MR-001 Test Certificate

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Test Certificate

Customer Name & Address Report No : RRKABEL/TC/AP/RRKL-033807495


CABLES & CONDUCTORS Report date : 09/09/2020
5-2-128/A , HYDERBASTIR.P.ROAD , SECUNDERABAD HYDERABAD Invoice No : DAP-210000829
Telangana IND 500003
Party order No :

Product : FLAMEX FR-LSH ABC 2 FR-LSH 2.5 SQ MM RD 180M


Product Type : FLAMEX FR-LSH
No of core & size : 2.5
Class Of Conductor : PLAIN ANNEALED COPPER CLASS 2, IS:8130
Voltage : 1100
Type of Insulation : TYPE A ( FR-LSH ), IS 5831

Type of Inner sheath :

Type of sheath : NA
Brand Name : RR KABEL 2.5 SQ MM 1100V FLAMEX FR-LSH (ISI LOGO) IS 694
Cable standard : IS 694
Batch Number : 190807-FC-180839511

Sr. No Test Name Unit Level Specific requirement Observed

1 No of conductor Min 3.000 36.0000


2 Insulation Thickness mm Nominal 0.800 0.8300
3 Overall Diameter of cable mm Max 4.000 3.6500
4 Conductor Resistance @ 20°C Ω/km Max 7.410 7.3700
5 Insulation Resistance test at 27°C Mega Ω km Min 36.700 1185.6000
6 Insulation Resistance test at 70°C Mega Ω km Min 0.037 1.0000
7 Volume Resistivity at 27°C 10^13 Ω/cm Min 1.000 45.8000
8 Volume Resistivity at 70°C 10^10 Ω/cm Min 1.000 30.5000
9 High Voltage AC 3 kV @ 5 minutes kV Standard Withstood Withstood
10 Period of burning after removal of flame Sec Max 60.000 2.0000
11 Unaffected portion from the lower edge of mm Min 50.000 372.0000
top clam
12 Limited Oxygen Index % Min 29.000 30.0200
13 Limited Temperature Index °C Min 250.000 300.0000
14 Halogen acid gas evolution % Max 20.000 17.0000
15 Smoke Density Rating % Max 60.000 55.0000

Notes: 1. The results relate only to the sample tested.


2. Test certificate shall not be reproduced except in full.
3. This is computer generated test certificate hence does not require signature.

D.NO.3-45, Opp. Prathap Industries, Enikepadu VIJAYAWADA KRISHNA Andhra Pradesh (New) 521108 Tel.No. Email :