Ficha Tecnica Aires Bard
Ficha Tecnica Aires Bard
Ficha Tecnica Aires Bard
5
WALL-MOUNT
to 3 Ton 208V
TM
Air to
Conditioners
460V 60hz 6.41kw - 20.8kw Capacity
Air Conditioner W24A - W72A Models 200V - 415V 50hz
Specifications
W36AB-A Wall-Mount™
W36AB-A Wall-Mount™
1 1 EBARDHVAC.COM
E R WA SE R I E S WA L L -MOU N T TM
PAGE 1 OF 27 F O R M N O . S357 3 -1118 • SUPERSEDES NEW
Digit # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
W 6 0 A C - D 0 Z X P X X X X
SUPPLY OUTLET
PLACEHOLDER X - Standard
NEW! EXCLUSIVE *Non-Fiberglass Foil Faced Insulation: Environmentally friendly high “R”
value non-fiberglass insulation that is made with recycled denim and cotton materials used
with a FSK foil face that is both durable and cleanable.
Durable Cabinet Construction: Multiple cabinet construction options are available for
different outdoor conditions. Optional cabinet coatings may be ordered for extreme
outdoor environments. See cabinet finish and coatings section for further details.
Easy Filter Access: A separate filter door is provided for ease of filter access during routine
unit maintenance. 1” and 2” filters are available with a rating of up to MERV13. See filter
section for further details.
Field or Factory Installed Vents: Multiple ventilation options are available to provide
outdoor air for ventilation and/or energy savings. Ventilation options may be factory or
field installed. See vent section for further details.
Electric Strip Heat: Reliable, comfortable heater packages feature an automatic limit
and thermal cut-off safety control. Heater packages may be factory or field installed.
See optional electric heat section for further details.
Built-in Circuit Breakers: Standard on all electric heat versions of single (208/230 volt)
and three phase (208/230 volt) equipment. Toggle disconnects are standard on all
electric heat versions of three phase (460 volt) equipment.
Reliable, Easy-to-Use Controls: Easily accessible through left or right control panel locations.
A lockable hinged access cover to circuit protection is provided. Phase rotation monitor
is standard on all 3 phase models. Adjustable compressor on/off delay timer (CCM) with
diagnostic lights is standard on all models. Both right and left control panel locations
available. Electrical entrances provided through the back and side areas.
Green Fin Hydrophilic Evaporator Coil: Green fin stock enhances coil wettability to
help prevent mold growth, aids with condensate drainage, and provides a limited amount of
protection to corrosive particulates in the airstream.
*Balanced Climate™ Technology (patent pending): High latent capacity humidity & sound
reduction removes up to 35% more humidity than any other on the market with the use
of a 2 stage thermostat or controlling device. Bard Balanced ClimateTM innovation comes
standard on all models.
ECM Indoor Motor Technology: 5 speed dual shaft motor provides quiet airflow operation
when used with a twin blower assembly. Motor overload protection standard on all models.
Enclosed Condenser Motor: An enclosed casing condenser motor with ball bearings is used for
reliable operation and extended motor life. Enclosed condenser motors are standard on all
units.
High Efficiency Cooling: Scroll compressors for quiet, efficient cooling. Designed with
R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol
and 2010 EPA requirements. A liquid line filter-drier is used to protect the system from
moisture, and is standard on all units.
Durable Cabinet Construction: Multiple cabinet construction options are available for
different outdoor conditions. Optional cabinet coatings may be ordered for extreme
outdoor environments. See cabinet finish and coatings section for further details.
ECM Indoor Motor Technology: 5 speed dual shaft motor provides quiet airflow operation when
used with a twin blower assembly. Motor overload protection standard on all models.
Electric Strip Heat: Reliable, comfortable heater packages feature an automatic limit
and thermal cut-off safety control. Heater packages may be factory or field installed.
See optional electric heat section for further details.
Field or Factory Installed Vents: Multiple ventilation options are available to provide
outdoor air for ventilation and/or energy savings. Ventilation options may be factory or
field installed. See vent section for further details.
Green Fin Hydrophilic Evaporator Coil: Green fin stock enhances coil wettability to
help prevent mold growth, aids with condensate drainage, and provides a limited amount of
protection to corrosive particulates in the airstream.
Built-in Circuit Breakers: Standard on all electric heat versions of single (208/230 volt)
and three phase (208/230 volt) equipment. Toggle disconnects are standard on all
electric heat versions of three phase (460 volt) equipment.
Easy Filter Access: A separate filter door is provided for ease of filter access during routine
unit maintenance. 1” and 2” filters are available with a rating of up to MERV13. See filter
section for further details.
Reliable, Easy-to-Use Controls: Easily accessible through left or right control panel locations.
A lockable hinged access cover to circuit protection is provided. Phase rotation monitor
is standard on all 3 phase models. Adjustable compressor on/off delay timer (CCM) with
diagnostic lights is standard on all models. Control panel is located in the front of the unit
with electrical entrances on both sides and back.
*Balanced Climate™ Technology (patent pending): High latent capacity humidity & sound
reduction removes up to 35% more humidity than any other on the market with the use
of a 2 stage thermostat or controlling device. Bard Balanced ClimateTM innovation comes
standard on all models.
Enclosed Condenser Motor: An enclosed casing condenser motor with ball bearings is used for
reliable operation and extended motor life. Enclosed condenser motors are standard on all
units.
High Efficiency Cooling: Scroll compressors for quiet, efficient cooling. Designed with
R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol
and 2010 EPA requirements. A liquid line filter-drier is used to protect the system from
moisture, and is standard on all units.
Heating Operation:
The Bard WA Series products offer optional single or two stage heating operation using resistance heaters. Circuit breaker disconnect
protection is standard in all units equipped with electric heat.
Ventilation:
The Wall-Mount product provides the perfect platform to not only cool and heat an indoor area, but also provide a means of bringing outdoor
air into the building. By including ventilation in the Wall-Mount, expensive costs associated with additional outdoor air systems can be
avoided. The Bard WA Series products offer optional ventilation operation that brings outdoor air into the structure, and vents can be factory
or field installed. Ventilation can be used to bring in outdoor air for occupants, save energy by using outdoor air for free cooling, or positively
pressurize a structure. Exhaust air options allow room air to be vented outdoors when fresh air is being brought into the structure.
Note: The LAC kit also includes a freeze stat installed on the unit indoor evaporator coil. The freeze stat helps monitor the indoor evaporator
coil temperature and will cycle compressor operation when temperatures below freezing are indicated. Use of Balanced Climate or applications
where indoor airflow will be reduced require the use of the LAC kit to help maintain adequate evaporator coil temperatures.
Blower and Vent Only Speed: The WA series uses this speed when fan only (G) or ventilation operation (A) is used. See airflow performance chart for CFM
amount. If cooling and heating speed is adjusted from LO to MED or HI, the Blower and Vent Only speed will not change.
Balanced Climate Speed: The WA series uses this speed when the Balanced Climate option (Y1) or mechanical dehumidification option (D) is used. The Bal-
anced Climate speed reduces unit airflow by approximately 30% which increases moisture removal (latent capacity) during cooling operation. Units with the hot
gas reheat dehumidification option also use this speed to increase moisture removal when running in dehumidification mode. Unit capacity performance when
using Balanced Climate can be calculated using the -30% capacity multipler factor provided in the Cooling Application Data.
To use Balanced Climate, remove the jumper between Y1 and Y2 on the low voltage terminal strip. A 2 stage cooling thermostat is then used to control blower
airflow stages. Be sure to follow all guidelines provided in the installation manual. A controls kit that includes a low ambient control (LAC) must be used for
Balanced Climate Operation if ventilation options are to be used or cooling operation will occur below a 60° outdoor temperature. Balanced Climate can be used
for duct free and ducted applications below ESP total static shown in indoor airflow performance charts. Balanced Climate provides increased moisture removal
during the cooling cycle.
LO Speed (Default): The WA series uses this speed by default when using standard cooling (Y2) or heating operation (W1/W2). This speed is labeled as LO on the
speed selection terminal strip inside the unit control panel. All units ship with cooling and heating operation at LO cooling and heating speed, and provides the
optimal airflow amount for normal use. See airflow performance chart for CFM amount.
MED Speed (User Selectable): This speed is user selectable when using standard cooling (Y2) or heating operation (W1/W2). This speed is labeled as MED on
the speed selection terminal strip inside the unit control panel. The MED speed tap provides an increase in unit airflow per the airflow performance chart.
HI Speed (User Selectable): This speed is user selectable when using standard cooling (Y2) or heating operation (W1/W2). This speed is labeled as HI on the
speed selection terminal strip inside the unit control panel. The HI speed tap provides maximum unit airflow per the airflow performance chart.
Supply Duct Static: Supply duct static will include duct work connected to the unit supply opening, supply registers, filtration installed in the supply duct, or any
other device in the supply airstream that will restrict airflow. All ducts must be sealed to reduce duct air leakage, and flex duct work must not include restriction
due to installation. Duct static must be calculated by a HVAC professional and include all factors of the duct design.
Return Duct Static: Return duct static will include duct work connected to the unit return opening, return registers, filtration installed in the return duct, or any
other device in the return airstream that will restrict airflow. All ducts must be sealed to reduce duct air leakage, and flex duct work must not include restriction
due to installation.Duct static must be calculated by a HVAC professional and include all factors of the duct design.
Unit Filter Static: The WA series uses a unit filter installed before the indoor blower assembly that filters both indoor air from the room and outdoor air entering
through the ventilation device. When additional filtration is required (higher MERV rating), additional static will need to be added to the total external static
pressure (ESP). The following chart is to be used to estimate additional static pressure for a installed clean filter.
FILTER CODE FILTER MERV RATING FILTER STATIC INCHES WC. FILTRATION LEVEL
X MERV 2 0” WC Low Filtration, 1” Thickness Disposable Media.
W MERV 2 -.02” WC Low Filtration, 1” Thickness Permanent Media.
P MERV 8 .03” WC Average Filtration, 2” Thickness Pleated Disposable Media.
M MERV 11 .05” WC Above Average Filtration, 2” Thickness Pleated Disposable Media.
N MERV 13 .08” WC High Filtration, 2” Thickness Pleated Disposable Media.
Calculating Total External Static Pressure: Supply duct static, return duct static, unit filter static, and any other source of additional static pressure are added
together. Once this is calculated, the actual unit airflow amount can be reviewed by using the Indoor Airflow CFM charts provided.
Supply Duct Static + Return Duct Static + Filter Static + Additional External Static = Total External Static Pressure (ESP)
Non-Ducted Applications: Applications that do not include supply or return ducts inside the structure, use Bard supplied supply and return louvers, and do not
have additional sources of external static will typically reflect rated airflow amounts shown in the Indoor Airflow CFM charts. Additional filter static must still be
added as necessary to the rated airflow total external static pressure (ESP). Field supplied supply and return louvers must match Bard supplied supply and return
louvers to achieve shown in the Indoor Airflow CFM charts. Adjustment of 4-way deflection supply louver may effect unit supply airflow. See louver deflection and
throw characteristics provided in this document.
/////// Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
200V 220V 240V 380V 415V
NOMINAL
KW 3-PH 1-PH 3-PH 1-PH 3-PH 3-PH
WATTS WATTS WATTS WATTS WATTS WATTS
4
5 4201 5000 4095 4883
6 4167 5042
7 5641 6728
8 6722
9 7562
10 10000
12 8333 10083 9401 11213
15 12604
(1) Listed electric heaters are available for 230/208V units only.
(2) Listed electric heaters are available for 480V units only.
/////// Heater Packages - Field Kits for W24A to W36A Right-Hand Control Panel Units
• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed
• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models
/////// Heater Packages - Field Kits for W24L to W36L Left-Hand Control Panel Units
Air -D00 MODELS -E00 MODELS -F00 MODELS
Conditioner 240/220-1 230/200-3 415/380-3
Models Heater Model # KW Heater Model # KW Heater Model # KW
WMPD-01CL 0Z
W24LB N/A N/A N/A N/A
EHWH24B-C06L 05
WMPD-01CL 0Z
W36LB N/A N/A N/A N/A EHW3TA-C09L 7
EHW3TA-C15L 12
/////// Heater Packages - Field Kits for W42AC to W72AC Front Control Panel Units
• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed
• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models
FAD-BE2 W18AB/LB, W24AB/LB Barometric Intake Damper with Room Outdoor air intake damper that may be used to bring an adjustable
Exhaust amount of outdoor air into a structure. The damper opens during
A FAD-BE3 W30AB/LB, W36AB/LB
indoor blower operation and an exhaust damper provides barometric
FAD-BE5 W42AC, W48AC, W60AC, W72AC room pressure relief.
BOP-2 W24AB/LB No ventilation, provides best protection Insulated plates are installed over the vent intake and exhaust
against water, dirt, and debris infiltration. openings. When used, the plates provide a degree of protection from
B BOP-3 W30AB/LB, W36AB/LB
splashing water and dirt/debris entry into the unit.
BOPLATE-5 W42AC, W48AC, W60AC, W72AC
CRV-F2-* W24AB/LB Motorized Intake Damper with Room The CRV-F provides a simple means of bringing in outdoor air when a
Exhaust. Vent opens to user adjustable open modorized spring closed damper is required. Vent option provides up
CRV-F3-* W30AB/LB, W36AB/LB
position when energized. Vent is energized to 50% outdoor air intake. It also provides room pressure relief. Motor
M
when 24VAC is applied to the "A" terminal uses linkage to operate damper blades and springs closed when power
CRV-F5 W42AC, W48AC, W60AC, W72AC located on the unit low voltage terminal to the damper motor is removed. No intake hood is required for all
strip. models.
CRV-V2-* W24AB/LB Motorized Intake Damper with Room The CRV-V provides a control board with advanced options for bringing
Exhaust. Vent opens to user adjustable in outdoor air when a modorized spring closed damper is required.
CRV-V3-* W30AB/LB, W36AB/LB
minimum position when "A" terminal locat- Vent option provides up to 50% outdoor air intake. It also provides
V ed on the unit low voltage terminal strip is room pressure relief. Motor uses linkage to operate damper blades and
energized with 24VAC. 0-10VDC modulating springs closed when power to the damper motor is removed. Includes
CRV-V5 W42AC, W48AC, W60AC, W72AC
operation option. Room pre-purge option. solid state control board for multiple ventilation settings. No intake
hood is required for all models.
ECON-NC2-* W24AB/LB Motorized Intake Damper with Room Ex- The no controls economizer option is used where the controls con-
haust. Vent opens to user setting based on tractor will provide a field installed logic board and indoor/outdoor
ECON-NC3-* W30AB/LB, W36AB/LB
0-10VDC input. 10k outdoor sensor is in- sensors or other means to decide when conditions are favorable for
cluded with vent option. This vent does not free cooling. Vent option provides up to 100% outdoor air intake.
D
include solid state board or JADE controller It also provides room pressure relief. Motor uses linkage to operate
ECON-NC5 W42AC, W48AC, W60AC, W72AC to operate economizer functionality. damper blades and springs closed when power to the damper motor is
removed. 7" intake hood (included) required for ECON-NC2 and ECON-
NC3 options. No intake hood is required for ECON-NC5 option.
ECON-S2-* W24AB/LB Motorized Intake Damper with Room The economizer with enthalpy control is often used to provide free
Exhaust. JADE economizer control uses out- cooling for applications where humidity levels outdoors are relatively
door temperature and humidity to provide high, or indoor humidity levels need to be kept at a low amount. Vent
free cooling operation based on enthalpy option provides partial outdoor air intake based on outdoor temperature
S curve setting. Optional 0-10VDC input for and humidity. It also provides room pressure relief. Motor uses linkage
ECONS3-* W30AB/LB, W36AB/LB modulating ventilation control. Optional to operate damper blades and springs closed when power to the damp-
user selected minimum position when “A” er motor is removed. No intake hood is required.
terminal located on the unit low voltage
terminal strip is energized with 24VAC.
ECON-DB2-* W24AB/LB Motorized Intake Damper with Room The dry bulb economizer option is often used in areas with low outdoor
Exhaust. JADE economizer control uses humidity levels or applications where indoor humidity levels can be rel-
ECON-DB3-* W30AB/LB, W36AB/LB
outdoor temperature to provide free cooling atively high. Vent option provides up to 100% outdoor air intake based
operation based on user settings. Optional on outdoor temperature. It also provides room pressure relief. Motor
Y 0-10VDC input for modulating ventilation uses linkage to operate damper blades and springs closed when power
control. Optional user selected minimum to the damper motor is removed. 7" intake hood (included) required
ECON-DB5 W42AC, W48AC, W60AC, W72AC
position when "A" terminal located on the for ECON-DB2 and ECON-DB3 options. No intake hood is required for
unit low voltage terminal strip is energized ECON-DB5 option.
with 24VAC.
ECON-WD2-* W24AB/LB Motorized Intake Damper with Room The economizer with enthalpy control is often used to provide free
Exhaust. JADE economizer control uses out- cooling for applications where humidity levels outdoors are relatively
ECON-WD3-* W30AB/LB, W36AB/LB
door temperature and humidity to provide high, or indoor humidity levels need to be kept at a low amount. Vent
free cooling operation based on enthalpy option provides up to 100% outdoor air intake based on outdoor
Z curve setting. Optional 0-10VDC input for temperature and humidity. It also provides room pressure relief. Motor
modulating ventilation control. Optional uses linkage to operate damper blades and springs closed when power
ECON-WD5 W42AC, W48AC, W60AC, W72AC
user selected minimum position when "A" to the damper motor is removed. 7" intake hood (included) required
terminal located on the unit low voltage for ECON-DB2 and ECON-DB3 options. No intake hood is required for
terminal strip is energized with 24VAC. ECON-DB5 option.
“A” Vent Code Option – Standard Barometric Fresh Air Damper with Barometric Exhaust (FAD-BE)
The barometric fresh air damper with exhaust is an optional feature on all models, and can be ordered pre-
installed from Bard or may be field installed with the FAD-BE vent kit. Fresh air dampers are typically used when
a small amount of outdoor air is required in a room or structure when the indoor blower is on. The intake damper
opens when the indoor blower is operational and negative pressure in the vent area of the unit pulls the blade
open. When the blade is open, the damper allows outdoor air to be brought into the structure. Blade stops are
provided that allow for intake airflow adjustment. See FAD-BE airflow charts provided in this specification for
airflow amounts. Room air exhaust using room air pressure is provided with a separate assembly. This allows room
air to pass through the vent area and out of the unit. Blade stops allow for adjustment of exhaust air amounts.
Operation of the damper is dependent on room pressurization to open the exhaust blade and allow room air to
leave the structure.
The barometric fresh air damper without exhaust includes the following options:
• The damper opens when the indoor blower is operational. Fresh Air Damper Exhaust (FAD-BE only)
• The vent provides up to 25% of the total airflow rating of the unit.
• Adjustable blade pins allow different amounts of outside air to be introduced into the building and can be
easily locked closed if required.
• Adjustable room exhaust is provided through secondary exhaust damper assembly.
• Room pressurization is adjustable during indoor blower operation.
Economizer Assembly
“S” and “Z” Vent Code Option – Economizer with JADE Controls and Enthalpy Outdoor Sensor (ECON-S and ECON-WD)
The Economizer with JADE controls and enthalpy outdoor sensor is an optional feature on all models, and can be ordered pre-installed from Bard or may be field
installed with a vent kit. The “S” economizer option (ECON-S) is available for the W24 thru W36 models and provides up to 75% outdoor air intake without the
need for an intake hood. The “Z” economizer option (ECON-WD) is available for all unit models and provides 100% outdoor air intake. W18 thru W36 models
include 7” intake hood. Economizers are designed to provide free cooling when outdoor conditions are acceptable, and provide a small amount of ventilation
air if needed during non-economizer operation. This saves energy and reduces compressor run time extending the life of the cooling equipment components.
The ventilation options use the JADE economizer controller and an outdoor enthalpy (temperature and humidity) sensor to decide when outdoor conditions are
acceptable for free cooling operation. During free cooling economizer operation, the indoor blower will draw air through the economizer assembly mixing room
air and outdoor air to provide a standard leaving supply temperature. The damper blade is operated by a 24VAC actuator motor and blade linkage. See ECON-
WD airflow charts provided in this specification for airflow amounts. Air exhaust is provided that allows room air to pass through the vent area and out of the
unit. Room air pressure forces air through the exhaust opening. Exhaust damper linkage controls the exhaust air amount and air intake amount simultaneously.
Minimum vent position feature allows ventilation air to be brought into a room or structure if required during non-economizer use when the unit ventilation
terminal (A) is energized with 24VAC.
The economizer with JADE and enthalpy outdoor sensor includes the following options:
• Saves energy and reduces compressor-cooling runtime.
• The intake and exhaust damper opens to provide free cooling based on outdoor temperature and humidity. Enthalpy curves are pre-set and user selectable to
maximize free cooling runtime or minimize indoor humidity levels during free cooling.
• An economizer supply mixed air sensor provides a mixed air temperature of 53°F (11.6°C) by default.
• An enthalpy sensor is supplied with the vent option assembly to measure outdoor temperature.
• Spring closed motorized damper closes within 30 seconds when unit power is removed.
• When completely open, the vent provides outdoor air intake of the full airflow rating of the unit.
• Room exhaust is provided through the ventilation assembly reducing room pressure.
• Minimum vent position feature for outdoor air intake during non-economizer operation. Minimum position is used for meeting ANSI/ASHRAE Standard 62.1
air quality requirements or slight positive room pressurization for light industrial applications.
• 2-10VDC input for modulating ventilation when used with a CO2 sensor or other control device.
• Economizer may be used to provide cooling down to -40°F (-40°C) outdoor temperatures without compressor use.
• The JADE controller provides an easy to use LCD interface with user settings and diagnostics.
• Economizer assembly including damper seals and linkage meets 4cfm per ft2 leakage requirements.
“X” (FAD-NE2 and FAD-NE3) Barometric Damper Without Exhaust Vent Code Options
“A” (FAD-BE2 and FAD-BE3) Barometric Damper With Exhaust Vent Code Options
“D” (ECON-NC), “Y” (ECON-DB) and “Z” (ECON-WD) Vent Code Options
“Y” (ECON-DB), “Z” (ECON-WD), and “D” (ECON-NC) Vent Code Options
Aluminum Finish
Aluminum external cabinet finish option “A” units are constructed of ASTM B 209 grade .06” thickness panels A—Aluminum
with a stucco appearance.
“1” Code Option – Corrosion Resistance Coated Evaporator and Standard Condenser Coil
Option includes a Technicoat AA protective coating applied to the entire evaporator coil. After the evaporator coil is assembled, the entire coil is dipped in
the coating process. This provides the best resistance to corrosive agents, and the coating process ensures the core of the aluminum fin pack is covered.
Dehumidification units also include a dipped hot gas reheat coil. Standard condenser coil construction is a copper hairpin with aluminum fin design that is easy to
clean and maintain. This option provides the best indoor coil protection when harmful chemicals or agents may be present in the indoor airstream. The exterior and
interior unit cabinet is not coated with this option.
“3” Code Option – Corrosion Resistance Coated Evaporator and Corrosion Resistance Coated Condenser Coil
Option includes a Technicoat AA protective coating applied to the entire evaporator coil. After the evaporator coil is assembled, the entire coil is dipped in
the coating process. This provides the best resistance to corrosive agents, and the coating process ensures the core of the aluminum fin pack is covered.
Dehumidification units also include a dipped hot gas reheat coil. A Technicoat AA protective coating is applied to the entire condenser coil. After the condenser coil
is assembled, the entire coil is dipped in the coating process. This provides the best coil resistance to corrosive agents, and the coating process ensures the core of
the aluminum fin pack is covered. The exterior and interior unit cabinet is not coated with this option.
“4” Code Option – Corrosion Resistance Coated Evaporator and Condenser Coil, Condenser Section Only Coating
Option includes a Technicoat AA protective coating applied to the entire evaporator coil. After the evaporator coil is assembled, the entire coil is dipped in
the coating process. This provides the best resistance to corrosive agents, and the coating process ensures the core of the aluminum fin pack is covered.
Dehumidification units also include a dipped hot gas reheat coil. A Technicoat AA protective coating is applied to the entire condenser coil. After the condenser coil
is assembled, the entire coil is dipped in the coating process. This provides the best coil resistance to corrosive agents, and the coating process ensures the core of
the aluminum fin pack is covered. The interior of the lower unit condenser section is corrosion coated for additional protection including the unit base, compressor,
and condenser area copper tubing, filter/drier, and condenser fan.
“5” Code Option – Corrosion Resistance Coated Evaporator and Condenser Coil, Interior/Exterior Unit Coating
Option includes a Technicoat AA protective coating applied to the entire evaporator coil. After the evaporator coil is assembled, the entire coil is dipped in
the coating process. This provides the best resistance to corrosive agents, and the coating process ensures the core of the aluminum fin pack is covered.
Dehumidification units also include a dipped hot gas reheat coil. A Technicoat AA protective coating is applied to the entire condenser coil. After the condenser coil
is assembled, the entire coil is dipped in the coating process. This provides the best coil resistance to corrosive agents, and the coating process ensures the core of
the aluminum fin pack is covered. The entire exterior of the unit including the lower condenser section is coated along with all copper tubing, refrigeration, and air
moving components. The interior components of the unit are also coated for the best cabinet component corrosion protection available.
Special Properties:
• Anti-Odor
• Hydrophilic / Hydrophobic
• Anti-Corrosive
EXPOSURE CONDITIONS INCLUDE: Food Processing & Storage, Airports, Office Buildings, Hotels, Schools, Warehouses, Water Treatment, Breweries, Paper
Mills, Refineries, Power Plants, Meat Processing Industries, Automotive Industries and other locations near shorelines and salt water.
Contact your local Bard distributor or representative for a list of all chemicals and additional chemical resistance information.
Contact your local Bard distributor or representative for a list of all chemicals and additional chemical resistance information.
/////// Controls Options Definitions Including Switches, Sensors, Relays, and Start Kits
Unit controls include safety devices and accessories that can be used to customize the Bard Wall-Mount for uses in multiple applications. Controls can be supplied
from the factor or field installed. The below listing provides a description of the controls options available for the Bard WA Series unit.
Hi Pressure Control (HPC) - Factory installed in all units. The high pressure control provides a means of protecting the refrigeration circuit when high system
pressures occur. It is a auto-reset device that is connected to the Compressor Control Module. When activated, the compressor is disabled until pressures reach
an acceptable level. If activated twice in the same cooling call, compressor operation is locked out until the cooling call is interrupted.
Low Pressure Control (LPC) - Factory installed in all units. The low pressure control provides a means of protecting the refrigeration circuit when extremely
low system pressures occur. It is a auto-reset device that is connected to the Compressor Control Module. When activated, the compressor is disabled until
pressures reach an acceptable level.
Compressor Control Module (CCM) - Factory installed in all units. The compressor control module locks out compressor operation to protect the refrigeration
system based on signals from the hi and low pressure switches. It provides diagnostics to indicate when a refrigerant pressure event occurs, and also sends
a signal to the alarm relay. Low incoming unit power protection suspends compressor operation when incoming voltage is too low. Suspending compressor
operation avoids reverse scroll operation. The low voltage feature is adjustable or can be disables. An adjustable delay on break timer is provided. Delay on
make is 2 mins. plus 10% of delay on break setting.
Alarm Relay (ALR) - Factory or field installed option. The alarm relay provides a set of NO and NC pilot duty contacts that operate when the compressor control
module locks out compressor operation because of a high or low system refrigerant pressure event.
Low Ambient Control (LAC) - Factory or field installed option. The low ambient control pressure sensor is attached to the suction line of the system, and monitors
low side system pressure. Operation of the LAC occurs as outdoor temperatures drop below the 60°F. On/Off or modulating controls are used. On/Off LAC
operation cycles the condenser fan operation based on outdoor temperature. Modulating LAC operation is factory adjusted and slows the condenser fan speed
RPM based on outdoor temperature.
Crankcase Heater (CCH) - Field installed option only. The heater is a belly band that is installed around the base of the compressor that applies heat when the
refrigeration system is not operational. This heat is meant to prevent refrigerant oil migration when the unit is not running. Normal scroll compressor use does
not require the use of the CCH, and this option is only recommended for northern areas of the US and Canada with extreme cold operation. Field Install Option
Only.
Outdoor Thermostat (ODT) - Field installed option only. The outdoor thermostat measures outdoor temperatures and includes relay contacts (NO). The relay is
located on the outer control panel and the sensor bulb is mounted to the fan shroud in the outdoor condenser section. When wired into the cooling signal inside
the control panel, compressor operation can be disabled when temperatures are below the adjustable setting. Adjustment range is 0°F to 50°F.
PTCR Start Kit - Field installed option only. PTCR (Precision Temperature Coefficient Resistor) start kit includes the start device and wires needed for
installation. The device is located inside the unit control panel near the compressor capacitor and provides an increase in starting torque. The PTCR Start Kit is
not normally required when a clean, stable power source is available for the unit. The kit can only be used in 230 Volt single phase units.
Start Capacitor and Potential Relay Start Kit - Field installed option only. The kit includes a start capacitor and relay that is energized during startup of the
compressor. The capacitor, relay, and needed wires are provided in a metal enclosure that is field installed in the outdoor section attached to the back. The
Start Capacitor Kit is not normally required when a clean, stable power source is available for the unit. The kit can only be used in 230 Volt single phase units.
Start capacitor kit cannot be used with the PTCR start kit installed.
Dirty Filter Switch Indicator (DFS) - Factory or field installed option. The switch is adjustable and measures pressure drop across the unit filter surface. When
pressure drop is higher than the switch setting NO and NC contacts are provided to indicate the filter needs to be serviced.
Discharge Air Sensor - Factory or field installed as part of the DDC controls kit. The discharge air sensor provides a temperature reading of the supply air leaving
the unit. The sensor is a 10K OHM @ 77°F measuring device. It is installed in the supply airstream in the heater bracket.
Airflow Switch - Factory or field installed as part of the DDC controls kit. The airflow switch measures the pressure differential between the blower inlet and
outlet. It is located directly above the blower partition. Relay contacts (NO) are provided for V controls option that indicates the indoor blower assembly needs
to be serviced. The F controls option has indicator light only.
Compressor Current Sensor - Factory or field installed as part of the DDC controls kit. The compressor current sensor indicates when the compressor is
operational by measuring Amp draw. It is located inside the unit control panel. Relay contacts (NO) are provided to indicate the compressor is not operating.
/////// 24VAC Low Voltage Connections for Unit Control and Feedback
Bard Wall-Mount products provide 24VAC power to controllers and thermostats. They also are able to receive 24VAC signals from a controlling device. The V
controls option provides additional sensors for use with a field supplied DDC controls systems. The information below provides terminal designations and how
they are used in the Wall-Mount unit. More information on low voltage connections and operational sequences is provided in the unit installation manual.
Connection terminals listed below include both factory and field installed options (alarm relay, filter, and DDC kits).
RT terminal has jumper to R terminal. When jumper is removed, R and RT can be used with normally closed
RT All Units
contacts for fire/smoke detector for unit shutdown.
C All Units Ground/Common
1st Stage cooling input. Economizer stage when used. Balanced Climate stage when used. Remove jumper
Y1 All Units
between Y1 and Y2 for 2 stage blower operation.
Y2 All Units 2nd Stage cooling input. Compressor cooling stage when Econ or Balanced Climate is used.
W2 All Units 2nd State electric heat. Jumper between W1 and W2 must be removed for staged heat
A Vent option units only Ventilation option input. Calls for occupied vent air intake for CRV, ERV, ECON
E Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control
F Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Dirty Filter Press. Switch
J Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Alarm Relay
K Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, PTCR Start Kit
M Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Alarm Relay, PTCR Start Kit
Hi Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Alarm Relay, Discharge
V
temperature sensor, Indoor Blower Airflow Press. Switch, Compressor Current Sensor, Dirty Filter Pressure Switch
/////// Field Kit Controls Options Chart Including Switches, Sensors, Relays, and Start Kits
Field installed kits provide accessories that can be installed in the field. Required components, wires, enclosures, screws, and instructions that are
needed are provided within the kit.
CONTROL
KIT PART NO. UNITS USING KIT DESCRIPTION OF FIELD INSTALLED KIT
CODE
Low Ambient Control allows compressor cooling between 0°F and 50°F out-
E CMA-37 W24A, W24L
door temp. - modulating
W30A, W30L,W36A, W36L W42A, Low Ambient Control allows compressor cooling between 0°F and 50°F
E CMA-39
W48A, W60A, W72A outdoor temp. - fan cycling
W24A, W24L, W30A, W30L, W36A, PTCR Start Kit. Increases starting torque by 2 to 3x. 230V-60hz-1 phase (A
NA CMC-15
W36L voltage) only. Cannot be used in combination with SK start kit
PTCR Start Kit. Increases starting torque by 2 to 3x. 230V-60hz-1 phase (A
NA CMC-32 W42A, W48A, W60A, W72A
voltage) only. Cannot be used in combination with SK start kit
Start Capacitor and Potential Relay Start Kit. Increases starting torque by
W24A, W24L, W30A, W30L, W36A,
NA SK-111 9x. 230V-60hz-1 phase (A voltage) only. Cannot be used in combination with
W36L
CMC start kit
W24A, W24L, W30A, W30L, W36A, Outdoor Thermostat Kit used to disable compressor cooling below 50°F
NA CMA-14
W36L outdoor temp. Adjustable between 50° and 0°F
Outdoor Thermostat Kit used to disable compressor cooling below 50°F
NA CMA-43 W42A, W48A, W60A, W72A
outdoor temp. Adjustable between 50° and 0°F
W24A, W24L, W30A, W30L, W36A, Cooling Failure Alarm Relay Kit
NA CMC-34
W36L
NA CMC-35 W42A, W48A, W60A, W72A Cooling Failure Alarm Relay Kit
* CMA-40 and CMA-44 Kit does not include low ambient control. Low ambient control can be ordered separately either as field kit/factory installed.
CONTROL
KIT PART NO. UNITS USING KIT DESCRIPTION OF FIELD INSTALLED KIT
CODE
W24A, W24L, W30A, W30L, W36A, Dirty Filter Alarm Pressure Sensor Kit. Provides Normally Open Contacts to
NA CMC-31
W36L send an alarm signal to a thermostat or controller.
Dirty Filter Alarm Pressure Sensor Kit. Provides Normally Open Contacts to
NA CMC-33 W42A, W48A, W60A, W72A
send an alarm signal to a thermostat or controller.
DIMENSIONS OF W18-36A BASIC UNIT FOR ARCHITECTURAL & INSTALLATION REQUIREMENTS (NOMINAL)
WIDTH DEPTH HEIGHT SUPPLY RETURN
MODEL
(W) (D) (H) A B C D E F G I J K L M N O P Q R S T
W24AB 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 3.94 12.00 9.00
W30AB
38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 3.94 12.00 9.00
W36AB
D E
Built In O
Rain Hood
4° Pitch
W Heater .44
Access
Panel 2.13
Side Wall R
Electric A Mounting
Supply Air Opening
Heat
Brackets
C. Breaker/ (Built In)
Disconnect S
B
Access Panel 1.250 I
(Lockable) Top Rain
Flashing
Hood for ECON Shipping S
models only Location
Hood for ERV
5.88 1 Filter Access Panel models only Optional
Standard
C H Electrical Return Air Opening S
3" Entrances
F Ventilation Air flush vent
door for non-
ERV/CRV
Econ. S
models 7.00
Low Voltage K
L P
G Condenser Electrical Cond. J M
Air Outlet Entrance Air S
High Voltage Inlet
Electrical
.375 Entrance T
TYP.
Drain Bottom Installation
Front View Side View Back View Bracket
MIS-3796 B
DIMENSIONS OF W18-36L BASIC UNIT FOR ARCHITECTURAL & INSTALLATION REQUIREMENTS (NOMINAL)
WIDTH DEPTH HEIGHT SUPPLY RETURN
MODEL
(W) (D) (H) A B C B E F G I J K L M N O P Q R S T
W24LB 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 3.94 12.00 9.00
W30LB
38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 3.94 12.00 9.00
W36LB
Built In Electric
E Rain Hood Heat Heater
O 4° Pitch Access
.44 .375 Panel
D W
TYP. C. Breaker/
2.13 Disconnect
R Access Panel
Side Wall (Lockable)
Supply Air Opening Mounting A
Brackets Standard flush
S (Built In) vent door for
B non-ERV/CRV
Econ. models
1.250
I
Top Rain
Flashing Hood for
S Shipping ECON models
Location only
S H
7.000
L K
Hood for
M Cond. ERV models
J Air only
Condenser G
S P
Inlet Low Voltage Air Outlet
Electrical
Entrance
T
High Voltage
Electrical
Drain Bottom Back View N Side View Entrance Front View
Installation Q MIS-3737 B
Bracket
DIMENSIONS OF W42AC-72AC BASIC UNIT FOR ARCHITECTURAL & INSTALLATION REQUIREMENTS (NOMINAL)
WIDTH DEPTH HEIGHT SUPPLY RETURN
MODEL
(W) (D) (H) A B C B E F G I J K L M N O R S T
W42AC
42 25.52 84.88 9.88 29.88 15.88 29.88 43.88 12.63 39.06 30 53.75 26.94 55.59 52.59 8.82 43 1.438 16 1.88
W48AC
W60AC
42 25.52 93.00 9.88 29.88 15.88 29.88 43.88 12.63 45 30 59.75 35.06 61.72 58.72 8.82 43 1.438 16 10.00
W72AC
Drain T
N MIS-3978 B
WMICF2-* W24A, W24L Provides vibration isolation for reduced sound transmission through wall
WMICF3-* W30A, W30L,W36A, W36L Provides vibration isolation for reduced sound transmission through wall
WMICF5-* W42A, W48A,W60A, W72A Provides vibration isolation for reduced sound transmission through wall
Install to use with existing 2, 3, or 5 ton wall openings. Wall openings must provide
WWC3-* W30A, W30L, W36A, W36L sufficient airflow. Follow all instructions in curb and unit manual including clearances to
combustibles and maximum duct static pressure.
Install to use with existing 3 and 5 ton wall openings. Wall openings must provide sufficient
WWC5-* W42A, W48A, W60A, W72A airflow. Follow all instructions in curb and unit manual including clearances to combustibles
and maximum duct static pressure.
* Color Option
8403-089 1 Heat/1 Cool Temp. Settings per Day 4, 2, 1, 0 Programs per Week 7, 5-2, 5-1-1 or Nonprogrammable
8403-090 2 Heat/2 Cool Temp. Settings per Day 4, 2, 1, 0 Programs per Week 7, 5-2, 5-1-1 or Nonprogrammable
8403-095 2 Heat/1 Cool Temp. Settings per Day 4, 2, 1, 0 Programs per Week 7, 5-2, 5-1-1 or Nonprogrammable
THERMOSTAT
SIZE DESCRIPTION
COVER*
(Inside) 5-1/16" H x 6-1/16" W
8405-003 Clear acrylic with ventilation. Fits all thermostats except 8403-060
(Outside) 6-1/2" H x 7-1/2" W x 2-15/16" D
(Inside) 5-7/8" H x 8-3/8" W
8405-005 Clear acrylic with ventilation. Fits all thermostats.
(Outside) 7-1/4" H x 9-3/4" W x 3-3/8" D
(Inside) 5-1/16" H x 6-1/16" W
8405-006 Clear acrylic with ventilation. Fits all thermostats except 8403-060
(Outside) 6-3/8" H x 7-3/8" W x 2-7/8" D
* Thermostat covers include ventilation, but may effect temperature control reaction time. If security control lockout is needed, the
8403-060 thermostat provides input control lockout features.
Bard Manufacturing Company, Inc. Due to our continuous product improvement policy,
1914 Randolph Dr., Bryan, OH 43506 all specifications subject to change without notice.
419-636-1194
www.bardhvac.com
11 E E R WA S E R I E S WA L L - M O U N TTM PAGE 37 O F 37 F O R M N O . S35 81- 032 3 • SUPERSEDES 0823