PMT Hps Honeywell Enraf Small Volume Prover Installation Operation Service Manual 005 025

Download as pdf or txt
Download as pdf or txt
You are on page 1of 136

FOR MODEL 05, 15, 25

Honeywell Enraf
Small Volume Prover Installation,
Operation & Service Manual

HONEYWELL ENRAF
SMALL VOLUME PROVER INSTALLATION,
OPERATION & SERVICE MANUAL

FOR
MODEL 05, 15, 25

3rd Edition
Released March 2016
Table of Contents

Safety instructions for installation, commissioning, . . . . . . . . . . . . . . . . . . . . ix


operation and maintenance
CHAPTER 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 General Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3 Honeywell Enraf small volume prover design specifications . . . . . . . . . . . . 1-2
1.4 Tests and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
1.5 Principle of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
CHAPTER 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1 Receipt of Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Return Shipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.3 Mechanical Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.4 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.4.1  Field wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.4.2 Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.4.3 Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.4.3.1  Customer Connection Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.4.3.2vPower Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.4.3.3  SVP Controller Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
CHAPTER 3 Controller Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Initial Power up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Navigating the SVP Controller Menus Using the LAD. . . . . . . . . . . . . . . . . . 3-1
3.2.1  Text Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.2 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2.3 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.3 Menus and Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.3.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.3.1.1  Key benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.3.2  Main Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.3.3  Screen Input Fields. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.3.3.1  Text Input Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.3.3.2  Numeric Input Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, iii


Operation & Service Manual
Table of Contents

3.3.3.3  Enumeration Input Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5


3.3.3.4  Status Bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.4  Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.5  Device Locking Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.3.6 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.3.6.1  Using the Configuration Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.3.6.2 Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.6.2.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.6.2.2 Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.6.2.3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.6.2.4 Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3.3.6.2.5 Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3.3.6.2.6  Sensor Pair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3.3.6.3  I/O Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.3.6.3.1  Alarm Relay Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.3.6.4 Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.3.7  Prover Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.3.8  System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.3.9 Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.3.9.1  Transaction Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.3.9.1.1  Transaction information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.3.9.2  Calibration Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.3.9.3  Alarm Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.3.10 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
3.3.11 Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
3.3.12  LAD Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
CHAPTER 4 Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Meter Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.3 Prover Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.4 Prover Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
CHAPTER 5 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Static Leak Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.3 Volume Water Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

iv Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Table of Contents

5.4 Gravimetric Water Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12


5.5 Calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
CHAPTER 6 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1 Run Prover Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2 Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2.1  Sensor out of sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2.2  Motor time out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2.3  Sensor stuck. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2.4  Service due . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.3 Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.3.1 Dashboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.3.2  System Health. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.3.3  Active Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.4 Troubleshooting Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
CHAPTER 7 Electrical Schematics & Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1 Schematics for prover wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2 Connections to Flow Computers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7.2.1 Omni . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7.2.2  CONDAT CIU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.2.3 Daniels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.2.4 Dynamic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
CHAPTER 8 Prover Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 Portable Prover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2 Stationary prover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.3 General Prover Maintenance Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.4 Downstream Shaft Seal Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.5 Prover Piston Assembly Seal Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.6 Upstream Shaft Seals Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8.7 Bolt Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
8.8 Drive System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
8.8.1  Before working on the Drive System . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
8.8.2  Checking Alignment of Drive System (general checking). . . . . . . . . 8-15
8.8.3  Checking Alignment of Guide Block. . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
8.8.4  Check the Alignment of the Flag . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
8.8.5  Check the Alignment of the Puller . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, v


Operation & Service Manual
Table of Contents

8.8.6  UHMW Chain Rail Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27


8.8.7  Adjust the Chain Tensioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27
8.8.8  Securing the Drive End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-28
8.8.9  Check Shocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-28
8.10 Thread Locker Fluid Location List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-32
8.11 After Sales Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-32
8.12 Frequently asked questions.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33

LIST OF FIGURES
Figure 1-1 Prover in Stand-By Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Figure 1-2 Prover During Prove Run - Mid-Run. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Figure 2-1 Process Connections and General Arrangement . . . . . . . . . . . . . . . . . . . . . 2-2
Figure 2-2 Prover Lifting Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Figure 2-3 Prover Service Clearance Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Figure 2-4 Designated anchor points (plates) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
                located on the bottom side of the prover frame
Figure 2-5 Electrical Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Figure 2-6 Customer Connection Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Figure 2-7 Power Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Figure 2-8 SVP Controller Box with LAD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Figure 3-1 The Local Access Device (LAD) and its system overview. . . . . . . . . . . . . . . 3-2
Figure 3-2 Main Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-3 Text Input Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-4 Numeric Input Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-5 Enumeration Input Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-6 Status Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-7 Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-8 Device Locking Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-9 Password Input Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-10 Configuration Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Figure 3-11 Configuration Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Figure 3-12 Prover Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Figure 3-13 System Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Figure 3-14 System Information Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Figure 3-15 Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16

vi Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Table of Contents

Figure 3-16 Logs Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16


Figure 3-17 Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Figure 3-18 Diagnostics Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
Figure 3-19 Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Figure 3-20 Transfer Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Figure 3-21 LAD Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Figure 3-22 LAD Settings Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Figure 5-4 Static Leak Detection set-up overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 5-5 Recommendation for seal change. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Figure 5-6 Water Draw Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Figure 5-7 Water Draw Plumbing Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Figure 7-1 Wiring Diagram 1 Phase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Figure 7-2 Wiring Diagram Dc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Figure 7-3 Wiring Diagram 3 Phase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Figure 8-1 Downstream Side Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Figure 8-2 Downstream Seal Retainer Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Figure 8-3 Guide Block Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Figure 8-4 Piston Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Figure 8-5 Piston Assembly Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
Figure 8-6 Piston Insertion into Flow Tube – Pulling Method . . . . . . . . . . . . . . . . . . . . 8-9
Figure 8-7 Upstream flange and seal retainer assembly. . . . . . . . . . . . . . . . . . . . . . . . 8-11
Figure 8-8 Guide Block Exploded View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
Figure 8-9 Gearbox Lubrication Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
Figure 8-10 Pinning Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
Figure 8-11 Tighten Guidebar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
Figure 8-12 Grounding the Prover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
Figure 8-13 Guide Block Shims. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
Figure 8-14 Stud Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-20
Figure 8-15 Correctly Seated Optical Switch Bottom and Side View. . . . . . . . . . . . . . . 8-21
Figure 8-16 Switchbar Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-22
Figure 8-17 Pipe Clamp Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Figure 8-18 Puller Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24
Figure 8-19 Adjustment Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-25
Figure 8-20 Shaft Loctite Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26
Figure 8-21 Chain Support Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, vii


Operation & Service Manual
Table of Contents

Figure 8-22 Recommended Chain Sag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-28


Figure 8-23 Shock Installation Depth. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29
Figure 8-24 Correct Optical Switch Installation Bottom View. . . . . . . . . . . . . . . . . . . . . 8-30
Figure 8-25 Correct Optical Switch Installation Side View. . . . . . . . . . . . . . . . . . . . . . . 8-31
Figure 8-26 Improper Optical Switch Installation Side View . . . . . . . . . . . . . . . . . . . . . 8-31
Figure 8-27 Improper Optical Switch Installation Bottom View 1 . . . . . . . . . . . . . . . . . 8-31
Figure 8-28 Improper Optical Switch Installation Bottom View 2. . . . . . . . . . . . . . . . . . 8-31

LIST OF TABLES
Table 1 Environmental Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Table 1 Environmental Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Table 2 Prover Flow Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Table 3 Wetted Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Table 4 Pressure Condition Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Table 5 Inlet and Outlet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Table 6 Motor Voltage Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Table 6 Motor Voltage Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Table 7 Electrical hazardous classification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Table 8 Flow Tube Finish. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Table 9 Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Table 10 Process temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Table 11 Optical switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Table 12 Nitrogen purge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Table 13 Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 14 Pullers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 15 Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 16 Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 17 Transmitters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Table 18 PED/PMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Table 19 NACE and water draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Table 20 Maximum allowable inlet and outlet flange loads . . . . . . . . . . . . . . . . . . . 1-11
Table 21 Prover Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Table 22 Maximum pressure drop per prover size. . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Table 23 Volumetric Water Draw Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Table 24 Gravimetric Water Draw Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18

viii Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Table of Contents

Table 25 Honeywell Enraf Troubleshooting Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3


Table 26 Bolt Torque Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Table 27 Guide Block Bolt Torque Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . .8-13
Table 28 Frequently Asked Questions.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, ix


Operation & Service Manual
Table of Contents

Intentionally left blank.

x Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
THE HONEYWELL ENRAF PROVER SERIES

Safety instructions for installation, commissioning, operation


and maintenance

Preface

The Honeywell Enraf (HE) SVP (Small Volume Prover) is a high precision
instrument for verification of calibration of flow metering equipment. The
SVP Controller and the Fusion4 Local Access Device (LAD) form the
control aspects of the SVP. The LAD is a hand held controller used to
interface to the SVP Controller allowing tasks such as the adjustment of
parameters, resetting of alarms and calibration. The LAD facilitates two way
data communications between the SVP Controller and the LAD, allowing
the rapid transfer of transaction data, configuration files and calibration
records and even upgrading of firmware in the field. The following warnings
apply to all components of the SVP.

Warning

Only use the instrument for its intended purpose.

EC declaration of conformity

Refer to the EC declaration of conformity and ATEX certificate(s), shipped


with the instrument.

Installation

The mechanical and electrical installation shall only be carried out by


trained personnel with knowledge of the requirements for installation of
explosion proof equipment in (potentially) explosive atmospheres.
The entire installation procedure shall be carried out in accordance with
national, local and company regulations. The entire electrical installation
shall be carried out in accordance with the International Standard
EN 60079-14 for electrical equipment to be installed in (potentially)
explosive atmospheres.
No specific installation requirements apply to the LAD; the device is
factory ready for connection to Fusion4 parent devices (for example the
SVP Controller).

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, xi


Operation & Service Manual
The Honeywell Enraf Prover Series

Warning – Risk of Explosion



Do not open any of the electronics enclosures when an explosive
atmosphere may be present.

Warning – Risk of Explosion



Explosion proof (Ex d) compound cable glands or conduit sealed directly at
all cable entries must be used.
Which type depends on local & national requirements and legislation.
For the SVP Controller these glands and seals are installed at the factory.

Warning – Risk of Explosion



Unused cable entries must be sealed with an approved metric or NPT
threaded stopping (“Stopper”) plugs. Take care to select whichever is
appropriate and contact Honeywell Enraf in case of doubt. Improper
installation of cable glands, conduit or stopping plugs will invalidate the
Ex approval.

Warning – Risk of Explosion



Intrinsically safe connections to the SVP are factory wired. No unauthorized
changes are allowed as these would invalidate the approval.
The LAD and the SVP Controller are intrinsically safe devices and as
such may only be connected to devices with compatible intrinsically safe
parameters. Intrinsically safe cabling may only be connected to the outside
5 pin socket of the SVP Controller. Connection of non-intrinsically safe
signals will invalidate the approval. The electrical data of the intrinsically
safe circuits is to be taken from the ATEX/IECEx certificates (numbers see
below) which are shipped with the instruments.

Warning – Risk of Explosion



In order to withstand the explosion pressure the bolts of the SVP Controller
lid must be fastened hand-tight (approximately 13.5 to 17.6 Nm [10 to 13
Lbf-Ft]) but don’t overtighten so as not to damage the threads.

Warning – Risk of Explosion



For ensuring intrinsic safety, ground connection of one of the internal
boards to the enclosure and the box to the local grounding system is
crucial. The former is done at the factory but the local grounding is required
to ensure compliant installation.

xii Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
The Honeywell Enraf Prover Series

Warning

For information on the dimensions of the flameproof joints, contact
Honeywell Enraf.

Warning – Risk of injury



Honeywell Enraf recommends mains power to be shut off, including
lockout-tagout at that mains switch to ensure safety during maintenance
and related work being performed on the inside of the drive end cover.

Warning – Risk of injury



Ensure that the motor drive end and downstream shaft covers are always
in place before operating the device, to guard against human injury.

Warning – Risk of injury



Pressurize system slowly to avoid a hydraulic shock which could result in
damage to prover, personnel, and/or piping systems.

Warning – Risk of injury



Ensure that the unit is fully depressurized and drained prior to disassembly
or service.

Commissioning

The commissioning of the instrument shall be conducted by qualified


engineers, trained by Honeywell Enraf and with knowledge of the
(local and national) requirements for electrical equipment in (potentially)
explosive atmospheres.

Operation

After commissioning the Honeywell Enraf SVP and its associated


SVP Controller can be used for its intended purpose. After connecting
to the SVP Controller the LAD can be used for its intended purpose. The
memory card can be removed and inserted also in hazardous areas but be
aware that the device is then no longer suitably protected against ingress
of water.

Maintenance and troubleshooting

In the unlikely event of malfunction, only a qualified service engineer, trained


by Honeywell Enraf and with knowledge of safety regulations for working in
(potentially) explosive atmospheres is allowed to repair the instrument.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, xiii


Operation & Service Manual
The Honeywell Enraf Prover Series

Additional information

If you require additional information, contact Honeywell Enraf or


its representative.
Approvals :
Refer to the EC declaration of conformity and ATEX certificate(s), shipped
with the instrument (as it may vary per configuration)
CE Directives and approvals:
CE Directive Certificate number
94/9/EC ATEX electrical LCIE 05 ATEX 6068X
94/9/EC ATEX mechanical Honeywell Enraf declared
2006/42/EC Machinery Directive Honeywell Enraf declared
97/23/EC Pressure Equipment Directive 60330-2009-CE-HOU-DNV

Environmental conditions:
Ambient pressure : atmospheric
Relative humidity : 5 – 95 %
Ingress Protection : IP56
(IP rating)
Ambient temperature : ATEX Approval
Standard Temperature: -20°C to +40°C
(-4°F to +104°F)
Extended Temperature Options: As broad as
-40°C to +40°C (-40°F to +104°F) or -20°C to
+60°C (-4°F to +140°F)

CSA Approval
Standard Temperature: -20°C to +40°C
(-4°F to +104°F)
Extended Temperature Options: As broad
as -40°C to +40°C (-40°F to +104°F)

IECEx Approval
Standard Temperature: -20°C to +40°C
(-4°F to +104°F)
Extended Temperature Options: As broad as
-40°C to +40°C (-40°F to +104°F) or -20°C to
+60°C (-4°F to +140°F)
Special Approvals : up to 60°C (140°F)

xiv Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
The Honeywell Enraf Prover Series

Additional information specific to the SVP Controller

Approvals :
ATEX: II 2 G Ex d [ia] IIB T6 Gb IECEx: Ex d [ia] IIB T6 Gb
Certificates:
Approval Certificate number
ATEX 12ATEX0101 X
IECEx DEK 12.0021X
CSA 11.2370409

Additional information specific to the Fusion4 LAD

Approvals :
II 2 G Ex ia IIB T4 Gb
Ex ia IIB T4 Gb
Certificates:
Approval Certificate number
ATEX KEMA 10ATEX0152
IECEx IECEx KEM 10.0070
CSA 11.2395571

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, xv


Operation & Service Manual
The Honeywell Enraf Prover Series

Intentionally left blank.

xvi Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
INSTALLATION PROCEDURE

 Warning

Please read this section carefully before installing, using, or maintaining


your Honeywell Enraf small volume prover. Failure to follow directions
may result in personal injury and/or property damage. Honeywell Enraf
is not responsible for injury/damages/losses as a result of deviation from
installation procedure.
 The Honeywell Enraf small volume prover is fitted with transit seals in both
the up & downstream shaft seal retainers upon its shipment from the
factory. It is important to replace these seals during the commissioning
procedure and prior to the process fluid being introduced into the unit.
An additional set of seals are supplied with every Honeywell Enraf small
volume prover for this purpose.

1. 
Before performing any operations with the Honeywell Enraf small
volume prover read this operation manual completely! Also read API
MPMS 4.8 “Operation of Prover Systems”, Current Edition. If there are
any uncertainties please consult your Honeywell Enraf representative
or the factory directly.
2. The Honeywell Enraf small volume prover has been designed to meet
certain operational conditions. Using the prover outside of these
boundaries may cause permanent damage and will void warranty
(ref. Section 1.3)
3. All provers are designed as per pressure standard ANSI B16.5. For
process temperatures above 37.8°C (100°F), pressure must be
de-rated, following the above mentioned standard.
4. Each Honeywell Enraf small volume prover is functionally tested at
different flow rates starting from the lowest to the maximum flow rates,
pressure tested (hydrostatic pressure test) and water draw calibrated
at the factory prior to shipment. When the equipment is received,
inspect the outside of the packing case(s) for damage. Any visible
damage should be reported to the carrier immediately, for the purpose
of liability. If anything is missing or incorrect from your shipment,
please contact your local Honeywell Enraf sales representative or
sales office. Have the serial number and sales order number available
to help expedite any assistance needed.
5. The Honeywell Enraf small volume prover has been designed to be
used as either a portable or stationary mounted flow prover. The
Honeywell Enraf small volume prover may be installed upstream
or downstream of the meter under test, as the displaced volumes
are equal.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, xvii


Operation & Service Manual
Installation Procedure

6. The Honeywell Enraf small volume prover should be installed on a flat


surface and secured using 4 bolts through the pre-determined anchor
points on the prover frame (Refer to Figure 2-4). It is recommended to
bolt the prover to the slab/trailer at these four locations only. It is not
recommended to use any other method or type of securing the prover
against the movement during operation. Honeywell Enraf will not be
responsible for possible damages to the prover or system parts if
these recommendations are not followed.
7. It is mandatory to provide enough space around the prover to
accommodate any removal of components during maintenance
(see Figure 2-3).
8. When installing the Honeywell Enraf small volume prover, follow all
recommended procedures regarding positioning of prover in relation
to the flow meter. To assure that all flow is passed through the flow
prover, double block & bleed diverter valves are recommended.
9. Ensure not to overload prover inlet & outlet nozzles. Maximum
allowable loads on prover nozzles are provided in the Table 10. It is
the customer’s responsibility to design piping systems and maintain
nozzle loads within the provers maximum allowable loads. It is also
important to provide adequate support of inlet and outlet piping.
10. Prover vent and drain lines must be plumbed to drain/collection
sumps. Do not vent directly from the bleed valves as personal injury
may occur.

 Warning
For proper operation of the SVPs it is mandatory to properly vent the
prover and to make sure that fluid vapor is removed from the SVP. SVPs
can fully function when proving fluids are in the liquid form only.

11. Install a correctly sized strainer/filter upstream of the prover in order


to ensure the flow entering the prover is free from debris and foreign
material. Honeywell Enraf’s recommendation would be to use strainers
with minimum 40 mesh screen.
12. To avoid over-pressuring of the prover and prover components, a
correctly sized pressure relief (as per API 520, API 521 and API 526),
should be installed on the downstream side of the prover. The option
for the installation of the relief valve would be to use one of the spare
openings in the downstream end flange or to install the relief valve
in the downstream section between the prover outlet flange and the
closest discharge valve.
13. Lifting instruction. (Ref. Figure 2-2).

xviii Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Installation Procedure

14. When connecting prover to pipeline, be certain that:


a. Flow direction is correct. Flow must go through the prover in the
proper direction. Severe damage may occur if flow direction is
not correct!
b. Bolts, flanges, and piping of sufficient strength are to be used for all
pressure retaining connections.
c. All connection bolts are tightened to correct torque specifications.
d. No foreign bodies, i.e.: weld slag, will be introduced into the prover.
15. Carry out the removal and replacement of transit seals with the
operation seals (as supplied) prior to introducing liquid into the
Honeywell Enraf small volume prover.
16. Pressurize system slowly to avoid shock which could result in damage
to prover, personnel, and/or lines.
17. Be certain that ALL applicable electrical codes are met when
connecting and using the Honeywell Enraf small volume prover,
especially in hazardous area locations. The Honeywell Enraf small
volume prover is certified by one of the following:
CSA/US certified for Class 1 Group D T2C
CSA/US certified for Class 1 Group C T3B
ATEX certified for II 2 (1) G Ex d [ia Ga] IIB T4 Gb
 IECEx compliant for Ex db [ia Ga] IIB T4 (See Individual Certificates)

It is the responsibility of the user to satisfy the relevant electrical code
requirements on connections made to the Honeywell Enraf small
volume prover.
18. Covers must be in place on all explosion-proof electrical enclosures
at all times when prover is energized. If it is necessary to troubleshoot
electrical components, it must be done in a “safe” area following
site procedure.
19. All drive covers must be in place during operation or anytime electrical
power is applied to the prover to avoid personal injury.
20. Shaft cover located on the downstream side of the flow tube must be
in place during prover operation to avoid personal injury.
21. Do not alter or modify the Honeywell Enraf small volume prover
without prior written consent from the factory. Honeywell Enraf will
not be responsible for possible damages, loss, or injury as a result of
unauthorized use or modification.
22. Ensure that the unit is fully depressurized and drained prior to
disassembly or service.
23. Prover frame must be correctly earth grounded prior to electrical
service. Grounding connector is located on the prover frame.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, xix


Operation & Service Manual
Installation Procedure

24. Follow all hazardous warning stickers! Pinch and crush points are
present on this equipment in addition to electrical shock hazards.

Important Notice to ALL Honeywell Enraf small volume prover users:


It is mandatory that all Honeywell Enraf small volume prover users
implement a method of preventing an over pressurization of the flow
prover. This task is most readily achieved through the use of a pressure or
safety relief valve. The use of a pressure or safety relief valve will reduce,
if not eliminate, possible failures due to over pressurization of the prover.
Due to the fact that each installation will require a different pressure relief
valve (based upon system pressure, fluid properties, flow rate, etc.), the
equations provided in API 520, API 521 and API 526 should be used to
size the appropriate relief valve.
The pressure rating of the relief valve should be calculated by taking the
maximum operating pressure and adding 10% for a momentary over
pressurization or line surge of the system.

IMPORTANT: WATCH DISCHARGE FROM RELIEVING DEVICES!


Additionally, take extra care when pressuring the flow prover at cold
temperatures. All Honeywell Enraf small volume prover tubes are
manufactured from stainless steel which experiences a reduction in
ductility at reduced and elevated temperatures i.e.: below -29°C (-20°F) or
above 37.8°C (100°F). Therefore, pressurization of flow provers in these
temperature regions should be done slowly!

Caution: Evidence has shown pitting in chromed surfaces can be caused


by water trapped in piston and shaft seal areas for long periods of time
(result of water draws).
Chrome pitting can also be caused from welding to or near structural
components of the prover such as the skid frame or piping (installation,
repair or modification work).

xx Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 1 INTRODUCTION

1.1 Overview
This manual provides the necessary information and procedures for the
proper operation of the Honeywell Enraf small volume prover manufactured
by Honeywell Enraf Americas, Inc.
The Honeywell Enraf small volume prover uses a wear and corrosion
resistant precisely honed flow tube. Contained within the flow tube is the
piston/bypass valve arrangement. Piston/bypass valve arrangement has
been designed in such a way that during the proving runs disturbance to
the flow is minimal. The free flowing piston has an inherent fail-safe feature
that will not cause disruption to the flowing fluid in case that the poppet
actuator shaft becomes disconnected or otherwise fails. The poppet
valve is coaxially mounted within the free moving piston. At the time a
calibration run is initiated by the operator, the piston assembly is moved
to the upstream end of the flow tube by a mechanical drive driven by an
explosion-proof electric motor. When upstream position has been reached,
the poppet valve actuator shaft is released by the return mechanism,
allowing the poppet valve to close and the flowing fluid to move the piston
through the measurement cylinder.
Slotted precision optical switches are utilized to define volume
displaced. These switches are reliable, fast (5 X 10-6s), and precise,
showing a maximum deviation of +/- 0.0005 % on repeatability of linear
measurement. For maximum fluid compatibility the only seals in contact
with the flowing fluid in the Honeywell Enraf small volume prover are filled
PTFE. A static leak detector is provided with the prover. This consists of
a device to generate a differential pressure across the piston. When filled
with fluid, and the blocking valves closed, the operator simply provides
a differential pressure gauge or transmitter to monitor any leakage while
differential is applied. (Refer to static seal leak test). The latest version of
the Honeywell Enraf small volume prover incorporates a hazardous area,
intelligent controller, utilizing state-of-the-art microprocessor technology
and a display to provide a window to the operation of the prover. When
used with its associated Local Access Device (LAD) you are able to view
the status of the calibration and perform diagnostics.
The contents of this manual provide general information and operational
characteristics for the Honeywell Enraf small volume prover. This
manual does not include information regarding auxiliary equipment for
unique applications. Consult your factory approved service center for
this information.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-1


Operation & Service Manual
Introduction

1.2 General Features


 Field replaceable precision optical volume measurement switches
without recalibration
 Flow-through poppet valve piston to minimize flow disturbances
 Patented electromechanical chain drive piston return mechanism
 Operates from a conventional electrical circuit (options include single or
3 phase power in most standard voltages and frequencies)
 24 Volt DC models available for portable proving applications requiring
no outside electrical service. Please note that 24 VDC motors are
available for installation on the prover sizes from the model S/O/P05
through S/O/P35 only
 Low consumables design reduces operating cost
 Quick and easy seal change. All seals are serviceable without removing
the unit from the pipeline
 Free flowing piston greatly reduces induced line disturbances
 Operates with industry standard flow computers for meter proving
capability and double chronometry
 Local display with menus driven by Local Access Device (LAD)
 Direct reading of sweep time (proving time)
 Alarm on/off display for flow computer
 Prover cycle counter
 Diagnostic dashboard
 Adjustable motor off delay which reduces wait time
 Scalable motor time off (system failure safe protection)
 Firmware in-situ upgradeable
 Alarm log records
 Calibration log records

These unique features provide greater confidence and operator


convenience while attaining more accurate performance tests of a fluid
flow meter in an operational line.

1.3 Honeywell Enraf small volume prover design specifications

Environmental Configuration: Honeywell Enraf small volume prover can


be installed and used in different configurations as specified in the Table 1
(see next page).

1-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

Standard operating process temperature range: -40°C to +80°C (-40°F to


+176°F). Consult factory for higher or lower temperature ranges.
Standard ambient temperature range: -20°C to +40°C (-4°F to +104°F).
Extended Temperature Options: ATEX/IECEx range as broad as -40°C to
+40°C (-40°F to +104°F) or -20°C to +60°C (-4°F to +140°F)
CSA range as broad as -40°C to +40°C (-40°F to +104°F)
Refer to the name plate for an individual units designed ambient and
process temperature ranges.
Local Access Device (LAD)
Operating temperature: -20°C to +65°C (-4°F to +149°F)
Storage temperature: -40°C to +85°C (-40°F to +185°F)

Environmental Configuration (Position 1)

S Standard prover for onshore installation

Offshore prover: 316 Stainless Steel for wetted parts and for drive end mechanical components (chains, bars,
O
sprockets etc)

P Portable prover with trailer supplied

Table 1: Environmental Configuration

Operating flow range: The operating flow range depends of the meter
type as stated in the Table 2 below. (Please Note: Below mentioned
maximum flow rates must be de-rated when the fluids with viscosity above
100 cSt are used.)

FLOW RATE (Position 2, 3, 4)

Model Displaced Volume Maximum Flow Maximum Flow Maximum Flow


Type (Gallons) (Barrels per Hour) (U.S. Gallons per minute) (cubic meters per hour)

05 5 715 500 114

15 20 2140 1498 340

25 20 3570 2499 568

35 25 5000 3500 795

50 40 7200 5040 1145

85 75 12500 8750 1987

120 120 17500 12249 2782

Table 2: Prover Flow Range

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-3


Operation & Service Manual
Introduction

"Manufactured pulses" Coriolis and Ultrasonic Flow meters : The


maximum flow rate usable with these new generation meters depends on
its pulse quality, its damping factor and response time. Consult the flow
meter manufacturer for information on de-rating.

AISI 316/316L (UNS31600/UNS31603) stainless steel: Honeywell Enraf


small volume provers can be supplied with wetted parts from 304 (AISI
304/304L - UNS30400/UNS30403) or 316 (AISI 316/316L - UNS31600/
UNS31603) Stainless Steel material as specified in the Table 3 below.
(Note: Materials choice should be based on product MSDS and application
information supplied by the end user.)

Wetted Parts (Position 5)

C 304 Stainless Steel flow tube with chrome plated bore. 304SS piston assembly, end flanges & shafts

316 Stainless Steel flow tube with chrome plated bore. 316SS piston assembly, flanges, & shafts
E
(Required for ‘O’ Models)

Table 3: Wetted Parts

Operating pressure range: Honeywell Enraf small volume provers comply


with ANSI 16.5 regulations depending on the prover flange rating and operating
temperature. (Note: Any operating temperature outside the -29°C to +37.8°C
(-20°F to +100°C) temperature range requires de-rating of maximum allowable
pressure as per ANSI B16.5.

ANSI B16.5 Flange Rating (Position 6) 005 015 025 035 050 085 120

1A Class 150 RF connection flanges # # # # # #

2B Class 300 RF connection flanges # # # # # #

3C Class 600 RF connection flanges # * * * * *

4D Class 900 RF connection flanges # * * * *

4F Class 1500 RF connection flanges

6A Class 150 RJ connection flanges * * * * * *

7B Class 300 RJ connection flanges * * * * * *

8C Class 600 RJ connection flanges * * * * * *

5D Class 900 RJ connection flanges * * * * *

9F Class 1500 RJ connection flanges *

"*" : available
"#" reduced lead time

Table 4: Pressure Condition Ranges

1-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

Inlet and Outlet Configuration: For easy installation and connection to


the end user’s piping system Honeywell Enraf small volume prover can be
configured per Table 5 below.

INLET AND OUTLET CONFIGURATION (Position 8 and 9)

0 Inlet both sides & Outlet flange left side

1 Inlet & Outlet flanges opposite-inlet right side

2 Inlet & Outlet flanges same side-right side

3 Flanges at 90°, Inlet on right side Outlet on top

4 Inlet & Outlet flanges same side-left side

5 Inlet & Outlet flanges both sides-double set

6 Inlet & Outlet flanges both on top

7 Inlet & Outlet flanges opposite-Inlet left side

8 Inlet flanges both sides & Outlet on top

9 Inlet flange on top & Outlet on left

11 Inlet flange on top & Outlet on right

12 Flanges at 90°, Inlet on right side Outlet on top

13 Inlet on right, Outlet on left, Outlet on top

14 Inlet and Outlet on the Bottom


Table 5: Inlet and Outlet Configuration

Motor Voltage Supply Options: The SVP motor characteristics have


been established to satisfy the industry needs globally for most facility
needs. Consult factory for other combinations.

Motor Voltage Supply (Position 10)

CSA 005 015 025 035 050 085 120

D 24 VDC Y Y Y Y

A 120 VAC, 60 Hz Y1 Y1 Y1 Y1 Y1

B 220 VAC, 60 Hz Y1 Y1 Y1 Y1 Y1 Y1

H 220/240 VAC, 60 Hz, 3 phase Y Y Y Y Y Y Y

E 460/480 VAC, 60 Hz, 3 phase Y Y Y Y Y Y Y

Motor Power 0.5 HP 1 HP 1 HP 1 HP 1 HP 2 HP 5 HP


Y from -40°C to +40°C
Y1 only available from -20°C to +40°C
Table 6: Motor Voltage Supply

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-5


Operation & Service Manual
Introduction

ATEX or IECEx 005 015 025 035 050 085 120

D 24 VDC Z2 Z2 Z2 Z2

C 220 VAC, 50 Hz Z Z Z Z Z

N 220/240 VAC, 50 Hz, 3 phase Z1 Z1 Z1 Z1 Z1 Z1

L 380/400/415 VAC, 50 Hz, 3 phase Z Z Z Z Z Z Z

E 460/480 VAC, 60 Hz, 3 phase Z Z Z Z Z Z Z

W 690 VAC, 60 Hz, 3 phase Z Z

Motor Power 0.5 HP 1 HP 1 HP 1 HP 1 HP 2 HP 5 HP


Z Available 20°C to +60°C or -40°C to +40°C
Z1 only available -20°C to +60°C
Z2 only ATEX, no IECEx available
Table 6: Motor Voltage Supply

Electrical Agency Approvals & Certifications: The SVP provers has


electrical agency approval for hazardous area classification installation that
cover the industry requirements.

Electrical hazardous classification (Position 11)

3 CSA/UL Class 1 Division 1 Group D T2C [CSA 70041568]

4 CSA/UL Class 1 Division 1 Group C T3B [CSA 70041568]

5 ATEX certified for II 2 (1) G Ex d [ia Ga] IIB T4 Gb

6 IECEx Ex db [ia Ga] IIB T4 [See Individual Equipment Markings]

X Special approval (On request)

Table 7: Electrical hazardous classification

Prover Finish: The prover comes standard with a brushed finish to


enhance the stainless steel materials. There is also an option for a white
paint seal coat for a higher level of environmental protection if required.

Flow Tube finish (Position 12)

A Stainless Steel - Brushed

B Painted (White)

Table 8: Flow Tube Finish

1-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

Temperature rating: The SVP is designed to operate continuously and


reliably within its domain of temperature. Consult factory for higher or lower
temperature ranges.

Ambiant temperature (position 13)

1 Low Ambient temperature range (-40 °C to +40 °C) (-40°F to +104°F)

2 High Ambient temperature range (-20 °C to +60 °C) (-4°F to +140°F)

3 Middle temperature range (-20°C to +40°C) (-4°F to +104°F)

Table 9: Ambient temperature

Process Fluid temperature (position 14)

A Standard (-40°C to +80°C) (-40°F to 176°F)

B Extended process temperature

Table 10: Process temperature

Options Extra optical switch: This switch reduces the volume signal to
a lower displaced volume to reduce the calibration runtime on low flow
rates. The smaller stroke volume is selected via a menu option. Position of
the third optical switch depends on the application : Please contact your
nearest sales office.

Third optical switch (position 15)

0 Without third optical switch

1 With third optical switch

Table 11: Optical switch

Nitrogen purge system: The purge covers consist of both a cover on the
downstream shaft and a cover for the drive end and are needed to prevent
icing of the shaft that can occur when the product temperature is below
0 °C (32 °F) when in operation. Covers are made of stainless steel and
will have O-ring sealing. The kit includes a pressure relief valve. The drive
end will also be purged via a purge control system. Purge system may be
manual or automatic, but the automatic purge is not available below
-20 °C (-4 °F) ambient temperature.

Nitrogen purge (position 16)

0 Without Nitrogen purge system

1 Nitrogen purge system, Automatic

2 Nitrogen purge system, Manual

Table 12: Nitrogen purge

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-7


Operation & Service Manual
Introduction

Insulation
This option is for applications on process fluid temperatures low or high
(above 60 °C - 140°F). It consist of two parts:
1. An insulation plate between the drive unit and flow tube.
2. An insulation jacket for the flow tube. This is model-dependent and not
suited for tracing. –– For low temperature applications the insulation
plate is a minimum requirement to protect the drive end.

Insulation (position 17)

0 Without insulation

1 Insulation plate

2 Insulation jacket and plate


Table 13: Insulation

Pullers: Models 35, 85 or 120 come with one puller as standard on the
chain drive pulling system. Adding an additional puller decreases the idle
time between runs and increases the frequency of the proving runs.

Additional puller (position 18)

0 Standard (Two pullers except models 35, 85, 120)

1 Additional puller on model 35, 85 or 120


Table 14: Pullers

Seal material: Standard seals are made of Ekonol® filled PTFE. For crude
oil applications it is advisable to use carbon-reinforced seals to increase
their lifetime.

Reinforced seal (position 19)

0 Standard Ekonol filled PTFE seal

1 Carbon Fiber Reinforced PTFE seal for crude oil applications


Table 15: Seals

Location and power of controller: On the standard design the controller is


facing right, as on the pictures. For constrained spaces it is possible to locate
the controller facing left. The SVP controller can be supplied in AC (100-240
VAC, Single Phase) or 24 VDC version. 70 Watts service recommended.

Controller (position 20)

0 AC voltage, facing right

1 AC voltage, facing left

2 24VDC power supply, facing right

3 24VDC power supply, facing left


Table 16: Controller

1-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

Pressure and temperature transmitters: The prover is delivered


as standard with Honeywell Smart transmitters ST800 and STT 250.
Other brands, or delivery without transmitters, are available on request.

Transmitters (position 21)

0 Standard Honeywell Transmitters

1 Other transmitters

2 No transmitters

Table 17: Transmitters


Pressure approvals: Testing & material certificates can be provided
according to 97/23/EC Directive. Material certificates will be according to
ISO EN10204: 2004 3.1 or ISO EN10204: 2004 3.2
Positive material identification on welds and pressurized parts will be
performed according API 587 on the parts as these enter the factory in
Roswell, GA.

Pressure approvals (position 22)

0 No approval

1 PED (Pressure Equipment Directive) 97/23/EC

2 PMI (positive material identification) on welds and pressurized parts

3 PMI +PED

Table 18: PED/PMI

NACE and Water Draw: NACE MR-0175 conformity for wetted


and pressurized parts (for use in corrosive environments in oil and
gas production).
The standard factory test is volumetric water draw by gravimetric
calibration (API Chapter 4.9.4). On request the factory can calibrate the
prover with volumetric method water draw according to API MPMS 4.9.2

(Position 23)

0 No NACE, gravimetric water draw

1 NACE MR-0175 (ISO 15156)

2 Volumetric water Draw according to API MPMS 4.9.2

3 NACE and volumetric water draw

Table 19: NACE and water draw

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-9


Operation & Service Manual
Introduction

Using the values from Table 1 through 9 allows information of the


design of the prover. (EXAMPLE: S25C1A4H4AH)

Maximum allowable flange loads: It is customer’s responsibility to design


the piping system so that the forces (loads) on the inlet and outlet nozzles
of the prover are lower than the maximum allowable loads specified in
the Table 10.

S/O/P05 – Inlet/Outlet Nozzle Nominal Diameter: 3 inch

FX = 467 N 105 lbf Mx = 664 Nm 490 lbf•ft

Top Nozzle Fy = 747 N 168 lbf Each Nozzle My = 503 Nm 371 lbf•ft

Fz = 623 N 140 lbf Mz = 332 Nm 245 lbf•ft

FX = 747 N 168 lbf

Side Nozzle Fy = 623 N 140 lbf Resultant Fr = 1993 N 448 lbf

Fz = 934 N 210 lbf Mr = 1329 Nm 980 lbf•ft



S/O/P15, S/O/P25 – Inlet/Outlet Nozzle Nominal Diameter: 6 inch

FX = 1090 N 245 lbf Mx = 1613 Nm 1190 lbf•ft

Top Nozzle Fy = 1744 N 392 lbf Each Nozzle My = 1234 Nm 910 lbf•ft

Fz = 1432 N 322 lbf Mz = 826 Nm 609 lbf•ft

FX = 1744 N 392 lbf

Side Nozzle Fy = 1432 N 322 lbf Resultant Fr = 4671 N 1050 lbf

Fz = 2180 N 490 lbf Mr = 3322 Nm 2450 lbf•ft



S/O/P35, S/O/P50 – Inlet/Outlet Nozzle Nominal Diameter: 8 inch

FX = 1650 N 371 lbf Mx = 2468 Nm 1820 lbf•ft

Top Nozzle Fy = 2647 N 595 lbf Each Nozzle My = 2577 Nm 1901 lbf•ft

Fz = 2180 N 490 lbf Mz = 1234 Nm 910 lbf•ft

FX = 2647 N 595 lbf

Side Nozzle Fy = 2180 N 490 lbf Resultant Fr = 7162 N 1610 lbf

Fz = 3425 N 770 lbf Mr = 4935 Nm 3640 lbf•ft


1-10 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

S/O/P85 – Inlet/Outlet Nozzle Nominal Diameter: 12 inch

FX = 2865 N 644 lbf Mx = 4271 Nm 3150 lbf•ft

Top Nozzle Fy = 4671N 1050 lbf Each Nozzle My = 3227 Nm 2380 lbf•ft

Fz = 3737 N 840 lbf Mz = 2088 Nm 1540 lbf•ft

FX = 4671 N 1050 lbf

Side Nozzle Fy = 3737 N 840 lbf Resultant Fr = 9030 N 2030 lbf

Fz = 5605 N 1260 lbf Mr = 7782 Nm 5740 lbf•ft


S/O/P120 – Inlet/Outlet Nozzle Nominal Diameter: 16 inch

FX = 3737 N 840 lbf Mx = 5125 Nm 3780 lbf•ft

Top Nozzle Fy = 5916 N 1330 lbf Each Nozzle My = 3796 Nm 2800 lbf•ft

Fz = 4671 N 1050 lbf Mz = 2562 Nm 1890 lbf•ft

FX = 5916 N 1330 lbf

Side Nozzle Fy = 4671 N 1050 lbf Resultant Fr = 11521 N 2590 lbf

Fz = 7162 N 1610 lbf Mr = 10535 Nm 7770 lbf•ft

Table 20: Maximum allowable inlet and outlet flange loads

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-11


Operation & Service Manual
Introduction

Prover critical dimensions: See prover’s critical dimensions provided below.

Enraf Small Volume Prover

Dimension
005 015 & 025 035 050 085 120
Description MODEL
ANSI 600 ANSI 150 ANSI 150 ANSI 150 ANSI 150 ANSI 150
mm [inches]
2756 4089 4089 4572 5258 5576
Length A
[108.5''] [161.0''] [161.0''] [180.0''] [207.0''] [219.5'']
Width at Frame B 813 [32.0''] 986 [38.8''] 1092 [43.0''] 1245 [49.0''] 1448 [57.0''] 1549 [61.0'']

Width at Feet C 947 [37.3''] 1118 [44.0''] 1227 [48.3''] 1378 [54.3''] 1588 [62.5''] 1702 [67.0'']
Inlet & Outlet
D 424 [16.7''] 513 [20.2''] 565 [22.3''] 673 [26.5''] 756 [29.8''] 840 [33.1'']
Height**
Inlet & Outlet
E 780 [30.7''] 1369 [53.9''] 1299 [51.2''] 1473 [58.0''] 1930 [76.0''] 2045 [80.5'']
Separation**
Inlet Distance
F 955 [37.6''] 1499 [59.0''] 1534 [60.4''] 1873 [73.7''] 2106 [82.9''] 2244 [88.4'']
from End**
Highest Point** G 1207 [47.5'']* 1257 [49.5'']* 1257 [49.5'']* 1308 [51.5'']* 1316 [51.8''] 1481 [58.3'']
Inlet & Outlet
3 Inch 6 Inch 8 Inch 8 Inch 12 Inch 16 Inch
Flange Size

NOTES:
1. All dimensions are in mm (inches)
2. Dimensions 'D', 'E', 'F' and 'G' may vary according to
model type/configuration
3. All dimensions vary according to pressure rating
4. All dimensions are subject to change
Table 21: Prover Dimensions

1-12 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Introduction

Pressure drop: Pressure drop measured between inlet and outlet of the
prover is specified in the Table 12 (see below). The drop is obtained at
maximum flow rate using water as a fluid.

Honeywell Enraf SVP MODEL FLOW RATE (BPH) PRESSURE DROP

S05 785 69 kPa (10.0 psig)

S15 2,140 28 kPa (4.0 psig)

S25 3,570 52 kPa (7.5 psig)

S35 5,000 69 kPa (10.0 psig)

S50 8,000 69 kPa (10.0 psig)

S85 12,500 69 kPa (10.0 psig)

S120 17,500 55 kPa (8.0 psig)

Table 22: Maximum pressure drop per prover size

1.4 Tests and Certifications


The Honeywell Enraf small volume provers are factory tested on the
following before shipment:
I. Electrical Tests: Dielectric strength and ground bond test.
II. H
 ydrostatic Pressure Test: Hydrostatic pressure test is done per
ASME, Section 8, Pressure Vessel Code. Prover wetted parts are
pressurized for four hours and the pressure has been recorded.
III. Water Draw Calibration Test: Water Draw calibration using NIST
traceable test equipment on an NMI certified test stand. The water draw
is performed by the gravimetric method using the Honeywell Enraf
dual-valve assembly in conjunction with an electronic scale. Base
volume on the certificate of calibration is corrected to 0 psig and 60°F
(or to meet alternate standard conditions specified by customer).
If requested, the water draw calibration can be completed using
volumetric method.
IV. Piston Seal Leak Test: During the execution of the piston seal leak test
the differential pressure will be maintained across the piston assembly
for at least 20 minutes.
V. 
Function Test: As a final stage of the testing procedure the Honeywell
Enraf small volume provers are functionally tested on water test loop.
Each prover is operated at all flow rates including minimum and
maximum flow rates.

1.5 Principle of Operation

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 1-13


Operation & Service Manual
Introduction

Figure 1-1: Prover in Stand-By Mode

In the stand-by mode the piston is down-stream and stationary, see


Figure 1-1. The piston’s inner flow-thru poppet valve is open allowing
free flow of the fluid through the measurement cylinder with minimal
pressure drop.
When the operator initiates a proving run sequence, the flow computer
signals the return drive motor to pull the piston to the up-stream position.
The piston then mechanically disconnects from the chain drive return
mechanism. When the piston is released, the flow-thru poppet valve closes
by spring tension as seen in Figure 1-2. The piston is now free to follow
the fluid flow with the least possible effect on the flow stream. The piston
velocity is now synchronized with the fluid velocity.

Figure 1-2: Prover During Prove Run - Mid-Run

After the piston has been released and synchronized with the fluid flow, the
precision optical start of volume switch is actuated, which sends a signal
to the flow computer to start the timing sequence. The piston continues
downstream with the flow. Upon reaching the end of volume switch, a
signal is sent to the flow computer to stop the timing sequence. After
passing the end of volume switch, the piston shaft is stopped mechanically.
The fluid pressure in the prover pushes the perimeter of the piston further
downstream, opening the flow-thru poppet valve, allowing the flow to
continue with little to no pulsation or surge in line pressure. The return drive
motor is started electronically to pull the piston back upstream if the flow
computer requires more passes and the above sequence is repeated.

1-14 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 2 INSTALLATION

2.1 Receipt of Equipment


The Honeywell Enraf small volume prover is pressure and function tested
and water draw calibrated at the factory prior to shipment. When the
equipment is received, inspect the outside of the packing case or cases to
see if the case has been damaged. If there has been any damage to the
case, the carrier should be notified immediately concerning their liability for
damage to the equipment.
If anything is missing or incorrect from your shipment, please contact your
local Honeywell Enraf sales representative or sales office. Have the serial
number and sales order number of your order available to help expedite
any needed assistance.

2.2 Return Shipment


Before any attempt is made to return the shipment, in part or whole,
contact a Honeywell representative. The Honeywell Global Technical
Support group (HFS-TAC) should be contacted for all requests or inquiries
relating to service, operation, repair and/or replacement.
By telephone: 1-800-423-9883
By email: [email protected]

2.3 Mechanical Installation


The Honeywell Enraf small volume prover has been designed to be used
as a portable or as a stationary mounted flow prover. The Honeywell Enraf
small volume prover may be installed upstream or downstream of the
meter under test as the displaced volumes are equal.
When installing the Honeywell Enraf small volume prover, follow all
recommended procedures regarding placement of the prover in relation
to the flow meter. To assure that all the flow goes through the prover, use
double block and bleed type diverter valves.
Refer to the system overview in the Figure 2-1 (Process Connections and
General Arrangement) for connecting the Honeywell Enraf small volume
prover to the process line. Before connecting the prover, be certain that all
piping and connections are clean and unobstructed. Also, ensure that no
debris, i.e.: weld slag; will be introduced into the system. Check all drain
and vent valves on the prover to make certain that they are closed.
Please Note: It is an advantage to provide sufficient back pressure on
the down-stream side of the flow prover in order to achieve satisfactory
repeatability results.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 2-1


Operation & Service Manual
Installation

CONTROL &
VOLUME SIGNAL
POWER SUPPLY

FLOW

T
PROVING T
Enraf Small Volume Prover
COMPUTER
P
DRIVE END
OPEN INLET OPEN OUTLET
VALVE VALVE

PRESSURE RELIEF VALVE


CLOSED
FLOW METER DOUBLE BLOCK
SIGNAL CONDITIONER AND BLEED
SIGNAL
P T VALVE P T

STRAINER THE HONEYWELL SMALL


FLOW METER UNDER TEST VOLUME PROVER MAY BE
INSTALLED UPSTREAM OR
P PRESSURE TRANSMITTER DOWNSTREAM OF THE METER
UNDER TEST AS THE
T TEMPERATURE TRANSMITTER DISPLACED VOLUMES ARE
EQUAL
Figure 2-1: Process Connections and General Arrangement

 Warning
Do not exceed the maximum working pressure of the prover as detailed on
the nameplates.
It is the customer’s responsibility to install the prover in a system that is
protected by correctly sized over-pressure protection.

Process lines should be cleaned thoroughly by flushing before installation,


to eliminate potentially damaging foreign material from entering the prover.
 A correctly specified strainer should be installed upstream of the prover
to protect it from the introduction of foreign material.

2-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Installation

  Caution: Be certain that all flanges, bolts, dry break couplers, hammerlock
fittings, hoses/loading arms, and pressure containing components have
sufficient pressure rating. Also be absolutely certain that the flow direction
through the prover is correct!

 The Honeywell Enraf small volume prover is equipped with integral


lifting points. Figure 5 shows the location of these points along with an
approximate weight distribution of the prover. Please use these lifting
points for all movement of the prover to avoid damage to the unit.

INTEGRAL FRAME LIFTING POINTS (4X)

Enraf

APPROX 70-75% APPROX 25-30%


WEIGHT WEIGHT
FLOW

Figure 2-2: Prover Lifting Diagram

As with all pressure containing equipment, it is essential to protect your


Honeywell Enraf small volume prover from any possible route of suffering
the impact of a foreign body. This especially applies to provers located
in high vehicular traffic areas and portable units. Permanent vehicle
barricades or pylons are highly recommended around the perimeter of the
unit and again at the inlet/outlet connections.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 2-3


Operation & Service Manual
Installation

Extra inspection should be given to portable units after transport


operations to ensure that no foreign body impacts have been encountered
that would sacrifice pressure containing components.

Please remember to place permanent structures of any type outside the


required Service Clearance area detailed in Figure 2-3.

B B

A A

FLOW

E Enraf Small Volume Prover


F

MODEL A B C D E F

05 610 (2) 610 (2) 610 (2) 1220 (4) 1520 (5) 1520 (5)
15 610 (2) 610 (2) 610 (2) 2140 (7) 1520 (5) 1830 (6)
25 610 (2) 610 (2) 610 (2) 2140 (7) 1520 (5) 1830 (6)
35 610 (2) 610 (2) 610 (2) 2140 (7) 1520 (5) 1830 (6)
50 920 (3) 920 (3) 920 (3) 2750 (9) 1830 (6) 2140 (7)
85 920 (3) 920 (3) 920 (3) 3050 (10) 2140 (7) 2140 (7)
120 1220 (4) 1220 (4) 1220 (4) 3360 (11) 2440 (8) 2440 (8)

NOTES:
1. The lettered dims represent a minimum recommended service
clerance around the prover
2. All dimensions are in mm (ft)
3. Clearance must be provided by customer
Figure 2-3: Prover Service Clearance Diagram

2-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Installation

The Honeywell Enraf small volume prover should be installed on a flat


surface and secured using 4 bolts through the pre-determined anchor
points on the prover frame (see Figure 2-4). It is recommended to bolt the
prover to the slab/trailer at these four locations only. It is not recommended
to use any other method or type of securing the prover against the
movement during operation. Honeywell Enraf will not be responsible for
possible damages to the prover or system parts if these recommendations
are not followed.

Figure 2-4: Designated anchor points (plates) located on the bottom side of the prover frame.

  The Honeywell Enraf small volume prover is fitted with transit seals in both
the up & downstream shaft seal retainers upon its shipment from the
factory. It is important to replace these seals during the commissioning
procedure and prior to the process fluid being introduced into the unit.
An additional set of seals are supplied with every prover for this purpose.

2.4 Electrical Connection

The Honeywell Enraf small volume prover can be certified as compliant


with one of the following:
CSA/US certified for Class 1 Group D T2C
CSA/US certified for Class 1 Group C T3B
ATEX certified for II 2 (1) G Ex d [ia Ga] IIB T4 Gb
IECEx compliant for Ex db [ia Ga] IIB T4 (See Individual Certificates)
Be certain to conform to all applicable national and local electrical codes
when making electrical connections to the Honeywell Enraf small volume
prover to maintain electrical safety ratings.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 2-5


Operation & Service Manual
Installation

Refer to Section 7 of this manual for connection to several brands of flow


computers. The proving computer used for the operation of the provers
must be equipped with the double chronometry function. For brands not
detailed, consult Honeywell Enraf and the flow computer manufacturer.
If equipped with CONDAT® or Prove-It prover control systems, refer to
the operators’ manual for instructions for installation and operation.

The Honeywell Enraf small volume prover must be correctly earth
grounded prior to electrical service connection.

2.4.1 Field wiring


The installation of this device must be carried out in accordance with all
appropriate international, national and local standards and site regulations
for intrinsically safe apparatus.

2.4.2 Breaker
A readily accessible disconnecting/breaker device shall be incorporated
external to the equipment.

2.4.3 Enclosures
The picture below shows the three electrical enclosures mounted on the
Small Volume Prover. The connections to the SVP Controller Box are made
at the factory and must not be modified. All of your connections are to be
made in the Power Box and the Customer Connection Box.

SVP
ENCLOSURE

CUSTOMER
POWER CONNECTION
BOX BOX

Figure 2-5: Electrical Enclosures

2-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Installation

2.4.3.1 Customer Connection Box


The picture below shows the Customer Connection Box where you can
connect your flow computer and other signals to the SVP.

Figure 2-6: Customer Connection Box

2.4.3.2 Power Box


The picture below shows the Power Box with two separate power
connections: one for the motor which generates electrical noise during
operation and one for clean or instrument power.

Figure 2-7: Power Box

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 2-7


Operation & Service Manual
Installation

2.4.3.3 SVP Controller Box

Connection of the LAD is as shown below.

Figure 2-8: SVP Controller Box with LAD

2-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 3 CONTROLLER INFORMATION

3.1 Initial Power up


Upon initial power up of the SVP Controller the Prover Status screen will
be displayed showing the operating mode of the prover (Meter Calibration,
Prover Calibration, or Prover Test) and the following information:
 Piston status or position
 Motor status
 Error status
 Number of cycles
 Stop time
 Sweep time
An example of a Prover Status screen is shown below.

Prover Status · Meter Calibration


Piston Parked Position
Motor Idle
Error Status No Error
Cycle 776
Stop Time 10-31-12 11:29:32 AM
Sweep Time 00:00:01:102

Press OK to enter menu Stop

3.2 Navigating the SVP Controller Menus Using the LAD


Pressing the OK button on the Local Access Device (LAD) will result in the
Main Menu screen being displayed on the SVP Controller.

3.2.1 Text Conventions


In the following sections of this document the entity and entity related text
are shown in a distinctive format as shown below.
All [Entity] and <entity-related> text is recognizably formatted.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-1


Operation & Service Manual
Controller Information

3.2.2 General
The SVP Controller can be configured through the wired Ex i interface with
a Local Access Device (LAD).
The LAD (Local Access Device) is a hand held controller used to interface
with the Fusion4 product family, allowing tasks such as parameter
adjustment, alarm resetting, and calibration. The device facilitates two-way
data communications between the SVP Controller and the LAD, allowing
the rapid transfer of transaction data, configuration files and calibration
records, and even firmware upgrading while in the field.

Figure 3-1: The Local Access Device (LAD) and its system overview

3.2.3 Commissioning
The LAD is used to commission the SVP Controller by configuring entities
(or parameters) to the desired specific values. This is done by using the
LAD to navigate through the Menu functions of the SVP Controller
(See 3.3.4).

3-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3 Menus and Navigation

3.3.1 General

An intuitive and informative Human Machine Interface (HMI) is available to


the user to operate, configure, and service the SVP Controller. This
menu-based user interface is as clear and accessible as possible, using
easily understandable colored icons for the Main Menu and logically
structured sub-menus.

3.3.1.1 Key benefits

 Clean, intuitive, and informative user interface


 No need to memorize parameter codes, enumeration value
 Diagnostic screens
 Record-based approach to transactions and calibrations make
re-use possible
 Interoperable with the Local Access Device (LAD)
 Provides a graphical user interface to the LAD

3.3.2 Main Menu

Title

Main Menu icon

Name of selected item

Selected item
(focus rectangle)

Only available
if LAD is connected

Figure 3-2: Main Menu

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-3


Operation & Service Manual
Controller Information

3.3.3 Screen Input Fields

3.3.3.1 Text Input Screen

Title bar
Single line edit field

Selected letter

Action message

Numbers grouped

Letters grouped

Figure 3-3: Text Input Screen

3.3.3.2 Numeric Input Screen

Figure 3-4: Numeric Input Screen

3-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3.3.3 Enumeration Input Screen

Scrollbar
Focus rectangle

Action message

Figure 3-5: Enumeration Input Screen

3.3.3.4 Status Bar

Figure 3-6: Status Bar

 Always visible on all screens


 Contains the following information:
• Context-specific information/directions to user
• Status of the transactions (e.g., Idle, Running, Error)
• Device Locking Icon

3.3.4 Menu Structure

For a high level overview of the entities and parameters, see the
following diagram (Figure 3-7).
For a detailed view of all menu items, see the individual section.

Continued on next page

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-5


Operation & Service Manual
Controller Information

Continued from previous page

Figure 3-7: Menu Structure

3-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3.5 Device Locking Menu

Within this screen, the user can lock and unlock the SVP Controller.
 A single password is used to lock the controller from further
configuration via HMI.
 Password is alphanumeric
• Only capital letters
• A-Z, 0-9, _, and ’.’
• No spaces
• Maximum of 6 characters
 Device remains unlocked until explicitly locked again
The "lock status" is shown at the status bar in the bottom right corner
(padlock) as seen in the following screen.

Figure 3-8: Device Locking Menu

To lock the device, the user must enter a password.

Figure 3-9: Password Input Screen

To unlock the controller, the user must enter the password as entered
during the locking of the controller. The password will be stored in
non-volatile memory.
Note that the locking feature is not infallible as the password is visible to
any user with a LAD connected to the controller. It is intended to keep
the uninformed user from accidentally changing configuration settings.
Changing the configuration parameters will not affect the performance of

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-7


Operation & Service Manual
Controller Information

the prover although caution must be used if changing the Motor parameters
or the Sensor Pair. Changing of the Sensor Pair is only applicable if you
have the optional third optical switch installed.
  Changing of the Motor parameters should only be done after consultation
with Honeywell Enraf experts as damage to the drive end could occur;
the Motor parameters are set at the factory for the specific model of
your prover.

When the device is locked, the following configuration parameters cannot


be changed via the LAD menu until the user unlocks the controller again.
>>Device
1. Identification
Site Name
Device Name
2. Units
Units of volume
3. Display
Display brightness
Display Contrast
Session time out value
4. Time
Date display format
Time display format
Date
Time
5. Motor
Motor switch timeout
Motor off delay
6. Sensor Pair
7. Volume
Total volume
Upstream volume
Downstream volume
>> I/O Setting
1. Output
Alarm Relay output
>> Alarm
1. Service due reminder
Alarm action
2. Machine Fault
Alarm action
3. Cycle count Threshold
Cycle count
3-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3
Operation & Service Manual
Controller Information

>> Cannot apply configuration (path is Transfer/Configuration/


Apply Configuration).
>> Cannot see and acknowledge or reset alarms (path is Diagnostics/
Active Alarm or Diagnostics/Prover Service Test/Clear Task).
>> Cannot upgrade any firmware (path is LAD Functions/
Firmware update).
The following tasks can be performed even if the controller is locked:
1. Navigate to Calibration and Enter, Run, Exit, Enter Average Volume, and
Abort Calibration
2. Navigate and see System Info
3. Navigate to Logs and see and retrieve Transaction, Calibration and
Alarm logs
4. Retrieve configuration (path is Transfer/Configuration/
Retrieve Configuration)
5. Navigate and view Diagnostics/Dashboard menu and activate or
deactivate alarm output
6. Navigate and view storage info (path is Diagnostics/Storage Info)
7. Navigate to Diagnostics/Prover Service Test/Run Prover Service Test to
activate the prover test
8. Navigate to LAD Function and view LAD information
9. Navigate to LAD Function and Format SD card

3.3.6 Configuration

3.3.6.1 Using the Configuration Menu

Figure 3-10: Configuration Menu

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-9


Operation & Service Manual
Controller Information

 Via the Configuration menu, you can access the device


configuration parameters
 The diagram below (Figure 3-11) allows you to locate all of the
configuration parameters
 Always the current device configuration values are shown
 All configuration values are edited one at a time in type-specific data
entry window

Figure 3-11: Configuration Menu Tree

3-10 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3.6.2 Device

3.3.6.2.1 Identification

Entity Description Value range


[Site name] The name of the site at which the SVP Can be a text string of maximum
is located 20 characters

[Device name] The name of the SVP itself. In order to have Can be a text string of maximum
a unique identification of the device by a 20 characters
text string
Will be shown in the running screens.

3.3.6.2.2 Units

Entity Description Name Unit


[Units of volume] With this entity the user can Liter L
select the engineering units Cubic meter m3
for volume Cubic centimeter cm3
Cubic decimeter dm3
US Gallons US gal
UK Gallons UK gal
Barrel bbls

3.3.6.2.3 Display

Entity Description Value range


[Display brightness] With this entity the user can select the 0% (low) - 100% (high)
brightness of the display. The brightness is
controlled by the backlight of the display
[Display contrast] With this entity the user can select the 0% (low) - 100% (high)
contrast of the display
[Session timeout value] This value selects the time in seconds
between last key press on LAD and the
moment the display will switch back to one of
the running screens
[User display language] This entity selects the display language for the • English US
running screens •L ist may expand as additional languages
are supported

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-11


Operation & Service Manual
Controller Information

3.3.6.2.4 Time

Entity Description Value range


[Date display format] This entity selects the format of the date • DD-MM-YY
• MM-DD-YY
• YY-MM-DD
• DD-MM-YYYY
• MM-DD-YYYY

Note: Only the first 3 selections will be


completely visible on the SVP screen
[Time display format] This entity selects the format of the time • 24 hours
• 12 hours

Note: When setting the clock, first set the


controller to 24-hour mode, then set the time.
This will allow the proper AM or PM to be
displayed when 12-hour mode is selected.

[Date] This entity selects the actual date and will


be used for time stamping of transactions,
calibrations, and alarms
[Time] This entity selects the actual time and will
be used for time stamping of transactions,
calibrations, and alarms

3.3.6.2.5 Motor

  These parameters are set at the factory and must not be changed without
consulting Honeywell Enraf experts or damage to the prover may occur.

Entity Description Value range


[Motor switch timeout] Configurable time interval by which piston puller Configurable range is from 5 seconds to
must have reached motor stop switch before 120 seconds; factory recommended settings
detection of a motor timeout error. Covers per model are shown below.
retraction of piston from parked position to S05 16 S35 38 S120 62
motor stop switch. Units are in seconds S15 14 S50 26
S25 22 S85 58
[Motor off delay] Configurable delay which controls when motor Configurable range is from 0 to 60 seconds;
turns off after piston puller has retracted to factory recommended settings per model are
motor stop switch. Can be adjusted to affect shown below.
optimal positioning of puller in preparation for
S05   0 S35   2 S120   2
next retraction sequence. Units are in seconds
S15   0 S50   2
S25   1 S85   2

3.3.6.2.6 Sensor Pair

Standard provers have an Upstream optical sensor and a Downstream


optical sensor. An option is available for a third optical switch. The
configuration entities are as shown below.

3-12 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

Sensor used as Sensor used as


Entity Description
“high sensor” “low sensor”
[Total] Selects the Upstream Sensor to be Upstream Sensor Downstream Sensor
used as the “high” volume gate and the
Downstream Sensor to be used as the
“low” volume gate. This is the default
configuration

[Upstream] Selects the Upstream Sensor to be Upstream Sensor Midstream Sensor


used as the “high” volume gate and the
Midstream Sensor to be used as the
“low” volume gate

[Downstream] Selects the Midstream Sensor to be Midstream Sensor Downstream Sensor


used as the “high” volume gate and the
Downstream Sensor to be used as the
“low” volume gate

3.3.6.3 I/O Settings

3.3.6.3.1 Alarm Relay Output

The Alarm Relay Output can be configured to be Energized (normally


closed) or De-energized (normally open).

3.3.6.4 Alarms

The following alarm entity applies to Service Due Reminder and Machine Fault.

Entity Description Value range


[Alarm action] With this entity the user can configure the • <Disabled>: The alarm is ignored
alarm behavior in case this particular alarm • <Display>:
will occur - Alarm shown on the display
- Alarm-indication output set to ON
- Next prover cycle will be allowed
• <Shutdown>:
- Alarm shown on the display
- Alarm-indication output set to ON
- Operation of further machine run cycles
are disabled until the alarm is cleared
- Still able to perform diagnostics via
RunProver Test or via Dashboard screen
from LAD

The Service Due Reminder alarm is activated when the cycle count
reaches the threshold value programmed by the user at the Cycle Count
Threshold menu. The default setting for the Cycle Count Threshold
is 1000.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-13


Operation & Service Manual
Controller Information

3.3.7 Prover Calibration

The menu screens for Prover Calibration are shown in the diagram below
(Figure 3-12). See Chapter 5 for detailed calibration procedures.

Figure 3-12: Prover Calibration

3.3.8 System Information

The SVP Controller “About” box is showing important information about:


 The Device (SVP Controller)
 The individual boards (HMI, SVP and Option)
 The firmware versions

Figure 3-13: System Information

Within this screen identification information is shown of the following


device components:
 Device serial number
 Production date
 Serial number of each FlexConn board
 Hardware version of each FlexConn board
 Application firmware version of each FlexConn board
 Build information of the firmware of each FlexConn board
 Boot firmware information of the firmware of each FlexConn board
 FlexConn stack firmware version of each FlexConn board
 Build information of the FlexConn stack firmware of each FlexConn board

3-14 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

The menu tree below shows how the information menus are accessed.

Figure 3-14: System Information Menu Tree

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-15


Operation & Service Manual
Controller Information

3.3.9 Logs

This is the user interface to various logs maintained in non-volatile


memory including:
 Transaction logs: complete information for each transaction
 Calibration log: shows the sequence of SVP calibrations over time
 Alarm Log: a chronological list on when alarms occurred and what type
of alarms they were

Figure 3-15: Logs

The log memory will be a rolling memory file with the oldest data being
overwritten first when the memory is full. Note that the log will be simply
overwritten without issuing a warning message.

Figure 3-16: Logs Menu Tree

3.3.9.1 Transaction Logs

The transaction log will contain the following data for each Prover run:
 Date and time
 Sweep time in seconds
 Number of prover cycles

3-16 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3.9.1.1 Transaction information

The details of any transaction can be viewed by going to that transaction


and pressing OK. After every prover run cycle in calibration of meter mode
the following parameters will be logged after completing the prover run
 Transaction ID
 Stop Transaction date and time
 Cycle count
 Sweep time
 Alarm information
 Sensor Pair
 Device Serial Number
 Transaction record version

3.3.9.2 Calibration Logs

The details of any transaction can be viewed by going to that transaction


and pressing OK. After every prover run cycle in prover calibration mode
the following parameters will be logged after completing the prover run.
The calibration log contains the following information:
 Date and time
 Sweep time in seconds
 Average volume
 Repeatability

There are no units displayed for the average volume as they will be
known by the user and to avoid complications if the units specified in the
Configuration/Device/Units menu are changed.

3.3.9.3 Alarm Logs

The Alarm log forms a permanent record of the same information that
can be viewed while an alarm is active from the Diagnostics/Active
Alarms screen. This information consists of the date and time stamp and
descriptive text.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-17


Operation & Service Manual
Controller Information

3.3.10 Diagnostics

This menu provides the following features:


 High-level view of all device I/O functions showing their state as
“High”/“Low”
 Each output function can be tested by selecting and activating it
 Internal memory usage overview
 System health overview
 Active alarms overview
 Clear alarms
 Activate the Run Prover Test mode

Figure 3-17: Diagnostics

Within this screen, the user can view the diagnostics about the
following subjects:
 Overview of all I/O (Dashboard)
 Overview of system health
 Overview of all active alarms
 Overview of device tasks such as clearing tasks, clearing alarms, and
running prover test task
 Overview of available memory storage space for data logs and total
number of available logs
The diagram below shows all of the information available to you. Note that
the parameters marked with an * are not relevant for the first release of the
SVP Controller. They are reserved for future use or for internal testing.

3-18 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

Figure 3-18: Diagnostics Menu Tree

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-19


Operation & Service Manual
Controller Information

3.3.11 Transfer

Note: Only when the LAD is connected!


Via this user’s interface, the following type of records can be transferred
between the SVP Controller and the LAD:
 Transaction records
 Configurations

 Events/logs (alarms)
 Calibration records

Figure 3-19: Transfer

The diagram below shows all of the information available to you.

Figure 3-20: Transfer Menu Tree

3-20 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Controller Information

3.3.12 LAD Settings

Note: Only when the LAD is connected!


This is the user interface to the LAD specific functionality:
 Firmware download to the SVP Controller and the LAD
 Management of the LAD’s stored records
 Format SD card

Figure 3-21: LAD Settings

The diagram below shows all of the information available to you.

Figure 3-22: LAD Settings Menu Tree

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 3-21


Operation & Service Manual
Controller Information

Intentionally left blank.

3-22 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 4 OPERATIONS

4.1 Operating Instructions

1. Firstly, carry out the removal and replacement of transit seals with
the operation seals (as supplied) prior to introducing liquid into the
Honeywell Enraf small volume prover.
2. Open fluid inlet valve slowly. After the inlet valve is completely open,
open fluid outlet valve, connecting the prover to the process line,
Figure 2-1.
3. Vent trapped air from the prover by opening the vent valves located at
the top of the prover flow tube.
4. Close process diverter valve, Figure 2-1, slowly to divert the flow
through the prover.
5. The Honeywell Enraf small volume prover is now ready for meter
proving. Refer to the appropriate proving computer manual for
procedures for performing meter proving runs.
6. After meter proving runs have been completed, open process diverter
valve, and slowly close the prover connection valves.
If you have the optional third optical switch installed on your prover refer to
Chapter 3 section 3.3.6.2.6 for Sensor Pair configuration prior to operating
your prover in any of the following three modes of operation.

4.2 Meter Calibration


Upon initial power up of the SVP Controller the Prover Status screen will
indicate that the operating mode of the controller is Meter Calibration. This
is the default operating mode of the controller. The other two operating
modes, Prover Test and Prover Calibration, require entering into those
modes via the LAD. In order to do proving runs on a meter make sure
that you are operating in the Meter Calibration mode as indicated by the
“Prover Status – Meter Calibration” screen as shown below.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 4-1


Operation & Service Manual
Operations

Prover Status · Meter Calibration


Piston Unknown Position
Motor Idle
Error Status No Error
Cycle 779
Stop Time 10-31-12 11:32:32 AM
Sweep Time 00:00:01:102

Press OK to enter menu Stop

On the first power up and after any machine fault alarm, the piston position
will be unknown and one proving run needs to be successfully completed
in order to initialize the piston position status. Upon sending the signal
from the PROVEit software or the other flow computers, the prover motor
will retract the piston assembly and the proving run will start. At the end of
the proving run the flow rate will be displayed on the screen and the next
proving run can be initiated.
During the return and proving mode different piston positions and
the motor status will be displayed on the SVP controller screen.
At the end of the proving run the sweep time, cycle count and the
stop time will be updated. If any errors occur during the proving
run the error will be reported on the screen and will need to be
cleared via the LAD (Main menu/Diagnostics/Dashboard/Alarm Clear –
see Chapter 6 - Troubleshooting).

4.3 Prover Test

The Prover Test mode can be useful to become familiar with your prover
and to verify proper operation. This mode is accessed by navigating with
the LAD through the following menus: Main Menu/Diagnostics/Prover
Service Test/Run Prover Test.
Pressing OK on the LAD at Run Prover Test causes a prover run cycle to
be executed, and the SVP Controller display will appear as shown below.
With the piston at the extreme downstream position, the Parked Position,
the motor will pull the piston upstream and the piston position will be
shown on the Prover Status screen as the associated optical sensor flag
passes through the Downstream sensor and the Upstream sensor until
the motor stop switch is activated. Run Prover Test can be executed

4-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Operations

repeatedly while the liquid flows through the prover pushing the piston
towards the downstream side. This test will only run in the absence of
a Flow Computer run permissive signal; it will not be executed if the run
permissive has been asserted by a Flow Computer.
See Chapter 6 - Troubleshooting if an error status is indicated.
To exit this operating mode use the LAD to navigate to Main Menu/
Diagnostics/Prover Service Test/Exit Prover Test

Prover Status · Prover Test


Piston Parked Position
Motor Idle
Error Status No Error
Cycle 787
Stop Time 10-31-12 11:39:32 AM
Sweep Time 00:00:01:020

Press OK to enter menu Stop

4.4 Prover Calibration

The third operating mode of the controller is Prover Calibration and will be
described in more detail in the next chapter.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 4-3


Operation & Service Manual
Operations

Intentionally left blank.

4-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 5 CALIBRATION

5.1 General
It is recommended that prior to doing any volumetric calibration that
the personnel involved read the API Manual of Petroleum Measurement
Standards (MPMS) Chapter 4 – Proving Systems sec 4.8, and the MPMS
Chapters 4.9, and 12.2.4 – pertaining to the calculation for the volume of
provers.
Although the prover may be calibrated with procedures traceable
to the National Institute of Standards and Technology (NIST) by a
number of techniques, only two techniques for volume determination
will be described here, a volumetric calibration and a gravimetric
(mass) calibration.
The gravimetric calibration method requires collecting the volume of water
displaced by the prover during a prove pass and determining its mass by
weighing it with a precision scale or balance. Corrections are made for the
density of the water and the buoyancy of the air displaced by the volume
of water per API 14.6, and applying various other correction factors such
as the temperature and pressure effects on the flow tube and the volume
switch position. De-ionized or distilled water should be utilized for the
gravimetric method. API 4.9.4 is the API standard used for the density
determination of water.
The displaced volume has been calibrated as described in the MPMS API
chapters,: 4.2, 4.9 and 12.2.4.
The Honeywell Enraf small volume prover base volume has been
determined at the factory. Recalibration is recommended either at 1 year
intervals, or as determined by the authorities and parties responsible for
the measurement. Recalibration is also required after any maintenance
which may affect the base volume, i.e.: complete switch bar replacement.
Honeywell Enraf small volume prover optical switches are field replaceable
and adjusted to an extremely high degree of precision. Individual switch
replacement does not necessitate re-calibration. See Section 6.7 for more
information on optical switches.

5.2 Static Leak Detection


The Honeywell Enraf static leak detection procedure should be used prior
to water draw or at any time that meter proof repeatability is difficult to
attain. It is not necessary to remove the prover from the process line to
perform a leak test. It is only necessary to block off the inlet and outlet of
the prover with it full of fluid. Block off the drain valves and verify there is
no leak path from the prover. If necessary, insert blind flanges into the inlet
and outlet ports to isolate the prover from the system. It is also necessary

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-1


Operation & Service Manual
Calibration

to have a differential pressure gauge with a sufficient pressure rating to


withstand line pressure if the prover is not removed from the process
line. Temperatures, both ambient and fluid, should be stable during
the procedure.

5.2.1 Equipment

1. Static leak differential pressure creator assembly, included with prover.


2. Differential pressure gauge 0-69 kPa (10 psi) or greater with sufficient
static pressure specifications to be equal or greater than the current
prover pressure.
3. Plumbing and valve arrangement similar to that shown in Figure 5-1.

5.2.2 Static Leak Detection Procedure

1. Block all inlet and outlet ports on the prover (including drains).
2. Refer to Figure 5-1, 5-2 & 5-4 below and install the differential
pressure gauge (1) between the inlet and outlet ends of the prover.
3. Fill the prover with liquid and vent off all air from the system.
4. Determine there are not leaks from the prover ports.
5. If necessary, blind the inlet, outlet and drain lines with blind flanges.
6. Power up the proving computer and the Honeywell Enraf prover.
7. From the proving computer, initiate a proving run to pull the
piston upstream.
8. Remove the plug from the drive cover end panel.
9. Install the differential pressure creator (2) in the threaded hole provided
in the drive system end plate and hand tighten, refer to Figure 5-3.
10.Rotate the adjustment screw (3) Figure 5-4 clockwise to push the
plunger out to apply force to the piston shaft and create a differential
pressure between the inlet and the outlet of the prover. Rotate the
adjustment screw until a differential pressure of 6 psid has been
created. Pressurize the unit slowly and watch the pressure gauge.
In some cases it might happen that applied pressure of 6 psid will
be significantly lost in the first couple of minutes. The reason is
that the poppet valve will need short period of time to fully close
and stabilize.
Therefore, it is our recommendation to allow at least 5 minutes
between the applied pressure and actual data recording.
11. Look the prover over for any obvious external leaks.
12. Start observing the differential pressure gauge for a period of 20
minutes. If the pressure has not dropped by more than 25% of the
starting differential pressure, it may be assumed that there are no

5-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

piston seal leaks. If the pressure has dropped to lower levels, it should
be assumed that there is a seal leak, and the prover piston seals
should be replaced. Refer to Figure 5-5.

Figure 5-1: Static Leak Detection Set-up Figure 5-2: Gauge with HI & LOW markings

Figure 5-3: D
 ifferential pressure creator inserted in drive end plate.

DIFFERENTIAL PRESSURE CREATOR 2 DIFFERENTIAL PRESSURE CREATOR 1


LOW PRESSURE HIGH PRESSURE

Enraf Small Volume Prover

ADJUSTMENT SCREW 3
FLOW

Figure 5-4: Static Leak Detection set-up overview

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-3


Operation & Service Manual
Calibration

Figure 5-5: Recommendation for seal change

5.3 Volume Water Draw


Equipment

1. Water draw kit: Contact Honeywell Enraf representative or factory


directly to obtain a water draw kit, (see Figure 5-6).
2. Source of clean potable water. Pump or water supply must have steady
flow of approximately 38 Lpm (10 GPM) at 172-690 kPa (25-100 psi)
Water supply must maintain non-pulsating pressure.
3. Certified volume test measures (conforming to API chapter 4 section 7)
traceable to the U.S. NIST (or other National standards). The test
measure should be of the same volume as the displaced volume of the
prover. If, however, the test measure is smaller than the prover volume,
there must be at least two test measures, as the flow during water
draws should be continuous for the greatest precision. Example: For a
20-gallon prover uses a single 76 L (20 gal) test measure.
4. Certified high resolution pressure gauge: 0-690 kPag (0-100 psig) psig
5. Three traceable thermometers with 0.1°C (0.2°F) degree graduations
(for thermometer reference positions see Figure 5-7).
6. Water overboard container, volume to be at least as large as test
measure, and approximately the same height.
Note: H
 oneywell Enraf Water Draw P&T kit or equivalent assembly eases
installation of water draw prover instrumentation. The Honeywell
Enraf Water Draw P&T kit consists of four traceable temperature
thermometers (one spare thermometer included) and one pressure
gauge. All thermometers come with the calibration certifications if
ordered from Honeywell Enraf.

5-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

WATERDRAW POWER SUPPLY CUSTOMER CONNECTION ENCLOSURE


SOLENOID VALVE CONNECTION AND
- + POWER SUPPLY

+ -

PN #44100375
CABLE FROM
SOLENOID VALVES
TO ENCLOSURE

POWER ENCLOSURE
POWER SUPPLY CONNECTION

PN #10601197
WATER DRAW
PLUMBING ASSY

TUBING TO
TUBING TO WASTEWATER
TEST CATCH CONTAINER
MEASURE

INCLUDED IN WATER DRAW KIT


1/2" SS BRAIDED HOSE
CONNECT TO PROVER
DOWNSTREAM SIDE

Customer Connection Enclosure


Description Terminal Number Wire Color
Water Draw SV1 1 Red - Water Draw Cable
Water Draw SV2 2 White - Water Draw Cable
Water Draw Common 3 Black - Water Draw Cable
Figure 5-6: Water Draw Kit

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-5


Operation & Service Manual
Calibration

Procedure
Water draw notes:
Perform steps 12-17 at least twice prior to taking data to purge the system of
air, assure the temperature is stable, and to get familiar with the procedure.
Repeat the water draw procedure until at least 3 consecutive draws
repeat within 0.02% or other repeatability criteria that the certifying parties
agree upon. The flow rate on at least one run must vary by 25% to assure
integrity of prover seals and absence of leakage.
Failure to achieve the necessary repeatability may be caused by leaking
valves, air in the system, varying pressure, leaking seals, or faulty
calibration technique.
1. Be certain that all maintenance that needs to be done to the prover
has been accomplished before starting the volumetric calibration. It
is advisable to perform a static leak test prior to performing a water
draw, see Section 5.2. Replace the seals on the prover if there is any
doubt as to their integrity.
2. Block prover inlet and outlet by using a blind flanges or double block
and bleed valves.
3. Refer to Honeywell Enraf water draw configuration, Figure 5-7, and
install Honeywell Enraf available water draw kit, see Figure 5-6. Install
certified thermometers and certified pressure gauge, even if the prover
is equipped with P&T transmitters.
If using Honeywell Enraf Water Draw P&T kit, remove the plug in the
wafer spacer and connect the pressure gauge P1 to the opening (see
Figure 5-7 for reference).
The thermometer used to monitor prover fluid temperature T1 is
supposed to be installed into the spare thermowell located on the
downstream side of the flow tube (see Figure 5-7 for reference).
The thermometer used to monitor switch bar temperature T2 is
supposed to be installed on top of the switch bar close to the center
line between two optical switches (see Figure 5-7 for reference).
The thermometer used to monitor test measure temperature T3
is supposed to be installed on the test measure (see Figure 5-7
for reference).
Have available Table 13 to record data from prover calibration using
volumetric water draw technique.
4. Connect water supply to prover, (refer to Figure 5-7).
5. Make sure that the water draw kit is wired to the customer connection
enclosure as specified in the Figure 5-6.
6. Turn water supply on, and open valves V1, V2, and V3. After all air is
bled off, close V2 and V3. Open V5 valve and allow water to circulate
until the temperature has stabilized and is not changing.

5-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

7. Valve V2 may be opened slightly to allow just a very small stream of


water to flow; this will bleed off air, which may be in the water supply.
At the end of the temperature stabilization close the V5 valve.
8. Place properly wetted and drained test measure under the water
draw valves.
9. Ensure power is applied to the prover. Navigate to Calibration screen
from the Main Menu as shown below.

Prover Calibration
Enter Calibration Mode
Run Calibration
Exit Calibration Mode
Enter Average Volume
Abort Calibration

Press OK to choose Stop

10. Enter the prover calibration mode using “Enter Calibration


Mode” submenu.
Notification to user after selecting Enter Calibration Mode will show
up on the SVP Controller screen (see below).
Please note that permissive signal from the flow computer will be
ignored while in prover calibration mode.

Entering Calibration Mode


Pressing OK will enter the controller
into Calibration Mode. The bypass
valve will open immediately.
To perform calibration run, select
Run Calibration from next menu

Press OK to proceed Stop

11. Bypass valve (SV2) will be turned ON immediately after entering the
prover calibration mode and the water from the prover will be drained
into the wastewater catch container.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-7


Operation & Service Manual
Calibration

12. Select “Run Calibration” which will cause the prover piston to be
returned to the upstream position and start the draw sequence.
See resulting Prover Status screen as shown below.
After selecting Run Calibration following screen appears.

Prover Status · Prover Calibration


Piston Retract To Down Sensor
Motor Waiting Motor Switch
Error Status No Error
Cycle 774
Stop Time 00-00-00 00:00:00 AM
Sweep Time 00:00:01:101

Press OK to enter menu Run

13. Water should now be draining into the wastewater container until the
flag reaches the first optical (volume) switch. When the first optical
switch is reached, the signal will be sent to the SVP controller to switch
the valves (turn the SV2 valve OFF and turn the SV1 valve ON). At that
time the water will start flowing into the Test Measure.
14. Record the prover pressure (Pp) at P1 while only the water draw
valve is open (SV1). Valves V5 and V6 must be closed while recording
this pressure, which is the pressure at the start and the end of
volume switching.
15. Record temperature (Td) at T2, which is the detector temperature,
by opening the drive cover and placing the thermometer midway
between volume switches, which is the location of the switch bar
temperature transmitter thermowell.
16. Record fluid temperature (Tp) at T1.
17. When the flag reaches the second optical (volume) switch, the draw
valve (SV1) is turned OFF and the bypass valve (SV2) is turned ON.
Carefully record scale reading (SR) and test measure temperature
(Ttm) at T3.
18. After all data is collected, drain the test measure.
19. Repeat steps 12 through 18 as necessary to obtain the required
number of well repeating runs (including one run at 25% flow
rate variance).
Please note that a log will be saved with start time and sweep time
after each calibration run.
20. Once you have completed the calibration, select the “Exit Calibration”
menu which will turn the bypass valve (SV2) OFF.

5-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

21. Calculate prover volume per Section 5.5.


22. Enter the average calibration volume calculated in the previous step
by selecting the “Enter Average Volume” menu. This screen can
be accessed while still in the Calibration mode or at a later time by
entering the Calibration menu and then accessing this screen directly.
After selecting Enter Average Volume following screen appears

Enter Average Volume

5.37000

7 8 9 Backspace
4 5 6 Confirm
1 2 3
0 - .

Enter value Stop

23. After the Average Volume has been entered and confirmed the
following screen is displayed to enter the Repeatability in percent (%).
The entered average volume and the repeatability values will be stored
in the log with a timestamp of the entry.
After selecting Enter Average Volume following screen appears

Enter Repeatability

0.00200 %

7 8 9 Backspace
4 5 6 Confirm
1 2 3
0 - .

Enter value Stop

Selecting “Abort Calibration” will stop the calibration process. This action
will stop the motor if in running state, bypass value (SV2) will be turned ON
and draw valve (SV1) will be turned OFF. If the Prover is in sweep mode
with the piston moving downstream no action will be taken for upstream
and downstream sensor inputs. Calibration log entry will not be made.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-9


Operation & Service Manual
Calibration

In calibration mode alarms will be generated as per the configuration, and


the run permissive signal from the flow computer or the run prover test
signal will be ignored. The operating mode of the prover will be saved in
NVM so that the mode will be restored if power is turned off while in Prover
Calibration mode.
To exit calibration mode navigate to the Exit Calibration Mode menu and
press OK.
A copy of Table 13 can be used to enter water draw data.

VENT VENT T1 Tp

T2 Td V2 V3 P1 Pp

FLOW
SVP
CONTROLLER

V1 V4

WATER
SUPPLY
Ta

T4
S S
V6 SV1 SV2 V5

Ttm WASTEWATER
CATCH
T3 CONTAINER

TEST MEASURE
Figure 5-7: Water Draw Plumbing Diagram

5-10 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

Volumetric Water Draw Data Sheet


Date:

Prover Serial Number:

Prover Model Number:

Report Number:

Location:

Base Temperature (Tb):

Base Measure Volume-from calibration cert. (BMV):

Volume Measure Thermal Coefficient (Gc):

Compressibility Factor (water) (CPL):

Flow Tube Area Thermal Expansion Coefficient (Ga):

Detector Linear Thermal Expansion Coefficient (Gl):

Modulus of Elasticity of flow tube (E):

Flow Tube Inside Diameter (inches) (ID):

Flow Tube Wall Thickness (inches) (WT):

Fill 1 Fill 2 Fill 3 Fill 4 Fill 5

Fill Time (minutes) =

Flow Rate (Nominal Volume/Fill Time) =

Temperature Prover (Tp) =

Temperature Detector (Td) =

Prover Pressure (Pp) =

Scale Reading on Volume Measure (SR) =

Volume of Water adjusted for SR (BMVa) =

Test Measure Temperature (Ttm) =

Correction for Temp. Differential (Ctdw) =

Effect of Temp. on Test Measure (CTStm) =

Effect of Temperature on Prover (CTSp) =

Combined effect of CTSM & CTSP (CCTs) =

Volume Waterdraw (WD) =

Effect of Pressure on Flow Tube (CPSp) =

Compressibility of water in prover (CPLp) =

Corrected Water Drawn Volume (WDzb) =

Table 23: Volumetric Water Draw Data Sheet

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-11


Operation & Service Manual
Calibration

5.4 Gravimetric Water Draw


Equipment

1. Water draw kit: Contact Honeywell Enraf representative or factory


directly to obtain a water draw kit, Figure 5-6.
2. Precision electronic weigh scales of the correct size and resolution: for
example for an S25 prover, balance must have a capacity of at least
100kg and +/-4 gram (200 lb. and +/- 0.01 lb.). resolution. (1 part out
of 20,000 or better resolution). For proper scale verification prior to the
gravimetric water draw refer to API 4.9.4.
3. Certified test weight set: ANSI/ASTM Class 3 equivalent or better.
4. Source of air-free or deaerated deionized or distilled water with
approximately 38 Lpm at 172-690 kPag (10 GPM at 25-100 psig)
steady, non-fluctuating, pressure.
5. A volume catch container ideally, large enough for the volume of fluid
dispensed by the prover. Container must be designed to be placed on
the precision balance or scales.
6. Certified high resolution pressure gauge: 0-690 kPag (0-100 psig).
7. Three traceable thermometers with 0.1°C (0.2°F) graduations
(for thermometer reference positions see Figure 5-7).
8. Water draw data sheet, Table 14.
9. Water overboard container, volume to be at least as large as
test measure.
Note: Honeywell Enraf Water Draw P&T kit or equivalent assembly eases
installation of water draw prover instrumentation. The Honeywell
Enraf Water Draw P&T kit consists of four traceable temperature
thermometers (one spare thermometer included) and one pressure
gauge. All thermometers come with the calibration certifications
if ordered from Honeywell Enraf.

Procedure
Water draw notes:
Perform steps 14 – 21 at least twice prior to taking data to purge the
system of air, assure the temperature is stable, and to get familiar with
the procedure.
Repeat water draw procedure until at least 3 consecutive draws repeat
within 0.02% or other repeatability criteria that the certifying parties agree
upon. The flow rate on at least one run must vary by 25% to assure
integrity of prover seals and absence of leakage.
Failure to achieve the necessary repeatability may be caused by leaking
valves, air in the system, varying pressure, leaking seals, or faulty
calibration technique.

5-12 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

1. Be certain that all maintenance that needs to be done to the prover
has been accomplished before starting the gravimetric calibration. It
is advisable to perform a static leak test prior to performing a water
draw, see Section 5.2. Replace the seals on the prover if there is any
doubt as to their integrity.
2. Block prover inlet and outlet by using a blind flanges or double block
and bleed valves.
3. Refer to Honeywell Enraf water draw configuration, Figure 5-7, and
install Honeywell Enraf available water draw kit, see Figure 5-6. Install
certified thermometers and certified pressure gauge, even if the prover
is equipped with P&T transmitters.
If using Honeywell Enraf Water Draw P&T kit, remove the plug in the
wafer spacer and connect the pressure gauge P1 to the opening (see
Figure 5-7 for reference).
The thermometer used to monitor prover fluid temperature T1 is
supposed to be installed into the spare thermowell located on the
downstream side of the flow tube (see Figure 5-7 for reference).
The thermometer used to monitor switch bar temperature T2 is
supposed to be installed on top of the switch bar close to the center
line between two optical switches (see Figure 5-7 for reference).
The thermometer T4 is supposed to be used to monitor ambient
temperature (see Figure 5-7 for reference).
Have available Table 14 to record data from prover calibration using
gravimetric water draw technique.
4. Calibrate the scale as specified in API 4.9.4.
5. Connect water supply to prover, (refer to Figure 5-7)
6. Make sure that the water draw kit is wired to the customer connection
enclosure as specified in the Figure 5-6.
7. Turn water supply on, and open valves V1, V2, V3. After all air is bled
off, close V2 and V3. Open V5 valve and allow water to circulate until
the temperature has stabilized and is not changing.
8. Valve V2 may be opened slightly to allow just a very small stream of
water to flow; this will bleed off air, which may be in the water supply.
9. Calibrate scales with test weights totaling +/- 10% of draw weight per
API 4.9.4.
10. With volume catch container on the scales and under water draw
valve, tare scales.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-13


Operation & Service Manual
Calibration

11. Ensure power is applied to the prover. Navigate to Calibration screen


from the Main Menu as shown below.

Prover Calibration
Enter Calibration Mode
Run Calibration
Exit Calibration Mode
Enter Average Volume
Abort Calibration

Press OK to choose Stop

12. E
 nter the prover calibration mode using “Enter Calibration Mode” submenu.
Notification to user after selecting Enter Calibration Mode will show up on the
SVP Controller screen (see below).
Please note that permissive signal from the flow computer will be
ignored while in prover calibration mode.

Entering Calibration Mode


Pressing OK will enter the controller
into Calibration Mode. The bypass
valve will open immediately.
To perform calibration run, select
Run Calibration from next menu

Press OK to proceed Stop

13. Bypass valve (SV2) will be turned ON immediately after entering the
prover calibration mode and the water from the prover will be drained
into the wastewater catch container.
14. Select “Run Calibration” which will cause the prover piston to be
returned to the upstream position and start the draw sequence.
See resulting Prover Status screen as shown below.

5-14 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

After selecting Run Calibration following screen appears.

Prover Status · Prover Calibration


Piston Retract To Down Sensor
Motor Waiting Motor Switch
Error Status No Error
Cycle 774
Stop Time 00-00-00 00:00:00 AM
Sweep Time 00:00:01:101

Press OK to enter menu Run

15. Water should now be draining into the wastewater container until
the flag reaches the first optical (volume) switch. Note: To decrease
the time necessary to reach the first volume switch, valve V5 may be
opened until just before the first volume switch has been reached.
16. When the first optical switch is reached, the signal will be sent to the
SVP controller to switch the valves (turn the bypass valve SV2 OFF and
turn the draw valve SV1 ON). At that time the water will start flowing
into the Test Measure.
17. Record the prover pressure (Pp) at P1 while only the water draw valve is
open (SV1). Valves V5 and V6 must be closed while recording this pressure,
which is the pressure at the start and the end of volume switching. Note:
The draw can be sped up by opening valve V6 after the valves have
switched to flowing into the Test Measure located on the scale and the
prover pressure (Pp) is recorded. Again close V6 at least 13mm or 2L
(1/2" or 1/2 gal) prior to solenoid draw valve switching.
18. Record ambient temperature (Ta) at T4.
19. R
 ecord temperature (Td) at T2, which is the detector temperature, by
opening the drive cover and placing the thermometer midway between
volume switches, which is the location of the switch bar temperature
transmitter thermowell.
20. Record fluid temperature (Tp) at T1 (at prover).
21. A
 llow Test Measure located on the scale to fill until the second volume
switch (downstream sensor) is reached resulting in the draw valve (SV1)
turning OFF and bypass valve (SV2) turning ON. Carefully record scale
reading (Ww).

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-15


Operation & Service Manual
Calibration

22. After all data is collected, drain the catch container and tare scales.
23. Repeat steps 14 through 22 as necessary to obtain the required
number of well repeating runs (including one run at 25% flow rate 
variance).
Please note that a log will be saved with start time and sweep time
after each calibration run.
24. Once you have completed the calibration, select the “Exit Calibration”
menu which will turn the bypass valve (SV2) OFF.
25. Calculate prover volume per Section 5.5.
26. Please Note: A copy of Table 14 for gravimetric calibration can be
used to enter water draw data. An Excel readable file is available from
Honeywell Enraf which will calculate the corrected prover volume using
the gravimetric method.
After selecting Enter Average Volume following screen appears

Enter Average Volume

5.37000

7 8 9 Backspace
4 5 6 Confirm
1 2 3
0 - .

Enter value Stop


27. E
 nter the average calibration volume calculated in the previous step by
selecting the “Enter Average Volume” menu. This screen can be accessed
while still in the Calibration mode or at a later time by entering the
Calibration menu and then accessing this screen directly.
28. After the Average Volume has been entered and confirmed the
following screen is displayed to enter the Repeatability in percent (%).
The entered average volume and the repeatability values will be stored
in the log with a timestamp of the entry.

5-16 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

After selecting Enter Average Volume following screen appears

Enter Repeatability

0.00200 %

7 8 9 Backspace
4 5 6 Confirm
1 2 3
0 - .

Enter value Stop

Selecting “Abort Calibration” will stop the calibration process. This action
will stop the motor if in running state, bypass value (SV2) will be turned ON
and draw valve (SV1) will be turned OFF. If the Prover is in sweep mode
with the piston moving downstream no action will be taken for upstream
and downstream sensor inputs. Calibration log entry will not be made.
In calibration mode alarms will be generated as per the configuration, and
the run permissive signal from the flow computer or the run prover test
signal will be ignored.
The operating mode of the prover will be saved in NVM so that the mode
will be restored if power is turned off while in Prover Calibration mode.
To exit calibration mode navigate to the Exit Calibration Mode menu and
press OK.
A copy of Table 14 can be used to enter water draw data.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-17


Operation & Service Manual
Calibration

Gravimetric Water Draw Data Sheet

Date:
Prover Serial Number:
Prover Model Number:
Report Number:
Location:
Standard Temperature (Tb):
Standard Pressure (Pb)
Elevation (h)
Field Test Weight Density
Reference Test Weight Density
Compressibility Factor (water) (CPL):
Flow Tube Area Thermal Expansion Coefficient (Ga):
Detector Linear Thermal Expansion Coefficient (Gl):
Modulus of Elasticity of flow tube (E):
Flow Tube Inside Diameter (inches) (ID):
Flow Tube Wall Thickness (inches) (WT):
Fill 1 Fill 2 Fill 3 Fill 4 Fill 5
Fill Time (minutes) =
Temperature Air (Ta) =
Temperature Prover (Tp) =
Temperature Detector (Td) =
Prover Pressure (Pp) =
Water Electrical Conductivity =
Total Mass of Water (Ww) =
Density of Air ( ρA) =
Calculated Density of Water ( ρw) =
Correction of Air Buoyancy of Weighing (CBW) =
Corrected Mass of Water (Mw) =
Volume of Water (Vw) =
Effect of Pressure on Water (CPL) =
Temperature Correction on Prover (CTS) =
Pressure Correction on Prover (CPS) =
Corrected Water Volume (WD) =
Table 24: Gravimetric Water Draw Data Sheet

5-18 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

5.5 Calculations
Volumetric Water Draw Calculations

Water draw volume corrections taken from API Manual of Petroleum


Measurement Standards API chapters,: 4.2, 4.9 and 12.2.4. and Appendix
B.4 F2.a, 11.2.3.5.
Symbols and Calculations from API 12.2.4:

Given:
RHOtm = Density of liquid (water) in test measure. (API 12.2.4)
RHOp = Density of liquid (water) in prover. (API 12.2.4)
CPL = Correction for the compressibility of liquid. (For water 3.2E-6)
Tb = Base calibration temperature. (60 deg. F. in US)
Ga = Area coefficient of expansion for flow tube. (API 12.2.1.11.2.1)
Gl = Linear coefficient of expansion for detector. (API 12.2.1.11.2.1)
Gc = Coefficient of expansion for the test measure
(from calibration certificate)
E = Modulus of elasticity for flow tube material (from API 12.2 Appendix A)
WT = Thickness of flow tube wall. (inches)
ID = Diameter of flow tube. (inches)

Calculate:
BMVa = Base Measured Volume adjusted for scale reading.
= BMV + SR
CTDW = Correction for prover/test measure liquid temperature difference.
= RHOtm ÷ RHOp
CTStm = Correction for effect of temperature on test measure.
= 1 + (Ttm - 60) × (Gc)
CTSp = Correction for effect of temperature on prover.
= {(1+[(Tp-Tb)*Ga]) * (1+[(Td-Tb)*Gl])}
CCTs = Correction for prover/test measure steel temperature difference
= (CTStm)/(CTSp)
WD = Adjusted Base Volume of Draw
= BMVa*CTDW*CCTs
CPSp = Correction for the effect of pressure on prover
= 1 + [(Pp*ID)/(E*WT)]

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-19


Operation & Service Manual
Calibration

CPLp = Correction for effect of pressure on liquid (water)


= 1/[1-(0.0000032*Pp)]
WDz = Average of all WD’s
= [@sum (WDz Fill 1..WDz Fill5)]/n
WDzb = Volume of Prover at 60 deg F and 1 atm
= WDz/(CPSp * CPLp)
Gravimetric Water Draw Calculations
Gravimetric Water Draw technique is completed in accordance with API
4.9.4. Volume correction factors are based on API Manual of Petroleum
Measurement Standards API chapters,: 4.2, 4.9 and 12.2.4.
Corrections and representations:
Given:
Td = Temperature of detector bar. (deg F)
Tp = Temperature of prover. (deg F)
Ta = Temperature of ambient air. (deg F)
Pp = Pressure in prover. (psig)
Ww= Weight of water. (grams)
h = Elevation above sea level. (feet)
Dtw= Density of test weights. (gm/cc)
Ga = Area coefficient of expansion for flow tube. (API 12.2.4)
Gl = Linear coefficient of expansion for detector. (API 12.2.4)
E = Modulus of elasticity for flow tube material. (API 12.2 Appendix A)
WT = Thickness of flow tube wall. (inches)
ID = Diameter of flow tube. (inches)
Calculate:
Calculation of Air Density in USC Units:
ρA = 0.001223068*(1-(0.032 x h/1000))*(519.67/(Tf + 459.67))
Where: ρA is the density of air (gm/cc) (Per API 4.9.4)
h is the elevation above sea level (ft)
Tf is the test temperature (°F)
Calculation for the Correction for Air Buoyancy on Weighing (CBW)
CBW= {[1-(0.0012/ρTWr)]/[1- (0.0012/ρTWf)]} * {[1-( ρA/ρTWf)]/
[1- ( ρA/ρFtp)]}
Where: CBW is the correction for air buoyancy on weighing,
ρTWr is the density of reference test weights (gm/cc),
 ρTWf is the density of the field test weights (gm/cc) as per
certificate of traceability,
 ρFtp is the density of fluid at test temperature and test
pressure (gm/cc),
ρA is the density of dry air (gm/cc)

5-20 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Calibration

Calculation for the Density of the Calibration Water


ρwtF = Density of water at temperature t °F (kg/cm) (From API 12.2.4 or
calculate by algorithm taken from API 4.9.4)
Using the algorithm taken from API 4.9.4
ρwtF = ρ0*[1-((A* ρtF)+(B*( ρtF)^2)-(C*( ρtF)^3)+(D*( ρtF)^4)-(E*
( ρtF)^5)))/1000]

Where: ρwtF is density at temperature t °F (kg/cm)


ρ0 is density at temperature t0, 999.97358 kg/m3
t is temperature (°F)
∆tF is [(t – 32)/1.8]- t0
t0 is 3.9818E+00 (°C)
A is 7.0134E-08 (°C)-1
B is 7.926504E-06 (°C)-2
C is -7.575677E-08 (°C)-3
D is 7.314894E-10 (°C)-4
E is -3.596458E-12 (°C)-5

Note: Above provided equation provide density correlations for density


of distilled water. If the water to be used in the Gravimetric Method
does not meet the criteria of distilled or deionized water, water from
an approved public water (potable) supply may be used in this
procedure. However, the conductivity must not exceed 50μs. If the
conductivity of the test water is between 50μs and 1,000μs, the
density shall be determined as per API 4.9.4 section A.5.
Mw = Corrected Mass of Water (gm)
= Ww ÷ CBW
Vw = Volume of Water (cc)
= Mw ÷ ρwtF
CPLp = Correction for the effect of pressure on water
= 1/[1 - (Pp * 0.0000032)]
CTSp = Correction for effect of temperature on prover
= {(1+[(Tp-Tb)*Ga])*(1+[(Td-Tb)*Gl ])}
CPSp = Correction for effect of pressure
= 1 + ((Pp - Pb) × ID)/(E × WT))
WD = Corrected Water Volume
= (Vw * CTS)/(CPL * CPS)

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 5-21


Operation & Service Manual
Calibration

Intentionally left blank.

5-22 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 6 TROUBLESHOOTING

6.1 Run Prover Test

Running the prover in the Prover Test operating mode is a good way to
verify proper operation. See Section 4.3 for more information.

6.2 Error Messages

If any device on the prover malfunctions the error will be shown on


the controller screen. The following are possible errors and how to
correct them.

6.2.1 Sensor out of sequence

This error message means that the proving sequence was not completed
successfully. In order to clear the error check if:
 the optical switches are functioning (using the dashboard function –
see 6.3.1),
 motor stop switch is functioning (using the dashboard function –
see 6.3.1),
 the ramp (located on the guide block) is adjusted properly,
 the flag (located on the guide block) is correctly positioned.

6.2.2 Motor time out

This error message means that the signal from the motor stop has not
been sent. To clear the error check if:
 motor stop switch is functioning (using the dashboard function –
see 6.3.1),
 the ramp (located on the guide block) is adjusted properly,
 or any part of the drive mechanism is broken (such as main driving
chain, etc.)

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 6-1


Operation & Service Manual
Troubleshooting

6.2.3 Sensor stuck

This error message means that one of the sensors is triggered and is
sending the signal to controller at the beginning of the proving run. To clear
the error check if:
 theoptical switches are functioning (using the dashboard function –
see 6.3.1),
 ensuring that the flag is not triggering one of the optical switches
(if repositioning is required user can use dashboard function – “Motor
run command” to relocate the piston assembly),
 motor stop switch is functioning (using the dashboard function –
see 6.3.1),

6.2.4 Service due

The prover is due for service as determined by the entry at Main Menu/
Configuration/Alarms/Service Due Reminder.

6.3 Diagnostics

There are several screens inside the Main Menu/Diagnostics menu to aid
in troubleshooting.

6.3.1 Dashboard

The dashboard screen allows you to verify the status of the inputs and
outputs of the SVP Controller. Each output function can be tested by
selecting it and activating it.

Dashboard
Down Sensor High Alarm Output Inactive
Middle Sensor High Alarm Clear High
Up Sensor High
Motor Stop Switch High
Motor Run Inactive
Optical Pulse Inactive
Run Permissive High
Handheld (OK/?)
Bypass Valve Inactive
Draw Valve Inactive

Press OK to change values Stop

A properly functioning optical switch will normally indicate “High” at the


dashboard screen. Inserting an opaque flag into the optical switch will
cause the state to change to “Low”.

6-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Troubleshooting

To check if the motor stop switch is working properly you should select
“Motor stop switch” and trigger the motor stop. The state should change
from “High” to “Low”.

To check if the motor is working you should scroll down to the “Motor run
command” and press OK. The state of the motor will be changed from
“Inactive” to “Active”. You will need to press OK again in order to stop
the motor.

6.3.2 System Health

The System Health screen allows you to check the status of the various
assemblies that are contained in the SVP Controller. Contact Honeywell
support if there are errors.

6.3.3 Active Alarms

The Active Alarms screen allows you to see if any alarms have been
activated and to re-enable the device.

6.4 Troubleshooting Chart

Prover does not cycle when proving pass is initiated


No power to Honeywell Enraf small volume prover Check for continuity of power to prover, see Section 7
Interface cable between CIU or flow computer Check connections and integrity of cables, see Section 7 and flow
and Honeywell Enraf small volume prover is not computer manual
properly connected
Above checks do not resolve problem See Section 6 for troubleshooting controller, optical switches, and
motor stop switch
Honeywell SVP Controller is not in Meter Exit Prover Test Mode (Section 4.3) or Prover Calibration Mode
Calibration Mode (Section 5.3 and 5.4)
Unsteady or absence of pulse from flow meter
Defective flow meter signal cable or connection Refer to applicable proving computer manual and check cables
and connections
Defective pickup or pulser Check for electrical or mechanical failure
Defective flow meter Observe for pulse width variation and possible noise from meter
(repair or replace flow meter)
Defective flow meter signal Test input and output signals preamplifier with an oscilloscope
Defective CONDAT® interface unit or signal Input a frequency signal with a signal generator and check for
conditioners, if using CONDAT® prover control signal at computer or output of signal conditioner with
an oscilloscope
If using flow computer of other manufacture Check flow computer’s operation manual for possible solution
to problem
Table 25: Honeywell Enraf Troubleshooting Chart

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 6-3


Operation & Service Manual
Troubleshooting

Intentionally left blank.

6-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 7 ELECTRICAL SCHEMATICS & DRAWINGS

This section contains various electrical schematics and drawings for the
Honeywell Enraf small volume prover. If there are electrical questions not
addressed by these figures contact your nearest Honeywell Enraf
representative or the factory directly.

7.1 Schematics for prover wiring

Figure 7-1: Wiring Diagram 1 Phase

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 7-1


Operation & Service Manual
Electrical Schematics & Drawings

Figure 7-2: Wiring Diagram DC

7-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Electrical Schematics & Drawings

Figure 7-3: Wiring Diagram 3 Phase

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 7-3


Operation & Service Manual
Electrical Schematics & Drawings

7.2 Connections to Flow Computers

Shown below are diagrams showing how to connect the SVP Controller
via the Customer Connection Box to various models of flow computers.
Note that the first diagram shows a simplified representation of the
Run Permissive Input and the Volume Pulse Output circuits in the SVP
Controller. The 1500 ohm current limiting resistor shown in the diagrams
is required with operating voltages from 12 to 24 volts DC. For operating
voltages from 6 up to 12 volts, the 1500 ohm resistor must be replaced
with a zero ohm jumper. The resistor and jumper must be connected to the
terminals in the Customer Connection Box.

7.2.1 Omni

An Omni flow computer requires that the meter be connected to one of


the two E Combo card pulse inputs. The E combo card will use the double
chronometry proving method. Although there are other ways to make the
connections, we will describe the connections according to the diagram
below. The Volume Pulse + (terminal 16 of the Customer Connection
Box) connects to the prover detector input of the E Combo Module. The
prover detector input on the Omni is usually Pin #7. Connect Volume
Pulse – (terminal 17 of the Customer Connection Box) to common on
the rear of the Omni. This is usually Pin #10 which is tied to common on
the power supply. The prover Run permissive + command (terminal 13 of
the Customer Connection Box) connects to any Omni Digital I/O point.
That point must be assigned a Boolean point that has been programmed
with the value of/1927. Then the Digital I/O point must be assigned the
Boolean point.
Example: Program the Boolean point 1025 with the statement/1927.
Then program Digital I/O point #12 with the number 1025. Connect the run
command wire to Digital Point # 12.
A 1500 ohm resistor must be installed between the Run permissive -
(terminal 14 of the Customer Connection Box) and the common (terminal
15) for the run command to work properly. This setup will launch the
prover when the I/O point goes high (voltage applied). When it is low
(no voltage) the prover motor will be idle. A jumper must be connected
between the Volume Pulse – (terminal 17 of the Customer Connection Box)
and the Common (terminal 15 of the Customer Connection Box). Please
read the Omni’s Operator’s manual prior to connection and or operation of
the Honeywell Enraf small volume prover.

7-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Electrical Schematics & Drawings

7.2.2 CONDAT CIU

The Condat Interface Unit (CIU aka PIU) connects to the SVP controller
using cable (Honeywell PN 44108889). The cable features a connector
that attaches to the CIU at the connector labeled “Control”. The opposite
end of the cable has colored leads for connection in the terminals in the
Customer Connect Box. Please refer to the PROVEit Manuals for further
connection instructions.
Note: The pin numbers listed adjacent to the colors signify the pin
locations on the CIUs “Control” connector.
Within the Customer Connection Box, the terminals 12 and 15 are
provided to securely land customer provided voltage or ground leads
as needed. For the CIU the ground (earth) reference is Black (Customer
Connection Box Terminal 17) and the nominal 15VDC supply is Red
(Customer Connection Box Terminal 12).
While idle, Green (Customer Connection Box Terminal 14) will read nominal
15VDC and White (Customer Connection Box Terminal 16) will read
nominally 5 VDC. When the run command is given, the CIU will drop Green
to ground (earth) and the SVP controller starts the proving run. When either
optical switch is triggered on the downstream pass, the SVP controller will
drop White to 0VDC for 25mS and the CIU will instruct the proving program
to start or stop recording meter pulses. After the run is complete the CIU
will return to idle conditions until the next run command is sent.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 7-5


Operation & Service Manual
Electrical Schematics & Drawings

7.2.3 Daniels

Actual terminal locations for the Daniel flow computer is dependent upon
the application software being used in the Daniel flow computer. See the
appropriate Daniel manual and software information for more information.

Warning

Due to scan speed, the 2500 has limitations in flow rate when used
with small volume flow provers due to short time period between
volume detectors.

7-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Electrical Schematics & Drawings

7.2.4 Dynamic

24VDC Power Supply


External by Customer
+ -

Customer Connection Box Dynamic Flow Computer


Description Terminal Number
DET1
Feed+ (Flow Computer) 12 DET2
1.5Kȍ SW3
Run permissive + 13 SW4
SW5
Run permissive - 14 ST2
ST3
Common (Flow Computer) 15 ST4
DET RET
Volume pulse + 16 SW3-5 RET
ST2-4 RET
Volume pulse - 17
TX
Resistors not labeled can
Resistors not labeled can RX
be 1 to 5 KŸ depending RTS
e 1-5 Kiloohms
on Supply strength RET

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 7-7


Operation & Service Manual
Electrical Schematics & Drawings

Intentionally left blank.

7-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
CHAPTER 8 PROVER MAINTENANCE

Servicing the prover should be done in a de-engergized state but may


require reactivating power for the motor or flow through the prover to
position the piston. Use extreme caution and keep clear of all moving
components including the downstream shaft. All covers should remain in
place while the prover is energized if at all possible. Metal tools should not
be used inside the flow tube so as not to damage the surface finish.

8.1 Portable Prover


 Lock out AC or DC power to motor with padlock
 Install Condat System and computer
 Install fake flow meter/signal generator (if checking optical switches)
 Turn on the 24VDC to the Condat

8.2 Stationary prover


 Lock out AC power to prover with padlock

8.3 General Prover Maintenance Information


Preventative Maintenance
Honeywell Enraf small volume provers are designed to require minimal
maintenance; however, several key components require periodic inspection
and/or replacement to prevent undue wear, damage, or possibly failure.
The following recommended maintenance intervals are based on an
average usage rate of 100 passes per day proving refined petroleum
products at average temperatures of 77ºF [25ºC]. The fluid is typified as
clean of foreign objects or debris and possessing moderate lubricity.
If the fluid being introduced into the prover is high in entrained solids, i.e.:
sand in crude oil, or low in lubricity, i.e.: LPG’s and certain chemicals, then
it is recommended to reduce the time between preventative maintenance
intervals by 50%. This also applies for applications involving high duty
load cycles, i.e.: 3rd party service portables. Extra time spent on careful
preventative maintenance can often prevent otherwise avoidable costly
repairs and calibration downtime.
Always remember to depressurize, drain, and block & blind your prover
in addition to meeting your site required electric power lockout/tag-out
procedures before performing maintenance procedures.

A - Prior to Each Proving Session:


1. Visually inspect pressure retaining components (i.e.: flow tube flanges, bleed
manifolds and valves, drain valves, shaft seal assemblies, transmitter ports)
for signs of leakage, damage, or failure. Repair or replace any suspect items.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-1


Operation & Service Manual
Prover Maintenance

2. Verify Return Drive Assembly protective cover set and Downstream


Shaft Cover are intact with no signs of tampering or unauthorized entry.
3. Verify all required safety devices are functioning and any exposed
pressure relief blow down is directed away from personnel.
4. Verify Purge Gas is present for units using Purge Cover Assemblies.

B - Monthly:
1. All items in A.
2. Remove Return Drive Assembly Side Panels. Visually examine return
drive assembly (i.e.: conveyor shaft assemblies with bearings and
pullers/chains, motor and speed reducer, drive end plates and anchor
bolts, guide bars, guide block assembly including optical switch and
ground assembly, switch bar assembly) for any loose fasteners or signs
of adverse wear and/or damage. Repair or replace any suspect items.
3. Visually inspect all electrical cabling for signs of wear or damage.

C – Semi-Annually:
1. All items in B.
2. Remove upstream and downstream bleed manifolds. Insert boroscope
with flashlight attachment into both upstream and downstream vent
flanges. Visually inspect both upstream and downstream piston seals for
and signs of damage or wear. Inspect poppet valve seal for any signs
of damage or wear. Inspect flow tube calibrated surface for damage to
chrome plating. Repair or replace any suspect items.
3. Verify prover anchor bolts are tight.
This maintenance section covers most of the routine maintenance
procedures to be performed on your prover. Trouble shooting information
is contained in Section 6 while wiring diagrams and schematics common
to all Honeywell Enraf small volume models are found in Section 7.
Please contact the Honeywell Enraf factory for information on problems or
repairs not covered by Honeywell Enraf small volume Operation Manual.

8.4 Downstream Shaft Seal Replacement

Please Note: When referring to an item # in the following instructions,


please refer to Figure 8-1 through Figure 8-8.
1. Do not remove upstream seal retainer at this time.
2. Move the piston to the downstream position.
3. Disconnect power from prover.
4. Disconnect prover from line, or block off from line, and drain it completely.
5. Remove downstream shaft cover by removing outer support, carefully
sliding tube cover from the shaft, and unscrew the threaded rod from
the downstream stop, Figure 8-1 #53101.

8-2 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

6. Remove the 4 bolts, Figure 8-1 #53107, in order to remove the


downstream stop from the downstream end flange,
Figure 8-1 #53001.
7. Disassemble the downstream seal retainer, Figure 8-1 #53109 from
the downstream stop.
8. Remove the retaining rings, seals and washers from the downstream
seal retainer as showed in the Figure 8-2.

53002
HOLE FOR LIFTING (1X OR 3X)

53001

53003

53109
53110
53108
53101

53107

ITEM NO. DESCRIPTION


53001 DOWNSTREAM FLANGE
53002 O-RING SEAL DOWNSTREAM FLANGE
53003 FLANGE RETAINING BOLT
53101 DOWNSTREAM STOP
53107 DOWNSTREAM STOP RETAINING BOLT
53108 O-RING SEAL DOWNSTREAM STOP
53109 DOWNSTREAM SEAL RETAINER
53110 DOWNSTREAM SEAL RETAINER BOLT
Figure 8-1: Downstream Side Exploded View

9. Clean and inspect seal retainer.


10. Check seal surfaces for scratches and a surface finish of 12rms. If
necessary, polish the seal surfaces.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-3


Operation & Service Manual
Prover Maintenance

11. Carefully install new seals and washers in proper orientation as


showed in the Figure 8-2. Note the direction of the seal lips for correct
installation of the new seals. In a case of cracked or broken washers
they need to be replaced when new seals are installed.
12. Assemble the downstream seal retainer, Figure 8-1 #53109, to the
downstream stop, Figure 8-1 #53101, using hex socket bolts, Figure
8-2 #53110. Make sure that the O-ring seal, Figure 8-2 #53111, is in
place before the seal retainer is assembled to the downstream stop.
13. Snug bolts evenly, using a cross pattern, so as to not damage the seal
or distort the flange. Refer to Table 16 for bolt torque specifications,
and carefully tighten bolts evenly, using a cross pattern, and moving in
increments to the full torque value.

ITEM NO. DESCRIPTION


53102 SHAFT SEAL
53103 IGUS BUSHING
53104 SHAFT SEAL
53105 NOTCHED RYTON WASHER
53109 DOWNSTREAM SEAL RETAINER
53110 DOWN STREAM SEAL RETAINER BOLT
53111 O-RING SEAL
53112 RYTON WASHER
53106 RETAINING RING
Figure 8-2: Downstream Seal Retainer Assembly
Please Note: On the provers models S05/O05, S15/O15, S25/O25 and S35/O35 all three shaft seals are the same.

8-4 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

8.5 Prover Piston Assembly Seal Replacement

1. Complete the steps from 1 thru 6 mentioned in the Section 8.4.


2. Remove the bracket securing the flow tube and downstream end
flange to the frame.
3. Remove pressure and temperature transmitters from the downstream
end flange.
4. Remove the hex socket bolts, Figure 8-1 #53003, securing the
downstream end flange Figure 8-1 #53001 to the flow tube except for
1 bolt at the top. Connect a hoist to the threaded hole in the top of the
downstream end flange. Remove the last hex socket bolt, and using
the hoist to support the flange, remove it from the flow tube.
5. Open the drive end cover and remove the securing nut (locking nut),
the standard hexagonal nut and the washer, Figure 8-3 position 1 ,
from the guide block, Figure 8-3 position 2 on the upstream side of the
flow tube.
3

1 2 4 5
Figure 8-3: Guide Block Assembly

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-5


Operation & Service Manual
Prover Maintenance

6. Remove the guide block Figure 8-3 position 2 and the mechanical
stop Figure 8-3 position 4 with the rubber bumper Figure 8-3 position
5 from the upstream piston shaft.
7. Remove the upstream seal retainer assembly, Figure 8-7 #52101, from
the upstream flange by first removing the shock absorbers, Figure 8-7
#52108, and then removing the hex socket cap screws, Figure 8-7
#52107 holding the seal retainer to the end flange. Then remove the
upstream seal retainer assembly.
8. With sufficient personnel and/or a hoist or crane at the downstream
end of the prover, lift the piston assembly and pull it out of the flow
tube, see Figure 8-4. Be extremely careful to remove the piston
assembly in such a manner to not cause damage to the piston or to
the precision bore flow tube. Note: Lift the piston assembly with a
nylon strap wrapped through piston support to prevent damage or
injury. NEVER lift the piston assembly with the strap positioned far
away from the piston support, Figure 8-5 #54002.
9. For piston disassembly on most models, use procedure 9a, for older
models, use 9b.
9a. Referring to Figure 8-5, disassemble the piston, by first removing
the downstream shaft #54005 from the poppet valve #54003. Then
remove the piston support #54002 from the piston body by placing
the piston body #54001 face down on a clean surface and hold
pressure to keep the spring #54009 compressed and removing the
#54020 hex head cap screws. The poppet assembly may now be
removed from the piston body. Remove poppet seal #54014 from
piston body #54001. Remove the main piston seals #54013 and
riders #54008 very carefully so as not to damage the seal surfaces on
the piston.

Figure 8-4: Piston Removal

8-6 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

54018 54003
54010 4X(SEE DETAIL A)
54006
54017
54005 54009 54002

54021
54013
54020
54008
54001 54018 54021
54013 54011
54014
54011

NOTE: DETAILS SHOW COMPONENT ORIENTATION ONLY.

DETAIL A: BELLEVILLE WASHER #54010 ORIENTATION

ITEM NO. DESCRIPTION


54001 PISTON BODY
54002 PISTON SUPPORT
54003 POPPET
54004 UPSTREAM SHAFT
54005 DOWNSTREAM SHAFT
54006 BELLEVILLE RETAINER WASHER (NOT INSTALLED ON ALL UNITS)
54008 PISTON SEAL RIDER (QUANTITY MAY VARY BASED ON PROVER MODEL)
54009 PISTON SPRING
54010 PISTON BELLEVILLE SPRING (NOT INSTALLED ON ALL UNITS)
54011 IGUS BUSHING
54013 PISTON SEAL (QUANTITY MAY VARY BASED ON PROVER MODEL)
54014 POPPET SEAL
54017 BELLEVILLE RETAINER SEAL (NOT INSTALLED ON ALL UNITS)
54018 SOCKET HEAD CAP SCREW
54020 HEX HEAD BOLT
Figure 8-5: Piston Assembly Exploded View

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-7


Operation & Service Manual
Prover Maintenance

9b. Referring to Figure 8-5, disassemble the piston, by first removing


the downstream shaft #54005 from the poppet valve #54003. Then
remove the piston support #54002 from the piston body by placing
the piston body #54001 face down on a clean surface and hold
pressure to keep the spring #54009 compressed and removing the
#54020 hex head cap screws. The poppet assembly may now be
removed from the piston body. Remove seal retainer flange #54023
(not shown) from #54003, and remove poppet seal #54014 from
#54003. Remove the main piston seals #54013 and riders #54008
very carefully so as not to damage the seal surfaces on the piston.
Note: Use caution on larger units (S85 and S120) as it takes three
people to remove the piston support, two to stand on the support and
the other one to remove the bolts. If the support should be stuck in the
piston body, the two people standing on the support should remain
until the third person can tap it loose using a dead blow hammer.
10. Clean and inspect all parts.
11. Check seal groove width for proper seal fit, use gauge if available.
If the groove is too small check with factory to get the proper
dimensions to have the piston body machined.
12. Reassemble the piston by reversing the disassembly procedure and
use new seals in all locations, refer to Figure 8-5. Note the direction
of the seal lips for correct installation of the new seals, see Figure
8-5. To assist in installing the riders and main piston seals, put them
in hot water [60 - 65°C (140 - 150°F)] to make the seals and riders
more flexible and to reduce the chance for damage. All piston bolts
should have a thread lock compound applied to them, Loctite 242 is
recommended. Note: If piston appears tight when installing new seal
kits into the tube a groove could be cut on the rider surface. This will
consist of two 45-degree grooves cut in the rider spaced 90 or 180
degrees apart. Use a sharp utility knife to create groove. Depth of
groove is to be 80% of the rider thickness and 3mm (1/8") wide. Cut
grooves after rider is installed on piston body. All riders should have
chamfered inside edges to allow for proper seating in the piston.

Note: Be extremely careful to not damage the piston seals in any way
or to lay the piston on the seals and cause them to be deformed.
13. Clean and inspect flow tube. Check for gouges, excessive wear, 
de-plating, pitting, etc.
14. Insert the piston by carefully guiding the piston assembly into the flow
tube being very careful to not damage the new seals or the precision
bore flow tube. It will be necessary to apply some considerable force
to the piston assembly to compress the piston seals to enter the flow
tube bore. It may be necessary to use a length of the appropriate size
threaded rod, inserted through the hole in the drive end plate where
the static leak detector is inserted, refer to Figure 8-6. Screw the
threaded rod into the piston shaft. A piece of 13mm (1/2") PVC

8-8 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

pipe over the threaded rod will prevent the threads from hanging up
in the upstream flange. Install a large flat washer and a nut on to the
threaded rod and pull the piston into the flow tube while wiggling the
downstream shaft to be certain of correct alignment with the seals and
the flow tube bore.

Figure 8-6: P
 iston Insertion into Flow Tube – Pulling Method
Notes: R
 efer to Table 16 for bolt torque values for assembling flow prover.
Upstream flange to flow tube seal does not usually need replacement during normal
maintenance, nor is it necessary to remove upstream flange, Figure 8-7 #52201.
15. Put a new o-ring seal, Figure 8-1 #53002, onto downstream end
flange, Figure 8-1 #53001, carefully re-install flange into flow tube.
Re-install hex socket bolts, Figure 8-1 #53003, securing the
downstream end flange, Figure 8-1 #53001, to the flow tube. Snug
bolts evenly, using a cross pattern, so as to not damage the seal or
distort the flange.
Refer to Table 16 for bolt torque specifications, and carefully tighten
bolts evenly, using a cross pattern, and moving in increments to the full
torque value.
16. With downstream seal retainer assembled to the downstream
stop (refer to Section 8.4 steps 11 & 12), finish re-assembly of the
downstream side of the prover using the reverse of the procedure
from # 1 through # 4 making sure that critical bolts are tightend as per
torque specification, see Table 16.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-9


Operation & Service Manual
Prover Maintenance

8.6 Upstream Shaft Seals Replacement

1. Make sure that the steps from 2 thru 4 mentioned in the Section 8.4
and the steps from 5 thru 7 mentioned in the Section 8.5 are
fully completed.
2. Remove the retaining rings, seals and washers from the upstream seal
retainer, Figure 8-7 #52101.
3. Clean and inspect seal retainer.
4. Check seal surfaces for scratches and a surface finish of 12rms. If
necessary, polish the seal surfaces.
5. Carefully install new seals and washers in proper orientation (see
Figure 8-7 for correct installation). Note the direction of the seal lips for
correct installation of the new seals. In a case of cracked or broken
washers they need to be replaced when new seals are installed.
6. Install the upstream seal retainer, Figure 8-7 #52101, in the upstream
flange, Figure 8-7 #52201.
7. Re-install hex socket bolts, Figure 8-7 #52107 in order to secure
the upstream seal retainer to the upstream end flange. Snug bolts
evenly, using a cross pattern, so as to not damage the seal or distort
the flange.
Refer to Table 16 for bolt torque specifications, and carefully tighten
 
bolts evenly, using a cross pattern, and moving in increments to the full
torque value.
8. Re-install the shock absorbers, Figure 8-7 #52108. Make sure to
adjust the setting on all four shock absorbers at the same setting
number (see instructions in Section 8.8.10).
9. Install the mechanical stop, Figure 8-3 position 4 with the rubber
bumper, Figure 8-3 position 5 on the upstream piston shaft. Note: It is
recommended to replace existing rubber bumper with the new one at
this time. Make sure to clean the surface on the mechanical stop prior
to gluing the rubber bumper to it. Use Loctite 422 or equivalent.
10. Carefully slide the guide block, Figure 8-3 position 2 over the threads
of the dimple stud and secure it using the washer, standard hexagonal
nut and locking nut, Figure 8-3 position 1. Note: Make sure to clean
the threads on the dimple stud and be careful not to damage the
optic switches.

8-10 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

ITEM NO. DESCRIPTION


52201 UPSTREAM FLANGE
52202 BELLEVILLE SPRING
52203 WASHER BELLEVILLE RETAINER
52204 RETAINING RING
52205 UPSTREAM FLANGE O-RING SEAL
52206 SOCKET HEAD CAP SCREW
52207 HEX HEAD CAP SCREW
52101 UPSTREAM SEAL RETAINER
52102 SHAFT SEAL UPSTREAM OUTER
52103 IGUS BUSHING
52104 SHAFT SEAL
52106 RETAINING RING
52107 SOCKET HEAD CAP SCREW
52108 SHOCK ABSORBER
52109 TEFLON O-RING SEAL
52110 RYTON WASHER
52111 SHAFT SEAL
52112 NOTCHED RYTON WASHER
Figure 8-7: Upstream flange and seal retainer assembly
Please Note: On the provers models S05/O05, S15/O15, S25/O25 and S35/O35 all three shaft seals are the same.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-11


Operation & Service Manual
Prover Maintenance

8.7 Bolt Torque Specifications

Prover Item# Item# Item# Item# Item# Item# Item# Item#


Model
Number 52206 52107 53003 53107 53110 54018 54020 See Note 1
05X3C 120 lbf•ft 150 lbf•ft 120 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 19 lbf•ft 150 lbf•ft
15X1A 120 lbf•ft 150 lbf•ft 120 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
15X2B 120 lbf•ft 150 lbf•ft 120 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
25X1A 120 lbf•ft 150 lbf•ft 120 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
25X2B 120 lbf•ft 150 lbf•ft 120 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
25X3C 500 lbf•ft 150 lbf•ft 500 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
25X4 and 5 500 lbf•ft 150 lbf•ft 500 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
35X1 thru 5 500 lbf•ft 150 lbf•ft 500 lbf•ft 150 lbf•ft 75 lbf•in 75 lbf•in 45 lbf•ft 150 lbf•ft
50X1A 170 lbf•ft 150 lbf•ft 170 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft
50X2B 170 lbf•ft 150 lbf•ft 170 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft
50X3 thru 5 1200 lbf•ft 150 lbf•ft 1200 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft
85X1A 295 lbf•ft 150 lbf•ft 295 lbf•ft 150 lbf•ft 75 lbf•in 11 lbf•ft 170 lbf•ft 250 lbf•ft
85X2B 295 lbf•ft 150 lbf•ft 295 lbf•ft 150 lbf•ft 75 lbf•in 11 lbf•ft 170 lbf•ft 250 lbf•ft
85X3C 1200 lbf•ft 150 lbf•ft 1200 lbf•ft 150 lbf•ft 75 lbf•in 11 lbf•ft 170 lbf•ft 250 lbf•ft
85X4D 1400 lbf•ft 150 lbf•ft 1200 lbf•ft 150 lbf•ft 75 lbf•in 11 lbf•ft 170 lbf•ft 250 lbf•ft
120X1A 500 lbf•ft 150 lbf•ft 500 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft
120X2B 500 lbf•ft 150 lbf•ft 500 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft
120X3C 1200 lbf•ft 150 lbf•ft 1200 lbf•ft 150 lbf•ft 11 lbf•ft 11 lbf•ft 170 lbf•ft 250 lbf•ft

Prover Model Item# Item# Item# Item# Item# Item# Item# Item#
Number 52206 52107 53003 53107 53110 54018 54020 See Note 1
05X3C 163 Nm 203 Nm 163 Nm 203 Nm 9 Nm 9 Nm 26 Nm 203 Nm
15X1A 163 Nm 203 Nm 163 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
15X2B 163 Nm 203 Nm 163 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
25X1A 163 Nm 203 Nm 163 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
25X2B 163 Nm 203 Nm 163 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
25X3C 678 Nm 203 Nm 678 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
25X4 and 5 678 Nm 203 Nm 678 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
35X1 thru 5 678 Nm 203 Nm 678 Nm 203 Nm 9 Nm 9 Nm 61 Nm 203 Nm
50X1A 230 Nm 203 Nm 230 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
50X2B 230 Nm 203 Nm 230 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
50X3 thru 5 1630 Nm 203 Nm 1630 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
85X1A 400 Nm 203 Nm 400 Nm 203 Nm 9 Nm 15 Nm 230 Nm 340 Nm
85X2B 400 Nm 203 Nm 400 Nm 203 Nm 9 Nm 15 Nm 230 Nm 340 Nm
85X3C 1630 Nm 203 Nm 1630 Nm 203 Nm 9 Nm 15 Nm 230 Nm 340 Nm
85X4D 1900 Nm 203 Nm 1900 Nm 203 Nm 9 Nm 15 Nm 230 Nm 340 Nm
120X1A 678 Nm 203 Nm 678 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
120X2B 678 Nm 203 Nm 678 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
120X3C 1630 Nm 203 Nm 1630 Nm 203 Nm 15 Nm 15 Nm 230 Nm 340 Nm
Table 26: Bolt Torque Specifications
Note 1: Hexagonal standard nut, Figure 8-3 position1, holding guide block, Figure 8-3 position 2, to upstream shaft.

8-12 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

Item# Item# Item# Item# Item#

Model 24006 24012 24018 24002 24019 Model

Screw Screw Screw Cam follower Cam follower

5 4.0 Nm 35 lbf•in 5

15 15
11 Nm 95 lbf•in
25 25
1.1 Nm 2.2 Nm 3.6 Nm
35 28 Nm 250 lbf•in 35
9.6 lbf•in 19.8 lbf•in 31.7 lbf•in
50 28 Nm 250 lbf•in 73 Nm 650 lbf•in 50

85 73 Nm 650 lbf•in 85

120 141 Nm 1250 lbf•in 120

Table 27: Guide Block Bolt Torque Specifications


Note: See Figure 8-8 for items referenced in Table 17.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-13


Operation & Service Manual
Prover Maintenance

ITEM NO. DESCRIPTION


24001 GUIDE BLOCK
24002 CAM FOLLOWER
24003 BEARING GUIDE BAR
24004 BEARING GUIDE BAR SHIM
24005 FLAG
24008 MOTOR STOP RAMP
24009 SOCKET HEAD CAP SCREW
24010 LOCK WASHER
24011 GROUND STRAP
24012 SOCKET HEAD CAP SCREW
24018 SOCKET HEAD CAP SCREW
24019 CAM FOLLOWER
Figure 8-8: Guide Block Exploded View

8.8 Drive System Maintenance


The Honeywell Enraf small volume prover mechanical piston return
mechanism is rugged and trouble-free, requiring little maintenance. All
bearings are sealed, and chains are stainless steel. Maintenance on the
drive system normally would be done at the same time as normal prover
maintenance, such as seal change and water draw. If at any time the
piston return chains need adjustment, adjust only the bearings at the end
closest to the flow tube. Adjust chains for even tension.
A. Chains should be lubricated with a dry chain lube or lubricant that has
a carrier fluid which evaporates and does not cause dirt and dust to
collect. Recommended is a PTFE filled chain lubricant.

 Warning
Do not lubricate chains with normal oils which collect dirt and cause wear.

B. Gearbox oil level should be checked periodically. Oil level should be


approximately 13mm (1/2") below vent port for horizontally mounted
provers, see Figure 8-9. The gear reducers will be supplied with the
oil in it based on the ambient temperatures. The reducers will be filled
with synthetic ISO VG 320 oil based on polyglycol when used in
applications above -20°C (-4°F) and with synthetic ISO VG 68 or
80 oil based on polyglycol when used in applications below -20°C
(-4°F). If the oil level is low or performing a seasonal change, drain
the remaining oil and refill the reducer to the correct level - do not mix
types of oil.

8-14 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

Figure 8-9: Gearbox Lubrication Diagram

8.8.1 Before working on the Drive System


a. Ensure that the power to the motor is removed and locked and tagged.
b. Check that the piston is in the downstream position the distance
between the mechanical stop and the upstream seal retainer should be
approximately 51 - 76mm (2 - 3 inches).
c. Close and lock the block and bleed valves at inlet and outlet to prover.
d. Bleed and drain prover.
e. Remove the motor (main drive) chain (the chain between the output
sprocket on the gear reducer and the main drive sprocket.

8.8.2 Checking Alignment of Drive System (general checking)


a. Check the drive system to see if there are any lose bolts or parts.
b. Be certain to check the washers on the end of the guide bars. If these
washers are not thick stainless steel washers replace them, even if they
appear to be tight (standard bolt washers do not work correctly).

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-15


Operation & Service Manual
Prover Maintenance

c. Check to see if all six pins have been installed Figure 8-10.

PIN 2 PLACES PIN 4 PLACES


1 1 1 1
4" X 4" SPRING PINS 4" X 4" SPRING PINS
#21051 #21051

Figure 8-10: Pinning Locations 

8-16 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

d. When checking alignment, loosen bolt on end of guide bar and use a
wrench to check that the guide bar is tight to the flange Figure 8-11.

WRENCH FLATS

TIGHTEN HEX BOLT TO LOCK GUIDEBAR IN PLACE


TURN CLOCKWISE TO TIGHTEN
GUIDE BAR AGAINST FLANGE
Figure 8-11: Tighten Guidebar

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-17


Operation & Service Manual
Prover Maintenance

e. Check the ground spring to ensure it is in contact with the ground bar.
In the case of larger provers, check that the ground cable is connected
to both the ground strap and frame Figure 8-12

Figure 8-12: Grounding the Prover

8-18 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

8.8.3 Checking Alignment of Guide Block


a. With the piston close to the downstream position, remove the piston
shaft nut. Being careful not to break the optic switch, slide the guide
block off the stud.
b. Check side play of guide block, clearance should be .076 to 0.127mm
(.003 to .005"). If play is excessive, remove and shim Ryton bushing see
Figure 8-13.

Figure 8-13: Guide Block Shims

c. Check that the Dimple Stud is straight and square in all direction to the
end of the piston.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-19


Operation & Service Manual
Prover Maintenance

 are should be taken to ensure that the hole in the guide block aligns
C
with the Dimple stud in the piston shaft. If the hole does not align with
the stud, adjust shims accordingly. Slide the guide block upstream and
check the side play. If side play is too tight upstream, you will have to
readjust shims, remembering that the guide block MUST always align
with the Dimple stud in the downstream position see Figure 8-14

Figure 8-14: Stud Alignment

d. Reinstall the guide block to the piston shaft.


e. Pull the piston upstream being careful not to break the optic switches.

8-20 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

f. Use a wrench on the hub of the large drive sprocket and move the
piston to the position that you want. Remove nut, slide guide block off
the Dimple stud, and check alignment with the guide block.
g. The hole in the guide block should be aligned side to side with the
Dimple stud and the shaft should have .8 to 1.6mm (1/32 to 1/16") sag
when upstream see Figure 8-14.
h. If the Dimple stud is not aligned properly, adjust the upstream plate by
loosening the respective bolts and removing the M6 (1/4") spring pins
used to maintain alignment. Once you remove the alignment pins you
must drill and tap new holes, after all adjustments have been made
see Section 8.8.9. Adjust the upstream drive end plate so that the side
of the plate is perpendicular to the frame. Tighten all the bolts, and
check the alignment again.
i. To avoid a twist on the drive system, squareness between the two
plates in the drive end must be maintained.

8.8.4 Check the Alignment of the Flag


a. Inspect the upstream and downstream optical switches to verify they
are correctly seated, see Figure 8-15. If not, reposition and replace
springs and seals as needed.

Figure 8-15: Correctly Seated Optical Switch Bottom and Side View

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-21


Operation & Service Manual
Prover Maintenance

b. Position the flag with the guide block in the opening of the downstream
optical switch and check the alignment. The flag should be centered as
showed in the Figure 8-16. This can be observed through the hole in
the upstream drive end plate or using a mirror positioned close to the
optical switch.
1/4-20 BOLT

THREADED ROD

SWITCH BAR
SHIM

PLATE

PROPERLY
CENTERED FLAG

Figure 8-16: Switchbar Position


c. If necessary, gently shift the flag until it is centered.
d. Repeat first two steps at the upstream optical switch.

8-22 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

e. If adjusting the flag does not provide centering of the flag on both
switches, the switch bar may not be aligned with the piston assembly.
a. First confirm that the guide block is aligned with the piston shaft see
Section 8.8.3.
b. Use a pipe clamp and pull the switch bar, if possible, in the direction
needed being careful not to affect other adjustments. You may have
to move both ends see Figure 8-17.

Figure 8-17: Pipe Clamp Position


f. If the pocket in the plate is bigger than the switch bar, the gap will need
to be shimed. The shim must be installed between the 16mm (5/8") rod
and the switch bar itself. This shim must be bolted to the plate. These
adjustments will most likely need to be performed at both ends of the
switch bar on opposite sides see Figure 8-16.
g. Recheck the flag alignment.

8.8.5 Check the Alignment of the Puller


a. With the piston close to the downstream position, rotate by hand
the main drive sprocket to position puller behind guide block
(in pull position).
b. Check clearance between puller and two cam followers using a
feeler gage set at 0.076mm (.003"). Please note: Tablet paper is an
approximate measurement.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-23


Operation & Service Manual
Prover Maintenance

c. The drag should be the same at both cam followers (see Figure 8-18).
If the drag is not the same, adjust pillow blocks to get the correct
clearance of the cam followers (see Figure 8-19).

Figure 8-18: Puller Alignment

8-24 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

Figure 8-19: Adjustment Blocks

d. When you are making the above adjustments you need to check the
chain to be sure that it does not climb on the side of the sprocket as
the puller approaches the sprockets. If this occurs, adjust the sprockets
to eliminate the problem. Sprocket adjustment must be checked both
downstream and upstream.
  If the sprockets are loosened or are loose from the shaft they must be
fastened with #290 Green Loctite after all adjustments have been made
(see Figure 8-20).

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-25


Operation & Service Manual
Prover Maintenance

Figure 8-20: Shaft Loctite Locations

8-26 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

e. On models where the sprocket shafts are not set at a fixed distance
(S05, S15, S25) the chain must have 19mm (¾") play, checked at the
bottom. Any adjustments made for this purpose should be done with
the downstream pillow blocks, as this will not affect the adjustment
of the puller (see the next section, UHMW Chain Rail Adjustment, for
more details).

8.8.6 UHMW Chain Rail Adjustment


a. Adjust plastic rail so it holds chain flat and even with the top of the
sprockets and is centered in the chain see Figure 8-21.

Figure 8-21: Chain Support Adjustment

b. Verify by observing a flat smooth transition from the sprockets to the


chain support while moving the chain back and forth.

8.8.7 Adjust the Chain Tensioners


1. Checking the motor chain tension:
a. There must be 19mm (¾") of play in the motor chain. Any
adjustments can be made using the adjustment bolts in the
adjustment blocks.
b. Check everything twice to avoid any missed items. DO NOT OVER
TIGHTEN.
c. Loctite the adjustment bolts with #242 Blue Loctite see Figure 8-20.
If the adjustment blocks are missing install new ones as needed.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-27


Operation & Service Manual
Prover Maintenance

2. Checking the tension on two drive chains (chains with puller


in between):
a. Check the drive chain alignment and tension. Any adjustments can
be made using the downstream adjustment bolts in the adjustment
blocks.
b. There must be 19mm (¾") of play in the chain. DO NOT OVER
TIGHTEN see Figure 8-22.

Figure 8-22: Recommended Chain Sag

c. Loctite the adjustment bolts with #242 Blue Loctite. If the adjustment
blocks are missing install new ones as needed.

8.8.8 Securing the Drive End


a. After all mentioned adjustments have been completed, prover must
be pinned to maintain drive end alignment see Figure 8-10. Check
everything twice to avoid any missed items.
b. Check to see if there are pins securing the flange plate to the frame.
If these pins are not in place install one on each side, next to the
mounting bolts of the flange plate see Figure 8-10.
c. Drill two holes through the mount bracket and the end plate, next to the
mounting bolts. Drill two holes through the mount plate and the frame,
next to the mounting bolts.
d. All holes must be tight fit with the pins which will need to be installed
into the drilled holes.

8.8.9 Check Shocks


a. Push down on the shock very fast and it should stop, then continue
moving some more.

8-28 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

b. If you push down on the shock and it bottoms out check the
adjustment. Almost all of the shocks are adjustable. All shocks must
be on the same setting.
c. If after adjusting and retesting the shock it still does not perform
correctly, the shock needs replacement.
d. The shocks depth must also be adjusted on the prover itself see Figure
8-23. This insertion depth must be correct and the same on all four shocks.

Figure 8-23: Shock Installation Depth

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-29


Operation & Service Manual
Prover Maintenance

8.9 Volume Switch Replacement


If optical volume switch replacement is necessary, as determined by
trouble shooting procedures found in Section 6, follow steps 1 through 5.
1. Remove (3) as shown in Figure 8-3 to access electrical connector.
2. Lift electrical connector very gently from the hole, and disconnect the
cable from the switch wires.
3. With a stiff wire with a hook bent in the end, or small needle-nosed
pliers, gently disconnect the switch retaining springs from the switch bar
and remove the old switch. Prior to dropping the switch out of position,
note orientation of the switch in the switch bar L-bracket.
4. Install the one end of the switch retaining springs in the holes of the new
optical switch.
5. Position the new switch in the same position noted in step 3, and
reverse steps 3 through 1 for re-installation of the new volume switch.
Note: T he Honeywell Enraf volume switch assembly has been precision
adjusted at the factory. Water draw after switch replacement is
not required. Older models may be using optical switches with
aluminum base plates. While these switches are still valid for
use, the new standard is a stainless steel base plate. Under no
circumstance should one aluminum and one stainless steel switch
be used together, optical switch base plate material must be
identical for both switches.

NOTICE to Honeywell Enraf small volume prover users.


The following figures detail new optical switch shape. As seen below, the
optical switch plate has one straight side and one rounded side. Figures
8-24 and 8-25 below illustrate a correct optical switch installation.

Figure 8-24: Correct Optical Switch Installation Bottom View

8-30 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

Figure 8-25: Correct Optical Switch Installation Side View

Figure 8-26, Figure 8-27, and Figure 8-28 below show an improper
installation. To maintain correct installation, the optical switch must be
pushed tightly to the inner corner of the L-bracket and must be seated
entirely in the machined pocket of the switch bar. Finally, before installing
any optical switches, be sure that the machined pockets of the switch bar
and inner faces of the L-brackets are free of any debris.

Figure 8-26: Improper Optical Figure 8-27: Improper Optical Figure 8-28: Improper Optical
Switch Installation Side View Switch Installation Bottom View 1 Switch Installation Bottom View 2

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-31


Operation & Service Manual
Prover Maintenance

8.10 Thread Locker Fluid Location List


Back out the bolt and apply Loctite to threads. After application of the
Loctite readjust bolt back to a tight position. This procedure must be
completed at all the following locations.
a. All bolts on the inside of the prover use # 242 Blue Loctite.
b. Dimple stud assembled in to the piston shaft uses #272 Red Loctite.
c. 2H nut for the Dimple stud uses # 242 Blue Loctite.
d. Tension bolts used to hold the adjustment of the pillow blocks and
gear box use #242 Blue Loctite.
e. Sprockets to shafts use # 290 Green Loctite.
f. Pillow blocks to shaft use #290 Green Loctite.

8.11 After Sales Support


Honeywell GTS (Global Technical Services) support the Honeywell Enraf
provers globally.
All after sales support enquiries should be channeled to GTS in the
first instance.
Honeywell Enraf have strategically positioned global service partners in
USA, Europe & Asia to support Honeywell Enraf provers worldwide.
In order to analyze the problem the following information is required:
 Serial number of prover
 Model number
 Point of contact
 Contact details
 Location of prover
 Process conditions when problems occurred (flow rate, viscosity,
product, temperature, number of prover runs)
 Historic information about prover (date installed, repair history)
 Pictures of damage
Honeywell Enraf can offer;
 Commissioning & start-up (including replacement of the transit seals).
 A periodic maintenance service which normally consists of changing
seals, checking alignment of drive end and changing optical
switches and a differential pressure test to check for seal leakage.
(Recommended annually)
 Water draw is (Recommended every 2 years)
 Small Volume Prover Inspection and Refurbishment
 Project consultation
 Honeywell GTS:  Email - [email protected]
Call: 1-800-423-9883

8-32 Small Volume Prover Installation, Part No.: 44200002 - Revision 3


Operation & Service Manual
Prover Maintenance

8.12 F
requently asked questions.
What type of prover is the Honeywell Enraf? The Honeywell Enraf prover is classified as a Small Volume
Unidirectional Piston Displacement Prover.
Why is the Honeywell Enraf prover considered to be The small volume classification is based on the volume displaced
small volume when it can hold up to 350 gallons in relationship to the number of flow meter pulses collected. A
of fluid? large volume prover requires greater than 10,000 meter pulses
be collected to generate a meter factor (typically a pipe prover). A
small volume prover in conjunction with ‘Double chronometry’ can
generate a meter factor in less than 10,000 meter pulses.
How can the Honeywell Enraf flow prover be used on By slowing the prover down to allow for longer run up time, the
Corriolis and UltraSonic meters? flow disturbance caused by the internal valve closure will have had
enough time to stabilize and generate accurate repeatable readings.
What is ‘Run up time’? The run up time is the time it takes from the release of the piston to
reach the start measurement switch. (1st Optical Switch)
Why is the upstream and downstream volume The Honeywell Enraf flow Prover has a piston shaft on both sides
the same? of piston body therefore the displaced volume is the same.
How does the flow prover measure volume pulses? The Honeywell Enraf prover does not measure anything. It is a very
accurate, but simple instrument that waits for a start signal from
the flow computer and sends back the pulses as it passes the
volume switches.
Can the fluid flow through the prover all the time? Yes, many Honeywell Enraf provers are installed in “Standby
Mode”, but it is recommended to consider the more durable
elastomer option when operating a prover in this way. This is the
best practice for fluids that are at temperatures higher or lower
than ambient continuous to allow for faster warm up time.
How much pressure drop does the Honeywell Enraf Under normal operating conditions the prover will generate 28 - 69
Flow Prover Have? kPa (4 – 10 psi) pressure drop at maximum flow rate. This is based
on water and is applicable to refined products such as diesel,
jet, gasoline, etc. Products such as heavy crude oil can generate
pressure drops of up to 20psi in some cases.
What motor sizes are used on Honeywell It depends on the prover model but in general an 05 uses
Enraf provers? 0.5hp/.35kW electric motor; 15, 25, 35, & 50 use a 1hp/.75kW
electric motor; 85 uses a 2hp/1.5kW electric motor; 120 uses
5hp/3.7kW electric motor.
What are the installation considerations for a Correct installation of the Honeywell Enraf prover is vital to a long
Honeywell Enraf prover? and trouble-free operation. Critical elements include suitable
foundations, pipe stress and load analysis on provers inlet and
outlet ports, adequate upstream filtration and thermal pressure
relief. If you have any questions, please consult the factory.
How is the installed base of Honeywell Enraf Honeywell Global Technical Support (GTS) is the focal point for
provers supported? all Honeywell Enraf related after-sales support questions and
GTS is supported by a network of Honeywell service centers and
strategically positioned service partners.
How can I receive information and support for the Contact your local sales specialist. There is a Honeywell Enraf
Honeywell Enraf prover? specialist located in each global region (Americas, Asia Pacific and
Europe Middle-East & Africa - EMEA).
Table 28: Frequently Asked Questions.

Part No.: 44200002 - Revision 3 Small Volume Prover Installation, 8-33


Operation & Service Manual
Honeywell Enraf Americas, Inc.
2000 Northfield Court,
Roswell, GA 30076-4908
U.S.A.
Tel: +770-475-1900
Fax +770-475-1717 44200002
March 2016
www.honeywellprocess.com © 2016 Honeywell International Inc.

You might also like