Tank 14m x12 M Height
Tank 14m x12 M Height
Tank 14m x12 M Height
PROJECT NAME
Jubail IGH Carbon Capture and Steam
Power
Generation
Jubail, KSA
DESIGN ENGINEER
AIC STEEL
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Comments
Comments
Shell
Shell Course 1 requires impact testing per the standard.
Joint efficiency for all shell courses = 100%. X-rays are required. Quantity of x-rays
shall be per 8.1.2.
Shell Course 2 requires impact testing per the standard.
Shell Course 3 requires impact testing per the standard.
Shell Course 4 requires impact testing per the standard.
Shell Course 5 requires impact testing per the standard.
Bottom/Compression Ring
Low liquid level is adequate to resist uplift on bottom due to vacuum.
Annular ring thickness exceeds 6.0028mm. Impact testing is required per 4.2.9.
Roof
Roof is single lap welded
Tank is anchored for the internal pressure
Roof manway and nozzles shall meet the requirements of F.2.4.
Tank is to be pressure tested per F.8.3.
Wind
Anchorage of the tank for wind is required
Per 5.2.1 (k)(1)(b), wind loads are based on ASCE 7-10.
Shell External Pressure
The design external pressure exceeds the value from V.8.1.2. Shell must be stiffened.
The minimum required shell thickness from V.8.1.3 exceeds tmin. Shell must be
stiffened.
Hsafe = 7.11 and 1 stiffeners are required.
Shell Stiffener
Available section modulus for Wind Girder (215.12) is greater than required section
modulus (36.14).
Seismic
Tank is mechanically anchored. The tank shall be shimmed and grouted per E.7.1.
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Design Data
Tank Diameter .......................................... 14,000 mm (Inside)
Exposure ........................................... C
Seismic:
Site Class ......................................... D
Importance Factor .................................. 1.50
Use Group .......................................... III
Ss Value ........................................... 10.00 %
Page 1 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Corrosion Allowance:
Bottom ............................................. 3.0000 mm
Annular Ring ....................................... 3.0000 mm
Shell Courses 1 - 1 ................................ 3.0000 mm
Courses 2 - 2 ................................ 3.0000 mm
Courses 3 - 5 ................................ 3.0000 mm
Roof ............................................... 3.0000 mm
Total for web
None on flange
Compression Ring ................................... 3.0000 mm
Wind Girder/External Pressure Rings ................ 3.0000 mm
Anchor Bolts ....................................... 3.0000 mm
Anchor Chairs ...................................... 3.0000 mm
Page 2 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Summary
Total Weight of Tank: 141,799 kg
Total Operating Weight: 1,976,595 kg
Total Testing Weight: 1,976,595 kg
Bottom
Bottom with Annular Plate Sloped Up across entire tank diameter (requires anchoring)
1.0000 in 100:
9.0000 mm (A36) PL (weight: 7,989 kg)
Annular Plate:
9.0000 mm (A36) PL (weight: 3,135 kg)
Outside projection = 80.0000 mm
Total width: 1000.0000 mm
Annular ring thickness exceeds 6.0028mm. Impact testing is required per 4.2.9.
Shell
Shell Course 01: 10.0000 mm (A36) PL x 2480.0000 mm wide (weight: 8,562 kg)
Shell Course 1 requires impact testing per the standard.
Shell Course 02: 8.0000 mm (A36) PL x 2480.0000 mm wide (weight: 6,849 kg)
Shell Course 2 requires impact testing per the standard.
Shell Course 03: 8.0000 mm (A36) PL x 2480.0000 mm wide (weight: 6,849 kg)
Shell Course 3 requires impact testing per the standard.
Shell Course 04: 8.0000 mm (A36) PL x 1980.0000 mm wide (weight: 5,468 kg)
Shell Course 4 requires impact testing per the standard.
Shell Course 05: 8.0000 mm (A36) PL x 2579.6000 mm wide (weight: 7,124 kg)
Shell Course 5 requires impact testing per the standard.
Page 3 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Compression Ring
Vacuum Ring
Distance from bottom of tank to stiffener = 6.7051 m
Member thickness (A) = 15.0000 mm B
Horizontal leg (B) = 150.0000 mm
Vertical leg (C) = 150.0000 mm
Material grade: A36 C
Minimum fillet weld size = 6.0000 mm A
Anchor Bolt
Anchor Chairs
Quantity: 16
Material: A36
Total Anchor Chair Weight: 744 kg
250.0000 mm
30.0000 mm
150.0000 mm 300.0000 mm
30.0000 mm
Page 4 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Bottom Design
Bottom with Annular Plate Sloped Up across entire tank diameter (requires anchoring) 1.0000 in 100
Material Grade: A36
Thickness (tb): 9.0000 mm
Corrosion Allowance (CA): 3.0000 mm
Minimum thickness per 5.4.1 = 6.0000 mm
Minimum thickness + corrosion allowance = 6.0000 + 3.0000 = 9.0000 mm
Page 5 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Annular Plate
Material Grade: A36
Thickness (tb): 9.0000 mm
Corrosion Allowance (CA): 3.0000 mm
Minimum required outside projection per 5.4.2 = 50.0000 mm
Actual outside projection (p) = 80.0000 mm
Page 6 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Design
Per 5.6.3.2
td = 4.9_(H_-_0.3)D_G + CA where
Sd Diameter (D) = 14.0000 m
Specific Gravity (G) = 1.0000
tt = 4.9_(H_-_0.3)D
St
Shell Course 01
Material Grade: A36 Shell Height: 2.4800 m
__0.8800_-_0.9100__
Per Table M-1, M = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000) = 0.8811
(4.9)(12.7143_-_0.3)(14.0000)(1.0000)
td = 146.8452 + 3.0000 = 8.7994 mm
tt = (4.9)(12.8929_-_0.3)(14.0000)
171.0000 = 5.0519 mm
Page 7 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 02
Material Grade: A36 Shell Height: 2.4800 m
__0.8800_-_0.9100__
Per Table M-1, M = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000) = 0.8811
(4.9)(10.2343_-_0.3)(14.0000)(1.0000)
td = 146.8452 + 3.0000 = 7.6409 mm
tt = (4.9)(10.4129_-_0.3)(14.0000)
171.0000 = 4.0570 mm
Page 8 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 03
Material Grade: A36 Shell Height: 2.4800 m
__0.8800_-_0.9100__
Per Table M-1, M = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000) = 0.8811
(4.9)(7.7543_-_0.3)(14.0000)(1.0000)
td = 146.8452 + 3.0000 = 6.4823 mm
tt = (4.9)(7.9329_-_0.3)(14.0000)
171.0000 = 3.0621 mm
Page 9 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 04
Material Grade: A36 Shell Height: 1.9800 m
__0.8800_-_0.9100__
Per Table M-1, M = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000) = 0.8811
(4.9)(5.2743_-_0.3)(14.0000)(1.0000)
td = 146.8452 + 3.0000 = 5.3238 mm
tt = (4.9)(5.4529_-_0.3)(14.0000)
171.0000 = 2.0672 mm
Page 10 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 05
Material Grade: A36 Shell Height: 2.5796 m
__0.8800_-_0.9100__
Per Table M-1, M = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000) = 0.8811
(4.9)(3.2943_-_0.3)(14.0000)(1.0000)
td = 146.8452 + 3.0000 = 4.3988 mm
tt = (4.9)(3.4729_-_0.3)(14.0000)
171.0000 = 1.2729 mm
Page 11 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Per :
Modulus of Elasticity at 93° (M1): 199000 MPa
Modulus of Elasticity at 148° (Table ) (M2): 195140 MPa
M = M1/M2 = 199000/195140 = 1.0198
Per 5.10.5.1:
__B__
tr = 2x1000D
sinø { 1000E } + CA =
(2)(1000)(14.0000)
sin(9.4623) { (1,000.0000)(195140)
_7.3160_
} + 3.0000 = 35.9778 mm
For Unbalanced Snow Load: Su = 1.0 Sb = 1.0 * 0.0000 = 0.0000 kPa
Page 12 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Per 5.10.5.1:
__ U __
tr = 2x1000D
sinø { 1.33x1000E } + CA =
(2)(1000)(14.0000) _ 6.2160 _
sin(9.4623) { (1.33)(1,000.0000)(195140)
} + 3.0000 = 29.3582 mm
Per 5.10.5.2:
p = Greater of B or U = 7.3160 kPa
Page 13 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Compression Ring
L 120 x 120 x 15 per Detail b
120 mm Vertical leg of rim angle is lap welded to the outside of the
shell with the horizontal leg turned out
Rim Angle is attached 0.3750 mm above the top of shell
Material: A36
API-650_Figure_F-2
Rc = 7000.0000 mm
th = 8.0000 mm
tc = 8.0000 mm
wc = 0.6 (Rctc) = 0.6 (7000.0000 * 8.0000) = 141.9859 mm
ta = 15.0000 mm
Horizontal projection of angle (a1) = 105.0000 mm
Maximum horizontal projection = ta * 250/ (Fy)= 15.0000 * 250/ (220.2679)
= 252.6712 mm
therefore a1 = 105.0000 mm
Vertical projection of angle (a2) = 120.0000 mm
Maximum vertical projection = wc = 141.9859 mm
therefore a2 = 120.0000 mm
Available area from compression ring (Ac) = (a1 + a2)ta =
(105.0000 + 120.0000)15.0000 = 3375.0000 mm²
Page 14 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
The required compression ring area of 8137.46 exceeds the actual available
area (corroded) of 3858.48
Page 15 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
__0.8800_-_0.9100__
Per Table M-1, M1 = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000)= 0.8811
Yield strength (Fy) = lesser of Fyr, Fyc, and Fys = 220.2679 MPa
Per F.4.1
(1.000)(A)(Fy)(tan ø) (0.00127)(DLR) =
P = 200D² + D²
= 6.1564 kPa
Per 5.2.1(k)(2), design uplift pressure on the roof need not exceed
1.6P - Pi = (1.6)(6.1564) - 7.0000 = 2.8503 kPa
Page 16 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
A = 200D²(Pi - (0.0013)(DLR)/D²)
1.000Fy(tan ø) =
Design pressure per F.4.1 is less than the design pressure. Increase
the compression ring.
Tank is anchored for the internal pressure
Compression area required per F.5.1 exceeds the compression area
available
Corroded Condition
Roof thickness (th) = 5.0000 mm
Area resisting compressive force (A) = 3858.4812 mm²
Weight of shell and framing (DLS) = 240991.8929 N
Weight of roof and structural attached to roof (DLR) = 60083.6481 N
Per F.4.1
(1.000)(A)(Fy)(tan ø) (0.00127)(DLR)
P = 200D² + D² =
= 4.0028 kPa
Per F.5.1
200D²(Pi - (0.0013)(DLR)/D²)
A = 1.000Fy(tan ø) =
Page 17 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Roof thickness has been exceeded. Increase roof thickness or roof pitch.
Page 18 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
__0.8800_-_0.9100__
Per Table M-1, M1 = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000)= 0.8811
Allowable tensile stress for compression ring per Table 5-2 (fc) = 160.0000 MPa
__0.8800_-_0.9100__
Per Table M-1, M1 = 0.9100 + 150.0000 - 94.0000 * (148.0000 - 94.0000)= 0.8811
__83D___ ___Pr___
Per V.7.2.1, tcone = sin ø 1.7200E =
(83)(14.0000) _____7.3160_____
sin 9.4623 (1.720)(195140) = 32.9994 mm
Actual roof thickness less corrosion is less than the calculated thickness of
32.9994 per Appendix V
Page 19 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
__125PrD²___ __(125)(7.3160)(14.0000)²__
Per V.7.2.2, Areqd = 1 f tan ø = (1)(146.8452)(tan 9.4623) = 7323.7104 mm²
__Dtc___ (14.0000)(5.0000)
Per V.7.2.3, Xcone = 13.40 sin ø = 13.40 sin 9.4623 = 276.5058 mm
Page 20 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Wind Calculations
Wind Velocity per ASCE 7-10 Figure 26.5-1B = 180 kph
Tank diameter (D) = 14.0000 m
Thinnest shell course thickness (t) = 5.0000 mm
Exposure C
Risk Category = IV
For Shell:
Centroid of shell Cs = 6.0000 m
z = Cs but not less than 4.57 m
z = 6.0000 m from bottom of tank
Per ASCE7, zg = 274.30 m
= 9.50
Kz = 2.01(6.00/274.30)^(2/9.50) = 0.899
Kd = 0.95
Kzt = 1.00
qz = 0.61300KzKztKdV²/1000 =
(0.61300)(0.899)(1.00)(0.95)(39.00)²/1000 = 0.80 kPa
Cf = 0.95
G = 0.85
Pw = qzGCf = (0.80)(0.85)(0.9500) = 0.6429 kPa
but not less than 0.4800 kPa
= 0.6429 kPa
Page 21 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
For Roof:
Top of roof Cs = 13.17 m
z = Cs but not less than 4.57 m
z = 13.17 m from bottom of tank
Per ASCE7, zg = 274.30 m
= 9.50
Kz = 2.01(13.17/274.30)^(2/9.50) = 1.061
Kd = 0.85
Kzt = 1.00
V = 39.00 m/s
qz = 0.61300KzKztKdV²/1000 =
(0.61300)(1.061)(1.00)(0.85)(39.00)²/1000 = 0.8406 kPa
GCp = 0.90
Uw = qzGCp = (0.8406)(0.90) = 0.7565 kPa
V = 140.40 kph
H1 = 9.47t[ (t/D)³](1.72/Pwd) =
(9.47)(5.0000)[ 5.0000 / 14.0000)³](1.72/1.05) = 16.2624 m
tuniform 5
For each shell course, Wtr = W
tactual
(Shell courses are numbered from bottom to top)
Shell Course W (m) Tactual (mm) Wtr (m)
5 2.5796 5.0000 2.5796
4 1.9800 5.0000 1.9800
3 2.4800 5.0000 2.4800
2 2.4800 5.0000 2.4800
1 2.4800 7.0000 1.0694
Page 22 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Overturning moment:
Total shell vertical height (H) = 12.0000 m
Bottom thickness used (tb-CA) = 9.0000 - 3.0000 but shall not exceed
bottom shell course corroded thickness of 7.0000 mm = 6.0000 mm
Bottom material yield strength (Fby) = 250.0000 MPa
G = lesser of 0.70 or product specific gravity = 0.7000
wL = 59.0000tb (FbyH) =
(59.0000)(6.0000) (250.0000 * 12.0000) = 19389.3785 N/m
Page 23 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Page 24 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Per V.8.1.1
0.75
( __D__
tsmin ) [( HDTS )( FEy )0.5 ] =
( 14.0000
5.0000 )
0.75
[( 10.5890
14.0000 )(
220.2679
195140 )0.5] = 0.0550 > 0.00680
Page 25 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
15203 ( (1.37)(10.5890)
14.0000 )( 14.0000
5.0000 )2.5
= 0.9453 kPa < Ps
15203 ( (3.00)(10.5890)
14.0000 )( 14.0000
5.0000 )2.5
= 0.4312 kPa < Pe
The design external pressure exceeds the value from V.8.1.2. Shell
must be stiffened.
Per V.8.1.3, for condition 1
Page 26 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Hsafe = 2.5
1.0(tsmin)__(E) 2.5
= 1.0(5.0000)__(195140) = 7.1086 m
1.5 (Ps)
15203 (D) (15203)(1.37)(14.0000) 1.5 (1.4081)
Per V.8.2.1.3
Ns = HTS/Hsafe -1 = 10.5890/7.1086 -1 = 1
Per V.8.2.2.1
445.00D³ 445.00(14.0000)³
N² =
( tsminHTS² ) =
( (5.0000)(10.5890)² )= 46.6695
Per V.8.2.3.1
H = 12.0000 m
Vl = 250PsH/1 = 250(1.4081)(12.0000)/1 = 4224.4319 N/m
Per V.8.2.3.2
Ireqd =
37.5VlD³
=
(37.5)(4224.4319)(14.0000)³ = 63.6456 cm4
E(N²-1) 195140(6²-1)
Per V.8.2.3.3.1
Page 27 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Stiffener Ring:
12.0000 120.0000 1440.0000 60.0000 86400.0000 31.8572 1461426.0420 1728000.0000
######## 12.0000 1296.0000 6.0000 7776.0000 -22.1428 635435.2530 15552.0000
Shell:
######## 5.0000 560.5622 -2.5000 -1401.4055 -30.6428 526358.4556 1167.8380
-------- ---------- ---------- -----------
92774.5945
3296.5622 e²A + Is = 4367939.5886 mm4
= 436.7940 cm4
Per V.8.2.3.3.2:
Astiff = Areqd - tsXshell - trXroof =
201.3754 - (5.0000)(112.1124) - (5.0000)(276.5058) = -1741.7158 mm²
Page 28 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Bottom extending inside tank per V.3.1 (Xbtm) = 16tb = (16)(6.0000) = 96.0000 mm
Chime = bottom outside projection + shell thickness = 80.0000 + 7.0000 = 87.0000 mm
Bottom chime:
6.0000 87.0000 522.0000 36.5000 19053.0000 44.3344 1026011.9095 329251.5000
Bottom (Xbtm):
6.0000 96.0000 576.0000 -55.0000 -31680.0000 -47.1656 1281365.4091 442368.0000
Shell:
######## 7.0000 928.5726 -3.5000 -3250.0042 4.3344 17445.2094 3791.6716
-------- ---------- ---------- -----------
-15877.0042
2026.5726 e²A + Is = 3100233.6996 mm4
= 310.0234 cm4
Per V.8.2.3.3.2:
Astiff = Areqd - tsnXshell -tbtmXbtm =
201.3754 - (7.0000)(132.6532) - (6.0000)(96.0000) = -1303.1972 mm²
Page 29 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Stiffener Ring:
####### ####### ######## ####### ########## -5.9812 64395.3069 #########
####### ####### ######## ####### ########## 63.0188 ########### #########
Shell:
####### 5.0000 ######## -2.5000 -2802.8111 -83.4812 ########### #########
-------- -------- -------- --------
######### ########### e²A + I s = 17851429.9100 mm4
= 1785.1430 cm4
For transposed shell height per V.8.2.2(c) and V.8.1.4 where ts1 = 5.0000 mm:
H = 2.4800 m and ts = 7.0000 mm
H = 2.4800 m and ts = 5.0000 mm
H = 1.7451 m and ts = 5.0000 mm
2.5
HTS = H(ts1/ts) = 5.2945 m
Page 30 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
L1 = 5.2949 m
L2 = 6.7051 m
Ls = (L1 + L2)/2 = (5.2949 + 6.7051)/2 = 6.0000 m
Per V.8.2.2.3:
Q = 1000PsLs/1 = (1000)(1.4081)(6.0000)/1 = 8448.8637 N/m
Per V.8.2.2.5:
E = 195,140 MPa
N = 6
Page 31 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Stiffener Ring:
12.00 150.00 1800.00 75.00 135000.00 -4.90 43236.82 3375000.00
138.00 12.00 1656.00 144.00 238464.00 64.10 6803962.90 19872.00
Shell:
236.22 5.00 1181.12 -2.50 -2952.81 -82.40 8019759.09 2460.68
-------- -------- -------- --------
4637.1244 370511.1889 e²A + Is = 18264291.4782 mm4
= 1826.4291 cm4
= 215.1244 cm³
For transposed shell height per 5.9.6.2 where tuniform = 5.0000 mm:
W = 2.4800 m and ta = 7.0000 mm
W = 2.4800 m and ta = 5.0000 mm
W = 1.7451 m and ta = 5.0000 mm
Page 32 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Z = [(6.0h1D²)/(0.5Fy)][Pwd/1.72] =
[(6.0*5.2949*(14.0000)²)/(0.5*210.00)][1.05/1.72]= 36.1383 cm³
Stiffener Attachment Weld
Ls = 6.0000 m
Ps = 0.6429 kPa
Vs1 = (1000)PsLs = (1000)(0.6429)(6.0000) = 3857.5694 N/m
vs = 10.00PsLsD = (10.00)(0.6429)(6.0000)(14.0000) = 540.0597 N
Vs2 = 1000vsqs/Is = (1000)(540.0597)(215124.4052)/18264291.4782 = 6361.0475 N/m
Page 33 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Weights
Page 34 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Seismic Calculations
Tank is mechanically anchored. The tank shall be shimmed and grouted per E.7.1.
E.4.5.2-c:
Ks = ______0.578_______ = __________0.578___________ = 0.5791
3.68H (3.68)(12.0000)
tanh ( D ) (
tanh 14.0000 )
Per E4.5.2-a: Tc = 1.8Ks D = (1.8)(0.5791) 14.0000 = 3.8999
Page 35 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
TL = 5.0000
K = 1.5
Tc TL , Per E.4.6.1-4
However, Ac Ai
Therefore, Ac = 0.0277
Per E.6.1.1
Weights:
Ws = 377967 N
Wf = 109131 N
Wr = Roof weight + 10% of snow = 896650 N
WP = 17999348 N
Per E.6.1.2.1
Page 36 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Per E.6.1.2.1-3,
Xc =
[ 1.0 - __cosh(3.67H/D)_-_1__
3.67H/D sinh(3.67H/D) ]H =
____cosh(3.67/1.1667)_-_1____
[1.0 - (3.67/1.1667)sinh(3.67/1.1667) ](12.0000) = 8.5001 m
Per E.6.1.2.2
D/H < 1.333
Per E.6.1.2.2-3,
Xcs =
[ 1.0 - _cosh(3.67H/D)_-1.937
3.67H/D sinh(3.67H/D) ] H =
[1.0 - (3.67/1.1667)sinh(3.67/1.1667)
__cosh(3.67/1.1667)_-_1.937_
](12.0000) = 8.8083 m
Per E.6.1.5
Per E.6.2.1.1.1
Ws = 377967 N
wrs = 20386.6013 N/m
ts = 5.7994 mm
Per E.6.2.1.1.1-2, wt = Ws/( D) + wrs = 377967/( 14.0000) + 20386.6013
= 28980.2279 N/m
Shell compression per E.6.2.2.2-1a
Page 37 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Per E.6.2.1.1.1
Ws = 250802 N
wrs = 19566.9490 N/m
ts = 5.7994 mm
Per E.6.2.1.1.1-2, wt = Ws/( D) + wrs = 250802/( 14.0000) + 19566.9490
= 25269.2863 N/m
For GHD²/t² 44
Per E.6.2.2.3-1a, Fc = 83ts/D = (83)(5.7994)/14.0000 = 34 MPa
Tc TL
Per E.7.2-4, Af = KSD1I/Tc = (1.5)(0.0960)(1.50)/3.8999 = 0.0554
Page 38 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 01
Y = 12.0000 m
1.85AcGD²cosh[3.68(H - Y)/D]
Per E.6.1.4-4a, Nc = cosh[3.68H/D] =
(1.85)(0.0277)(1.0000)(14.0000)²cosh[3.68(12.0000_-_12.0000)/14.0000]
cosh[(3.68)(12.0000/14.0000)]
= 0.8554 N/mm
Nh = 4.90D(Y-0.3)G = (4.90)(14.0000)((12.0000)-0.3)(1.000) = 802.6200 N/mm
Page 39 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 02
Y = 9.5200 m
2
(5.22)(0.0400)(1.000)(14.0000)² [ (0.75)(14.0000) - 0.5
___9.5200___ ___9.5200___
( (0.75)(14.0000) )]
= 20.2841 N/mm
1.85AcGD²cosh[3.68(H - Y)/D]
Per E.6.1.4-4a, Nc = cosh[3.68H/D] =
(1.85)(0.0277)(1.0000)(14.0000)²cosh[3.68(12.0000_-_9.5200)/14.0000]
cosh[(3.68)(12.0000/14.0000)]
= 1.0436 N/mm
Nh = 4.90D(Y-0.3)G = (4.90)(14.0000)((9.5200)-0.3)(1.000) = 632.4920 N/mm
Page 40 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 03
Y = 7.0400 m
2
(5.22)(0.0400)(1.000)(14.0000)² [ (0.75)(14.0000) - 0.5
___7.0400___ ___7.0400___
( (0.75)(14.0000) )]
= 18.2405 N/mm
1.85AcGD²cosh[3.68(H - Y)/D]
Per E.6.1.4-4a, Nc = cosh[3.68H/D] =
(1.85)(0.0277)(1.0000)(14.0000)²cosh[3.68(12.0000_-_7.0400)/14.0000]
cosh[(3.68)(12.0000/14.0000)]
= 1.6913 N/mm
Nh = 4.90D(Y-0.3)G = (4.90)(14.0000)((7.0400)-0.3)(1.000) = 462.3640 N/mm
Page 41 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 04
Y = 4.5600 m
2
(5.22)(0.0400)(1.000)(14.0000)² [ (0.75)(14.0000) - 0.5
___4.5600___ ___4.5600___
( (0.75)(14.0000) )]
= 13.9138 N/mm
1.85AcGD²cosh[3.68(H - Y)/D]
Per E.6.1.4-4a, Nc = cosh[3.68H/D] =
(1.85)(0.0277)(1.0000)(14.0000)²cosh[3.68(12.0000_-_4.5600)/14.0000]
cosh[(3.68)(12.0000/14.0000)]
= 3.0836 N/mm
Nh = 4.90D(Y-0.3)G = (4.90)(14.0000)((4.5600)-0.3)(1.000) = 292.2360 N/mm
Page 42 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Shell Course 05
Y = 2.5800 m
2
(5.22)(0.0400)(1.000)(14.0000)² [ (0.75)(14.0000) - 0.5
___2.5800___ ___2.5800___
( (0.75)(14.0000) )]
= 8.8204 N/mm
1.85AcGD²cosh[3.68(H - Y)/D]
Per E.6.1.4-4a, Nc = cosh[3.68H/D] =
(1.85)(0.0277)(1.0000)(14.0000)²cosh[3.68(12.0000_-_2.5800)/14.0000]
cosh[(3.68)(12.0000/14.0000)]
= 5.1232 N/mm
Nh = 4.90D(Y-0.3)G = (4.90)(14.0000)((2.5800)-0.3)(1.000) = 156.4080 N/mm
Page 43 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Note: Anchor bolt shall be tightened snug fit (hand tight plus a maximum of 1/8 turn
with wrench). Measures such as peening the threads, adding lock nut, or tack welding
the nut to the top plate shall be taken.
W2 = 301075.5410 N
PWR = 0.7565 kPa
MWS = DPwsH²/2 =(642.9282)(14.0000)(11.9996)²/2 = 648028.4614 N-m
Page 44 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Allowable bolt load per Table 5-21 = 0.8Fyb = 0.8 * 250.0000 = 200.0000 MPa
Bolt Load due to Seismic
Allowable stress per Table 5-21 = 0.8Fyb = 0.8 * 250.0000 = 200.0000 MPa
W1 = 301075.5410 N
PWR = 0.7565 kPa
MWS = 648028.4614 N-m
Page 45 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Page 46 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Page 47 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
(For seismic does not have to exceed AFyb = 834.8300 * 250.0000 = 208707.5000 N
Page 48 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
____________________25.4__________________________ = 0.9542
(0.177_*_250.0000_*_9.0000)(9.0000/10.0000)² + 25.4
(7000.0000 * 10.0000)
184944.2728_*_150.0000 1.32_*_0.9542___________________________________________________ +
(10.0000)²
[ _1.43_*_250.0000_*_(300.0000)²
7000.0000 * 10.0000
+ (4 * 250.0000 * .333
(300.0000)²)
________0.031__________
(7000.0000 * 10.0000)
] = 418.5770 MPa
____________________25.4__________________________ = 0.9665
(0.177_*_250.0000_*_6.0000)(6.0000/7.0000)² + 25.4
(7000.0000 * 7.0000)
Page 49 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
(7.0000)²
[
184944.2728_*_150.0000 1.32_*_0.9665___________________________________________________ +
_1.43_*_250.0000_*_(300.0000)²
7000.0000 * 7.0000
+ (4 * 250.0000 * .333
(300.0000)²)
________0.031__________
(7000.0000 * 7.0000)
] = 734.6754 MPa
Page 50 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
For DMT:
DMT (Td) = -12 °C
Temperature difference (T) = Ta - Td = 20 - -12 = 32 °C
Coefficient of thermal expansion (Et) = 12.00x10^-6 mm/mm-°C
Contraction = 500EtDT = (500)(12.00x10^-6)(14.0000)(32)
= 2.6880 mm
Page 51 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Fe = ²E/([l/r]²) =
² * 195140.35/([34.6380]²) = 1605.24 MPa
Fc = {[0.658]^(Fy/Fe)}(Fy) = {[0.658]^(250.00/1605.24)} * 250.00 = 234.22 MPa
(S) = 1.00 * Fc / 1.67 = 1.00 * 234.22 / 1.67 = 140.25 MPa
____________________25.4__________________________ = 0.9542
(0.177_*_250.0000_*_9.0000)(9.0000/10.0000)² + 25.4
(7000.0000 * 10.0000)
Page 52 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
48496.5287_*_150.0000 1.32_*_0.9542___________________________________________________ +
(10.0000)²
[ _1.43_*_250.0000_*_(300.0000)²
7000.0000 * 10.0000
+ (4 * 250.0000 * .333
(300.0000)²)
________0.031__________
(7000.0000 * 10.0000)
] = 109.7602 MPa
____________________25.4__________________________ = 0.9665
(0.177_*_250.0000_*_6.0000)(6.0000/7.0000)² + 25.4
(7000.0000 * 7.0000)
[
48496.5287_*_150.0000
(7.0000)²
1.32_*_0.9665___________________________________________________ +
_1.43_*_250.0000_*_(300.0000)²
7000.0000 * 7.0000
+ (4 * 250.0000 * .333
(300.0000)²)
________0.031__________
(7000.0000 * 7.0000)
] = 192.6483 MPa
Page 53 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Fe = ²E/([l/r]²) =
² * 199000.00/([34.6380]²) = 1636.99 MPa
Fc = {[0.658]^(Fy/Fe)}(Fy) = {[0.658]^(250.00/1636.99)} * 250.00 = 234.52 MPa
(S) = 1.00 * Fc / 1.67 = 1.00 * 234.52 / 1.67 = 140.43 MPa
Page 54 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
____________________25.4__________________________ = 0.9542
(0.177_*_250.0000_*_9.0000)(9.0000/10.0000)² + 25.4
(7000.0000 * 10.0000)
55123.9827_*_150.0000 1.32_*_0.9542___________________________________________________ +
(10.0000)²
[ _1.43_*_250.0000_*_(300.0000)²
7000.0000 * 10.0000
+ (4 * 250.0000 * .333
(300.0000)²)
________0.031__________
(7000.0000 * 10.0000)
] = 124.7599 MPa
Page 55 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Foundation Loads
Page 56 of 57
FIRE FIGHTING TANK (1000 m3) DOC.NO.
Software :ITS Design J3A-CAL-EAIC -ZDZ-220-0006
Version :21.1.1.7
Page 57 of 57