarm list......................................................... 22
Panel....................................................................... 25  
Fault alarm, Mute................................................... 25
Fault alarm, Reset from the Fault list..................... 26
R
Fault report............................................................. 33 Reconnecting disabled alarm delays...................... 32
Fault alarm, Reset .................................................. 26 Reconnecting disabled items.................................. 31
Fault alarm, Reset all faults ................................... 26 Reconnecting periodic disablements...................... 31
Fault key, Control Panel M 4.3 .............................. 7 Remove all disablements ....................................... 32

62 5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA


Index

Repeater M 4.3, Description of keys and


indicators................................................................ 18
Report a fault.......................................................... 33
Reset key, Fault alarm............................................ 26
Reset key, fire alarm .............................................. 24
Reset test mode ...................................................... 37
Reset key, Control Panel M 4.3 ............................. 8
 
S
Service Menu ......................................................... 32
Service menu, Control Panel M 4.3 ....................... 9
Settings menu, Control Panel M 4.3 ...................... 9
Shortcuts key, Control Panel M 4.3 ....................... 7
Status key, Control Panel M 4.3............................. 7
System fault indicator, Control Panel M 4.3.......... 6
System log files...................................................... 33
 
T
Test Equipment ...................................................... 37
Test mode overview ............................................... 35
Test indicator, Control Panel M 4.3 ....................... 6
Test the control panel display ................................ 37
Testing a fire-detecting zone .................................. 36
Timer disablement.................................................. 28
 
U
USB connection, Control Panel M 4.3................... 6
 
W
Warning List........................................................... 27
Warning indicator, Control Panel M 4.3 ................ 6
 
Z
Zone indicator, Control Panel M 4.3...................... 6
Zone, text mode ..................................................... 35
 

5100332-00_Salwico Cruise_User Guide_M_EN_2018_AA 63


FOR ALL THOSE MOMENTS
WHEN SAFETY MATTERS
Consilium is a producer of safety and safety-related technologies for the marine, oil and gas,
transport and building sectors. Our commitment goes beyond the products: We protect the
lives of mothers and fathers, sisters and brothers, colleagues and friends. With representation in
more than 25 countries in all time zones, we are always close to you.

www.consilium.se

You might also like