Synco - Web Server OZW772-V12.0
Synco - Web Server OZW772-V12.0
5 701
Web server OZW772.. allows for remote plant control and monitoring via the
web and Smartphone App.
Four versions of the web server OZW772.. are available: To connect 1, 4, 16,
or 250 Synco devices from product ranges Synco 700, room controllers
RXB/RXL, RDG/RDF/RDU room thermostats, and the QAX9… Synco living
central apartment units.
Operate web browser via PC/laptop or Smartphone.
Operation via Smartphone App (iPhone and Android)
Operation via the Synco IC Internet portal with auxiliary functions
Operation and monitoring of KNX S-Mode devices
(Lighting, blinds, energy and volume meters, etc.)
Visualize the plants in the web browser based on standard plant diagrams
and customized plant web pages.
Gateway for remote operation of the M-bus web server WTV676-HB6035
via Synco IC
Display fault messages in the web browser.
Send fault messages to a maximum of 4 e-mail recipients.
Periodic sending of system reports to a maximum of 4 e-mail recipients.
Consumption data recording, display, and sending to 2 e-mail recipients
or to the FTP server
Create trends, trend graphs and send trend data to 2 e-mail recipients
or to the FTP server
CE1N5701en
2022-05-10 Smart Infrastructure
Function "Energy indicator" for monitoring data points
for energy-technical limit values, so-called “Green limits", and sending
them to 2 e-mail recipients
Web services for external applications via Web API
(Web Application Programming Interface)
Encrypted with https and TLS V1.3 for e-mails (all connections).
ACS790 functionality.
Secure tunnel connection for ACS and ETS via Synco IC
Time sync via NTP network time server
Use
Functions
Commissioning Commissioning using a PC/laptop via web browser and as an option with ACS.
ETS (Version 4 or 5) is used to configure KNX S-Mode components.
Access via Synco IC Siemens offers with the Climatix IC / Synco IC Internet portal simple and secure
access to web servers (available as of web server version 5.2).
Benefits Simple and fast set up of access via the Internet – neither a fixed IP address,
nor forwarding of a dynamic IP address, nor port forwarding (NAT/PAT) is re-
quired
Synco IC provides additional functions:
- Manage one or multiple plants
- Central user management
- Display of plant overview, state of Energy indicators, and alarms
- Plant functional scope can be set for various plant roles
- Logging fault messages as common faults
- Send alarm notifications per e-mail
- Secured communications through encryption (https)
2 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Access in Synco IC via Web server OZW772.. can also be used as a gateway for remote operation of the
OZW gateway M-bus web server WTV676-HB6035 in Synco IC. Before accessing the M-bus web
server, you must register in Synco IC and configure and activate the OZW gate-
way. Once the OZW gateway is activated, you can no longer access the OZW web
page via Synco IC.
Benefits Remote operation of the M-bus web server anywhere at any time
Central management of multiple plants (M-bus web server and OZW) over a
common account in Synco IC
Direct access to the web view of the M-bus web server and OZW over Synco IC
Direct access to the web server is possible via USB or Ethernet (without Synco IC).
Access without
A direct connection in parallel to the Synco IC Internet portal is possible.
Synco IC Internet portal
(direct connection)
Direct Internet access A connection (e.g. DSL router) is required to connect directly via the Internet. The
(Synco IC) web server is not suitable for connecting directly to the Internet since it does not
have a firewall. A firewall is normally a component of the DSL router.
Port forwarding must be configured on the router to connect directly to the Internet.
We recommend against this, since this opens up the firewall.
For security reasons (data protection), we recommend using the Synco IC portal.
The secure tunnel connection used with the Synco IC portal is more secure than a
direct connection.
Set up a VPN connection as a secure alternative.
Web user interface The web server user interface is the same as when using the
Synco IC Internet portal and when connected directly to Synco IC also includes ad-
ditional functions and settings.
3 / 26
In the web server user interface, the user symbol and user name are in place of
the Synco IC portal symbol .
4 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
User interface portal
Synco IC
Click the symbol to open the web server user interface under a new tab and is
then the same as the view under a direct connection.
The Synco IC portal symbol and e-mail address is displayed in place of the user
symbol and user name.
5 / 26
Secondary navigation The secondary navigation (menu tree) allows users to select devices and operating
pages. As of OZW version 5.0, the KNX pages defined in ETS are displayed here
as well.
Display The display range displays content corresponding to the selected primary and sec-
ondary navigation.
Plant state The display indicates no fault or the most serious plant fault
depending on plant state.
Faults
Fault sources The web server recognizes failures and fault signals from KNX devices contained
in the device list. Own faults also are recognized.
Fault display, The LED signals a fault on the web server . LED blinks to indicate that a fault is
fault acknowledgement unacknowledged. The LED continues to be lit for as long as the fault is pending
after the fault is acknowledged with the button via web operation or ACS. (See
page 10 for LED displays and operating buttons).
Fault status message Fault status messages can be sent as an e-mail to as many as 4 e-mail recipients
and/or via a service provider to SMS recipients. You can set the fault priority for
each e-mail recipient (urgent/all). Each receiver has a "Time switch with calendar"
to program three sending times per day and holidays/special days.
Common fault On the Synco IC Internet portal, faults are logged as common faults. The Synco IC
portal sends alarm notifications to the defined e-mail addresses in the event of a
common fault.
6 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
System report
System messages The web server generates system reports and periodically sends the system oper-
ating state to e-mail recipients. Messages are sent as per the set time (hh:mm),
message cycle interval (1...255 days), and priority (urgent/non-urgent).
Connection test Press the button on the web server to send a system report to all defined e-mail
recipients regardless of fault priority.
History The last 500 fault events, fault messages and system reports are entered in the
web server's circular message buffer. The event or history data can be read via
web browser.
Time The web server has a system clock with adjustable time zone and daylight saving/
standard time changeover. As clock time master, it can send the set system time
(date and time) to KNX devices (clock time slave).
For the system clock, the NTP network time server can perform the time synchroni-
zation and, if used as a time clock master, forward the data to all KNX devices
(time clock slaves).
A system definition update and the firmware update requires one simple action via
the web browser.
Operator actions on the web server are required for the factory update. Procedures
are communicated when a factory update is issued.
ACS790 The web server is compatible with the service and operating software ACS790 ver-
sion 10.00 and higher.
Secured connection via On web servers as of V7.0, you can establish a secure connection to the web
Synco IC server with the ACS790 and the "Remote Tool Access" software via Synco IC por-
tal.
7 / 26
Example
Plant web pages for
heating plant
Example
Plant web pages for
HVAC and lighting, blinds
8 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Download You can download web-capable plant diagrams from the HIT online platform for
plant diagrams standard applications on Synco 700 devices, room controllers RXB/ RXL, and
room thermostats RDG/RDF/RDU.
Create own plant web You can freely design plant web pages. As a hybrid form, you can also modify and
pages extend downloaded plant diagrams.
Web page elements Users can also embed additional data in a plant diagram such as energy values
(version 5.0) or links to plant, function and maintenance descriptions or data
sheets. Moreover, users can integrate external links allowing, for example, for di-
rect browsing multiple plants. Users can embed current webcam images in a plant
diagram.
KNX S-Mode Integration of KNX S-Mode data points permits central control of heating, ventila-
tion, air conditioning, and electrical installations.
Data points recording by OZW can be used, for example, for trending, to depict the
plant diagram or reused for thermal or electrical energy consumption.
Number of S-Mode data Version OZW772.01 supports 7 standard data points for system time and alarm
points info functions.
For version OZW772.04/16/250, the following of data points can also be integrated:
Data point sub-types No.
1 bit value 100
2 bit switching controlled 5
1 byte value 40
1 byte scene 5
2 byte value 40
4 byte value display 40
Amount 230
KNX interfaces The web server OZW772.. also assumes the KNX/IP interface, (KNXnet/IP), using
its Ethernet interface.
Separate devices to connect the ETS to the KNX bus via Ethernet are no longer
necessary.
Group monitoring Web server OZW772… supports the ETS diagnostic function "Group Monitoring"
as of version 6.0.
Secure connection via You can establish a secure connection to web server as of version 7.0 using ETS
Synco IC and the "Remote Tool Access" software via the Synco IC.
9 / 26
Trend channels 5 trend channels are available: Each trend channel can include up to 100 data
points. The trend channel can be labeled using a plain text name.
Sample rate The sample rate can be created individually for each trend channel. Sample rates
from 1 second to 25 hours are available.
The shortest possible sample rate over all 5 trend channels is 1 data point per sec-
ond.
Trend period Memory determines the possible trend period of a trend channel. The trend period
varies with the number of selected data points and their sample rate.
Examples for various trend channels:
Interval Data points Trend period
Channel 1 Channel 2…5
1 sec 1 14 days 1.8 days
5 sec 5 30 days 4.3 days
1 min 10 210 days 30 days
15 min 100 371 days 53 days
Memory that is 7 times greater is available in trend channel 1 for long-term trending
with a lot of data points, or short sample intervals.
Synchronization Trends are synchronized to simply the evaluation of trend data. The various query
intervals for the trends are set up on one interval grid.
Operation A web browser or the ACS tool creates and manages trend functions.
Data query per web The trend data can be downloaded for each channel using a web browser and
browser viewed in a spreadsheet program or text editor. The calendar function permits limit-
ing the trend data to a desired time period within the trend.
Users can access the web server either directly or remotely via Synco IC.
10 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Trend graph The data for a trend channel can be graphically displayed on the web user inter-
face. The function is available for OZW772.. as of version 6.0.
Data transmission per Up to 2 e-mail recipients can be defined for the trend data.
e-mail Each trend channel can send its data to one or both e-mail recipients. The send in-
terval can be set individually for each trend.
Import/Export Trend definitions can be imported to the web server or exported from the web
server.
11 / 26
OZW772.. as of version Energy and volume meters that use KNX data points are supported with the inte-
5.0 gration of KNX S-Mode as of web server version 5.0.
The meter is connected directly or via KNX adapter to the KNX bus and transmits
its data as per the configuration made in ETS.
QAX / Synco 700 Every 4 hours, central apartment unit QAX9… receives
raw data via KNX radio.
Synco 700 controllers generate the meter data via pulse inputs as per
the configured values.
Consumption data can be viewed on individual QAX central units or Synco
controllers using the associated menus.
Web server, The web server offers comfortable access to consumption data:
local or remote Web browser operation users to navigate to the consumption data of the associ-
ated devices.
Easier still: Or a consumption data file can be downloaded from the web server.
The file contains a list of consumption data for all QAX units (apartment units)
and Synco controllers.
Users can access the web server either directly or remotely via Synco IC.
Web server, e-mail Consumption data can be sent periodically (set up via web server) to
max 2 e-mail recipients (e.g. billing company).
12 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Function The "Energy indicator" function is available in web server OZW772.. as of version
"Energy indicator" 4.0. The following devices are supported:
Synco 700: RMU7x0B, RMH760B, RMK770 (as of version 2.0),
RMS705B,
RMB795B
Synco living: Central apartment unit QAX903, QAX913, QAX910
(as of version 3.0)
Room controllers: RXB2x, RXL2x, RXB3x, RXL3x
Room thermostats: RDF301, RDU341, RDGx00KN
The web server uses the "Energy indicator" function to read selected data point
values from the bus devices and to compare the values to energy-related limit val-
ues, or so-called "Green limits".
The data points are also monitored for adherence to the "Green limits".
As a result, the "Energy indicator" is displayed in the form of a tree leaf.
Note The "Green limits" are used only together with the "Energy indicator" function. They
do not represent process or safety limit values which trigger e.g. fault messages or
turn off the plant in the event of limit violations.
Web server, e-mail The "Energy indicator" can send its information periodically (adjustable via web
server) to a maximum of 2 e-mail recipients.
Tree leaf as
"Energy indicator"
Green leaf "Green leaf" Green tree leaf, leaf pointing up.
The "Green leaf" symbol indicates that a data point value has not exceeded
its "Green limit", i.e. the value is within a "green" range in terms of
energy consumption.
Orange leaf "Orange leaf" Orange tree leaf, leaf pointing down.
The "Orange leaf" symbol indicates that a data point value has exceeded its
"Green limit", i.e. the value is outside a "green" range in terms of energy con-
sumption.
Standard EN 15232 The "Energy indicator" function is based on standard EN 15232 "Energy efficiency
in buildings".
Example: "Energy indi- Web page with "Energy indicator" function; example with data points from "Room
cator" web page func- 1" and open dialog box to set data point value "Comfort heating setpoint" and its
tion "Green limit" (for "Room 1").
13 / 26
If "Home Control IC” App is installed on a smartphone, the app accesses, using the
web services, via web API, data points for devices on the KNX network (Communi-
cation connection for smartphone, see page 14).
FTP server Trend and consumption data can be regularly sent to a FTP server.
The interval can be adjusted.
The following transmission protocols are supported:
Type summary
When ordering, please specify the name and product number. Example:
Web server OZW772.16
The web server is delivered in a cardboard box.
The following is included in the package:
Mounting instructions M5701xx (multilingual).
Package insert with activation key for portal access.
Power cable, power supply AC 230 V.
Ethernet cable.
USB cable.
2 cable ties.
14 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Equipment combinations
The following Synco devices can be connected to the web server OZW772..
Synco range
Synco devices Data sheet no.
Synco 700 Universal controllers RMU7x0, RMU7x0B N3144, N3150
Heating controllers RMH760, RMH760B N3131, N3133
Boiler sequence controllers RMK770, RMK770 V2 N3132
Central control units RMB795, RMB795B N3121, N3122
Switching & monitoring units RMS705, RMS705B N3123, N3124
Bus operator unit RMZ792 N3113
Room unit QAW740 N1633
Central communication unit OZW771, OZW775 N3117, N5663
Product documentation
15 / 26
Number of browsers Any number of browsers can be used simultaneously. The maximum data through-
put rate is distributed among the browsers. Operation slows down as the number of
users increases accordingly.
Operation, monitoring, Communication connections for local commissioning (USB) and remote operation,
alarming remote monitoring and alarming via Ethernet.
The web server is not suited for direct connection to the Internet, but rather must
be connected via a firewall. A router typically includes a firewall.
Web server OZW772.. can also be used as a gateway for remote operation of
the M-bus web server WTV676-HB6035.
Once the gateway is active, you can access the web page of the M-bus web server
via Synco IC. You can no longer access the OZW web server once the gateway is
activated.
The web page of the OZW web server displays if the gateway is inactive.
16 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Interfaces
USB The USB interface directly connects the PC/laptop on site. The required USB cable
type A – type Mini-B is delivered with the device.
Ethernet The router/network is connected to the Ethernet RJ45 plug. The Ethernet interface
features Auto-MDI(X) for crossed and non-crossed Ethernet cables. An Ethernet
category 5 cable is supplied.
KNX The KNX bus is connected to the CE and CE connection terminals labeled
"KNX". See data sheet N3127 for more information on the KNX bus.
Logs
Web operation Web operation via Synco IC takes place through an HTTPS encrypted connection
(Port 443) via TCP/IP. The required certificate is accredited.
Web operation without Synco IC takes place through an HTTPS encrypted con-
nection (Port 443) via TCP/IP. The required certificate is not accredited. The self
signed certificate by Siemens is saved on the web server for a period of 20 years
and cannot be changed.
In addition, an HTTP (Port 80) connection is supported. Port 80 is disabled as de-
livered. The access via http is not secured. The user is responsible for enabling
Port 80.
A RNDIS driver on the PC/laptop is required for USB communication. The RNDIS
driver is already included in the Windows operating systems for web server as of
version 7.0.
Send e-mail Fault messages, consumption data, energy indicator reports, and trend files are
sent in an e-mail via SMTP. The e-mail is encrypted using TLS V1.3 if supported
by the mail server.
DHCP Client The web server can take its network configuration as client from a DHCP server or
be manually configured.
17 / 26
Basic design The web server consists of a housing lower section containing printed circuit
boards with interfaces. The upper housing section covers the printed circuit boards.
The upper housing section contains the LED displays and one operating button.
The connection terminals and additional display and operating elements are lo-
cated under the removable cover for the upper housing section. All display and op-
erating elements are labeled.
LED indication
1 (red/green/orange) Off No power
Steady red Web server starts operating system.
Flashing red Web server starts application.
Steady green Web server operational, "Energy indicator" = "Green leaf"
Orange on Web server operational, "Energy indicator" = "Orange leaf"
Flashing green Web server operational, connected to Synco IC
green / orange (LED 0.8 s on, 0.2 s off)
2 (green) Off No bus power.
On KNX operational.
Flashing Communication on KNX.
3 (LED) No function.
4 Fault (red) Off No fault (normal operating state).
On Acknowledged fault.
Flashing Unacknowledged fault.
5 Addressing mode (red) Off KNX addressing mode off.
On KNX addressing mode on.
18 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Operating buttons
6 Remote button Short (< 2 s) Acknowledges fault message.
Long (> 6 s) Send the system report to the fault e-mail recipient
(not to consumption data, and "Energy indicator" and trend
data recipient).
7 Addressing mode Short (< 2 s) Press once: KNX addressing mode on
Press again: KNX addressing mode off.
Button combinations Long (> 6 s) Simultaneously press and
and restores default factory settings.
All configuration data and settings are reset.
The device list, plant diagrams, and unsent
messages are deleted. History data
is not deleted.
Notes
Mounting The Web server can be mounted in a panel, distribution box, or on a wall. Include
space for wiring when planning. Make sure service can easily access the unit and
the unit is ventilated properly.
Standard mounting On standard rail TH 35-7.5.
Wall mounting Attached with 2 screws.
Mounting position Horizontal or vertical.
Mounting and dimensions See "Dimensions".
Install
Important notes Observe the following when installing:
Run fuses, switches and wiring as per local regulations for electrical installa-
tions.
We do not recommend plant monitoring via USB interface in environments with
strong electromagnetic interference (e.g. in industrial environments with electri-
cal welding equipment).
See "Technical data" for electromagnetic compatibility.
Wiring The operating voltage, USB and Ethernet plugs are located on the upper part of
the housing.
The terminals on the device for the KNX bus are located under the removable
cover.
Connection terminals The connection terminals are designed for wire diameters of min. 0.5 mm or cross-
sections of 0.25...1.5 mm2 or stranded wire cross-sections of 0.25...1.0 mm2.
19 / 26
Router A connection (e.g. DSL router) is required to connect directly via the Internet. The
web server is not suitable for connecting directly to the Internet since it does not
have a firewall. A firewall is normally a component of the DSL router.
User groups User accounts are created and assigned to specific user groups for customized
user operation.
20 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Maintenance The OZW772.. web server is maintenance free (no battery changes, no fuses).
Use only a dry towel to clean the housing.
Repair The OZW772.. web server cannot be repaired on site. If faulty, return to the Repair
Center at the relevant Regional Company.
Disposal
The device is considered electrical and electronic equipment for disposal in terms
of the applicable European Directive and may not be disposed of as domestic
garbage.
Use only proper channels to dispose the device.
Comply with all local, applicable laws and regulations.
21 / 26
22 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Ambient conditions Operation IEC/EN 60721-3-3
Climatic conditions Class 3K23
Temperature (housing with electronics) - 5 …+50 °C
Humidity 5…95% r. h. (non-condensing)
Mechanical conditions Class 3M11
Transport IEC/EN 60721-3-2
Climatic conditions Class 2K12
Temperature -40...70 °C
Humidity < 95% r.h.
Mechanical conditions Class 2M4
Materials and colors Upper housing section PC + ASA, RAL 7035 (light-gray)
Lower housing section PC + ASA, RAL 5014 (dove blue).
23 / 26
Connection diagram
Pin assignment
DC 24 V plug 1 DC 24 V (+)
2 GND (–)
24 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10
Dimensions
25 / 26
26 / 26
Siemens Web Server OZW772.. V12.0 CE1N5701en
Smart Infrastructure 2022-05-10