Parallel Operation of The Transformers
Parallel Operation of The Transformers
Transformers connected must have the same polarity and for three phase, they need to have the same phase angle and phase
sequence.
Impedance (%) should be equal in magnitude and should have the X/R ratio to avoid circulating current.
If the kVA ratings are different, the equivalent impedance should be inversely proportional to individual kVA rating.
For large loads, it may be impractical or uneconomical to have a single large transformer so that many small transformers are
paralleled to meet the load demand.
By operating the transformers of standard size in parallel at the substations, the spare capacity of the substation can be reduced.
There is always a scope of future expansion of a substation to supply a load of capacity greater than that of the transformers already
installed. Hence, in future by connecting a new transformer in parallel with existing transformers, the total capacity of the substation
can be increased.
If a transformer is damaged in a system of transformers connected in parallel and is removed for repair and maintenance, then there
is no interruption of power supply for essential services.
Suppose E1 > E2, then due to the voltage difference between the secondaries of the two Transformers there will be a circulating
current of Ic flowing from the first Transformer to the second Transformer. The circulating causes over heating and hence, it should be
low as possible.
Let’s say that the Z1 > Z2, then I1 < I2 and vice-versa.